| 1 | L1₹16.0 LAccepted-AOC BOOTH NO 119 SECTOR 9 PANCHKULA 134109 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134109 | L1 | Accepted-AOC Being Lowest Bidder | |
| 2 | L2₹17.9 L+₹1.9 L (11.8%)Rejected-AOC | L2 | Rejected-AOC Other Than Lowest Bidder |
Tender Value
₹14.4 L
EMD Value
₹28,800
Closing Date
7 Jan 2022, 6:00 pmClosed
CWE, Shimla Hills Jutogh
CWE, Shimla Hills Jutogh, Jutogh Cantt, Shimla-171008
PROVN OF TROLLEY MOUNTED TRANSFORMER OF CAPACITY 400 KVA AT SUBATHU UNDER GE KASAULI
2021_MES_484762_2
CA NO. CWE/KAS-32 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Subathu
Please refer Tender documents
6 documents required · 6 mandatory
₹500
GE Kasauli
₹28,800
11 Jan 2022
11 Dec 2021
10 Jan 2022
11 Dec 2021
7 Jan 2022
24 Dec 2021
Amount
Supply, install, testing and commissioning of Outdoor Non-sealed type Mineral oil immersed Distribution Transformer ISI marked (IS-1180:2014) Step up/Step down, Copper wound, having Primary side voltage at 11 KV, 3-Phase and secondary side having 3-Phase and neutral (4 wire system ), 433 Volts at 50 Hz frequency of Capacity 400 KVA with following specifications :-
No load Voltage ratio : 11000/433-250 Volts
No of Phase - Three
Type of Cooling - ONAN
Frequency - 50 c/s
Vector Group - DYn11
Indoor or Outdoor type : Outdoor type
Application of Transformer : Distribution
Basic insulation level : 75 KV
No of Tap position on HV Side(offload & manual operated) : 7
Tapping range : +5% to -10% in steps of 2.5%
Two earthing terminals for body earthing and two additional for neutral brought out on a bushing
Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature
Rating and terminal marking plates
Lifting lugs
Dehydrating Breather with dehydrating agent
Cable end box - HV & LV side(both with Brass cable glands)
Percentage Impedance - 4.5%
Oil temperature indicator and winding temperature indicator
Arcing horns/Lightening arrestor for HT side - 03 Nos
Thermometer pocket with cap
Conservator with drain plug and a filling hole(1¼" normal size thread) with cover
Drain-cum-sampling valve (¾" nominal size thread, IS 554) preferably steel with plug for three phase transformer.
Pressure relief device or explosion vent.
One filter valve on the upper side of tank
Unidirectional flat rollers
Inspection hole
Buchholz relay
First filling of transformer oil of specifications as per IS-335
Maximum losses of transformer shall be as per energy efficiency level-3 as per IS-1180 (Part-I):2014
Altitude of installation - 1750m above MSL Note : 1. The transformer shall be ISI marked with energy efficiency level -3 category and having BEE certification. Routine and type test cerificate(as per IS-2026) shall be produced by the tenderer. Certification from BIS and BEE shall be produced against the manufacturer 2. Any subsequent amendment to IS or Govt notification on the subject shall be assumed as implemented in the schedule mentioned above on the date of supply. 3. Pre commissioning test of transformer shall be carried out by SEI from HQ CE (WC) and the unit rate quoted shall deemed to include cost of the same. 4. Drawing for the transformer shall be got approved by the GE before placing order by contractor.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3½ core complete all as specified and directed.
Trolley 4 wheeler size 3658(L) mm x 1829(W) mm x 1900(H) mm , of wieght approx 1760 kg with following specifications & Details :- Main chassis :- Made of M.S. channel 150 x 75 mm. Side Runner :- Side runner and cross members channel made of MS 100 x 50 mm, and 100 x 50 mm. Leaf springs :- 4 Nos Leaf springs size 70x11x900 mm, Consist 13 Leaf each. Axle :- 2 Nos Axles made of 75 x 75 mm M.S Square with Water Proof Steel Forged Hubs and Taper Roller Bearings. Turn-Table :- 2 Nos Angle Rings 50x6 mm with Male Female Pipe Bushes with Locking Bolt 36 mm. Draw-Bar :- Triangular Draw-Bar, Detachable Type made of M.S Channel 75 x 40 mm. Towing Arrangement :- Spring Loaded Steel Towing Hook of 36 mm round. Floor Sheet :- Floor fully covered with 6 mm thick MS sheet.
Landing Jacks :- 4 Nos Landing Jacks fitted on four corners of the Trailer. Roof : Covered with GI sheet & the height,400 mm from the side wall to top of the sheet with M.S channel (50x6 mm). Carrying capacity : 5 Ton ( Approx.) Isolator, Fuse mounting: 63x63x4 mm Box pipe, 50x50x5 mm M.S plate, 75x38 mm C channel clamp for transformer. Side wall :- Side wall height 1900 mm, openable with three sides, made of MS welded wire Mesh 4 mm and Angle 35 x 5 mm, supported with 40 x 5 mm MS flat, with danger notice board 11 kV HT ,Suitable enclosure with four pole 63 Amp MCCB be provided on LV side. Tyre Assembly :- 4 Nos New Tyres Assembly size 7.50 x 16 Nylon any Std. Make available CEAT, Apollo, JK, Birla. Finishing & Painting :- Finishing with Grinding and one coat Red-Oxide (Primer) and 2 coats of Super Synthetic Enamel Paint. (Any Colour ). Fittings :- Necessary Fittings like 4 Nos Light Reflectors, 2 Nos Number Plates.
Note : (I) Item rate shall be inclusive of connection of LV side of transformer with MCCB 630 Amp, 4 pole 415 Volts, rupturing capacity 50 KA Adjustable thermal fixed magnetic MCCB including fixing arrangements & suitable MS enclosure, by single core to run of 120 Sqmm copper cable having length 40 RM for each phase and neutral complete with lugs nuts volt ect. (ii) All four sides of trolley cage be provided with danger notice plate for 11 KV HT supply with standard skull and bone sign. The rate for the same will be inclusive in the quoted rate. (iii) All side of cage and door/roof top should be detachable type for easy dismantling during maint of transformer. (iv) Items rate will be inclusive of mounting the transformer on trolley with fixture and any T&P and labour reqd be provided by the contractor. (v) Before placing order of trolley , drawing of the same should be approved by GE.
Cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3.5 core XLPE, armoured, Al conductor cable of size 400 Sqmm complete all as specified and directed
Earth continuity conductor or main earthing lead made of PVC insulated single core copper multistranded cable 1100 volts grade 25sqmm of 15 RM long with copper lugs at both and with provision of nut bolts and washer complete as specified and directed. (For transformer body and neutral earthing from existing earth point).
Supply & laying insulated rubber mat size 1mx2mx19mm (WxLXT) suitable for electric supply 11000 Volt as per specified by Engg.-in-charge.
Supply & laying insulated rubber mat size 1mx2mx10mm(WxLXT) suitbale for electric supply 1100 Volt as per specified by Engg.-in-charge.
M/s Shiksha Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .