| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical 00 JALESAR MAHAVIR GANJ 00 VILLAGE TOWN JALESAR CITY ETAH ETAH UTTAR PRADESH 207302 INDIA | ETAH | UTTAR PRADESH | 207302 | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹41,000
Closing Date
30 Jul 2020, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC MEERUT
130 D PAARESHAN BHAWAN VICTORIA PARK MEERUT
WORK TENDER
2020_UPTCL_496314_1
T-60/20-21/ETC/MT
Open Tender
Electrical Works
Item Rate
90 days
MEERUT
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
SE ETC MEERUT
₹41,000
5 Aug 2020
24 Jul 2020
31 Jul 2020
24 Jul 2020
30 Jul 2020
24 Jul 2020
90 days
Amount
Part-A (Work)
Following work is to be carried out at 132 KV S/S Sardhana Under ETD-II Meerut
Opening/Cutting of R,Y & B phase of 132 KV existing Main bus bar-I made of tarantulla/Zebra conductor between bus sections below gantries, step by step during bus bar replacement work including dismantling of all types of associated clamps & fittings.
Dismantling of following existing jumpers form main bus bar by opening of all associated clamps, step by step during bus bar replacement work.
Of ACSR Zebra conductor of remaining Feeder
Of ACSR Panther conductor of remaining feeders.
Dismantling of 132 KV Old/ Damaged Main bus bar-I Sections (R, Y, & B) of Tarantulla/Zebra conductor and lowering down of conductor from sub-station gantry to complete dismantling work including dismantling of all associated Tension clamps, fittings & Disc insulators etc.
Stringing and proper sagging of new 132 KV Main bus bar I Sections (R, Y & B) by twin zebra conductor the work includes fitting of tension clamps, Hoisting of 70 KN Disc, tension fittings, Spacers PG Clamps etc. and cutting of conductor as required.
Reconnecting following new jumpers on different bays after fixing of spacers, clamps as required.
Of ACSR Twin Zebra conductor of Bus-coupler bays and Bus Bar.
Of ACSR Twin Panther conductor of remaining feeders ICT-I, ICT-II & ICT-III.
Replacement of damaged Jumper of different bays in the 132 KV Switchyard after opening of jumper one & Re-fixing of new jumper with the help of suitable PG Clamps & connectors etc. & cutting of conductor as required.
Following work is to be carried out at 33 KV Switch yard.
Opening / Cutting of R,Y & B phase of 33KV existing Main Bus of Tarantulla/Zebra conductor between Bus section below gantry step by step during Bus Bar replacement work including dismantling of all type of associated clamps and fitting.
Dismantling of following existing jumper from Main Bus Bar by opening of associated clamp step by step during Bus Bar replacement.
Of ACSR Zebra conductor 40 MVA, 63 MVA Transformer Bus Coupler.
Of ACSR Panther conductor of remaining Feeder.
Dismantling of 33 KV Old/ Damaged Main bus bar Sections (R, Y, & B) of Tarantulla/Zebra conductor and lowering down of conductor from sub-station gantry to complete dismantling work including dismantling of all associated Tension clamps, fittings & Disc insulators etc.
Stringing and proper sagging of new 33 KV Main bus bar Sections (R, Y & B) by Twin Zebra conductor the work includes fitting of tension clamps, Hoisting of 70 KN Disc, tension fittings, Spacers PG Clamps etc. and cutting of conductor as required.
Re-connecting following new jumper of different Bay after fixing of spacer & clamp as required.
ACSR Twin Zebra conductor of 40 MVA / 63 MVA Transformer/ Bus Coupler.
Of ACSR Twin Panther conductor of 33 KV feeder.
Of ACSR Single Panther conductor PT / LA
Replacement of damage jumper of different Bay 33 KV switchyard after opening of damage jumper & replacing of new jumper with suitable PG clamps & connector.
Complete dismentling of 33 KV 10 MVAR Capacaitor Bank including Isolator, Breaker, CT, NCT, Reactor, Bus Bar, Structure capacitor unit and opening of electrical connection & cutting of earthing strip.
Erection of Main and Auxiliary Sub-Station Structure
Proper stacking and shifting of main & auxiliary structure in open switchyard at erecting place as per shop bill norms.
Erection of main & auxiliary structure lattice type ATM, ABL, BCT, ALP, BPL etc. consisting of column, Beam, peak, mast etc. and auxiliary structure for installation of CTs, PTs, LA etc. erection of structure as per drawing with the help of GI nuts & Bolts flat spring washer matching the hole, cuttnig and matching the member if rquired include cost of all men and T & P excluding GI structure nut and bolts to complete the work erection of main & auxiliary structure lattice type ATM, BTM, AXM, ABL, CCM,CGM, EKR, BBR, BCT, ALP, BPL, BTI etc. upon foundation and its proper tightening.
Making hole in part of GI main/auxilary structre / cutting of GI angle drilling of hole existing/ deffective structure /plate/Angle and grinding machine with all cost of men, T & P etc.
Erection of following equipment as per instruction mannual of various equipments and technical specification including shifting of material / equipment from store to erection site including all other associated works to complete the job satisfactorily.
Erection of 145 KV Circuit Breaker
Erection of 36 KV Vacuum Circuit Breakr
Erection of 145 KV Current Transformer
Erection of 36 KV Current Transformer
Erection and mounting of 145/36 KV CT/PT junction box.
Erection of 145 KV Bus Isolator without earth switch (Moterized)
Erection of 36 KV Bus Isolator.
Erection of 145 KV Bus Post Insulator for support
Erection of 36 KV Bus Post Insulator for support
Erection of 120 KV Lighting Arrestors
Erection of 30 KV Lighting Arrestors
Erection of 10 MVAR capacitor Bank along with coloum, Beam, Isolator, CT , NCT, Breaker, Lightening arrestor, Reactor, CTs, NCT, Isolator, Capacitor unit Reactor and unit structure, Jumper and electrical connection and other associated work.
Erection of following control and relay Panels as per instruction mannual and technical specification including shifting of panel from store to erection site including all other associated works to complete the job satisfactorily.
Erection of 132 KV control relay panel for 63 MVA Transformer.
Erection of LT out door cubical for LT supply
Erection of 63 MVA RTCC Pannel.
Stringing of various main, Transfer bus bar and jack buses of 132 KV and 33 KV with different type conductor and different length of span as mentoied below .the work includes cutting &bending of conductor fixing of single /double bolted type tension fitting /suspension hoisting of disc Insulator and shifting of material from store .site to erection site and all other associated work to complete work satisfactorily as per drawing and techinical specification .
132 KV Jack Bus for 63 MVA Transformer
33 KV switchyard Capacitor bank Bus Bar single Panther.
Bay wise interconnection of equipment with specified conductor of various 132 KV & 33 KV Equipment with Main /Transfer / jack Bus bar of ACSR Zebra /Panther conductor . The work Includes cutting of conductor . Bending in proper shap .clamping with the help of clamp and all other associated work to complete job.
63 MVA Transformer Bay 132 KV side Jack Bus
33 KV side Transformer bay Twin Zebra
Laying and Termination of following size control cable in trench/cable trays from different control room equipment to 132/33 KV Isolator, circuit brekers CT/PT & their junction boxes. Transformer marshaling box. Isolator box & other outdoor equipments installed in 132/33 KV switch yard as per cable schedule . including carriage of cable drum from store and all other associated work.
Control cable of size 2 core x 2.5 mm2
Control cable of size 4 core x 2.5 mm2
Control cable of size 6 core x 2.5 mm2
Control cable of size 10 core x 2.5 mm2
Termination of control cable
Installation work of 63 MVA Transformer.
Shifting of main tank of 63 MVA Tranformer from unolading point to t he plinth up to 30 Mtr distance including turning of tank if required including all T & P and labour required to complete the job satisfactorily.
Complete erection of 63 MVA 132/33 KV Transformer by erection of radiator, conservator t ank all bushing oil pipe lines, cooling fans etc. to complete the job satisfactorily.
Circulation of complete Transformer oil in Transformer tank through centrifuging machine, centrifuging machine shall be provided by the contractor, oil capacity (Approx 25 KL)
Shifting of 20 KL Oil tanker from praposed S/S to 132 KV S/S Sardhana including loading. unloading and carriage. Distance about 100 Km.
