SE, EUDC-I, NOIDA
33/11 KV SUBSTATION, SECTOR-18 FIRST FLOOR, OPPOSITE SAB MALL, NOIDA
CAPACITY ENHANCEMENT LT SUBSTATION AT VARIOUS PLACES UNDER EUDD 5 NOIDA
2023_PVVNL_798318_1
08/EUDC-I/2023-24/NOIDA (WORKS) (SHORT TERM)
Open Tender
Electrical Works
Item Rate
IN AREA OF EUDSD-III/VIII/IX, NOIDA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
EE, EUDD-V, NOIDA
₹5,540
10 May 2023
21 Apr 2023
8 May 2023
21 Apr 2023
8 May 2023
21 Apr 2023
Amount
FOLLOWING WORK CAPACITY ENHANCEMENT OF 250 KVA T/F BY 400 KVA T/F AT 06 NOS. PLACES (A-32 SECTOR-12, Z-41 SECTOR-12, G-38 SECTOR-25, A-93 SECTOR-26, MANGE RAM BISANPURA & AT NEAR BARAT GHAR VILLAGE-GEJHA) IN AREA OF EUDSD-III/VIII/IX, NOIDA :-
Dismantling of 250 KVA T/F (Old & Used) from work site plinth with opening of jumper / connection etc.
Carriage of after dismantled 250 KVA T/F (old & used) from works site to JE store / central store & proper stacking with loading & unloading.
Safe loading and carriage of 400 KVA Transformer from ESC Noida/Sahibabad/ Ghaziabad /Any other ESC of Meerut Discom to JE Store and from JE store to site of work including loading and unloading at both ends.
Mounting, installation of 400 KVA Transformer on existing Plinth with refixing of jumper / connection etc., alongwith double earthing of the same, complete in all respect as per RESPO schedule.
Providing and installation of LT ACB 400 Amp. with cabinet / structure (Make L&T, Schneider, ABB, Hevell's) A-93 SECTOR-26 as per following specification with all relevant certificate :-
400 amp. 03 pole fixed manual ACB.
Red/yellow/blue light indication
ON & OFF Indication
Amp., Volt meter& energy meter digital
Metering C.T 400/5A,
Panel fabrication of size 1250mm x 900mm x 600 mm made of M.S sheet 14 gauge with powder coating with panel lock and key arrangement.(two nos). and additional locking arrangement seprately including providing hut type shape as per drg.
Fabrication of aluminium bus-bar for each phases
Incoming size 425 mm x 50mmx12 mm (twin)
Out going size 720 mm x 50mm x 12 mm(twin)
Neutral size 900mmx50mmx12 mm.
Fabrication of pannel stand made of M.S Angle of size 900mm x 600mm x 500 mm as per drg.
Assembly of above ACB, Indicators, Meters, Metering CT & bus bar arrangment in the panel, fitting the panel on Stand with nut and bolts with wiring etc. & grouting in ratio 1:4:8 with cement, coarse sand and brick blast.
Providing and fixing of aluminium bus bar of size 300mmx60mmx12 mm on L.T side of T/F.
Making all connections with ACB & Distribution T/F and commissioning the ACB complete in all respect.
PROVIDING AND INSTALLATION OF CHEMICAL EARTHING FOR ACB (WITH ALL MATERIAL AND LABOUR) AFTER INSTALLATION RESISTANCE SHOULD BE LESS THAN ONE OHM. AS PER FOLLOWING (The all material and labour shall be provided by the contractor with 12 month guarantee for resistance value less than one OHM.) :-
Providing of earth elctrode for chemical earthing Pipe in pipe type proper hot deep galvanization dia 50 mm length 3 mtr - 32mm x 6mm terminal connection hole dia 8mm The cavity between the pipe & pipe is filled with conductive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystalline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be galavanized the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of backfill compound each elctrode should be supplied with bags of 25 kg x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested for ACB installed at Above 11/0.4 KV L.T. Substation.
Providing and fixing of GI strip of size 32 mm x 6 mm suitable for ACB installed at above 11/0.4 KV L.T. Substation.
Providing and fixing of PVC Pit covers for above earthing electrode terminals.
Cartage of other line material such as LT PVC Lead 1x400 Sq.mm. (60 Mtrs.) & Eartjong complete set (02 Nos.) etc. from ESC Noida/Sahibabad/Ghaziabad /Any other ESC of Meerut Discom to JE Store and from JE store to site of work including loading and unloading at both ends.
Laying of LT PVC Lead 1x400 Sq.mm. including fixing of all accessories as per RESPO schedule Complete in all respects.
Excavation of earth and driving of M.S. earthing rod of size 20x2500 mm in earth and jointing through G.I wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts etc. as per RESPO schedule Complete in all respects.
Providing and installation of LT ACB 600 Amp. with cabinet / structure (Make L&T, Schneider, ABB, Hevell's) At Near Barat Ghar, Village-Gejha as per following specification with all relevant certificate :-
600 amp. 03 pole fixed manual ACB.
Red/yellow/blue light indication
ON & OFF Indication
Amp., Volt meter& energy meter digital
Metering C.T 600/5A,
Panel fabrication of size 1250mm x 900mm x 600 mm made of M.S sheet 14 gauge with powder coating with panel lock and key arrangement.(two nos). and additional locking arrangement seprately including providing hut type shape as per drg.
Fabrication of aluminium bus-bar for each phases
Incoming size 425 mm x 50mmx12 mm (twin)
Out going size 720 mm x 50mm x 12 mm(twin)
Neutral size 900mmx50mmx12 mm.
Fabrication of pannel stand made of M.S Angle of size 900mm x 600mm x 500 mm as per drg.
Assembly of above ACB, Indicators, Meters, Metering CT & bus bar arrangment in the panel, fitting the panel on Stand with nut and bolts with wiring etc. & grouting in ratio 1:4:8 with cement, coarse sand and brick blast.
Providing and fixing of aluminium bus bar of size 300mmx60mmx12 mm on L.T side of T/F.
Making all connections with ACB & Distribution T/F and commissioning the ACB complete in all respect.
PROVIDING AND INSTALLATION OF CHEMICAL EARTHING FOR 400 KVA TRANSFORMERS (BODY & NEUTRAL) AND ACB (WITH ALL MATERIAL AND LABOUR) AFTER INSTALLATION RESISTANCE SHOULD BE LESS THAN ONE OHM. AS PER FOLLOWING (The all material and labour shall be provided by the contractor with 12 month guarantee for resistance value less than one OHM.) :-
Providing of earth elctrode for chemical earthing Pipe in pipe type proper hot deep galvanization dia 50 mm length 3 mtr - 32mm x 6mm terminal connection hole dia 8mm The cavity between the pipe & pipe is filled with conductive mixture - for hermetically filling inside the cavity i.e. between secondary conductor & primary conductor, crystalline compound is to be injected in the electrode assembly. It is a combination of high conductivity metal alloys, copper & aluminum power, conductive carbon / cement and bonding material etc the electrode should be sealed from both the ends. The outer pipe of the elctrode should be galavanized the characteristics of this compound is highly cnductive, non magnetic & non corrosive in G.I. Including providing of backfill compound each elctrode should be supplied with bags of 25 kg x 2 bfc compound (ground resistance enhancement powder 50 kgs each CPRI tested for 400 KVA distribution t/f & ACB installed at Above 11/0.4 KV L.T. Substation.
Providing and fixing of GI strip of size 32 mm x 6 mm suitable for 400 KVA distribution t/f & ACB installed at Above 11/0.4 KV L.T. Substation.
Providing and fixing of PVC Pit covers for above earthing electrode terminals.
Cartage of other line material such as LT ABC 3x120+1x95+1x16 Sq.mm. (295 Mtrs.), LT Distribution Box 3 Phase (06 Nos.) & LT Lead 1x400 Sq.mm. (60 Mtrs.) etc. from ESC Noida/Sahibabad/Ghaziabad /Any other ESC of Meerut Discom to JE Store and from JE store to site of work including loading and unloading at both ends.
Laying, Lifting and final Binding, Sagging of LT ABC of size 3x120+1x95+1x16 Sq.mm. including fixing of all accessories as per RESPO schedule Complete in all respects.
Laying of LT Lead 1x400 Sq.mm. including fixing of all accessories as per RESPO schedule Complete in all respects.
Fixing of LT Distribution Box 3 Phase complete in all respect.
Vivek Electricals
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .