Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.3 LAccepted-AOC C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | ₹20.3 L Quoted ₹21.4 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹21.7 LRejected-Finance VILL MOKHAWA TEHSIL GUDAMALANI DIST BARMER RAJASTHAN 344031 | GUDAMALANI | BARMER | RAJASTHAN | 344031 | ₹21.7 L | L2 | Rejected-Finance Other than L1 Bidder |
| 3 | Rejected-Technical 580 INDRA COLONY JAISALMER RAJASTHAN 345001 | JAISALMER | JAISALMER | RAJASTHAN | 345001 | - | - | Rejected-Technical Not enlisted in appropriate cat |
| 4 | Rejected-Technical JAISALMER RAJASTHAN 345001 INDIA UDYAM RJ 18 0001538 | JAISALMER | RAJASTHAN | 345001 | - | - | Rejected-Technical Not enlisted in appropriate cat |
| Sl No | Description | Qty | Unit | SHRI HARI CONSTRUCTION L1 | NAGEL ENTERPRISES L2 |
|---|---|---|---|---|---|
| 1.00 | Disconnecting, dismantling of old unserviceable LT panel/ Feeder pillar box and Design, supply, erection, commissioning and testing of outdoor type LT Panel, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type main copper bus bars of 800 Amps, looping & branch connection system shall be made with suitable rating copper bus bar having sleeves of colour coded .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 9 tank pre-treatment of surfaces. The LT Panel shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The LT Panel shall be made out of 3.15mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (02 layers) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. All incoming MCCBs shall be marked with location and rating of MCCBs.
The Feeder Pillar shall be provided with ventilation facility in the form of louvers for better heat dissipation (Location - Grand Stand) in and including dismantling of old unserviceable LT Panel complete and including the followings :CONTROL WIRING : All control wirings shall have to be carried out with 1100 volts rated FR grade PVC insulated multi-flexible type copper wire of cross sectional area 1.50Sqmm and shall be properly bunched, tied and dressed, ferrule marked for proper identification and crimped with suitable size and type of tinned copper lugs and shall be wrapped with PVC spring type tube near the door hinges.CABLE ALLEY- Cable alley shall be provided in both side of the panel of suitable space for all incoming and outgoing cables. Cable terminals shall be provided for conecting of all incoming and outgoing cables , INCOMING-1:-On load change over switch 630 Amps, 4 pole, 415 volts, 50 Hz complete - 01 Nos INCOMING-2 :- MCCB 630 Amps, 4 pole, 415 volts, 50 kA, 50 Hz, electronic release - 01 Nos OUTGOING :
(a) MCCB 250 Amps, 4 pole, 415 volts, 36 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu, - 02 Nos
(b) MCCB 200 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu - 02 Nos
(c) MCCB 160 Amps, 4 pole, 415 volts, 25 KA, 50 Hz, thermal magnetic release, Ics = 100%Icu, - 03 Nos
(d) Digital volt meter 96mm x 96mm suitable to read 0 to 500 volts, accuracy class 1% - 01 Nos
(e) Digital Ammeter 96mm x 96mm suitable to read 0 to 630 Amps, accuracy class 1% - 01 Nos
(f) Current transformer (CT) of rating 630/5, tape wound, rated burden 5 VA - 03 Nos
(g) LED indicator lamps complete with integral circuit and cluster LED, suitable to operate in 230-240 Volts AC supply - 1set of 03 Nos (Red - 01, Yellow- 01, Blue - 01)
(h) Control fuse holder, made of bakellite, 16 Amps rating, stud type, pannel door mounting complete with 01 No 02 Amps HRC fuse of suitable type- 03 Nos
(j) Copper bus bar 20mm wide,5mm thick, of suitable length duly mounted on FRP bus bar insulators and marked with standard colour coded sleeves / tapes for all outgoing MCCBs - 04 Nos.
(k) LED Pilot Lamp of following colours : (i) RED - 01 No, YELLOW - 01 No, BLUE - 01 No.
(l) Danger Notice Plate -02 Nos
(m) Pannel box made up of CRCA mild steel 3.15mm thick, duly powder coated with busbar and internal wiring all as per CPRI approved (The panel shall not be less than 2.5 Sqm front area) Note : Panel will be manufactured by CPRI approved firm as indicated above. The contractor shall submit drawing of the panels to Engr-in-charge before procurementof LT panel for approval alongwith CPRI approval. Foundation will prepared as per instruction and rate of fondation deemed to be included in the quoted rates. | 1 | Each Job | 4,10,000 ₹4.1 L | 1,51,111 ₹1.5 L |
| 2.00 | Design, supply, erection, testing and commissioning of outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars (32mm x 5mm) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947 in and including providing of one No MCCB of 160 Amps, 4 Pole, 25 KA, 50 Hz 415 Volts .The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including dismantling/taking down of old unserviceable complete all as specified and as directed Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth). | 3 | Each | 24,000 ₹72,000 | 21,000 ₹63,000 |
| 3.00Supply, laying or fixing or passing through GI pipe, HDPE (DWC pipe) commissioning and testing of PVC / XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid separately under relevant items:- | |||||
| 3.01 | (a) 50 Sqmm 3.5 core | 500 | RM | 330 ₹1.6 L | 350 ₹1.8 L |
| 3.02 | (b) 70 Sqmm 3.5 core | 810 | RM | 464 ₹3.8 L | 450 ₹3.6 L |
| 3.03 | (c) 95 Sqmm 3.5 core | 100 | RM | 596 ₹59,600 | 580 ₹58,000 |
| 3.04 | (d) 120 Sqmm 3.5 core | 200 | RM | 725 ₹1.4 L | 725 ₹1.4 L |
| 3.05 | (e) 240 Sqmm 3.5 core | 100 | RM | 1,100 ₹1.1 L | 1,459 ₹1.5 L |
| 4.00 | Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil complete all as directed at site. | 400 | Cum | 120 ₹48,000 | 200 ₹80,000 |
| 5.00 | Excavation in post holes(or similar holes) each n. exc 0.5 cum getting out ,returning filling in and ramming earth or broken rubble mixed with around in layer n.exc.25 cm thick, watering and removing surplus soil to a distance n. exc 50 m and making good surface all complete all as specified and as directed . | 20 | Each | 650 ₹13,000 | 400 ₹8,000 |
Updated dates
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
22 Nov 2025, 6:00 pmClosed
CWE (AF) Jaisalmer
HQ CWE (AF) Jaislmer
REPAIR MAINT IMPROVEMENT OF EXTERNAL ELECTRIC SUPPLY AND ALLIED WORKS AT 3 AFRU UNDER GE AF JAISALMER
2025_MES_736555_1
80373
Open Tender
Electrical and Maintenance Works
90 days
GE (AF) Jaisalmer
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Jaisalmer
₹40,000
29 Dec 2025
23 Oct 2025
24 Nov 2025
23 Oct 2025
22 Nov 2025
8 Nov 2025
Amount
Design, supply, erection, testing and commissioning of outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars (32mm x 5mm) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947 in and including providing of one No MCCB of 160 Amps, 4 Pole, 25 KA, 50 Hz 415 Volts .The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including dismantling/taking down of old unserviceable complete all as specified and as directed Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Supply, laying or fixing or passing through GI pipe, HDPE (DWC pipe) commissioning and testing of PVC / XLPE insulated, armoured heavy duty, electric cable with aluminium conductor, 1100 volts grade of the following cross section area including suitable size lugs including taking out /dismantling of existing cable. Note:- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid separately under relevant items:-
(a) 50 Sqmm 3.5 core
(b) 70 Sqmm 3.5 core
(c) 95 Sqmm 3.5 core
(d) 120 Sqmm 3.5 core
(e) 240 Sqmm 3.5 core
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil complete all as directed at site.
Excavation in post holes(or similar holes) each n. exc 0.5 cum getting out ,returning filling in and ramming earth or broken rubble mixed with around in layer n.exc.25 cm thick, watering and removing surplus soil to a distance n. exc 50 m and making good surface all complete all as specified and as directed .
M&L for tibba Sand cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge.
M& L for Stone patti 40 to 50mm thick rough dressed Jodhpur stone slab cover in trenches for protection of cable 25 to 35cm wide and not less than 60cm in length laid dry abutting each other with gap between adjacent slab not exceeding 10mm over sand cushioning complete all as specified and directed.
Removing excavated material to a distance n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and as directed.
Returning , filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
M& L for Earthing complete with galvanished earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5 deep below normal ground level and connected to galvanished iron earth lead strip 32mmx6mm upto 7.50 metre, by means of GI nuts, bolt, check nuts, washers, thimbles, etc as shown in electrical plate No. 5 SSR Part-I and connection to main switch board or panel and testing on completion including excavation and earth work in any type to soil, returning fitting in and removal of surface spoil to a distance not exceeding 50 metre, PCC chamber (1:3:6) type C-2, charcoal and salt mixed layer 15cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe light grade 20mm bore for watering and 50mm bore GI pipe light grade for earth wire protection fixed with poles with two clamps, made from earth lead strip 32mm x 6mm, bolts, nuts and washers, 80mm thick pre cast RCC cover 1:2:4, type B-1, reinforced with hard drawn steel wire fabric weighing not less than 4 Kg/Sqm in lieu of CI cover etc including taking down old earth complete all as specified and directed. Note : (i) The unit rate shall be deemed to included for Test point, 32mmx6mm GI strip from top of the earth plate upto 7.50m above ground level. In case, GI protection pipe required is less than 7.50m, no price adjustment shall be made. (ii) PCC pit shall be provided at least 500mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipes and fittings, junctions, elbow etc shall be deemed to be included in the unit rate quoted by the contractor.
M&L in repair galvaniased iron (GI) strip 32mm x 6 mm buried in ground/ fixed on wall/ Passed through pipe/wall incuding connected by means of exothermic brazing, nuts and bolts where required complete all as specified and directed
Surface excavation and spreading of new aggreagate of size 40mm evenly inside the transformer yard area, and remove the all debris, hard soil upto a depth of 10cm manually without causing damage to the LT/HT under ground cables of any size and in the presence of under ground cable loop carefully clearing the area with out using excavating tools like crow bar, spades, showel etc and depositing excavated earth to a distance not exceeding 50m complete all as specified and directed.
M&L for PCC (1:4:8) Type D-2 (using 40mm graded stone aggregate) as in foundations filling and mass concrete complete all as specified and directed.
M&L for PCC (1:2:4) Type B-2 (using 20mm graded stone aggregate) as in foundations filling and mass concrete complete all as specified and directed.
M&L for MCCB 3 pole 100 Amps rupturing capacity 16 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
M&L for MCCB 4 pole 160 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
M&L for MCCB 4 pole 200 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
M&L for MCCB 4 pole 250 Amps rupturing capacity 36 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
M&L for MCCB 4 pole 400 Amps rupturing capacity 36 KA with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
M&L for MCCB 4 pole 630 Amps rupturing capacity 50 KA, with connecting links on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed.
Cutting of black top cover of existing road upto 0.6 mtr depth and upto 45cm wide for laying of UG cable and pipe line, refilling and making good after laying UG cable and pipe line with PCC 1:3:6 upto 30cm from top of the road surface complete all as specified and directed
M&L for Cable jointing kit for 1100 Volts grade LT cable for straight through heat shrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size above 25 sqmm 3.5 core to 120 sqmm 3.5 core including dismantling & taking out old unserviceable jointing kit complete all as specified and directed .
Preperation of surface of RCC LT poles and M&L for painting with one coat synthetic enamel paint upto 1.5m height in blue and white colour alternate strips each of 30cm wide, and making top strip of 30cm wide with signaling red colour complete all as specified and directed .
M&L for painting to steel tubular pole/Rail Pole, swan neck pole of LT over head line and all MS clamps, cross arm work on poles with one coat of superior aluminium paint including necessary preparation of surfaces and painting of alternate strip with black and blue for LT and Black and red for HT, synthetic enamelled paint strip 05 Nos each of 30 cm height up to 1.5mtr above PCC benching/coping complete all as specified and directed
Relaying LT cable after, jointing or necessary repair work and testing XLPE insulated PVC outer seathed and PVC inner sheath, galvanised steel strips armoured, and reconnecting the cable from over head line and panel suitable for rated voltage of 1100 Volts grade 25 sqmm to 240 sqmm 4/3.5 Core and laid in treches/ducts/pipe or on read/pole all as required and directed at site. Note: Excavation and earth work and joints will be measured and paid seprately
M&L for change over switch 315 Amps ON load in sheet enclosure four pole to be fixed on wall with FI 32X6mm, nuts, bolts, washers etc. fixed in repair complete with all electric connection complete all as specified and directed.
M&L for change over switch 200 Amps ON load in sheet enclosure four pole to be fixed on wall with FI 32X6mm, nuts, bolts, washers etc. fixed in repair complete with all electric connection complete all as specified and directed.
M&L for GI powder coated perforated type cable tray 14 SWG, (2mm thick) of width 150mm and height 50mm with necessary coupler plate and cable tray cover where required with PVC tie for fixing of cable including taking down old unserviceable existing compete all as specified and directed.
M&L for GI powder coated perforated type cable tray 14 SWG, (2mm thick) of width 300mm and height 50mm with necessary coupler plate and cable tray cover where required with PVC tie for fixing of cable including taking down old unserviceable existing compete all as specified and directed.
M&L for GI powder coated perforated type cable tray 14 SWG, (2mm thick) of width 450mm and height 50mm with necessary coupler plate and cable tray cover where required with PVC tie for fixing of cable including taking down old unserviceable existing compete all as specified and directed.
Scrubbing of existing paints of existing LT panel board/Bus Bar chambers where rusted, LT feeder Pillar boxes, LT bus bar chamber paints of any specification and removing old paints and preparation of surfaces for painting complete and M&L for painting of LT Panels, LT Feeder pillar boxes, LT bus bar chambers internaly and externaly with one coat of superior quality smoke grey paint to achieve fine finishing complete all as specified and directed .
Scrubbing of existing paints of existing voltage stabilizer of any type and size where rusted, and removing old paints and preparation of surfaces for painting complete and M&L for painting of servo voltage stabilizer externaly with one coat of superior quality smoke grey paint to achieve fine finishing complete all as specified and directed
Supply only servo torque motor complete suitable for upto75 KVA servo voltage stablizer . Make Vintec Electronic or equivalent
Supply only Electronic Sensing transformer. Make vintec electronic or equivalent
Supply only Indicators of RYB of suitable size upto the capacity upto75 KVA voltage stabilizer complete all as specified and as directed by Engr-in-charge. Make Vintec electronic or equivalent
Supply only Electronic sensing card ( PCB) suitable for servo voltage stabilizers. Make - Vintek Electronics or equivalent
Supply only Dimmerstate (Variac) suitable for servo voltage stabilizers of capacity upto75 KVA complete. Make- Vintec electronic or equivalent
Supply only copper winding conductor for servo voltage stabilizer of capacity up to 75 KVA complete with insulation, varnishing by vaccum impregnation and baking of coil assembly, etc complete all as specified & directed by the EIC
Supply and fixing of nature switch smart timer based Automatic street light control panel. The panel should be suitable enough to take single phase load of 10 KW with incoming-ougoing MCBs of 63 Amps and Contactors & Circuit wiring (Copper) of 16 Sqmm. Nature switch timer smart timer should be maintannace -free in design and settings accessible via a mobile app )with bluetooth connectivity). The mobile App should allow users to customize the ON & Off timing based on nature light (Sensor), Local Sunset/Sunrise (AStro) and time. The Mobile App should also have facility to set input Voltage range. The smart timer along with suitable Power Contactors and incoming-outgoing MCBs should be enclosed in a pole/wall mountable Rust proof, electric shock proof, termite proof and FR grade SMC enclosure confirming to IP66. The circuit should also have provision for manual operartion (Sensor By pass option) , contolling etc. Model No : Navdeep-66-10KW1P
NAGEL ENTERPRISES (BID ID -3471418)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Document
0.43 MB
BOQ
BOQ • 0.37 MB
Tender Documents
Tender Documents • 1.18 MB
Download all tender documents and submit your bid