Laying & Termation of following size PVC power cable from ACDB /DCDB installed on control room / 33/.04 KV station Transformer marashaling box etc. in 132/33 KV switchyard in side 500mm below ground level including excavation of trench & laying on its edge along with cable of both side filling the same with Ganga sand and then putting the bricks on 115mm side cover the trench & then filling with earth. Proper termination at both side by providing crimping type aluminum lugs as per requirment including cost of bricks sand cable route marker as per cable schedule including carriage of cable drum from store and all other associated works.
Power cable 31/2 core x 300 mm2 /150 mm2
300 mm2 Power cable termination.
Febrication of 3 meter long elelctrode with 40 mm dia M S round bar having 150 mm long conical shape by digging cutting, striaghtening etc. and then placing it verticall. inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Staiton to switchyard.
Delta earthig of 120/33 KV LA's of 132 KV Lines and 63 MVA Transformers neutral by consisting of 3/6 Nos. 3.0 Mtr long electrode of 40mm dai having 150mm long conical shape, its placing inside the ground in rectangular/tringular shap and connection all 3/6 Nos electrodes with 75x10/50x6mm MS flate laid on its edge and then this rectangle/tringle shape be connected to main earth mat at two place in opposite direction strictly as per drawing.
120 KV Lighting Arrestors (Rectangle shape 6 electrode )
30 KV Lighting Arrestors (Rectangle shape 6 electrode )
132/33 KV 63 MVA Transformer (Tringular shape 3 electrode )
Earthing of equipments by cutting straightining, bending, laying 700mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure, equipments structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed excavation of trenches its back filling. all other associated work as required to complete the work.
Laying of MS Flat of size 75x10 mm
Laying of MS Flat of size 50x6 mm
Laying of MS Flat of size 25x6 mm
Painting of MS flat of different size after cleaning of rusted surface 1st coat of Red Oxide and 2 coat of Bus Green Paint to complete the work.
MS Flat of size 75x10 mm
MS Flat of size 50x6 mm
MS Flat of size 25x6 mm
Periphery and switchyard lighting
Providing and fixing of round pole of MS pipe "B" class 9 mtr long duly painted 1st coat of Red Oxide and 2nd coat of aluminum paint from upto ground level 2 mtr black paint and gruoting upto 5 Ft in cement dust / concrete in ratio 1:3:6.
Pole bracket of 50mm dia 1.2 mtr long mounting arrangement upon pole along with nut & bolt bracket angle 300 suitable for 120 watt LED.
Providing and fixing of junction box on lighting pole of size 200x200x150mm made of MS sheet of 16 gauge duly powder coated inside fixing 1 No 6 Amp MCB, 1 No TB of 4 Terminal & 1 No Kit Kat 16 Amp fixed up on mica sheet and back side a half round MS clamp and along wih PVC pipe fixing on junction box as per technical specification.
Providing and fixing of half round GI pipe OD-50mm for mounting the 120 Watt LED light upon gaintry mounting of 2 No GI bracket up on gaintry and fixing GI pipe complete with nut bolt and washer as per technical specification.
Providing and fixing of junction box on gaintry structure with 1 No MS flat 40x5 mm of size 200x200x150 mm made of MS sheet of 16 guage dully powder coated inside mounting 1 No 6 Amp MCB 1 No TB of 4 terminal & 1 No Kit Kat 16 Amp fixed upon mica sheet and back side mounting a flat 40x5 mm with 1 No 16mm dia hole and mounting PVC pipe fron groud level to box as per technical specification.
Supply & fixing of new generation energy saving and enviroment friendly long life versatile pressure die cost aluminum out door high been flood light with high power 120 Watt LED as light source and exclusively designed polycorbonate cover along with electronic driver complete fitting suitable for 220 V input supply for ISI make CGL/Hevels/ Surya/ Philips/Bajaj of equivalent etc. including electrical connection also to be done by the contractor.
Laying of 2x2.5 mm/4x2.5mm PVC cable as below.
Laying in trunch after removal & replacement of trunch cover.
Laying of ISI mark PVC cable including the cost of PVC pipe laying below ground 500mm ( cable shall be provided by the department free of cost).
Laying of 2x2.5mm PVC cable on coloum of structure by clamping with the help of aluminum strip. ( cable shall be provided by the department free of cost.)
Fixing of 3 phase AC cubical box of size 600x600x200 mm MS sheet 16 guage duly powder coated inside mounting the 4 No aluminum insulated bar of size 25x6 mm 1 No mounting the 1 No isolator 100Amp and 6 No MCB 16 Amp for lighting erection.
Part-B (Supply)
Supply of 132 KV bolted type tenson fitting for Twin Zebra conductor 1x10 No disc insulator with turn buckle complete with hardware fitting d-shackle, d-sockete, Ball hook, yoke plate, d-cilip it tenson clamp etc. as per technical specification.
Supply of 132KV bolted type tenson fitting for Twin Zebra conductor 1x10 No disc insulator without turn buckle complete with hardware fitting d-shackle, d-sockete, Ball hook, yoke plate, d-cilip it tenson clamp etc. as per technical specification.
Supply of 33 KV bolted type tenson fitting for Twin Zebra conductor 1x4 No disc insulator with turn buckle complete with hardware fitting d-shackle. D sockete. Ball hook, yoke plate d-cilip it tenson clamp etc. as per technical specification.
Supply of 33 KV bolted type tenson fitting for Twin Zebra conductor 1x4 No disc insulator without turn buckle complete with hardware fitting d-shackle. D sockete. Ball hook, yoke plate d-cilip it tenson clamp etc. as per technical specification.
Supply of 132 KV bolted type single tenson fitting for single Panther conductor without turn buckle for 132 KV jack bus with hardware fitting d-shackle, d-sockete, Ball hook, d-cilip it tenson clamp etc. as per technical specification.
Supply of 132 KV bolted type suspension fitting for single Panther conductor for 132 KV Jack bus with hardware fitting d-shackle, d-sockete, Ball hook, d-cilip it tenson clamp etc. as per technical specification.
04 bolted type PG clamp made of alluminum alloy LM -6 complete with GI Nut , bolts and washer suitable for Zebra to Zebra conductor as per technical specification
4 boted type PG clamp made of alluminum alloy LM -6 with GI Nut , bolts and washer suitable for Zebra to Panther conductor as per technical specification
03 bolted type PG clamp made of alluminum alloy LM -6 with Gl Nut , bolts and washer suitable for Panther to Panther conductor as per technical specification
Bimatlallic 132 KV isolator clamp made of aluminum alloy LM-6 suitable for twin Panther conductor one side connecting the twin panther condutor and another side connecting a plate with 04 Nos 12mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimatlallic 132 KV isolator clamp made of aluminum alloy LM-6 suitable for twin Zebra conductor one side connecting the twin Zebra and another side connecting a plate with 04 Nos 12mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimatellic 132 KV Isolator clamp made of aluminum alloy LM-6 suitable for single Panther concductor one side connecting the Panther conductor and another side connecting the Isolator rod complete with HDG nut bolt and washer as per technical specification.
Bimatlallic 132 KV Breaker clamp made of aluminum alloy LM-6 suitable for Single Panther conductor one side connecting the Panther conductor and another side connecting a plate with 04 Nos 12mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimatlallic 132 KV CT clamp for made of aluminum alloy LM-6 suitable single Panther conductor one side connecting the Panther conductor and another side connecting CT rod of dia 30 mm complete with HDG nut bolt & washer as per technical specification.
132 KV LA Clamp made of aluminum alloy LM-6 suitable for Single Panther conductor complete with hot dip galvanized nut bolt and washer as per technical specification.
Bimetallic 63 MVA T/F Bushing clamp made of aluminum alloy LM-6 suitable for HV side one side connecting the bushing rod and anohter side connecting the Panther conductor complete with HDG nut bolt and washer as per technical specification.
Bimetallic 63/40 MVA T/F Bushing clamp made of aluminum alloy LM-6 suitable for LV side Twin Zebra conductor one side connecting the Twin Zebra and other side connecting a plate with 04 Nos. 12 mm dia hole to matching with LV side bushing complete with HDG nut bolt & washer as per technical specification.
Bimetallic 33 KV Isolator clamp made of aluminum alloy LM-6 suitable for Twin Zebra conductor one side connecting the Twin Moose conductor and another side connecting a plate with 04 Nos. 12 mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimetallic 33 KV Breaker clamp made of alumumum alloy LM-6 suitable for Twin Zebra conductor one side connecting the Twin Zebra conductor and another side connecting a plate with 04 Nos. 12 mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimetallic 33 KV CT clamp made of aluminum alloy LM-6 suitable for Twin Zebra conductor one side connecting the Twin Zebra conductor and another side connecting CT rod of dia 25 mm complete with HDG nut bolt and washer as per technical specification.
33 KV LA clamp made of aluminum alloy LM-6 suitable for Twin Zebra conductor one side connecting the Twin Zebra conductor another side connecting the plate complete with HDG nut bolt & washer as per tecvhnical specification.
33 KV Bus Post Clamp made of aluminum alloy LM-6 suitable for Twin zebra conductor one side connecting the Twin Zebra conductor and another side connecting a plate with 04 Nos. 12 mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimetallic 33 KV Isolator clamp made of aluminum alloy LM-6 suitable for Twin Panther conductor one side connecting the Twin Panther conductor and another side connecting a plate with 04 Nos. 12 mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimatlallic 33 KV CT clamp made of aluminum alloy LM-6 suitable for single Panther conductor one side connecting the Panther conductor and another side connecting CT rod, complete with HDG nut bolt & washer as per technical specification.
Bimatlallic 33 KV Breaker clamp made of aluminum alloy LM-6 suitable for single Panther conductor one side connecting the Panther conductor and another side connecting a pad with 04 Nos 12mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimatlallic 33 KV isolator clamp made of aluminum alloy LM-6 suitable for single Panther conductor one side connecting the Panther conductor and another side connecting a plate with 04 Nos 12mm dia hole complete with HDG nut bolt & washer as per technical specification.
33 KV LA clamp made of aluminum alloy LM-6 suitable for single Panther conductor one side connecting the single Panther conductor and another side connecting a plate with 04 Nos. 12 mm dia hole complete with HDG nut bolt & washer as per technical specification.
Bimetallic 33 KV PT clamp made aluminum alloy LM-6 suitable for Panther conductor one side connecting the Panther conductor and another side connecting PT rod dia 16 mm complete with HDG nut bolt & washer as per technical specification.
Spacers for 250 mm spacing suitable for Zebra conductor 02 bolted made of aluminum alloy LM-6 complete with hot dip galvanized nut bolt & washer as per technical .specification.
Spacers for 100 mm spacing suitable for Zebra conductor 02 bolted made of aluminum alloy LM-6 complete with hot dip galvanized nut bolt & washer as per technical .specification.
Spacers for 60 mm spacing suitable for Zebra conductor 01 bolted made of aluminum alloy LM-6 complete with hot dip galvanized nut bolt & washer as per technical .specification.
Spacers for Panther conductor 01 bolted made of aluminum alloy LM-6 complete with HDG nut bolt & washer as per technical .specification.
132 KV CT Junction box of size 450x450x300 mm made of 16 SWG sheet complete with 16 Amp link type TB 20 No and cable gland 06 No duly painted with one coat of red oxide & two coat of grey paint as per technical specification.
33 KV CT Junction box of size 400x300x150 mm made of 16 SWG sheet complete with 16 Amp link type TB 18 No and cable gland 06 No duly painted with one coat of red oxide & two coat of grey paint as per technical specification.
Supply of cable gland of different sizes
i- 2C x 2.5 mm (16mm)
ii- 4C x 2.5 mm (19mm)
iii-6C x 2.5 mm (22mm)
iv- 10C x 2.5 mm (25mm)
Supply of copper lug of different types.
i- Ring type of size 2.5 mm
ii- Pin type of size 2.5 mm
Meena Elect and Engg Works
Gupta Elect and Engg Works
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .