| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.6 LAccepted-AOC PLOT NO 28 SANTOSHIMA COLONY WEST MARREDPALLY SECUNDERABAD 500026 | HYDERABAD | TELANGANA | 500026 | ₹12.6 L Quoted ₹12.8 L | L1 | Accepted-AOC L1 bidder |
| 2 | L2₹13.0 L+₹18,240 (1.42%)Rejected-Finance | ₹13.0 L+₹18,240 (1.42%) | L2 | Rejected-Finance Other thanL1 bidder |
| 3 | L3₹14.9 L+₹2.1 L (16.0%)Rejected-Finance | ₹14.9 L+₹2.1 L (16.0%) | L3 | Rejected-Finance Other thanL1 bidder |
| 4 | L4₹16.4 L+₹3.6 L (28.1%)Rejected-Finance | ₹16.4 L+₹3.6 L (28.1%) | L4 | Rejected-Finance Other thanL1 bidder |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not having eligible category |
Tender Value
₹20.0 L
EMD Value
₹40,000
Closing Date
4 Jan 2025, 9:00 amClosed
CWE (ARMY) SECUNDERABAD
Commander Works Engineers Mudfort, MES Office Complex Secunderabad-500 003
REPAIRS MAINTENANCE OF SOLAR WATER HEATER AND CENTRAL AC PLANT nd AHU UNITS AND CONNETED ALLIED WORKS AT CDM AREA UNDER AGE E M NO I OF GE UTILITY SECUNDERABAD
2024_MES_687572_1
86282
Open Tender
Civil Works - Others
Item Rate
180 days
Secunderabad
as per NIT
7 documents required · 7 mandatory
₹500
GE(UTILITY) SECUNDERABAD
₹40,000
Yes
3 Mar 2025
7 Dec 2024
11 Jan 2025
7 Dec 2024
4 Jan 2025
21 Dec 2024
Amount
Testing and Commissioning Pressure test in the air conditioningh system (Air cooled system / ductable AC) up to capacity of 66 TR with dry Nitrogen upto 300 PSI and rectifiying the leakages , pressure hold upto 300 PSI for 48 Hrs , Vaccumizing the system upto 500 micrones & commissioning the unit, test running etc complete all as per specified & directed. (Refrigerant gas shall be paid seperate)
M&L for Cleaning/descaling of cooling coil fins of IT center AHU of 66TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing complete all as per specified & directed.
M&L for Cleaning/descaling of cooling coil fins of Library AHU of 33TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing complete all as per specified & directed.
M&L for Cleaning/descaling of cooling coil fins of Ductable ACs of 11 TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing complete all as per specified & directed
M&L for Cleaning/descaling of cooling coil fins of Ashoka Buildingh AHU of 33TR capacity for oxides, dust and improving the heat transfer capacity by using 50% concentration HCL/H2SO4 cleaning acid and brushing complete all as per specified & directed.
Repairs of Indoor PCB Controls of 11 TR AC complete all as per specified & directed.
Supply & Fixing in replacement of New Controls with remote for 11 TR Ductable unit incl taking down old unsv one complete all as per specified & directed.
Supply & Fixing in replacement of PCB of 11 TR HITACHI Outdoor unit as per requirement of site incl taking down old unsv one complete all as per specified & directed.
Supply & Fixing in replacement of Electronic Thermostate including taking down U/S Old Thermostate as per requirement of site. complete all as per specified & directed.
Supply and fixing in replacement of liquid line filter 5/8 as per requirement of site incl taking down old unsv one complete all as per specified & directed.
Supply and Charging of Refrigerant Gas R-410/407C or OEM recommended for respective system in Froen/Mafron family in sealed cylinders complete all as per specified & directed.
Supply and fill Compressor Oil complete all as per specified & directed. Make : Sheetal (IOC) or equivalent
Supply , fixing and commissioning in replacement of Scroll Compressor of Capacity 11 TR with all its specification including removing of Old Unsv compressor complete all as per specified & directed.
M&L for Servicing of Compressor Suction and discharge Shut-off Valves by replacing Teflon washers and hard ware for proper functioning complete all as per specified & directed.
Rewinding of 11 TR outdoor unit fan motor complete all as per specified & directed.
M&L for servicing and over hauling of 66/33 TR AHU Blower motor of 7.5 HP including varnishing the stator and replacing the worn out drive end/driven end bearings and greasing and reassembling and testing complete all as per specified & directed.
S & F for replacement of UNSV "V" belts suitable for 7.5 HP air blower motor size of "V" belt taking down old unsv one complete, all as specified and directed .
Supply and fixing in replacement of Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 6 run of size 10 Sqmm, earth continuity conductor of 2 run and size 10 Sqmm to be drawn through and including PVC conduit 32mm dia medium Grade, ISI mark surface in walls/roof/floors incl taking down old unsv one all as directed by Engineer in Charge.Notes:- (4 run of wires of 10sqmm and 2run of wire of 10 sqmm and one run of PVC conduit with clamping shall be measured as one unit.
M & L for cleaning and servicing of 10 KW Solar power plant ,invertor, DC wiring , tightening of solar panels including minor Spare part upto Rs 1000 each after disconnection the DC/AC Cable and resetting the plant after testing complete all as specified and directed.
M & L for cleaning and servicing of 20 KW Solar power plant ,invertor, DC wiring,tightening of solar panel including minor Spare part upto Rs 1000 each after disconnection the DC/AC Cable and resetting the plant after testing complete all as specified and directed.
Supply and Replacement of Solar Glass of 100 LPD suitable for existing panel incl taking down old unsv one complete all as specified and directed.
Supply and Replacement of Solar main heating Tank of capacity 200 LPD suitable for existing Tank incl taking down old unsv one complete all as specified and directed.
supply and fix in replacement of thermosate fixing the new one as requirement on site incl taking down old unsv one all as specified and directed.
M&L for Servicing of Solar water Heater 100/200 LPD HHC System including changing of gasket, minor spares part as per requirement on site complete all as specified and directed
M&L for Chemical washing of collector and storage tank by using Hydro chlorine chemical oil (with in three to four month) all as per site requirement complete all as per specified & directed.
M & L for Cleaning of panel glass with soap oil (within three to four months) complete all as per specified & directed.
Removing unserviceable and refixing the new one heating elements suitable for existing make and size single phase 2kw, 230 V complete all as specified and directed
M&L for checking the inlet and outlet piping, fixing GI pipes , value , flange joints up to bib cocks and arresting the leakage if any , recording the temperate of the hot water and servicing overall system complete all as specified and directed
Supply and fixing in replacement of Rotational moulded polyethylene water storage tanks 500ltrs (cylindrical vertical with closed top) hoisted and fixed in position and fixed in position all as specified in SSR part I
Supply and fixing in replacement of Sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 2.5 Sqmm, earth continuity conductor of size 2.5 Sqmm to be drawn through and including PVC conduit 20mm dia medium Grade, ISI mark surface in walls/roof/floors incl taking down old unsv one all as directed by Engineer in Charge.Notes:- (i)Two wires of 2.5 sqmm and one wire of 2.5 sqmm and one run of PVC conduit with clamping shall be measured as one unit.
M&L in replacement of MCB SPN 240 Volts, 'C' series, Double pole breaking capacity 10 KA of rating 32 Amps inluding covering box of suitable size incl taking down old unsv one complete all as specified and as directed.
M&L for duct insulation with resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation 50mm specified and including the following:- (a) M&L for cleaning the duct surface (to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) M&L for applying rubber based adhesive CPRX compound. (c) M&L for sealing of all longitudinal joints and circular overlaps with and including Aluminium foil tape 50 mm wide, to make the insulation leakproof. (d)M & L for securing the insulation with and including mechanically fastened nylon/steel straps of size 12 mm/50 mm at maximum intervals of 1.2 mtr.
S&F Pin type capacitor suitable for 11TR outdoor unit of package type AC and 3 phase supply System including taking out of old unserviceable capacitor complete all as specified and as directed.
Rewinding of indoor unit fan motor of packege type AC including taking down the unit from POP type false ceiling and fix the same after repaire of motor and making the disturbed false ceiling same as origional complete all as specified and as directed.
S&F Pin type capacitor suitable for indoor unit of package type AC and 3 phase supply System including taking out of old unserviceable capacitor complete all as specified and as directed.
srisaienterprises (BID ID -3204014)
Srinivash Engineers (BID ID -3203399)
BHATNAGAR ASSOCIATES (BID ID -3205723)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .