Loading…
Loading…
Tender Value
₹40.1 L
EMD Value
₹80,200
Closing Date
6 Feb 2026, 3:30 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
TOWNSHIP
12 conditions · 1 needing a document upload
Electrical Contractor License: Tenderer(s) have to submit a copy of valid Electrical Contractor License for carrying out installation work of voltage class involved, issued by any State/Central Government along with the tender documents, failing which the offer is liable to be rejected.
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
14 conditions
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Explanatory notes: Electrical work for "Upgradation of 511 nos. of type-II qtrs. by adding one room in existing type-I qtrs. in RCF Kapurthala.
1.1: Item No. 01 (Light/fan points) Modular : Supply, wiring, testing & commissioning of light /ceiling fan/exhaust fan points with drawing new copper wires as off wires of size 1.5 sq mm (phase, Neutral) along with 1.5 sq mm (green colour) as earth wire of 1100 volt grade, multi stranded copper conductor PVC insulated wire ISI marked including main circuit wiring (from MCB/DB to Switch plate) with 2 x 4 sq mm along with 2.5 sq mm (green colour) 1100 volt grade and sub main (from switch plate to switch plate, not covering more than Nine points in total) with 2x 2.5 sq mm with 1.5 sq mm (green colour), multi stranded copper conductor, PVC insulated wire ISI marked conforming to IS:694-1990 or latest. Also supply fixing, testing & commissioning of 6 Amp. Modular white switch of SSK cat. No.ACE-100 (ACE series), Anchor Cat. No. 47101 (Rider series),or Roma plus ct. no.289101, Legrand cat. No. 675501 (MyLinc series), to be fixed on modular plates, it also includes the supply and fixing modular plates (Roma Plus) of respective sizes and dummies as per requirement. All point to be connected with earth wire. Also keep the loop of wire 150 mm long on every end pt. of circuit & Point wiring. Earth connections are to be done, rubber ferrules to be used in conduits. All spouts/Jn. Boxes available in the building whether wired/unwired to be covered with laminated phenolic sheets and fixing with suitable stainless steel screws.
1.2: Item No.02:(6 Amp Plug socket(Modular):Supply, wiring, testing & commissioning of 6 Amp. Plug socket point with 2x1.5 sq mm 1100 volt grade multi stranded copper conductor PVC insulated wire and 1.5 sq.mm green colour copper wire as earth wire conforming to IS:694-1990 or latest to be laid in the existing New conduit, the circuit is to be taken from the 2x4 sq mm circuit in the main switch plates only. Also supply, fixing testing, & commissioning of 6 Amp white modular socket of legrand cat No. 675550 (mylinc series),anchor Roma plus cat No.289330 ,SSK Cat. No. ACE-219(ACE Series), Anchor Cat. No. 47325(Rider series) & 6 Amp. white modular switch of Legrand cat. No. 675501 (mylinc series) or SSK cat. No.ACE-100 (ACE series), Anchor Cat. No. 47101 (Rider series) or as per list of make to be fixed on modular plates of requisite sizes to be supplied along with switches of requisite sizes. All points to be connected to the earth wire and rubber ferrules to be used in the conduits. Also keep the loop of the wire 150 mm long on every end point of circuit and point wiring and fixing with suitable stainless steel screws. Earth connections are to be done and dummies if required are in the scope of tenderer.
1.3:Item No.03 (PVC Conduit): Supply, fixing of PVC Conduit pipe MMS (Medium mechanical strength) of 25 mm dia., inside Diameter (Min.) 21.4mm it also includes all junction boxes , bends and sockets required for fixing the conduit in the wall by making slit in the cemented wall, repairing the wall as it is original. The debris of plaster removed to be collected, make the place neat and clean and debris shall be disposed off in dump yard.
1.4:Item No. 04: Supply and fixing of 4"x6" GI box with earth terminals in the wall fixing in the by cutting in the pucca area as it was original. The debris of plaster removed to be collected, make the place neat and clean and debris shall be disposed off in dump yard on the daily basis.
1.5:Item No. 05 (GI BOX): Supply and fixing of 3"x 5" GI box with earth terminals in the wall fixing in the by cutting in the pucca area as it was original. The debris of plaster removed to be collected, make the place neat and clean and debris shall be disposed off in dump yard on the daily basis.
1.6:Item.No.06: Power Plug Point (Modular) : Supply, wiring, testing & commissioning of 16 Amp. modular power plug point with 2x 4 sq mm 1100 volt grade multi stranded copper conductor PVC insulated wire along with 2.5 sq.mm green colour copper wire as earth wire conforming to IS:694-1990 or latest to be laid in the existing new conduit. Also supply, fixing testing, & commissioning of 16 Amp white modular socket of legrand cat No. 675555 (mylinc series) or anchor Roma plus cat No.289316 or anchor cat No.47366 (Rider Series) or SSK Cat. No.ACE- 220(ACE series) & 16 Amp. White modular switch of Legrand cat. No. 675511 (mylinc series), or anchor cat No.47263 (Rider Series) or SSK Cat. No.ACE-207(ACE series) or as per list of makes to be fixed on modular plates of requisite sizes to be supplied along with switches of requisite sizes. All points to be connected to the earth wire. Also keep the loop of the wire 150 mm long on every end point of circuit and point wiring and fixing with suitable stainless steel screws. Earth connections are to be done.
1.7:Item.No.07: Power Plug Point (Modular) : Supply, wiring, testing & commissioning of 6/16 Amp. modular power plug point with 2x 4 sq mm 1100 volt grade multi stranded copper conductor PVC insulated wire along with 2.5 sq.mm green colour copper wire as earth wire conforming to IS:694-1990 or latest to be laid in the existing new conduit. Also supply, fixing testing, & commissioning of 6/16 Amp white modular socket of legrand cat No. 675555 (mylinc series) or anchor cat No.47366 (Rider Series) or anchor roma plus cat No.289316 or SSK Cat. No.ACE- 220(ACE series) & 16 Amp. White modular switch of Legrand cat. No. 675511 (mylinc series), or anchor cat No.47263 (Rider Series) or SSK Cat. No.ACE-207(ACE series) or as per list of makes to be fixed on modular plates of requisite sizes to be supplied along with switches of requisite sizes. All points to be connected to the earth wire. Also keep the loop of the wire 150 mm long on every end point of circuit and point wiring and fixing with suitable stainless steel screws. Earth connections are to be done.
1.8:Item No.08:- Fan Regulator(Modular): Supply, fixing, testing and commissioning of step type Modular electronic fan regulators 100watt hum free of legrand Cat. No. 675530 (mylink series),or anchor Roma plus cat No.289510(1M) ,289500 (2m) ,or Havells -Fabio / Crabtree / Adore Electronic Fan Regulator or anchor cat No.47131 (Rider Series) or SSK Cat. No.ACE-214(ACE series) in the existing new modular plate.
1.9:Item No. 09: (wiring for AC point):Supply, wiring, testing & commissioning 2x4 sq mm copper wire multistrand along with 1 X 2.5 sq mm for AC wiring copper wire multistrand of green colour as earth wire to be drawn in the recessed conduits in the slab/wall from SPN/TPN/DB to required AC points.
1.10:Item No. 10:(LED Tube light fixing): Fixing, testing and commissioning of LED Tube light fitting of 18/20 Watt on the wall or roof surface of the building. It includes suitable length of connection wire required for connecting with the point wiring.
1.11:Item No. 11:(Ceiling fan installation): Fixing, testing and commissioning of 1200mm dia. sweep ceiling fan.( ceiling fan will be supplied by RCF).It also includes the 1.0 sq mm copper wire for making electrical connection of the fan.
1.12:Item No. 12: Supply, fixing (flush type), testing and commissioning of Industrial socket (Metal plug DB) with 20/25A SPN of 'C'curve of legrand cat No.507811 or 507812 / 507813 or as per list of makes, it also includes the supply of metal plug top.
Electrical work for "Upgradation of 511 nos. of type-II qtrs by adding one room in existing type-I qtrs in RCF Kapurthala.
RCF-EL-TS-ET-145-2025-26~RCF
RCF-EL-TS-ET-145-2025-26
Open
Works - General
18 Months
Kapurthala, Punjab
₹0
₹80,200
6 Feb 2026
13 Jan 2026
23 Jan 2026
3 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 40,08,539.5 | ||
| — | — | — | 40,08,539.5 | ||
| General Lighting and power supply work of ty-II qtrs. by adding one room in existing ty-I qtrs. RCF, Kapurthala. | — | Item Breakup | for details. | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .