| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹23.2 CrAccepted-AOC | ₹23.2 Cr | 1 | Accepted-AOC L-1 |
| 2 | 2₹23.4 CrRejected-Finance HARSH ANAND YEVALEKAR MALA COLLEGE ROAD NASHIK 422005 | NASHIK | NASHIK | MAHARASHTRA | 422005 | ₹23.4 Cr | 2 | Rejected-Finance H |
| 3 | 3₹23.5 CrRejected-Finance PLOT NO 3 YOGANAND CO OP HOUSING SOCIETY BEHIND BIJAN HOSPITAL NEAR MALPANNI HOSPITAL VIGHA MALA CANADA CORNER COLLEGE ROAD NASHIK | NASHIK | NASHIK | MAHARASHTRA | ₹23.5 Cr | 3 | Rejected-Finance H |
| 4 | Rejected-Technical | - | - | Rejected-Technical all techincal document are Not clae |
| 5 | Rejected-Technical OFFICE NO 515 PLOT NO 194 NMS ICON SECTOR 19 ULWE NAVI MUMBAI MAHARASHTRA 410206 | NAVI MUMBAI | THANE | MAHARASHTRA | 410206 | - | - | Rejected-Technical all techincal document are Not claer |
Tender Value
₹22.3 Cr
EMD Value
₹11.2 L
Closing Date
4 Jan 2024, 6:00 pmClosed
Executive Engineer Public Works Division Sangamner
Office of the Executive Engineer Public Works Division Sangamner
Construction of 100 Bedded Sub District Hospital At. Kopargan Tal.Kopargaon Dist.Ahmednagar
2023_PWR_972111_1
PWD SGM/ Notice No.37 for 2023-2024-1
Open Tender
Civil Works - Buildings
720 days
TAL.KOPARGAON
Please refer Tender documents.
4 documents required · 4 mandatory
₹3,540
₹11.2 L
Chief Engineer P.W.Region Nashik
22 Mar 2024
21 Dec 2023
8 Jan 2024
21 Dec 2023
4 Jan 2024
21 Dec 2023
29 Dec 2023
Amount
(A) Work Portion Excavation for roadway in earth, soil of all sorts, sand, gravel or soft murum including dressing section to the required grade, camber and side slopes and conveying the excavated materials with all lifts upto a lead of 50 metre and spreading for embankment or stacking as directed.
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 metre beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting excetra complete. (Lift upto 1.5 metre.) By Mechanical Means
Pump House and Sump Well
Excavation for foundation in hard murum including removing the excavated material upto distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting excetra complete. (Lift upto 1.50 metre) By Mechanical Means
Pump House and Sump Well
Filling in plinth and floors with approved excavated material in 15 centimetre. to 20 centimetre. Layers including watering and compacting excetra complete.
Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 centimetre to 20 centimetre including watering and compaction excetra complete.
Pump House and Sump Well
Conveying materials obtained from road cutting including all lifts, laying in layers of 20 centimetre to 30 centimetre breaking clods, dressing to the required lines, curves, grades and section, watering and compacting to not less than 97% of standard Proctor density for a lead of over 50. to 300 metre. inclusive from the site of excavation to the site of deposition as directed.
Pump House and Sump Well
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the bottom surface and sides of excavation at the rate of 5 litres of emulsion concentrate of 1.0 percent of chlorophyrifos per square meter of surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) treatment by treating the backfill in immediate contact with foundation at the rate of 5 litres of emulsion concentrate of 1.0 percent of clorophyrifos per One Square Metre of vertical surface area covering 10 years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-II) by treating the top surface of plinth filling at the rate of 5 litres of emulsion concentrate at 1.0 percent of clorophyrifos per One Square Metre of surface area covering ten years guarantee on bond paper.
Providing preconstructional antitermite treatment as per I.S. 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 cement morter diametre about 30 -60 cm deep at 15 centimetre center to center as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper.
Providing soling using 80 millimetre size trap metal in 15 centimetre layer including filling voids with Crushed sand/grit, ramming, watering exctra complete.
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete in M-10 of trap/ granite/ quartzite/ gneiss metal for foundation and bedding including bailing out water, Steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing if required and curing complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for bed blocks, foundation blocks and such other items including bailing out water, Steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing excetra complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.), with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-15 of trap/ granite /quartzite/ gneiss metal for coping to plinth or parapet, moulded or chamfered as per drawing or as directed including steel centering, plywood/ steel formwork compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing excetra complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin excetra (Wooden centering will not be allowed.) With fine aggregate (Crushed sand VSI Grade)
Providing and laying in situ /Ready Mix cement concrete M-25 of trap / granite /quartzite/ gneiss metal for Reinforced cement concrete work in foundations like raft, strip foundations, grillage and footings of Reinforced cement concrete columns and steel stanchions excetra including bailing out water, Steel centering formwork, laying/pumping cover blocks, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) excetra complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite /quartzite/ gneiss metal for Reinforced cement concrete columns as per detailed designs and drawing or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite/quartzite/ gneiss metal for Reinforced cement concrete beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite / quartzite/ gneiss metal for Reinforced cement concrete slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing excetra complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mixcement concrete M-25 of trap/ granite/ quartzite/ gneiss metal for Reinforced cement concrete chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite / quartzite / gneiss metal for Reinforced cement concrete canopy as per detailed designs and drawings including steel centering, formwork, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing etc. complete (excluding reinforcement), with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for Reinforced cement concrete pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting , curing , finishing and rougheningthem if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Pump House and Sump Well
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / quartzite/granite /gneiss metal for Reinforced cement concrete Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with cement morter 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / granite/gneiss / quartzite metal for Reinforced cement concrete fins of required thickness in position as shown on the drawings or as directed by Engineer-in-charge including steel centering, plywood / steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with cement morter 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement, including cover block) Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) excetra complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for Reinforced cement concrete pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches excetra as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete.
First Floor
Second Floor
Pump House and Sump Well
Providing and fixing in position after hoisting, precast 1:2 cement mortar reinforced jali 50 millimetre thick with 3 mm diameter mild steel bar reinforcement, of approved design on both side, fixing in cement mortar 1:3 and curing excetra complete
First Floor
Second Floor
Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees excetra as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces excetra and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade excetra complete.
Providing expansion joints in Reinforced cement concrete framed structure (interior column) with plain premoulded filler 25 millimetre thick including fixing teak wood battens on both faces and finishing as directed excetra Complete.
First Floor
Second Floor
Providing expansion joints in Reinforced cement concrete framed structure (exterior Columns) with plain premoulded filler 25 millimetre thick and 3 millimetre thick alluminium plate, hold fast, fixing teak wood battens on internal face, finishing excetra complete as directed.
First Floor
Second Floor
Providing expansion joints in Reinforced cement concrete framed structure (at floor level) with premoulded filler 25 millimetre thick and 3 millimetre thick aluminium plate as required, bitumen poured filler and fixing teak wood battens on rear faces excetra complete as directed.
First Floor
Second Floor
Providing expansion joints in Reinforced cement concrete framed structure (at terrace level) with premoulded filler 25 millimetre thick and 3 millimetre thick aluminium plate as required, bituminous poured filler, fixing lead, flashing on upper side and teak wood battens on inner face finishing excetra Complete as directed.
Providing fly ash brick masonry with conventional / I.S. type fly ash bricks in cement morter 1:6 in foundation and plinth including bailing out water manually striking joints, racking out joints watering and scaffolding excetra complete.
Providing fly ash brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding excetra Complete
First Floor
Second Floor
Pump House and Sump Well
Providing Second class fly ash brick masonry with conventional / I.S. type bricks in cement mortar 1:4 in half brick thick wall including mild steel longitudinal reinforcement of two bars of 6 millimetre diameter / two hoop iron strips 25 millimetre x 1.60 millimetre at every third course, properly bent and bounded at ends scaffolding raking out joints and watering excetra complete.
First Floor
Second Floor
Providing cement based water proofing treatment to terraces (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in cement morter 1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with cement morter 1:3 admixed with approved water proofing compound and finally top finishing with average 20 mm. thick layers of same mortar added with jute fiber at 1Kilogramper bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300 x 300 millimetre making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test excetra complete.
Gound Floor
First Floor
Providing water proof bedding for flooring of Bath and water closet 25 millimetre thick in cement morter 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test excetra complete.
First Floor
Providing and applying two coats of High Albedo paint having minimum Solar Reflective Index (SRI) 108 (with solar reflectance and thermal emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively, VOC less than 10 cc/gm. The coating thickness and the methodology of application shall strctly as per manufacturer's specifitions and as approved by engineer in charge. Surface preparation includes cleaning with metal wire brush to remove all dust, fungus etc, washing with water all complete.The contractor shall give guarantee for the performance of SRI and also the durabitity of coating, all complete as per direction of Engineer - in- incharge.
Second Floor
Providing internal cement plaster 12 millimetre thick in single coat in cement mortar 1:5 without neeru finish to concrete or brick surfaces, in all positions including scaffolding and curing excetra complete.
First Floor
Second Floor
Pump House and Sump Well
Providing internal cement plaster 20 millimetre thick in Single coats in cement mortar 1:5 without neeru finish, to concrete, brick surface, in all positions including scaffolding and curing excetra complete
First Floor
Second Floor
Pump House and Sump Well
Providing and applying plaster / wall punning with plaster of paris ( with plaster of paris material) in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding excetra .complete.
First Floor
Second Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 millimetre thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 millimetre thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding excetra complete.
First Floor
Second Floor
Pump House and Sump Well
Providing fine cement finish 1.5 millimetre thick over green plaster surface including scaffolding curing excetra complete
Pump House and Sump Well
Providing patti/ band 75 millimetre wide on plastered surface 12 millimetre to 15 millimetre thick in cement morter 1:3 line and level including neat finishing scaffolding curing excetra complete.
First Floor
Second Floor
Providing patti/ band 100 millimetre wide on plastered surface 12 millimetre to 15 millimetre thick in cement morter 1:3 line and level including neat finishing scaffolding curing excetra complete.
First Floor
Second Floor
Providing patti/ band 150 millimetre wide on plastered surface 12 millimetre to 15 millimetre thick in cement morter 1:3 line and level including neat finishing scaffolding curing excetra complete.
First Floor
Second Floor
Providing and fixing chicken mesh of 22 gauge, with about 30 centimetre width at the junction of Reinforced cement concrete members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete / Brunt Brick.masonry and or tying by binding wire excetra complete.
First Floor
Second Floor
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, excetra complete.
First Floor
Second Floor
Pump House and Sump Well
Providing and fixing false ceiling with eco-friendly light-weight calcium silicate tiles of spintone surface texture aerolite make or equivalent of size 595 x 595 millimetre having 15 millimetre thick densified micro look edge and 100% humidity resistance incombustible as per BS 46part IV and thermal conductivity 0.043 w/m 0 KC and NRC 0.50 placed in true horizontal level suspended grid of size 600x600mm made from hot dipped galvanised iron steel sections ion silhouette profile, rotary stitched double webbed white with 6mm reveal profile (white/black), wherein, main T runner of size 42x14 millimetre between main tee 600 millimetre center-tocenter and secondary cross T of size 33x14x0.43 millimetre thick of length 600 millimetre long spaced inter-locked at middle of the first crossed T in each panel to form grid of 1200 x600 millimetre resting on periphery wall Profile wall section 19mm (7+7) x 19x0.40 thicknesses and laying false ceiling for services like diffusers grills including cutting, making opening for light fittings, fixtures, , smoke detectors excetra wherever required. Main T runners suspended from ceiling with using G.I. soffit cleats of size 25x35x1.6 millimetre of required length fixed to the ceiling with 6 millimetre diameter and 50 millimetre long dash fastener, 4 millimetre diameter galvanised iron adjustable rods with powder- coated/good quality galvanised iron level adjustment clips of 35x35x0.8 millimetre spaced at1200, center-to- center along main T all complete at all heights as per the specifications, drawings and as per
First Floor
Second Floor
Providing groove to required size at specified location as directed by Engineer, at junction of brick masonry wall and Reinforced cement concrete beams or Column, at junction of composite masonry, including scaffolding, finishing, curing excetra complete.
First Floor
Second Floor
Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 millimetre to 605 millimetre x 590 millimetre to 605 millimetre of 8 to 10 millimetre thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing excetra complete.
First Floor
Second Floor
Pump House and Sump Well
Providing and laying vitrified mirror / glossy finish tiles having size 590 millimetre to 605 millimetre x 590 millimetre to 605 millimetre of 8 to 10 millimetre thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and clearing excetra complete
First Floor
Second Floor
Pump House and Sump Well
Providing and fixing heavy duty inter locking concrete Coloured paving blocks of 80 millimetre thickness of having a strength of 300 Kilogram/ square centimetre. of approved quality and shape on a bed of crushed sand of 25 to 30 millimetre thick including skirting joints and cleaning excetra complete
Providing and laying ceramic tiles having size 30 centimetre x 45 centimetre confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing excetra complete.
First Floor
Second Floor
Providing and laying Antiskid Ceramic tiles of approved quality of size 30 centimetre x 30 centimetre and confirming to IS 15622-2006 (Group-B IIA) for antiskid flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing excetra complete.
First Floor
Second Floor
Providing and laying machine cut machine Polished Kota stone flooring 25 millimetre to 30 millimetre thick and required width in plain/ diamond pattern on bed of 1:6 cement morter. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning excetra complete.
First Floor
Providing Mirror polishing to Kota Stone including using all necessary stones and equipments cleaning, washing excetra complete. For Flooring
First Floor
Providing and laying machine cut machine polished machine cut Kota stone slabs 20 to 25 millimetre thick for treads and risers of steps and staircases, with rounded nosing for the treads on a bed of 1:4 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning excetra complete.
Providing and laying in position flooring of telephone black / Amba White / Cat bary brown / Ruby red / Ocean Brown granite stone of approved shade and size 18 millimetre to 20 millimetre thick on bed 1:6 cement mortar including cement floats striking joints, pointing in cement morter 1:3 curing and cleaning excetra complete.
First Floor
Providing and fixing machine cut machine polished 18 millimetre to 20 millimetre thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning excetra complete.
First Floor
Second Floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 millimetre thick for door frame/ dado/ window boxing etc. On cement morter 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, excetra complete.
First Floor
Second Floor
Pump House and Sump Well
Providing and laying chequered tiles of approved quality of size 30 centimetre x 30 centimetre confirming to corresponding I.S. for flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing excetra complete.
First Floor
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 millimetre x 450 millimetre size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 millimetre thick supports with kadappah top 35 to 40 millimetre thick and polished granite 16 to 20 millimetre top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 centimetre height and top granite of 75 x 40 centimetre including cutting, opening for sink of required size in kadappah as well as granite excetra complete. (Platform top size 5.00 metre x 0.60 metre and height is 0.75 metre)
Providing and applying priming coat on concrete/ masonary/ Asbestos Cement plastered surfaces including scaffolding if necessary, preparing the surface by thoroughly cleaning oil, grease, dirt and other foreign matter and sand papering as required excetra complete.
First Floor
Second Floor
Providing and applying washable oil-bound distemper of approved colour and shade to old and new surfaces in two coats including scaffolding, preparing the surfaces. (excluding the primer coat.) excetra complete.
First Floor
Second Floor
Providing and applying 2 coats of 100% Pure acrylic low VOC and APEO and HCHO free water based paint of approved colour that belongs to class 1 flame spread resistance of approved make Paint should provide durable and long lasting silk finish with a high crack tolerance of upto 1 millimetre Paint should have an oustanding washability with high resistance to wide range of bacteria and fungus. Paint has to be applied on smooth and uniform surface prepared by an acrylic copolymer low VOC and Odour putty. This surface should be primed with water based low VOC Primer. The work activity should cover all aspects of applying paints from surface preparation as directed by Engineer in charge.
First Floor
Second Floor
Providing and applying 2 Coats of 100% Pure acrylic water based paint with special heat reflectance property to withstand the harsh climate for period of atleast 10 years of approved make. Paint system should provide durable and long lasting finish with DFT of min 90 microns and should protect against concrete carbonation with R value of minimum 600 and equivalent concrete layer thickness value of min 150 cm. Paint should have breathability property and should be able to cover hairline cracks in the surface upto 0.5mm The paint has to be applied on a coat of high quality acrylic copolymer based alkali resistant primer with excellent penetrating properties including cleaning, with all leads and lifts at all levels etc complete, as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing frame with / without ventilator of size as specified with Country cut teak wood for doors and windows including chamfering, rounding, rebating, iron holdfast of size 300 millimetre x 40 millimetre x 5 millimetre with oil painting, excetra complete
Providing and fixing Country teak wood Four leaf paneled shutters, 35 millimetre thick style and rail and 25 millimetre thick panels without ventilator as per detailed drawing excluding the door frame, stainless steel fixtures and fastening and finishing the wood work with oil painting three coats complete
Providing and fixing 34 millimetre thick moulded door shutter consisting of solid core single leaf flush door of 30 millimetre thickness lipped with 15 millimetre ( 5 millimetre x 3) thick x 30 millimetre width on one style and top rail and 10 millimetre (5 millimetre x 2) thick x 30 millimetre width on other style and bottom rails. The inner panels laminated with 2 millimetre thick termite proof, water proof and fire resistant moulded PVC sheet with 2,4,6 design in different plain and /or prelim colours on one side after routing the moulded design on flush doors and 2 millimetre plain and /or pre lam PVC on other side using rubber adhesive on flush door and solvent cement adhesive on the PVC lipping etc. as per direction of Engineer in charge and manufacturers specification and drawing excetra complete.
First Floor
Second Floor
Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 millimetre x 1.22 millimetre box type, 5 millimetre thick sheet glass louvers, of approved quality excetraa complete.
First Floor
Second Floor
Providing and Fixing 30 millimetre thick BOTH SIDE PRELAMINATED SOLID PANEL PVC DOOR SHUTTER consisting of frame made out of mild steel tubes of 19 guage thickness and, size 19 x 19 millimetre for styles and 15 x15 millimetre for the top and bottom rails, mild steel frame shall have a coat of metel primer of approved make and manufacture. mild steel frame shall be covered with heat mouled PVC 'C' channel made from 5 millimetre (+/0.25) thick prelaminated sheet of density 600 Kilogram/cbm ,of size 30 millimetre thickness 70 millimetre width out of which 50 millimetre shall be flat and 20 millimetre shall be tapered in 45? angle on either side forming stiles ; and 5 millimetre thick ,95 millimetre wide PVC sheet out of which 75 millimetre shall be falt and 20 millimetre shall be tapered in 45 on the inner side to form top and bottom rail and 115 mm wide PVC sheet out of which 75 millimetre shall be falt and 20 millimetre shall be tapered on both sides to form lock rail.Top,bottom and lock rail shall be provided either side of the panel. An additional 5 millimetre (+/0.25) thick PVC strip of 20 millimetre width is to be stuck on the bottom side of the ' c ' channel prelaminated paneling of 5 millimetre (+/0.25) thick PVC sheet to be fitted inside the mild steel frame welded/ sealed to the styles and rails with 5 millimetre (+/0.25) x 30 millimetre PVC sheet beading on either side and joined together with solvent cement adhesive etc ,10 millimetre thickness (5 millimetre (+/0.25) x 2 numbrs ) 20 mm wide cross PVC sheet as gap insert for the rail and bottom rail. Door to be fixed to frames with 3 numbers mild steel .powder coated but hinges of size 100 x 25 x 2 millimetre using 32 millimetre long steel screws drilled suitable to pass through both the walls of the mild steel tube. Other hardwares
First Floor
Second Floor
Providing and fixing in position. (as per I.S.1868 / 1982) Aluminium sliding window of two tracks with rectangular pipe having overall dimension 63.50 x 38.10 x 1.02 millimetre at weight 0.547 Kilogram/One Running Metre. and window frame bottom track section 61.85 x 31.75 x 1.20 millimetre at weight 0.695 Kilogram/One Running Metre. Top and side track section 61.85 x 31.75 x 1.30 millimetre at weight 0.659 Kilogram/One Running Metre. The shutter should be of bearing bottom 40 x 18 x 1.25 millimetre at weight 0.417 Kilogram/One Running Metre. Inter locking section 40 x 18 x 1.10 millimetre at weight 0.469 Kilogram/One Running Metre. And handle section 40 x 18 x 1.25 millimetre at weight 0.417 Kilogram/One Running Metre. and top section 40 x 18 x 1.25 millimetre at weight 0.417 Kilogram/Running metre. As per detailed drawings and as directed by Engineer in charge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 millimetre thick plain glass with all required screws and nuts etc, complete. With powder coating with box
First Floor
Providing and fixing in position (as per 1868 / 1982) Aluminium sliding window of three tracks with rectangular pipe 95 x 38.10 x 0.90 millimetre at weight 0.637 Kilogram/One Running Metre. with window frame bottom track section 92 x 31.75 x 1.30 millimetre at weight 1.070 Kilogram/One Running Metre.. Top and side track section 92 x 31.75 x 1.30 millimetre at weight 0.933 Kilogram/Running metre. The shutter should be of bearing bottom 40 x 18 x 1.25 millimetre at weight 0.417 Kilogram/One Running Metre. Inter locking section 40 x 18 x 1.10 millimetre at weight 0.469 Kilogram/Running metre. and handle and top section 40 x 18 x 1.25 millimetre at weight 0.417 Kilogram/Running metre. As per detailed drawings and as directed by Engineerincharge with all necessary Aluminium sections fixtures and fastenings such as roller bearing in nylon casting and self locking catch fitted in vertical section of shutter including 5 millimetre thick plain glass and aluminium mosquito net shutter with stainless steel jail with all required screws and nuts excetra complete. With powder coating with box
First Floor
Second Floor
Pump House and Sump Well
Providing and fixing M40 grade thick vibrated pull cast or similar type concrete frame with chamfer conforming to I.S. 65241983 having 6 millimetre diameter. bars 3 numbers And stirrups at 250 millimetre center to center and fixing in wall with 6 numbers of hold fast of 12 millimetre diameter bars 500 millimetere long including primer and oil painting excetra complete) frame size 60 millimetre x 100 millimetre .
Providing and fixing mild steel grill work for windows, ventilators excetra 20 Kilogram/ One Square Metre as per drawing including fixtures, necessary welding and painting with one coats of anticorrosive paint and two coats of oil painting complete
First Floor
Second Floor
Pump House and Sump Well
Providing and Fixing mat finish stainless steel (of 302 grade ) railing with top pipe of 50 millimetre diameter and vertical pipe of 38 millimetre diameter at 0.60 metre center to center or as required and horizontal pipes of 25 millimetre diameter in three rows, all pipes of 2 millimetre thick including buffing,fabricating fixtures and fastening including pipe base of appropriate diameter and ball base of 75 millimetre diameter above newel post of 75 millimetre diameter excetra complete (Prior approval of sample and brand by Ex.Engineer is necessary before use)
First Floor
Second Floor
Pump House and Sump Well
Providing and fixing C.P. 2 Way BIB cock with wall flange of approved make including necessary sockets/ union nut excetra complete as directed by Engineer in charge
First Floor
Second Floor
Providing and fixing 25 millimetre diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangement and lock. [Without chamber].
Providing and fixing 15 millimetre diameter. screw down bib/ stop tap of brass including necessary socket union nut complete.
First Floor
Second Floor
Providing and fixing 20 millimetre diameter. screw down bib/ stop tap of brass including necessary socket union nut complete.
First Floor
Second Floor
Providing and fixing screw down 15 millimetre diameter. wheeled stop tap of brass including necessary sockets/union nut complete
First Floor
Second Floor
Providing and fixing push cock (Self closing tap) symet type of 15 millimetre diameter. including necessary socket, testing excetra complete.
First Floor
Second Floor
Providing and fixing White glazed with bottle trap earthenware Wash Hand Basin of 63x45 centimetre size including cold water piller taps, brackets, rubber plugs and brass chain, stop tap, chromium plate bottle trap and necessary pipe connections including UPAC waste pipe and trap upto the outside face of the wall, making good the damaged surface, testing excetra complete.
First Floor
Second Floor
Providing and fixing Oval Type Under Counter Wash Hand Basin of 420 x 590 x 195 millimetre size with pillar cock, C.P.Angular stop cock, long thread of approved make continental including SS bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 millimetre thick fixed on Black Kadappa Framework, etc. Complete as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing 15 centimeter x 10 centimetre salt glazed stoneware gully trap in cement concrete 1:4:8 outside the building including cast iron grating in the sink, connecting glazed stoneware pipe, brick masonry chamber with cast iron lid and cast iron grating for the gully trap.
First Floor
Second Floor
Providing and laying concrete pipes of I.S.NP. class of 150 millimetre diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete.
Providing and laying concrete pipes of I.S.NP. class of 300 millimetre diameter in proper line, level and slope including necessary collars, excavation, laying, fixing with collars in cement mortar 1:1 and refilling the trench complete.
Providing , constructing and fixing 250 millimetre diameter. Inspection chamber made up of UPVC material of thickness 3.5 millimetre and height of 259 millimetre with inlet and outlet of 110 millimetre diameter. with 75 millimetre diameter. U Trap, Ultra shaft pipe of Upvc material having height of 470 millimetre and fixing Ultra 250 millimetre diameter. UPVC cover and frame in 150 millimetre thick in cement concrete 1:2:4, having crushed sand bed of 100 millimetre thick of size 550 millimetre diameter. Including excavation and refilling the sides of chamber by crushed sand cushioning 150 millimetre thickness, connecting all required UPVC fittings with rubber lubricant excetra complete.
Providing , constructing and fixing 450 millimetre diameter Inspection chamber made up of Polypropylene / polyethylene material of thickness 3.5 millimetre and height of 388 millimetre with 160 or 200 millimetre main inlet (s) outlet and 110 and / or 160 millimeter branch inlets, with 450 millimetre diameter Ultra shaft pipe of HDPE material having height of 460 millimetre having Reinforced cement concrete cover and frame fixing in 150 millimeter thick in cement concrete.1:2:4, having crushed sand bed of 150 millimeter thick of size 750 millimetre diameter Including excavation and refilling the sides of chamber by sand crushed cushioning 150 millimetre thickness, connecting all required UPVC fittings with rubber lubricant excetra complete.
Providing and fixing 450 millimetre x 550 millimetre size superior type Belgium mirror with 16 millimetre diameter. nickel plated towel rod excetra complete.
First Floor
Second Floor
Providing and fixing chromium plated towel rod 16 millimetre diameter and 75 centimetre in length including all accessories complete.
First Floor
Second Floor
Providing and fixing C.P. Angular stop clock with wall flange of approved make continental including necessary sockets/union nut excetra complete.
First Floor
Second Floor
Providing and fixing C.P. BIB cock with wall flange of approved make including necessary sockets/ union nut excetra complete.
First Floor
Second Floor
Providing and fixing 40 millimetre diameter Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements excetra complete.
First Floor
Second Floor
Providing and fixing 15 millimetre diameter Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements excetra complete.
First Floor
Second Floor
Providing and fixing wall mixer with overhead shower,shower arm,hand shower with wall bracket having flow rate up to 12 liters/minutes of Jaquar/Cera/Hindware /Perryware or equivalent make including all necessary pipes,fittings etc.complete as directed by Engineer In Charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
First Floor
Second Floor
Providing and fixing C.P. wall mixer with provision for overhead shower with 115 millimetre long bend pipe and wall flange of approved make including necessary sockets/union nut excetra complete.
First Floor
Second Floor
Providing and fixing Orissa Pan of size 580x445x260 millimetre with approved make flush valve including trap, cast iron soil and vent pipe upto outside face of wall including 100 millimetre diameter cast iron. plug, bend and necessary pipe connection, exceta complete. As directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing white Opal series European type wall-hung, of size 400 millimetre x 370 millimetre x 575 millimetre with approved make flush valve including soil pipe, vent pipe upto outside face of wall, 100 millimetre diameter cast iron. plug bend inlet pipe all fittings, cutting and making good walls, floors excetra as directed by Engineer in charge
First Floor
Second Floor
Providing and fixing white glazed earthenware lipped flat back/corner type Urinal with PVC 5 liters flushing cistern with fittings, inlet pipe with stop tap, brackets for fixing the cistern, 32 millimetre diameter P.V.C. flush pipe with fitting including lead soil pipe, lead trap and soil pipe connection up to the outside face of wall.
First Floor
Second Floor
Providing and fixing 75 millimetre diameter stabiliser pipe/ P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps excetra complete
First Floor
Second Floor
Providing and fixing 100 millimetre diameter stabiliser pipe/ P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps excetra complete
First Floor
Second Floor
Providing and fixing H.D.P container one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres
Providing and fixing on walls/ ceiling/ floor 15 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 20 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 25 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 32 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 40 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 50 millimetre diameter. CPVC pipe with necessary fittings, remaking good the demolished portion excetra complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
First Floor
Second Floor
Providing and fixing 15 centimetre rigid PVC Nahani trap including PVC grating ,bend, connectingpiece of UPVC pipe up to the outside face of wall ,making the good damaged surface and testing excetra complete ( Prior approval of sample and brand by Ex. Engr. is necessary before use)
First Floor
Second Floor
Providing and fixing P.V.C. Rain water pipes of 160 millimetre outer diameter and having wall thickness of 2.2 to 2.7 millimetre confirming to I.S. 13592-1992 including proper rainwater receiving recess with P.V.C. plug, bend, necessary fittings, such as, offsets, shoes, inluding fixing the pipe on wall using approved wooden cleats projecting 25 millimetre to 40 millimetre from face of wall a fixing with clips of approved quality and One Number ,filing the joint using rubber gasket with solvent cement and properly resting the shoe of pipes on cement mocnrete or masonry blocks, including necessary scaffolding and maintenance for 3 years for any leakages or dislocations of pipes. All the P.V.C. fittings and additional 2 piece socket clips shall be got approved from engineer in charge excetra complete.
First Floor
Second Floor
Providing and laying in trenches 15 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and laying in trenches 20 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and laying in trenches 25 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and laying in trenches 32 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and laying in trenches 40 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and laying in trenches 50 millimetre diameter CPVC pipe including necessary excavation, fittings. Refilling trenches excetra complete Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed excetra complete.
Providing and fixing in position UPVC ultra violet stabilized 110 millimetre outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement excetra complete
First Floor
Second Floor
Providing and fixing Glass self 125 millimetre wide and 600 millimetre long with necessary chromium plated brackets providing T.W.gutties excetra complete
First Floor
Second Floor
Providing and fixing 90 centimetre x 60 centimetre Granite plate engraving 10 cm. Height letter, figures including painting the lefters/figures with approved colour and shade complete
Providing and fixing in position alluminium strips of size 50 millimetre x 3 millimetre for nosing the steps including fixing with screws and raval plugs, bending and cutting to the required shape and size, finishing with paint, necessary mortar bedding of 1:3 cement mortar to get exact line and level including watering and curing excetra complete
First Floor
Second Floor
Providing and fixing lioghtening conductor system comprising of erecting Air-Termination consisting of tubular copper rod of 25 millimetre diameter 1.2 millimetre thick with multiple points head 1.2 metre long ( Heavy Duty) welded or clamped to galvanised iron pipe pole B grade 50 millimetre diaof requiired length with mild steel round bnase plate 25 centimetre diam and 10 millimetre thick at bottom embeded in cement concrete 1:3:6 dfoundation of size 45 centimetre diam x 45 centimetre Height and providing earthing with copper earth plate of size 60 x 60 x 0.3 centimeter with cadmium plated nut bolts to fix earthing strip burried in specially prepared earth pits 1.5 metre below ground level with 40Kilogramcharcoal and salt with altemate layers of charcoal and salt and galvanised iron pipe 40 millimetre diameter 2 meter length burried in earthe upto earthling plate remining portion above ground level for watering and refilling comcpete Note- Copper strip fropm lightening conductor is not considered in this item.
Providing and fixing copper strip 25 millimetre wide and 3 millimetre thick for lightening conductor including fixing with screws required scaffolding excetra complete Note- Lightening conductor and earthinf pits is not considered in this item
Supply, fixing and installation of 4 millimetre thick Aluminium Composite Panel (ACP) of approved colour for external cladding in combination of solid and metallic colours, including all necessary Framework, support and complete weather sealing as per architectural drawing. The Aluminium Composite Panel (ACP) should be made out of thermoplastic core of low-density polyethylene LDPE (100% virgin mix), sandwiched between two aluminium sheets of ALLOY GRADE- 5000 series, each not less than 0.50 millimetre thick, total thickness of aluminium composite panels not to be less than 4 millimetre the exposed surface thereof shall have Stove lacquered finishing coat not less than (26 + - 2) micron (containing minimum 70% kynar 500 based PVDF) of colour and shade as per architectural design. The inside surface (facing the building exterior surface)shall have polyster based powder coating not less than 25 Micron with protective peel-off foil on the exterior face (peel off film will in no case leave any adhesive mark over the composite panel surface after it is peeled off). The supporting framework shall be made out of 50 X25 X 3 millimetre thick Aluminium section to be spaced horizontally and vertically for fixing of panel of size 900 X 1200 millimetre and fixed to the building structure as per design through 50 X50 X5 millimetre mild steel angle clamps prefixed to masonry or slab, columns with Hilti make anchor fastener screws. The fixing of panel to be done with the help of VHB tapes and screws and all the sealing of joints to be done with weather sealent Silicon as directed by Engineer-in-charge.
First Floor
Providing soak pit of size 120 centimetre x 120 centimetre x 120 centimetre including excavating and filling with brick-bats.
RWH - Shallow Percolation Pit providing, constructing 2.0metre deep shallow depth percolation pit comprising of 1.0metre diameter pre-cast Reinforced cement concrete rings, 300 millimetre thick side filling around outside of Reinforced cement concrete rings (annular space) with 40 millimetre size boulders including filling of percolation pit up to 0.5metre depth (from bottom up) with 25-75 millimetre clean washed gravels followed by 0.5 metre depth of 10-25 millimetre of clean washed stones followed by 0.5metre of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) media layer including covering with RCC slab, manhole frame and cover, PVC rungs excetra including arrangement for inlet and outlet pipe, excavation and backfilling as shown in the drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge
Providing and installing bio digester unit based on DRDO technology made of fibre reinforced plastic (FRP) having composition and following technical specifications and including necessary pipe and accessories up to 3 meter length, excluding the necessary excavation for installing the bio digester. Percentage of fibre glass (glass content in fibre glass should be minimum 30%): -33.33% Percentage of polyester resin: - 66.67% Water absorption (as per ASTM):-0.30% Flammability as per ASTM Tensile strength:-115 MPA Specific Gravity at 25 degree centigrade 1.45 Izod impact strength:-65KJ/M2 Heat defection/distort temperature:-65deg C Corrosion resistance (Non Corrosive) fitted with Inlet pipe size rigid PVC: -100 millimetre Outlet pipe size rigid PVC:-80 millimetre Gas outlet rigid PVC with Valve: 20 millimetre Bacteria immobilization PVC mattes (on all partition) With DRDO TOT licensee and latest batch certificate(month and year of supply) and capacity as belowc) Up to 25 user size (1.5metrex1.0metrex1.0metre), Capacity of biodgester:-1500 liters, Area of top, bottom and side walls:- 8 square metre Area of partition walls: 2 square metre Total weight of frp: - 82.80 Kilogram, Bacteria inoculums quantity: - 600 liters, Minimum thickness of side walls / top and bottom: 5 millimetre One Number of inside partitions: - 3, Minimum thickness of partition wall: 3 millimetre
d) Up to 40 user size (2.0metrex1.0metrex1.0metre), Capacity of biodgester:-2000 liters, Area of top, bottom and side walls: - 10 squameter Area of partition walls: 3 square metre Total weight of frp: - 106.20 Kilogram, Bacteria inoculums quantity: - 600 liters, Minimum thickness of side walls / top and bottom: 5 millimetre One Number of inside partitions: - 3, Minimum thickness of partition wall: 3 millimetre
Providing and fixing 20 to 25 millimetre thick rough shahabad box type waterproofing for basement or underground floor on a base of Cement concrete 1:3:6, including sub base of 2.50 centimeter thick Cement mortar 1:3 with conceal, secrete (RMW), Algae proof or other alike waterproofing liquids, raking of joints upto 35 mm depth, filling the joints with 6 millimetre size crushed metal, hand grouting with cement slurry, curing and cleaning, with 7 years guarantee on court fee stamp of Rs. 100/- with ponding test excetra complete. (excluding Cement concrete 1:3:6 base concrete )
Providing and fixing 20 to 25 millimetre thick rough shahabad box type waterproofing treatment to vertical outside faces of Reinforced Cement concrete walls of basement or underground floor including filling the gap of 25 millimetre between rough shahabad and Reinforced cement concrete walls with cement grout mixed with water proofing liquid Algae proof or other alike with one tile lift method, brushing the joints horizontally with cement slurry mixed with water proofing liquid for width 30 to 35 millimetre and sloping coping over topmost tile with cement mortar 1:3, butting the bottom most with Cement concrete 1:2:4 mixed with water proofing liquid, curing, with 7 years guarantee on court fee stamp of Rs.100/- with ponding test excetra complete. (excluding Cement concrete 1:3:6 base concrete)
Providing neeru finish to plastered surfaces in all positions including scaffolding and curing excetra complete.
Providing and applying three coats of water proof cement paint of approved manufacture and of approved colour to old plastered surfaces including scaffolding if necessary, cleaning and preparing the surface, watering for two days excetra complete.
Providing and fixing rolling shutter fabricated from steel laths of minimum thickness 0.9 millimetre with lock plate of 3.15 millimetre thickness reinforced with 35 x 35 x 5 millimetre angle section fitted with sliding bolts and handles for both sides, deep mild steel channel section of depth and thickness not less than 65 millimetre and 3.15 millimetre respectively with hold fast arrangements, mild steel Bracket plate 300 x 300 x 3.15 millimetre minimum size and shape with square bar, suspension shaft of minimum 32 millimetre diameter, hood cover of mild steel sheet not less than 0.9 millimetre thickness and of any size at top and safety devices including mechanical gear operation arrangement consisting of worm gear wheels and worms of high grade cast iron or mild steel and one coat of red lead primer excetra complete. (I.S. 62481979) (With mechanical gear)
Boring work (including transport.) 200/215 mm diameter in the soil / gravel surface Bore diameter of 150 millimetre in solid rock. This includes diameter drilling work. (Wet drilling) MJP Bore Well SSR Shedule 'B' A (item no 1) Ë´ÉvÉxÉ EòÉ¨É (´ÉɽþiÉÖEòҺɽþ) ¨ÉÉiÉÒ / ¨ÉÖ¯û¨ÉÉSªÉÉ ¦ÉÖ|ɺiÉ®úÉiÉ 200 / 215 ¨ÉÒ±ÉÒ¨ÉÒ]õ®ú ´ªÉɺÉÉSÉä Ê´ÉvÉhÉEòÉ¨É ´É {ÉCCªÉÉ {ɹÉÉhÉÉiÉ 150 ¨ÉÒ±ÉÒ¨ÉÒ]õ®ú ´ªÉɺÉÉSªÉÉ Ë´ÉvÉhÉ EòɨÉÉSÉÉ ªÉÉiÉ ºÉ¨ÉÉ´Éä¶É +ɽäþ (´Éä]õ ÊbÅ÷±ÉÓMÉ)
After completion of drilling bore well, capacity test by flushing (air lift method) is measured with 90 degree "V" notch. MJP Bore Well SSR Shedule 'B' A (item no 2) Ë´ÉvÉxÉ Ê´É½þÒ®ú {ÉÖhÉÇ Eäò±ªÉÉ xÉÆiÉ®ú }±ÉʶÉMÉuùÉ®äú (B+®ú ʱÉ}]õ ¨ÉälÉb÷) IɨÉiÉÉ SÉÉSÉhÉÒ 90 +ƶÉÉSªÉÉ ´½þÒ xÉÉìSÉxÉä ¨ÉÉäVÉhÉä.
180 mm diameter PVC Casing pipe (8 kg / cm2) (IS 4985-1988) In exceptional circumstances / Casing pipes with a rock surface and if more than 40 feet of casing pipe is required, the casing should be used with the technical approval of the Deputy Engineer and Geologist. 180 ¨ÉÒ±ÉÒ¨ÉÒ]õ®ú ´ªÉɺÉÉSªÉÉ {ÉÒ.´½þÒ.ºÉÒ. Eäò˺ÉMÉ {ÉÉ<Ç{É (8 ÊEò±ÉÉäOÉì¨É / ºÉå]õÒʨÉ]õ®ú) (+ÉªÉ BºÉ 4985-1988) +{É´ÉÉnùÉi¨ÉEòò {ÉÊ®úκlÉiÉÒ¨ÉvªÉä nùMÉb÷ MÉÉä]õ¬ÉÆSÉÉ ¦ÉÖºiÉ®ú +ºÉ±É䱪ÉÉ Ê`öEòÉhÉ ´É 40 ¡Öò]õÉ{ÉäIÉÉ Eäò˺ÉMÉ {ÉÉ<Ç{É +iªÉɴɶÉEòò +ºÉ±ªÉÉ ={É+Ê¦ÉªÉÆiÉÉ ´É ¦ÉÖ´ÉèYÉÉÊxÉEò ªÉÉÆSªÉÉ iÉÉÆÊjÉEò ¨ÉÉxªÉiÉäxÉä ºÉnù®ú Eäò˺ÉMÉ ´ÉÉ{É®úhªÉÉiÉ ªÉÉ´ÉÉ.
180 millimetre diameter PVC Casing pipe (8 kg / cm2) (IS 4985-1988) Casing lowering, grounding. 180 ¨ÉÒ±ÉÒ¨ÉÒ]õ®ú ´ªÉɺÉÉSªÉÉ {ÉÒ.´½þÒ.ºÉÒ. Eäò˺ÉMÉ {ÉÉ<Ç{É (8 ÊEò±ÉÉäOÉì¨É / ºÉå]õÒʨÉ]õ®ú) (+ÉªÉ BºÉ 4985-1988) Eäò˺ÉMÉ ±ÉÉä+Ë®úMÉ OÉÉ>ð]õÓMÉ Eò®úhÉä
180 millimetre diameter cap for PVC pipe 180 ¨ÉÒ±ÉÒ¨ÉÒ]õ®ú ´ªÉɺÉÉSªÉÉ {ÉÒ.´½þÒ.ºÉÒ. {ÉÉ<Ç{ɺÉÉ`öÒ Eìò{É
Providing Internal Electrification, External Electrification, 500 KVA Transformer and 320 KVA DG Set, LV system, 20 Passenger Cum Stretcher/Hospital Lift System, Street Light & Water Pump for the Proposed (G+2 Floors) 100 Bedded Sub District Hospital At Kopargao, Tal. Kopargaon, Dist. Ahmednagar. [ Sub Work 01 to 04] Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC [1-1-10]
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately as per specification No WG-MA/CC [1-1-9]
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-2]
Supplying and erecting green colour earthing with 1x 2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-2]
Supplying and erecting mains with 4x 4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-3]
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-3]
Supplying and erecting green colour earthing with 1x 4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-3]
Supplying and erecting mains with 4x 6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-4]
Supplying and erecting green colour earthing with 1x 6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No WG-MA/BW [1-3-4]
Supplying erecting & terminating XLPE-HFFR armoured (strip) cable 4 core 10 sq. mm. copper conductor continuous 5.48 sq.mm. (12 SWG) GI earth wire complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [999-1-99]
Supplying erecting & terminating XLPE-HFFR armoured (strip) cable 4 core 16 sq. mm. copper conductor continuous 5.48 sq.mm. (12 SWG) GI earth wire complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [999-1-100]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 35 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-16]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 95 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-19]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 120 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-20]
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete. [1-6-1]
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete. [1-6-2]
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-10]
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-11]
Supplying and erecting modular type buzzer 220 / 250V duly erected on provided plate and box with wiring connections complete. [1-6-19]
Supplying and erecting modular type (two module) electronic step regulator for fan duly erected on provided plate and box with wiring connections complete. [1-6-23]
Supplying and erecting modular type blanking plate one module duly erected on provided plate & box. [1-6-24]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-35]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-36]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 8 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-39]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background. [1-6-40]
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 16 / 18 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background [1-6-41]
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-5]
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-6]
Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/HW [1-7-15]
Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/HW [1-7-16]
Wiring for plug on board with Switch socket surface/concealed type copper wiring and earthing and with modular accessories as per specification No WG-PW/CW [1-7-26]
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. THD<10% p.f. >0.95 operating range of 140-260V in built surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver IP66 IK09 rated on provided PVC Block / wooden board with 3 years warranty. [2-1-15]
Supplying and erecting LED square / circular Max. 14 W down lighter/Panel Light having pressure die-cast aluminium housing polystyrene diffuser having system lumens output of Min. 1500 Lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-4]
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing polystyrene diffuser having system lumens output of Min. 2000 Lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-5]
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 30 W having CRCA powder coated housing polystyrene diffuser having system lumens output of Min. 3600 Lumens min. efficacy of 120 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. max. ripple of 5% THD<10% p.f. >0.95 operating range of 120-270V surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty. [2-1-7]
Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-16]
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-18]
Supplying and erecting inverter LED batten 20W tube light fitting with polycarbonate housing heat sink integrated HF electronic driver Min. 2600 mAh Lithium ion Battery with charging time of 8-10 Hours and backup time of Min. 3 hrs. with minimum 25% of initial Watts having luminous efficacy of 100 lumen/watt CRI>80 CCT of 6500K and THD<=20% having useful life of minimum 25000 hrs. with overheating protection with 2 years warranty. [2-1-22]
Supplying and erecting Electronic type cordless call bell erected on T.W. board having portable bell push working on 9V D.C. battery and (effective range upto 45 meter) bell on 250 V A.C. supply. [2-3-15]
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades wire mesh duly erected complete. [2-10-14]
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF [2-10-21]
Supplying and erecting fan clamp of 30 x 5 mm. M.S. flat of required length and 10 mm. M.S. bolt and nuts erected with necessary hook of 10 mm. M.S. round bar and painted. [2-11-3]
Supplying and erecting fan hook box of 10 mm M.S. round bar bounded to the R.C.C. bars upto 50 mm length each side and pierced through a 16 S.W.G. thick aluminium/M.S. Bowl 100 mm dia. or equivalent square size and having depth upto 75 mm complete erected with duly painted by one coat of red oxide paint and two coats of paint erected in position and without any leakage of slurry of cement concrete on either side of the box and positioned to the bottom level of the slab. [2-11-5]
Supplying and erecting ‘B’ class G.I .pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire. [2-11-6]
Supplying, erecting, testing and commissioning of self contained water cooler 230/250V 50Hz nominal cooling capacity of 80 litres per hour and storage capacity 120 litres with partially stainless steel body as per specification no. AP-WCR/WC22 [3-3-9]
Supplying and erecting ultra violet storage type water purifier (RO+UV+UF) with softener for safe drinking water consisting of UV germicidal tube of 8W capacity choke made of copper wire and two indicator lamps with output of purified water minimum 0.33 litre/min with activated carbon filter and softener operating on 230V single phase A.C. supply with UV fail & filter change indication system .(for TDS more than 200) [3-5-1]
Supplying, installing, testing and commissioning of 3kVA capacity online pure sine wave with backup time of ....... hrs. PWM & IGBT based UPS with 0.8 to unity output pf single phase input & 1 phase output complete with all protections as per specification no. AP-UPS [3-7-3]
Supplying, installing, testing and commissioning of 10kVA capacity online pure sine wave with backup time of ....... hrs. PWM & IGBT based UPS with 0.9 to unity output pf single phase input & 1 phase output complete with all protections as per specification no. AP-UPS [3-7-5]
Supplying, installing, testing and commissioning of 20kVA capacity online pure sine wave with backup time of ....... hrs. PWM & IGBT based UPS with 0.9 to unity output pf 3 phase input and 3 phase output complete with all protections as per specification no. AP-UPS [3-7-8]
Supplying and erecting 12V/42Ah SMF battery with battery terminal wire duly charged with 24 months warranty complete [3-8-10]
Supplying and erecting 12 V/65Ah SMF battery with battery terminal wire duly charged complete with 24 months warranty complete [3-8-11]
Supplying and erecting 12V/100Ah SMF battery with battery terminal wire duly charged with 24 months warranty complete. [3-8-12]
Supplying, erecting and marking SPMCB 6A to 32A C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-2]
Supplying, erecting and marking SPMCB 6A to 32A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-3]
Supplying, erecting and marking TPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-10]
Supplying, erecting and marking TPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-11]
Supplying, erecting and marking FPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SPMCB of 4 ways/phase (12 poles) with door 1.2mm thickness surface/flush mounted IP 43 protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB [5-4-1]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SPMCB of 8 ways / phase (24 poles) with door 1.2mm thickness surface/ flush mounted IP 43 Protection on iron/GI frame (horizontal busbar type) as per specification no. SW-SWR/MCBDB [5-4-2]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 4 ways /12 Poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-4]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 8 ways /24 poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-5]
Supplying and erecting triple pole and neutral distribution board (TPNDB) 3 pole/ 4 pole MCCB as incomer & outgoing SP MCB (12 poles) or TP MCB of 4 ways (12 poles) with door 1.2mm thickness surface/flush mounted on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 [5-4-15]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 10 ways (10 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-9]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying and erecting triple pole and neutral distribution board (TPNDB) 3 pole/4 pole MCCB as incomer & outgoing SP MCB (24 poles) or TP MCB of 8 ways (24 poles) with door 1.2mm thickness surface/flush mounted on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1 [5-4-16]
Providing and erecting 4 Pole MCCB 415 V 100A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and fixed magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-1]
Providing and erecting 4 Pole MCCB 415V 200A rated short-circuit breaking capacity 25 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides with insulation withstand capacity 800V no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB [5-5-2]
Supplying, Erecting and Commissioning of 2 pole RCCB 16/25A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-1]
Supplying, Erecting and Commissioning of 4 pole RCCB 16/25A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-4]
Supplying, Erecting and Commissioning of 4 pole RCCB 40A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-5]
Supplying, Erecting and Commissioning of 4 pole RCCB 63A electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB [5-6-6]
Supplying, fixing, and commissioning 2 pole RCBO 6/10/16/20/25A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-9]
Supplying and erecting 100 kVAr 440 V 3 phase 50 Hz. Contactor Logic & Intelligent Relay micro APFC passive filter panel consisting of suitable steps of APP/MPP type capacitor units with Detuned (harmonic filter) reactors of suitable rating APFC panel shall be compliance to IEC 61439 and power quality IEC 61921 standard as per specification no CP-ED/APFC [6-7-5]
Providing and erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware. [7-11-6]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-2]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials testing & recording the results as per specification no. EA-EP [9-1-3]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting conventional spike type air termination suitable to carry lightning stroke made up of heavy gauge 40 mm dia copper pipe of standard length with 5 Nos. copper spikes fixed on copper ball as air terminals duly threaded in copper pipe erected on provided foundation complete. [9-3-1]
(Sub Work -02: Transformer & DG Set ) Supplying, installing, testing and commissioning of 11 kV 630A indoor type ring main unit with 1 VCB & 2 LBS with internal arc compliance complete erected on provided CC foundation/MS channels/trench etc. as per specification no SW-HTS / RMU [5-9-6]
Supplying and erecting iron work sheet metal work consisting of CRCA sheets various sections of iron plates chequered plates rods bars MS pipes etc. for panel board or any other purpose with bending cutting drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority. [6-1-19]
Supplying and erecting HT CT multifunction DLMS compliance of accuracy of class 0.5 3x63.5V 50 Hz with optical & RS 232 port backlit LCD measures kWh kVAh V I kW 6 months history of energy load survey & displays trivector energy load survey TOD tamper detection & logging power ON /OFF events instantaneous parameters of rating 1/5 A with display in absence of power complete with zero adjustment & test certificate from manufacturer erected on provided M.S. box. [6-3-6]
Supplying, erecting, testing and commissioning of 11KV HT metering cubical (compact / vertical type) approved by MSEDCL / licensee fabricated with 2 mm (14 SWG) M.S. sheets with supporting angle painted with powder coating / epoxy paint of required shade copper bus bar size 25 x 6 mm heavy duty mechanical lock with counter meter for measuring no of times the opening of meter door top side cover (CT PT cover) interlock with meter door epoxy casted 3 nos. CT having required ratio between 10/5A to 50/5A VA10 or 15 Class 0.5S epoxy casted 3 nos. PT having ratio 11000/V3/110/V3 VA 50 Class 0.5 suitable for provided trivector meter and provision for incoming and outgoing cables complete duly tested by licensee with necessary test certificates and erected on provided plinth/ cc foundation. [6-4-1]
Supplying and erecting LT current transformer with bar primary 50/5 to 1000/5 ratio with 15 VA burden erected in provided CRCA box duly secured with insulating materials connected to the meter with test certificates. [6-5-2]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 3½ core 300 sq. mm. aluminium conductor complete erected with glands & lugs on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL [7-1-24]
Supplying, erecting & terminating XLPE insulated galvanised steel formed wire armoured (strip) cable 11 kV(E) 3 x 185 sq. mm. aluminium conductor laid in provided trench / pipe as per specification no. CB-HT [7-3-5]
Providing and erecting Heat shrinkable indoor termination kit for 11 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT [7-5-2]
Providing and erecting Heat shrinkable outdoor termination kit for 11 kV ( E ) XLPE HT cable 3x120 to 185 sq. mm. with necessary material as per specification no. CB-JT/HT [7-5-6]
Supplying and erecting G.I. pipe ‘A’ class 75 mm dia. erected for enclosing XLPE armoured cable on wall/pole as per specification no. CB-CE [7-6-4]
Supplying and laying (including excavation) half round reinforced cement concrete pipe of IS 458 2003 NP-2 class of 150 mm internal diameter in proper line level and slope including providing and fixing collars in cement mortar 1 2 and curing etc. complete. [7-6-6]
Supplying and laying (including excavation) of suitable width & depth up to 90 cm) 160 mm outside dia double wall corrugated pipes (DWC) of HDPE for enclosing cable below ground/road surface to required depth complete. [7-6-14]
Supplying and erecting rolled steel joist (girder) pole 100 x 116 mm (23 kg/m) with base plate in provided foundation as per specification no. OH-PL/RSJ [8-1-13]
Supplying and erecting MS pole bracket for guarding/LT OH line fabricated from ISM channel 75x40x6mm and 550mm long for necessary nos. of provided insulators and erecting on pole with 50x6mm clamp complete as per specification no. OH-PL/BKT [8-3-3]
Supplying and erecting 100 x 50 x 6 mm with 4.7 mm thick web and 7.5 mm thick flange channel iron cross arm of suitable length for 2.4 m wide DP structure and erecting on DP with 50x6mm clamp complete as per specification no. OH-PL/BKT [8-3-11]
Supplying and erecting ACSR conductor of size 6/1-2.59 mm complete. (Weasel) (127.7 kg/km) as per specification No. OH-CON/ACSR [8-4-7]
Supplying and erecting porcelain disc type insulator 45KN with necessary hardware suitable for 11kV line complete as per specification no. OH-INS/DI [8-5-6]
Supplying and erecting distribution class 11 kV thyrite type lightening arrester with nut bolts on provided MS channel as per specification no. OH-INS/LA [8-5-15]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-1]
Providing earthing with copper earth plate size 30 x 30 x 0.315 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-2]
Supplying and erecting copper strip of high purity required size used for earthing on wall and/or any other purpose with necessary copper clamps fixed on wall painted with bituminous paint with joints required. As per specification no. EA-EP. [9-2-2]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting GI wire of high purity of required sizes used for earthing or any other purposes on wall with necessary G. I. Clamps fixed on wall/cable/ conduit with screws complete. [9-2-5]
Supplying, installing, testing and commissioning of 3 phase 11/0.433 kV 50 Hz. 500 kVA Mineral oil immersed and naturally cooled outdoor type Copper wound Non-sealed transformer delta/star connected with additional neutral brought out on load side temperature rise should not exceed 45? by thermometer in oil and 50? by the resistance method in winding at full load rating using type A winding insulation (kraft paper) with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5% having 7 number of tap positions with standard accessories complete with test certificate with losses below 1510 Watts at 50% load 4300 Watts at 100% load as per IS 1180 (part 1) 2014 with necessary permissions of Electrical Inspector as per specification no SS- TR-NSL. [10-1-9]
Supplying and erecting 11 kV outdoor type gang operated air break triple pole switch 200 A capacity with 3 post pin type insulator per phase mounted in horizontal or vertical position with necessary channels on provided cross arm with adequate length of C class G.l. pipe for operating handle erected on extended square shaft. The operating handle provided with lock and key at suitable height from ground level with necessary clamp. [10-6-1]
Supplying and erecting 11 kV outdoor type drop out fuse with insulator complete with fuse holders fuse barrel with metal fitting fuse element mounted on M.S. channel with working current of 15A capacity complete erected on provided cross arm. [10-6-5]
Supplying and erecting fencing of section having size 2450 mm in height from ground level and 1200 mm width with angle iron frame work erected in CC foundation and painted complete as per specification no SS-AS/FSG [10-6-18]
Supplying and erecting double leaf hinged door each 1500 mm in width x 1850 mm in height using B class GI pipe with angle iron supports chain link wire mesh (jali) complete supported on channel iron erected in foundation and painted complete as per specification no SS-AS/DLD [10-6-20]
Providing printed instruction chart for treating persons suffering from electric shock printed in English & Marathi and duly laminated complete. [10-6-22]
Supplying standard first aid box with necessary antiseptic cream medicine for use on wounds due burn crepe bandage gauge bandage medicated ready to use bandage (Band-Aid) adhesive tape for medicinal use scissors anti-septic solution etc. (All above contents shall be of standard makes) [10-6-24]
Supplying and fixing PVC synthetic elastomer electrically insulating mat with class A insulation conforming to IS 15652 – 2006 having 2 mm thickness up to 3.3 kV [10-6-25]
Supplying, erecting, testing and commissioning of diesel generating set with alternator of 320 kVA output continuous rating 3 Phase 415 V 50c/s 0.8 p. f. A.C supply a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours along with standard accessories self-excited self-regulated screen protected alternator with static excitation system running at 1500 RPM as per IS 4722-2001 with voltage regulation +/- 5 % with performance class G2 and maximum fuel consumption 54.89 Ltr/hr 75% loading. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising meters switchgears indicators connected with suitable wires/cables the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet sound absorbing material to restrict sound level up to 75 dB at 1.0 m provided with first filling of oil diesel not less than 480 Ltr etc. on provided M20 Grade CC Foundation and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG [11-1-19]
Supplying, erecting, testing and commissioning of microprocessor based AMF panel suitable for diesel generating set of above 250 kVA up to 320 kVA capacity Three phase 415 Volts 50Hz A.C. with all standard features safeties etc as per specification no. GEN-AMF. [11-2-16]
Supplying, installing, testing and commissioning of FR XLPE armoured cable 4 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU [13-9-11]
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete. ( 5.5 X 2 X 0.3 ) [16-1-5]
second class Burnt Brick masonry with conventional /I.S. type bricks in cement mortar 1 6 in foundation sand plinth of inner walls /in plinth external walls including bailing out water manually striking joints on unexposed faces raking out joints on exposed faces and watering etc. Complete. [16-2-1]
Supplying and spreading stone metal 25 mm size for 100 mm depth above the ground level complete. [16-2-3]
Providing and fixing reinforced cement concrete cover of size 60 cm x 45 cm with frame over inspection chamber etc. complete of medium duty (100 Kilogram). [16-2-4]
Making transformer plinth (1.5 x 1.5 x 1.5) m in size with necessary excavation in ground with 150 mm. thick M- 10 PCC at the bottom and top and 250 mm. thick burnt brick wall constructed at periphery and remaining hollow portion shall be filled with 40mm hard broken aggregate. External surface duly plastered by 12 mm thick including watering etc complete. [16-3-1]
Making cement concrete foundation in 1 2 4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps) ( 5.5 X 2 X 0.7). [16-3-5]
(Sub Work -03 : L.ift Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting green colour earthing with 1x 1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No WG-MA/BW [1-3-1]
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete. [1-6-2]
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter duly erected on provided plate and box with wiring connections complete. [1-6-11]
Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module duly erected. [1-6-29]
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-5]
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires modular type switch earthing and required accessories as per specification No WG-PW/CW [1-7-6]
Wiring for plug on board with Switch socket surface/concealed type copper wiring and earthing and with modular accessories as per specification No WG-PW/CW [1-7-26]
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens min. efficacy of 110 lumen/W CRI>80 CCT upto 6500K Beam Angle of 120 deg. THD<10% p.f. >0.95 operating range of 140-260V in built surge protection of 2.5 kV Life class of 50 000 Hrs. at L70B50 including driver IP66 IK09 rated on provided PVC Block / wooden board with 3 years warranty. [2-1-15]
Supplying and erecting anodized aluminium corridor / passage light LED fitting (4 feet) Max. 22W with high transitivity diffuser with system lumens output of Min.2200 lumens min. efficacy of 100 lumen/W CRI>80 CCT upto 6000K Beam Angle of 110 deg. Ripple<5% THD<10% p.f. >0.95 operating range of 200-270V surge protection of 2 kV Life class of 50 000 Hrs. at L70B50 including driver with end caps on provided PVC Block / wooden board with 3 years warranty. [2-1-18]
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 300mm. 1400 RPM rust proof body & blades wire mesh duly erected complete. [2-10-13]
Supplying and erecting energy saving ceiling fan 230 V A.C. 50 cycles 1200 mm complete erected in position as per specification no. FG-FN/CF [2-10-21]
Supplying, erecting and marking SPMCB 6A to 32A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-3]
Supplying, erecting and marking TPMCB 40A to 63A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-11]
Supplying and erecting triple pole and neutral distribution board (TPNDB) SP/TP MCBs total 4 ways /12 Poles with door 1.2mm thickness surface/flush mounted IP 43 Protection on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB [5-4-4]
Supplying and erecting single pole and neutral distribution board (SPNDB) with 2 ways for incoming and 6 ways (6 poles) for outgoing SP MCBs with door 1.2mm thickness surface / flush mounted IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB [5-4-8]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying, erecting and marking DPMCB 6 A to 32 A B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-7]
Supplying, fixing, and commissioning 4 pole RCBO 32/40A with overcurrent rated short-circuit breaking capacity (10 kA) and earth leakage protection with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO [5-6-13]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 2 core 2.5 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-8]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials testing & recording the results as per specification no. EA-EP [9-1-1]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
SITC of Electric Traction Passenger Lift with
Sub Work -04 : Fire Fighting ) Supplying, erecting and marking TPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-10]
Supplying, erecting and marking FPMCB 6A to 32A with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB [5-3-12]
Supplying, fixing, and commissioning MCB type change over switch 4 pole 25A with 3 positions (I-O-II) with centre off position as per specification no. SW-SWR / MCBCOS [5-3-24]
Supplying and erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame. [5-4-13]
Supplying and erecting plywood 12 mm thick fixed to wall or on provided panel board with necessary materials such as screws wall fasteners supports nuts bolts etc. complete. [6-1-12]
Supplying and erecting bus bar chamber triple pole with neutral with four aluminium bars 500V 100A having 15mm (Width) X 3 mm (Thickness) with 99.9 % aluminium purity as per E91E Grade & Current Density 0.8 A per sq. mm. compliance to IS 5082 and Enclosure fabricated with 16 SWG CRCA sheet and epoxy paint with suitable number of ways and with SMC/DMC Insulators and accessories of suitable rating complete as per specification no. CP-BB [6-2-1]
Supplying and erecting 525 V 3 phase 50 Hz. MPP type capacitor having minimum overcurrent capacity of 1.8 In peak inrush current capacity 300 In and minimum life 150000 hours kVAr bank of metalised polypropylene condensers (MPP) with the standard capacities of 2 3 5 7 10 12.5 and 15 kVAr units of P.F. correction for operation on 3 phase 50 Hz. with externally discharging resistances earthing terminals and built on angle iron or channel iron frame work and provided with terminal cover box complete erected on provided iron bracket or on floor duly tested by licensee. [6-5-3]
Supplying, erecting & terminating FR XLPE insulated galvanised steel formed wire armoured (strip) cable 1100 V 4 core 4 sq. mm. copper conductor complete erected with glands & lugs on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU [7-2-31]
Providing earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm with funnel with a wire mesh for watering and brick masonry block C.l. cover complete with all materials testing & recording the results as per specification no. EA-EP [9-1-3]
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP. [9-2-3]
Supplying and erecting minimum Three & above star rated submersible pump set of 2.25 KW/3 HP with 415 V 50 c/s AC supply suitable for 150 mm dia. borewell suitable for 120 to 390 LPM discharge at 55 to 11 m head & discharge & delivery Pipe of Size-50mm diameter with a necessary H type clamps as per specification No. WP-SMP [12-2-1]
Supplying and erecting minimum Three & above star rated submersible pump set suitable for erection on open well of 3.75 KW/5 HP with 415 V 50 c/s. A.C. supply having delivery head from 43 to 11m and discharge from 120 to 840 litres. per minute & pipe of Suction 65mm / Delivery 50 mm diameter erected with necessary H type clamps as per specification No. WP-OSP [12-3-2]
Supplying and erecting flat flexible 3 core 4 sq.mm PVC sheathed submersible type copper cable suitably clamped at fixed intervals with column pipe assembly complete. [12-4-9]
Supplying and erecting PVC insulated PVC round sheathed 1.5 sq.mm (30 no. x 0.25 mm dia.) 3 core flexible multi stranded copper Industrial cable for voltage grade up to 1.1 kV [1-3-14]
Supplying and erecting Water level controller 230/415 V A.C. Four way under ground & Over head tank operation only. [12-4-15]
Supplying and erecting PVC coated 5 mm dia. Brass sensor/ electrode duly wired with nuts & bolts complete (Set of 3 Nos) [12-4-16]
Supplying and erecting automatic control panel for 3 Phase 415 volt A.C Submersible/centrifugal pump set up to 7.5 HP consisting of DOL starter having relay range 9-14 AMP S.P.P. Combined ammeter/ voltmeter phase indicating lamp enclosed in CRCA powder coated Vibration proof enclosure with IP 54 protection. Control Panel should offer single phasing phase reversal phase imbalance etc . [12-4-17]
Supplying, installing, testing and commissioning of FR XLPE armoured cable 4 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU [13-9-11]
Supplying and erecting ISI mark GI pipe 50 mm dia.‘B’ class at position with accessories complete as per specification no. CW-PLB/GP. [16-5-6]
Supplying and erecting high density polythene pipe ISI mark 50 mm. dia. suitable for pressure of 6 kg. / cm2 connected to jet/submersible pump with required material complete. [16-5-18]
Supplying and erecting 50 mm dia. gun metal sluice valve at position with necessary materials complete. [16-6-15]
Supplying and erecting non return valve 50 mm dia in position made of gun metal complete. [16-6-21]
M/s Kranti Construction
Harsh Constructions Pvt Ltd
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf