| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.8 LAccepted-AOC | L1 | Accepted-AOC RATES ARE REASONAVBLE | |
| 2 | L2₹13.3 L+₹33,273.99 (2.57%)Rejected-Finance | L2 | Rejected-Finance HIGHER THAN L1 BIDDER | |
| 3 | L3₹13.7 L+₹80,292.05 (6.21%)Rejected-Finance | L3 | Rejected-Finance HIGHER THAN L1 BIDDER | |
| 4 | L4₹13.8 L+₹87,154.14 (6.74%)Rejected-Finance | L4 | Rejected-Finance HIGHER THAN L1 BIDDER |
Tender Value
Refer Docs
EMD Value
₹24,000
Closing Date
22 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE
HQ 136 WORKS ENGRS
REPAIR REPLACEMENT OF 11 KV HT OVERHEAD AND UNDERGROUND ELECTRIC SUPPLY NETWORK AND CONNECTED ITEMS AT KALIMPONG MIL STN UNDER GE 867 EWS 3rd CALL
2020_MES_374213_3
CWE/136-WE/39 OF 2020-21
Open Tender
Civil Works
Item Rate
182 days
KALIMPONG
Class E, Category b(ii)
8 documents required · 8 mandatory
₹500
GE 867 EWS
₹24,000
Yes
10 Jul 2021
24 Nov 2020
23 Dec 2020
24 Nov 2020
22 Dec 2020
8 Dec 2020
24 Nov 2020 - 1 Dec 2020
60 days
Amount
Excavation in trenches/ foundation in soft/ loose soil not exc. 1.5 metre wide and n'exc. 1.50m deep for stay assembly /pole foundation and getting out including forming bottom surface to required level or slope, complete all as specified and directed by Engineer-in- Charge.
Add to item No.1.00 for each additional 1.5 mtr or part thereof in depth beyond the first 1.5mtr
Returning filling in including spreading, leveling ,and well ramming, in layers not exceeding 25 cm each layer of any kind of Soil as all specified and directed
Removing excavated material in soft/ loose soil n'exc 50 M and depositing where directed at a level n'exc1.5 M above the starting point, complete all as specified and directed.
Material & labour for Trimming of tree branches which touches the HT OH lines and 2.5 Mtr away from centre line of HT oh lines span not exceeding 60 Mtr distance between poles by using neccessory T&P items and depositing the tree branches/leaves at 30 Mtrs away from the site all as specified and directed . Note -Any number of tree branches cut in one span will be measured as one lenght of payment.
Dismantling / Taking down unserviceable /damaged insulator of any size , shape , grade or type from pole and as directed by engineer in charge.
Dismantling / Taking down old unsv stay assembly complete all as specified and as directed by engineer in charge.
Dismantling / Taking up unserviceable damaged Steel tubular poles of any size for reuse within 2 Km (for serviceable Poles) or removing from site of work all as directed and as specified.
Dismantling / Taking down of cross arms of channel or sections etc complete setting aside for reuse (serviceable one) or removing from site of work all as directed and as specified.
Dismantling / Taking down U/S GOD Air Break Switch assembly of any type / size / condition from HT 4 / 2 Pole structures complete all as specified and as directed.
Dismantling / Taking down unsv Galvanized Steel earth wire/ cradle guard any size as directed by Engr-in-charge.
Supply and fix in replacement of cable end joint kit in replacement heat shrinkable suitable (Make: Reychem/Birla /3M/M seal) for 11KV E grade XLPE cable of size 95 sqmm 3.0 core indoor typeall as specified and directed. Note:- Earth work will be measured and paid separately against relevant item all as specified and directed.
Supply and fix in replacement of cable end joint kit in replacement heat shrinkable suitable (Make: Reychem/Birla /3M/M seal) for 11KV E grade XLPE cable of size 120 sqmm 3.0 core outdoor type all as specified and directed. Note:- Earth work will be measured and paid separately against relevant item.
M & L for replacement of cable jointing kit for 11 kV grade (Earthed) HT cable with & including straight through type heat shrinkable jointing kit complete with jointing material and accessories suitable for 50 sqmm to 95 sqmm, 3 core XLPE armoured aluminium conductor cable of complete all as specified and directed. Note : Excavation/earth work will be measured and paid separately.
M & L for replacement of cable jointing kit for 11 kV grade (Earthed) HT cable with & including straight through type heat shrinkable jointing kit complete with jointing material and accessories suitable for 120sqmm to 185sqmm, 3 core XLPE armoured aluminium conductor cable of complete all as specified and directed. Note : Excavation/earth work will be measured and paid separately.
M&L for painting of four pole structure by one coat of aluminium paint including steel structure of 4 pole structure (above planting depth ) 11 meter long steel tubular pole and mild steel work i.e. cross arms, bracing , clamps,with painting Yellow and black strip 30 cm wide up to 1.5 Mtrs height from the copping level etc complete all as directed. Note : Contractor or his authorised representative should take necessary shutdown before painting work and should be present at sited during the work all as specified and directed
M&L for painting of two pole structure by one coat of aluminium paint including steel structure of 2 pole structure (above planting depth ) 11 meter long steel tubular pole and mild steel work i.e. cross arms, bracing , clamps,with painting Yellow and black strip 30 cm wide up to 1.5 Mtrs height from the copping level etc complete all as directed. Note : Contractor or his authorised representative should take necessary shutdown before painting work and should be present at sited during the work all as specified and directed
M&L for painting of steel tubular 11 Mtr Long HT pole , 410-SP-31, vertical complete with cross arms with one coat of aluminium paint after cleaning and preparation of surfaces of poles, cross arms,with painting 30 cm wide Yellow and black strip on poles up to 1.5 mtr high above coping level and numbering with writing letters or figures (Block), height n'exc 10 cm high & letters or figures n'exc 10 Nos for electric HT straight pole , strut pole, 2 pole/4 pole structure complete all as directed. Note : Contractor or his authorised representative should take necessary shutdown before painting work and should be present at sited during the work.
Supply only of new transformer oil all as specified and directed. Make -Power Oil / Castrol for topping up.
Filtration and dehydration of transformer oil to achieve test result as per IE rules with filtration plant all as specified and directed. Note :- a) The filtration of transformer oil of various transformers is to be carried out at different sub stations of Kalimpong mil area and Contractor should check the feasibility how to filter the oil of transformer before coating rate and if any additional pipe or material is required to reach the transformer, cost for the same is deemed to be included. b) The report before filtration and after filtration to be submitted by contractor in the approved format. c) The filtration is to be carried out on line ie without switching off supply. d) oil for topping up will be measured and paid seperately under respective items of Sch 'A'.
Material and labour for dismantling and refixing of existing dismantled copper bus bas to the existing VCB complete all as directed by Engr-in-Charge.
M&L for General Servicing & Testing of 11 KV Indoor Vacuum Circuit Breaker ( Cleaning, oiling, greasing, IR Value check, Electrical and mechanical operation check & adjustment, primary injection of CTs to check the TMS of relay and time coordination ) including checking auxiliary supply and control voltage, physical checking of breakers, epoxy housing, carryout physical verification of any wear and tear in breaker and rectified it, checking fixed and moving contracts, spring charging motor, control circuit & tighten the connections and close or trip coil, clean the breaker compartment through lubricate the breaker, apply grease/ petroleum jelly on required part complete all as directed by Engr-in-Charge.
M&L for General servicing and testing of 11KV PT( Ceaning, IR Value check and Ratio test, 11/0.110 KV complete all as directed by Engr-in-Charge.
Material and labour for fault finding and repair/ replacement of defective control wiring of tripping circuit, closing circuit, potential transformers, ampere meter, voltmeter,current transformers, thermostate & heating element circuits of indoor type 11 KV VCB using with 2.5 sqmm copper flexible PVC insulated wire and suitable size of copper lugs and thimbles and connector all as directed at site by Engr-in-Charge.
Supply and fix in replacement of 11 KV PT dropper sponts complete as required at site all as specified and directed.
Fixing only dismantled spring charging motor for Indoor, 11 KV, VCB, operated on 24/230 volts AC/ DC complete all as specified and directed by EIC.
supply and fixing in repair of LED type indicator lamp (Red/Blue/Yellow) suitable for 110 Volt DC in OCB's/VCB's all as specified and directed.
Supply and fix in replacement of PT dropper ling of 11 KV VCB complete all as directed at site all as specified and directed.
Supply and fix bus bar insulators of 11 KV VCB 130mm long suitable to fix in existing VCB of Schneider make or equivalent all as specified and directed.
Material and labour for replacement of unserviceable tripping/ closing coil as fitted in existing VCB of 24/110 Volt DC Supply suitable for 11 KV VCB all as specified and directed.
Material and labour for painting of 11 KV VCB with super enameled paint after scapping the existing paint complete all as directed by Engr-in-Charge.
Material and labour for repairing of 11 KV VCB trolley shuttering by providing greasing, oiling and replacement of nuts and bolts and repairing of mechnisam of schneider make VCB installed at power house complete all as directed by Engr-in-Charge.
Material and labour for servicing of HT 11 OCB 3 phase Indoor type of capacity 400/630 Amp from elect supply and dismantling of major parts for overhauling the same by providing petrolium jelly, greasing CRC-26 agent and oiling the mechanical moving parts such as moving contact, triping/closing lever and checking the complete tripping/closing system all as directed.
Material and labour for HT 11 KV VCB busbar HT sleaves 80X12mm complete suitable as per existing VCB of Schnieder make or equivalent all as specified and directed.
Note for item 20.00 to 34.00:- Contractor should visit the site to know the exact scope of the job for above item of BOQ before quoting rates. No claim arising out of any error or inaccuracy in understanding the scope of work shall be entertained. The work will be done by the authorised agency of Schneider/Areava.
Earhing complete with galvanized steel earth plate electrode 600X600X6mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to galvanized earth wire 4 mm dia , by means of galvanized iron or steel bolts, nuts, check nuts and washers, and conneced to equipments as directed, including funnel with GI Light grade watering pipe 20 mm bore, wire mesh charcoal and common salt in alternate layers, of 15 cm compacted thickness all around the earth electrode, with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1:2:4 type B1 cover slab reinforced with 8 mm dia reinforced bar 15 cm C/C and earth lead handle protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc.50m and necessary testing complete all as shown on electrical plate no.5 of MES SSR Part-I and as directed by Engineer-in charge .
Material and labour in repair for Tripping buffer of VCB 400A 11 KV complete all as directed by Engr-in- Charge
M & L for switch air break, gang operated triple pole, mechanically operated, mounted on insulators and steel frame with operating mechanism worked from ground level for current rating up to 200A for working pressure 11000 volts complete all as directed by Engrs-In-Charge
M& L stay assembly with accessories as shown in Elect plate No- 01 complete with diameter of rod 20 mm all as specified and directed. Note -loop type insulator , stay clamps , excavation and concrete will be measured and paid separately .
Supply & Fixing in replacement loop type insulator vitreous porcelain white, brown, or green of size 90 X 140 mm clearance of hole 25.5 mm all as specified and directed.
S & F stay strand galvanized steel wire stranded 7 / 4 mm all as specified and directed.
S & F Disc type insulator porcelain vitreous white brown or green as per IS 731-1963 of size 145 mm high and 255 dia ball & socketed type single disc with tension clamp for working pressure 11000 volts all as specified and as directed.
S & F Pin insulator porcelain vitreous white , brown or green insulator as per IS 731`-1963 including one Galvanised MS spindle two galvanized iron nuts, washer etc of 150 mm height and 150 mm dia of 11000 volts grade all as specified and directed.
Restringing of existing HT overhead line including removing the existing binding wire and rebinding with new binding wire after tightning of overhead lines including disconnecting existing jumper and connections and reconnecting after tightning of conductor all as directed by Engr -in -charge .Note -three wire run of conductor in HT lines shall be measured as one lenght for payment purpose .
Supply and fix in repair for closing buffer of VCB 400A 11 KV complete all as directed by Engr-in- Charge
Material and labour for spouts upper and lower both of 11 KV VCB complete all as directed.
Supply and fix of limit switch suitable for 11 KV VCB of Schnieder make complete all as directed by Engr-in-Charge.
Cleaning of area of 11 KV yards, Transformer yard,4/2 poles structures including cutting of shrubs & bushes all as directed at site whenever required at site.
S & F steel tubular swaged pole complete with cast iron base plate, finial taper plug, bots, nuts and screws, pole cap all as specified type 410 SP – 55 ( 11 mtr long ) as per IS 2713-1980 all as specified and as directed.
M & L cross arms, bracings, supports clamps, stay clamps etc fabricated from structural steel sections including nuts, bolts, washers welding bending cold or hot drilling holes for bolts any size of shape and including hooks & clamps for aerial bunch cable as indicated and directed and inclusive of 2 coats of aluminium painting over a coat of red oxide primer all as specified and as directed.
S & F galvanized steel earth wire 4 mm dia for earth continuity conductor all as specified and as directed
M & L for Cradles, hexagonal / rectangular fabricated with galvanized steel wire of 4 mm / 3.15 mm dia including binding, connecting to earth etc complete all as specified and as directed.
M & L for PCC 1 : 3 : 6 type C 2 using 40 mm graded stone aggregate for foundation of pole, stay, plinth of transformer etc all as specified and directed.
M & L for PCC 1 : 2 : 4 type C 2 using 20 mm graded for padestal copping incl necessory form work finished fair using extra cement all as specified and directed.
Material and labour for Fixing only steel tubular swaged pole complete from one location to other location up to 2 km distance at station complete all directed inluding cros arms all as spcified an directed by the Engr-in-Charge.
M&L for Cleaning of old painting surfaces by cleaning agents including removing dirt, dust, oil, grease etc of transformer capacity 75 KVA to 400 KVA at different sub station and providing two coats of synthetic enameled spray paint including writing SM/MES/Machine Numbers and date of painting as directed by engineer- in- charge.
M & L for painting of chain link fencing and cover fencing of transformer (where required) any mesh, size and type by means of two coat of aluminium paint including line wires, MS flat angle and barbed wire by means of two coat of bituminous paint of sub stn including completed all as specified and as directed by Engr-incharge. Note for item 56.00 & 57.00:- Contractor or his authorised representative should take necessary shutdown before painting work and should be present at sited during the work.
S & F in repair of silica Gel from breather of existing transformer of different capacity and make Transformer complete all as specified and as directed.
S & F in replacement heater suitable for indoor 11KV, 3 phase VCB upto 400Amps, 25 KA all as specified and directed.
M & L GI tube 80mm bore, light grade for passing through cables under the floor, along the wall or along the pole of following bore dia and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified.
M & L GI tube 40mm bore, light grade for passing through cables under the floor, along the wall or along the pole of following bore dia and fixed to the poles/walls with suitable size of MS clamps and nut and botls/washers etc including taking down old GI tubing complete all as specified.
Supply and laying. jointing, testing and commissioning HT cable, XLPE insulated, PVC Bedded , galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor conforming to IS:7098, cross sectional area 95 sq mm 3 core 11000 Volt complete all as specified and directed by Engineer in charge.. Make-Havells/Polycab/Mescab, Note- Joint shall be measured & Paid separatly.
Material and labour for repairing of damaged/unserviceable gang operate devices of 11 KV such as male & female contacts, flexible jumpers, MS jumper carrier and back connector plate incl cleaning and greasing of complete contacts of GOD unit, DO fuse unit and reluging of aluminium conductors connected to top & bottom contacts of GOD and DO units incl. welding and threading of operating rod mechanism complete making serviceable all as directed by Engr-in-Charge. Note:- (i) Necessary parts like knife, male/female contacts and aluminium conductor for jumpering will be Measured and paid separately against respective item. (ii) Rates for Welding machine, threading arrangements, grease, jumper, nut bolts tightening and binding wire, Aluminium conductor wire deemed to be included in quoted rates.
Supply only Male contact/moving contact blade complete suitable for 11 KV GOD vertical type all as specified and directed. Make - As existing
Supply only Female contact/fix contact jaw complete suitable for 11 KV GOD vertical type. Make- As existing
Supply only MS flexible jumper carrier complete suitable for 11 KV GOD vertical type all as specified and directed.
Supply only fixed top contact / L contact complete suitable for 11 KV GOD drop out fuse unit vertical type all as specified and directed.
Supply only fixed bottom contact complete suitable for 11 KV GOD drop out fuse unit vertical type all as specified and directed.
M&L for disconnecting the electric connection from over head line with care and removing the faulty step down transformer from two / four pole structure/platform and opening for inspection of Engr-in-Charge, fault finding and minor repairing/ servicing of transformer and repair/ replacement of worn out spares as directed at site and cleaning the transformer body thoroughly with cotton and sand paper and reassembling, refilling of transformer oil, installation the same on its existing position connecting and testing complete 11/0.433 KV transformer of 25 to400 KVA capacity all as specified and directed. Note: 1. The material required for replacement of faulty parts will be measured and paid separately under relevant item. 2. The cost for fault checking/ fault finding, servicing and minor repairing including minor parts is deemed to be included in quoted rate. 3. New transformer oil topping up after repair will be measured and paid separately against relevant item. 4. New items such as HT/LT bush insulators, HT/LT bush rod of brass, rubber gasket will be measured under respective items.
Supply only for replacement of HT 11 KV bush insulator suitable for distribution transformer of any type and of following size all as specified and directed:
(a) Up to 200 KVA,
(b) 250 KVA to 630 KVA
Supply only for replacement of LT bush insulator suitable for distribution transformer of any type and of following size all as specified and directed:
(a) Up to 200 KVA,
(b) 250 KVA to 630 KVA
Supply only for HT bush rod made out of brass with nut bolt and washer suitable for distribution transformer any type of following capacity all as specified and directed:
(a) Up to 200 KVA,
(b) 250 KVA to 630 KVA
Supply only for LT bush rod made out of brass with nut bolt, rubber packing and washer suitable for distribution transformer any type of following capacity all as specified and directed:
(a) Up to 200 KVA,
(b) 250 KVA to 630 KVA
Supply only for replacement of rubber/ cork sheet gasket set complete suitable for transformer of any type of following size all as specified and directed:
(a) Up to 200 KVA,
(b) 250 KVA to 630 KVA
M & L danger notice plate of 1.6 mm thick mild steel sheet vitres enameled , white with letter ( in English & Hindi ) Figured & conversional “Skull & Bone” in signal red colour & fixed with MS clamps bolt & nuts of approved size 25 X 20 cm for HT 11 KV, including taking out old unserviceable rusted out danger plate all as specified and directed
Note:- The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
SANJAY SAW MILL
MS MAYA PRAKASH GOEL AND SONS
GEETA CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .