Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.9 LAccepted-Finance | L1 | Accepted-Finance Quoting
Lower rate | |
| 2 | L2₹21.6 L+₹1.7 L (8.49%)Rejected-Finance 9TH FLOOR ABHIJEET MITHAKALI SIX ROADS MITHAKALI AHMEDABAD GUJARAT 380006 | AHMADABAD | GUJARAT | 380006 | L2 | Rejected-Finance Quoting
Higher rate | |
| 3 | L3₹22.3 L+₹2.5 L (12.3%)Rejected-Finance | L3 | Rejected-Finance Quoting
Higher rate | |
| 4 | Rejected-Technical 10B DR LAHIT BANERJEE SARANI GROUND FLOOR KOLKATA 700 073 | KOLKATA | KOLKATA | WEST BENGAL | 700073 | - | Rejected-Technical Due to insufficient documents |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
3 Jan 2024, 3:00 pmClosed
Superintending Engineer,Western El.Circle,PWD
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Proposed Construction of Collectorate Complex at Kalyanpur Housing for the office of the District Magistrate, Paschim Bardhaman----- Additional work for Air-Conditioning System..
2023_WBPWD_623744_1
WBPWD/SEWEC /AED /NIQ-131/2023-24_2nd Call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
Asansol
Please refer Tender documents.
5 documents required · 5 mandatory
₹40,000
Office of the Superintending Engineer, Western Ele
18 Jan 2024
15 Dec 2023
5 Jan 2024
15 Dec 2023
3 Jan 2024
18 Dec 2023
16 Dec 2023 - 18 Dec 2023
18 Dec 2023
Amount
Supply,Installation ,Testing & Commissioning of 4way VRV/VRF Ceiling suspended Compact Cassete Units complete with all accessories suspended from ceiling comprising with 4nos.6mm dia GI threaded down rod supports fixed with L type heavy duty GI clamp whose one side fixed on ceiling GI fastener bolt of each down rod and other site connected with indoor unit of suitable size of double nuts and double washers etc as required as per the following Capacity complete with drain pump and cordless remote etc. as required as per following capacity (As per OEM standard and should be compatible with Hitachi make ODU model No RAS24HNBCMQ1 and as per direction of EIC) 4 way Cassete type IDU with Minimum. a)5HP,Nominal Cooling Capacity:-14KW,Nominal Heating Capacity:16KW,,Refrigerant R-410A, Airflow(Hi2/Hi/Me/ Lo) -1306/1165/918/741 ,Motor Output-127W (Make-Mitsubishi / Blue Star / Toshiba /Hitachi / Carrier/ Voltas / Daikin) (For 1st Floor meeting hall)
b) 3HP,Nominal Cooling Capacity:-8KW,Nominal Heating Capacity:9KW,,Refrigerant R-410A,Airflow(Hi2/Hi/Me/Lo)-953/812/635/494,Motor Output-57W (Make-Mitsubishi / Blue Star / Toshiba /Hitachi / Carrier/ Voltas / Daikin) (04 Nos for 2nd floor meeting hall and 03 Nos for DM Chamber)
c)2HP,Nominal Cooling Capacity:-5.6KW,Nominal Heating Capacity:6.3KW,,Refrigerant R-410A Airflow(Hi2/Hi/Me/ Lo)-777/600/494/388 ,Motor Output-57W (Make-Mitsubishi / Blue Star / Toshiba /Hitachi / Carrier/ Voltas / Daikin) ( For 03 Nos ADM's Chamber)
Supply and fixing of AI powder coated continuous linear bar Grill (Make- Premier, Dynacraft/ EIC approved.) with necy. Screws,washer etc as required.[For 114nos. IDU]
Supply & fixing of fire retardant nonporous double layer flexible connection between HAT duct to False ceiling as per direction of E.I.C.
Providing and fixing Aluminium frame work with(25mm x 25mmx2mm thick) Aluminium angle and (38.5mmx25mm x2mm thick) Aluminium hollow bar duly fixed in wall and suitable for fixing composite panel false ceiling with necessary screw, clips etc as par direction of EIC incl providing and fixing exterior quality Aluminium Composite panel wall cladding on existing AL frame work with GI brackets, ACP fixed on the existing frame work by floding the edges of ACP panel (engraving the rear surface of ACP sheet wall matching color) with CP angle, cleats and stainless steel screw forming grooves at the periphery of AC panel, such grooves filler with foam and silicon sealent etc complete with all material (but included the cost of silicon sealent), labour, scafolding and other incidental charges incl. cutting ACP panel recessed LED fittings if required as par direction and specification of EIC (a) 3mm thick(0.25mm AL.+2.5mm LDPE + 0.25 AL PVDF Coating)
Charges for making Trap Door made of Aluminium Channel& Plywood/ board of approved make 16mm thick for IDU Maintenance provision in future.
JOHNSON CONTROLS HITACHI AIR CONDITIONING INDIA LTD.
IDEAL INCORPORATE SOLUTION
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .