| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.0 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | ₹25.0 L | L1 | Accepted-AOC AOC_Issued |
| 2 | L2₹33.0 LRejected-Finance BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | ₹33.0 L | L2 | Rejected-Finance That the bid is not L1 |
| 3 | L3₹39.2 LRejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | ₹39.2 L | L3 | Rejected-Finance That the bid is not L1 |
| Sl No | Description | Qty | Unit | GLYPTIC L1 | Computer Gallery L2 | Creative Projects L3 |
|---|---|---|---|---|---|---|
| 1.00SITC of Aspirating Smoke Detector which can offer early warning fire detection using a dedicated high sensitivity smoke sensor through a network of air sampling pipes by speed adjustable aspirator. The sampled air is filtered and passed into the detection chamber and analysed for the presence of very small amounts of smoke. After that air is exhausted from the detector and may be vented back into the protected zone designed to operate as a stand-alone device and performs required action as a consequence of action, alarm or fault, by using dedicated LED, relays and buzzer, product to be compliant with | ||||||
| 1.10EN54-20 Class C sensitivity requirements , the system shall be declared to the Construction Products Regulation (CPR) 305/2011 by a notified body such as VDS/UL when tested to the EN54-20 standard. 6.Be tested and approved to cover min 250 Sq mt for Single/dual channel to provide Very Early Warning Fire Detection (VEWFD) / Class A, Early Warning Fire Detection (EWFD) / Class B and Standard Fire Detection (SFD) / Class C. Double knock capability (Dual Channel) for coincident detection, Pipe length min 50m for single / dual channel allowing extended coverage and convenient detector mounting. ultrasonic flow sensing element per chamber for accurate and reliable flow detection A metallic mesh filter per chamber for optics protection and improved detector longevity, Action, Alarm and Fault relays per channel for connection to | ||||||
| 1.20 | FACP and BMS systems, Simplified and intuitive LEDs user interface for immediate status indication, Pre-engineered pipe networks for hassle-free and expedient design and installation. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
NB.1) Agency Should visit the site before participation
2.) As per design based on the room calculation agency should provide suitable capacity panel | 9 | Nos. | 1,50,000 ₹13.5 L | 1,80,000 ₹16.2 L | 2,43,000 ₹21.9 L |
| 2.00 | SITC of addressable aspirating smoke detector (ASD) EN54 standard & VDS/UL approved having dual-wavelength technology to trigger an alarm at the earliest possible moment, designed to protect small and mediumsized business-critical environments for monitoring areas of min 800 m2, USB interface to configure the detector,display that contains clear, comprehensible bar graphs for smoke and airflow, as well as an alarm indicator, an error indicator, and a dust indicator, operating temperature -20...+60 °C, Minimum pipe length - Single/Dual 100 mtr. with min 1000 event memories and IP30 rating. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
NB.1) Agency Should visit the site before participation
2.) As per design based on room the calculation agency should provide suitable capacity panel | 5 | Nos. | 1,50,000 ₹7.5 L | 2,00,000 ₹10 L | 2,43,000 ₹12.2 L |
| 3.00 | SITC of standalone power supply to external devices and components as per EN 54-4 and VDS/UL with operating and fault indicator, shown via a green and a yellow LED with potential-free relay contacts for fault messages, additional installation of an I/O module possible, uninterruptible power supply with battery charging and batteries / integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier) | 14 | Nos. | 5,000 ₹70,000 | 10,856 ₹1.5 L | 2,384 ₹33,376 |
| 4.00 | SITC of air intake pipe, exhaust UPVC pipe having Outer Ø 25 mm & Inner Ø 21 mm with fabricated ASD holes with sampling tube for air suction with mecessary joints, tee and clamps and necessary civil works if required. | 1,500 | Mtrs. | 50 ₹75,000 | 110 ₹1.6 L | 80 ₹1.2 L |
| 5.00 | SITC of IP Addressable Manual call point ( VDS, EN,UL & FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier) | 14 | Nos. | 3,000 ₹42,000 | 3,500 ₹49,000 | 2,620 ₹36,680 |
| 6.00 | SITC of Addressable Hooter-cum-Strobe ( VDS, EN,UL & FM approved ) (sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier) | 14 | Nos. | 3,000 ₹42,000 | 5,200 ₹72,800 | 3,039 ₹42,546 |
| 7.00 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex / Havells / RR Kabel /Gloster/ Polycab/KEI) with 20mm NB PVC 'FR' rigid conduit pipe (Red Colour) on the surface of the wall. (Make : Polycab/Presto/AKG/Precision-Medium). | 1,000 | Mtr. | 50 ₹50,000 | 98 ₹98,000 | 142 ₹1.4 L |
| 8.00 | Supply & Fixing 240 V, 3 nos. 20A plug socket with separate 3 nos. 20A Piano key type switch, indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required .(E-8 / 30) | 1 | Set. | 900 ₹900 | 2,000 ₹2,000 | 100 ₹100 |
Tender Value
Refer Docs
EMD Value
₹78,600
Closing Date
31 Jan 2024, 1:00 pmClosed
EEI,KNHED, PW Dte
KIT Building Annex, 4thFloor,P-16, India Exch. Place Extn., Kolkata -700073
Repair Renovation of SITC Fire Detection System at Central Medical Store, Bagbazer, Kolkata
2023_WBPWD_623044_1
WBPWD/EE/KNHED/NIQ-124/23-24
Open Tender
FIRE FIGHTING ORG
90 days
Kolkata
Please refer Tender documents.
5 documents required · 5 mandatory
₹78,600
28 Apr 2026
14 Dec 2023
2 Feb 2024
20 Dec 2023
31 Jan 2024
20 Dec 2023
Amount
SITC of Aspirating Smoke Detector which can offer early warning fire detection using a dedicated high sensitivity smoke sensor through a network of air sampling pipes by speed adjustable aspirator. The sampled air is filtered and passed into the detection chamber and analysed for the presence of very small amounts of smoke. After that air is exhausted from the detector and may be vented back into the protected zone designed to operate as a stand-alone device and performs required action as a consequence of action, alarm or fault, by using dedicated LED, relays and buzzer, product to be compliant with
EN54-20 Class C sensitivity requirements , the system shall be declared to the Construction Products Regulation (CPR) 305/2011 by a notified body such as VDS/UL when tested to the EN54-20 standard. 6.Be tested and approved to cover min 250 Sq mt for Single/dual channel to provide Very Early Warning Fire Detection (VEWFD) / Class A, Early Warning Fire Detection (EWFD) / Class B and Standard Fire Detection (SFD) / Class C. Double knock capability (Dual Channel) for coincident detection, Pipe length min 50m for single / dual channel allowing extended coverage and convenient detector mounting. ultrasonic flow sensing element per chamber for accurate and reliable flow detection A metallic mesh filter per chamber for optics protection and improved detector longevity, Action, Alarm and Fault relays per channel for connection to
FACP and BMS systems, Simplified and intuitive LEDs user interface for immediate status indication, Pre-engineered pipe networks for hassle-free and expedient design and installation. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier) NB.1) Agency Should visit the site before participation 2.) As per design based on the room calculation agency should provide suitable capacity panel
SITC of addressable aspirating smoke detector (ASD) EN54 standard & VDS/UL approved having dual-wavelength technology to trigger an alarm at the earliest possible moment, designed to protect small and mediumsized business-critical environments for monitoring areas of min 800 m2, USB interface to configure the detector,display that contains clear, comprehensible bar graphs for smoke and airflow, as well as an alarm indicator, an error indicator, and a dust indicator, operating temperature -20...+60 °C, Minimum pipe length - Single/Dual 100 mtr. with min 1000 event memories and IP30 rating. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier) NB.1) Agency Should visit the site before participation 2.) As per design based on room the calculation agency should provide suitable capacity panel
SITC of standalone power supply to external devices and components as per EN 54-4 and VDS/UL with operating and fault indicator, shown via a green and a yellow LED with potential-free relay contacts for fault messages, additional installation of an I/O module possible, uninterruptible power supply with battery charging and batteries / integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
SITC of air intake pipe, exhaust UPVC pipe having Outer Ø 25 mm & Inner Ø 21 mm with fabricated ASD holes with sampling tube for air suction with mecessary joints, tee and clamps and necessary civil works if required.
SITC of IP Addressable Manual call point ( VDS, EN,UL & FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
SITC of Addressable Hooter-cum-Strobe ( VDS, EN,UL & FM approved ) (sound output of minimum 90 db) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make : Finolex / Havells / RR Kabel /Gloster/ Polycab/KEI) with 20mm NB PVC 'FR' rigid conduit pipe (Red Colour) on the surface of the wall. (Make : Polycab/Presto/AKG/Precision-Medium).
Supply & Fixing 240 V, 3 nos. 20A plug socket with separate 3 nos. 20A Piano key type switch, indicator & 20A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 300x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required .(E-8 / 30)
SITC of Microprocessor based addressable fully networkable,expandable fire alarm control panel ( VDS, EN with UL & FM approved ) suitable for the devices as stated in thefollowing items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with VGA display.Thc panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice.
The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved make : Siemens/Honeywell/ Extralis / Securiton/Carrier)
N.B. i) The DLP period is of 12 Months from the date of Final bill.
ii) Rates should be quoted with minor Civil works. Wall cutting and mending good the damages to the original finish.
Terms and Conditions i) The Agency must procure the materials from the Manufacturer / OEM or from their authorise sales channel so that the standard warranty / Supportof of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. ii) Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work /submission of bill iii) If any refurbished material is supplied and installed penal action will be taken as per existing rules.
[ Rates should be Quotated inclusive of all taxes & duities applicable as per Govt. rules & regulations]
Computer Gallery
Creative Projects
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.44 MB
2911.pdf
Tender Documents • 1.46 MB
suspension.pdf
Additional Documents • 2.91 MB
BOQ_1329513.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid