Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹72.9 CrAccepted-AOC 201 202 2ND FLOOR FITWELL HOUSE OPP HOME TOWN LBS MARG VIKHROLI W MUMBAI 400083 | MUMBAI SUBURBAN | MAHARASHTRA | 400083 | ₹72.9 Cr Quoted ₹74.7 Cr | L1 | Accepted-AOC Low Rate |
| 2 | L2₹80.8 CrRejected-Finance | ₹80.8 Cr | L2 | Rejected-Finance High Rate |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹68.2 Cr
EMD Value
₹35 L
Closing Date
7 Sept 2022, 5:00 pmClosed
CEO MMB
Chief Executive Officer, Maharashtra Maritime Board, Indian Mercantile Chamber, 2nd floor, Ramjibhai Kamani Marg, Ballard Estate, Mumbai-400 001
Construction of Proposed Office Building on G- Block, Plot no. C-47, at Bandra Kurla Complex, Mumbai for Maharashtra Maritime Board
2022_MMB_820191_1
MMB/CEO/ ENGG/Thn/21-22/64
Open Tender
Civil Works - Buildings
730 days
G- Block, Plot no. C-47, at Bandra Kurla Complex
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
₹35 L
Mumbai
27 Jan 2023
21 Jul 2022
9 Sept 2022
21 Jul 2022
7 Sept 2022
3 Aug 2022
21 Jul 2022 - 3 Aug 2022
3 Aug 2022
Amount
Construction of Proposed Office Building on G-Block, Plot No. C-47, at Bandra Kurla Complex, Mumbai for Maharashtra Maritime Board
Item No. 01 Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 100 Km. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.)
Item No. 02 Excavation for foundation in earth, soils of all types, sand,gravel and soft murum, including removing the excavated material upto a distance of 100 Km. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m to 3.0m) By Mechanical Means. Including royalty and other taxes and lead upto 100 Kms
Item No. 03 Excavation for foundation in earth, soils of all types, sand,gravel and soft murum, including removing the excavated material upto a distance of 100 Km. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. ( Lift from 3.00m to 4.50m) By Mechanical Means Including royalty and other taxes and lead upto 100 Kms
Item No. 04 Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 100 km. beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth /murum, ramming, watering including shoring and strutting etc. complete (lift upto 1.5m) Including royalty and other taxes and lead upto 100 Kms
Item No. 05 Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 100 km. beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete. (Lift from 1.5m To 3.0 m.) Including royalty and other taxes and lead upto 100 Kms
Item No. 06 Excavation for foundation in Soft rock and old cement or lime masonry foundations including removing the excavated material upto a distance of 100 km. beyond the building area and stacking as directed, including dewatering, preparing the bed for the foundation and necessary back filling with available earth/murum, ramming ,watering including shoring and strutting etc. complete(Lift from 3.00m to 4.50m)Including royalty and other taxes and lead upto 100 Kms
Item No. 07 Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 100 km. beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift upto 1.5 m). Including royalty and other taxes and lead upto 100 Kms
Item No. 08 Excavation for foundation in Hard rock by chiselling, wedging, line drilling, etc. including trimming and levelling the bed, removing the excavated material upto a distance of 100 km. beyond the building area stacking as directed, dewatering and back filling with available earth/ murum watering, ramming etc. complete. (Lift from 1.50m to 3.0m) Including royalty and other taxes and lead upto 100 Kms
Item No. 09 Providing preconstructional antitermite treatment as per I.S. 6313 (Part-I) to the soil along the external face of building by punching holes of 1.2 of 1.5 C.M. diaMeter about 30 -60 cm deep at 15 cm c/c as close to the wall as possible and to inject 0.5 percent of aldrin or clorophyrifos at the rate of 7.5 litres per hole and sealing the same with proper filling and covering 10 years guarantee on bond paper.
Item No. 10 Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 cm to 20 cm including watering and compaction etc. complete.(Murum filling at Basement 2 level)
Item No. 11 Providing trap rubble stone soling 15 cm to 20 cm thick including hand packing and compacting etc. complete.
Item No. 12 Providing and laying Cast in situ/Ready Mix cement concrete in M20 of trap metal for bed blocks, foundation blocks and such other items including bailing out water, plywood/steel formwork, laying/ pumping, compacting, roughening them if special finish is to be provided, finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.), with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade) - PCC below Raft & footing
Item No. 13 Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap / granite/quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. columns as per detailed designs and drawing or as directed including centering formwork, cover blocks laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Item No. 14 Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap / granite /quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. columns as per detailed designs and drawing or as directed including centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade
Item No. 15 Providing and laying Cast in situ/Ready Mix cement concrete M-50 of trap metal for R.C.C. columns as per detailed designs and drawing or as directed including centering, formwork, cover blocks, laying/pumping, compactionfinishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
2nd Basement floor
1st Basement floor
Ground floor
1st floor
2nd floor
Item No. 16 Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap metal for R.C.C. columns as per detailed designs and drawing or as directed including centering, formwork, cover blocks, laying/pumping, compactionfinishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete.With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
3 Floor
4 Floor
5 Floor
6 Floor
Item No. 17 Providing and laying Cast in situ/Ready Mix cement concrete M-35 of trap metal for R.C.C. columns as per detailed designs and drawing or as directed including centering, formwork,cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
7 Floor
8 Floor
9 Floor
Item No. 18 Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap metal for R.C.C. columns as per detailed designs and drawing or as directed including centering, formwork,cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Above Terrace Floor
Item No. 19 Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Item No. 20 Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
PT + RCC Beam
Basement 2
Basement 1
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Terrace
Above terrace
Item No. 21 Providing and laying Cast in situ/Ready Mix cement concrete M-30 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including centering, formwork, cover blocks, laying/pumping, compactionfinishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Item No. 22 Providing and laying Cast in situ/Ready Mix cement concrete M-40 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including centering, formwork, cover blocks, laying/pumping, compactionfinishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Basement 2
Basement 1
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Terrace
Above terrace
Item No. 23 Providing and laying Cast in situ/Ready Mix cement concrete in M-50 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Basement 2
Basement 1
Ground
1 Floor
2 Floor
Item No. 24 Providing and laying Cast in situ/Ready Mix cement concrete in M-40 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
Basement 2 - Retaining Wall
Basement 1 - Retaining Wall
3 Floor
4 Floor
5 Floor
6 Floor
Item No. 25 Providing and laying Cast in situ/Ready Mix cement concrete in M-35 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
7 Floor
8 Floor
9 Floor
Item No. 26 Providing and laying Cast in situ/Ready Mix cement concrete in M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete.(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
10 Floor
11 Floor
12 Floor
Terrace Floor
Above Terrace
Item No. 27 Providing and laying Cast in situ/Ready Mix cement concrete in M-40 of trap / quartzite /granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
2nd Basement floor
1st Basement floor
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Terrace Floor
Item No. 28 Providing and laying Cast in situ/Ready Mixcement concrete M-30 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings including centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
For Ground Floor
Above Terrace
Item No. 29 Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete.
2nd Basement floor
1st Basement floor
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Terrace Floor
Above Terrace
Item No. 37 Providing and fabricating structural steel work in rolled sections like joists, channels, angles, tees etc. as per detailed design and drawings or as directed including cutting, fabricating, hoisting, erecting, fixing in position making riveted / bolted /welded connections without connecting plates, braces etc. and including one coat of anticorrosive paint and over it two coats of oil painting of approved quality and shade etc. complete.
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace
Above Terrace
Item No. 38 Providing and applying two coats of synthetic enamel paint of approved colour to new /old structural steel work and wood work in buildings, including scaffolding if necessary, cleaning and preparing the surface (excluding primer coat) etc. complete. For DG Set Area
Item No. 39 Providing and fixing in position to the exact profile and prestressing the high tensile strands to specified ultimate strength, standard end anchorages, cable ducts, grouting ducts after prestressing and bearing plates with wedges as per detailed drawings including necessary plant and machinery for prestressing etc. complete.
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 40 Providing and laying Hyperplas standard or equivalent polymeric multiple monolithic five layer water proofing flexible, pliable and high tensile strength membrane (3 Kilogram/Square Meter) & consist of centre core of 90 micron thick High Molecular High density Polyethylene film (HMHDPE) which is protected on both the side with polymeric mix. Applying the membrane by thermofusing to roof & parapet after applying thin film of hot blown bitumen 85/25 or 90/15 grade @ 1.2 Kilogram/Square Meter maximum as per surface condition or Hyperplas primer @ 250 gms/Square Meter as per site condition on the surface to be treated with 10 cm overlapping including finishing etc. complete and covering guarantee of 7 years on stamp paper of Rs. 100/- and as directed by Engineer-in-charge. (Prior permission of S.E.in writing is necessary before inclusion of this item in estimate).
Item No. 41 Providing and applying required coats of a water based Evercrete Deep Penetrating Sealer (DPS) on cement concrete surface like roads, beams, and columns, plastered walls, basements, roofs, potable water tanks etc to react with cement and to penetrate concrete structure thereby making it resistant to chemicals / chlorides water to make it dust proof and to act as a water resistant at the same time which Strengthens the treated surface and reduce the curing period etc complete. - Note -- for item Number 7 to 4 prior approval of Superintending Engineer will be necessary
2nd Basement floor
Terrace Floor
Above Terrace
Item No. 42 Providing and laying mechanical protective layer over water proofing membrane with cement screed plaster 1:5 after laying chicken mesh over membrane including curing etc. complete 20 mm thick with cost of chicken mesh etc. complete and covering 7 years guarantee on court stamp paper of Rs.100/- including necessary testing specified by Engineer (Prior permission of S.E. is necessary before inclusion of this item in estimate) (Note :- This item shall be executed over item Number 5 of BD-J Water Proofing)
Item No. 43 Providing and applying a base coat comprising of 1KilogramPolydee-MC and 1Kilogramfresh cement after wetting the surface followed by drying the surface for 2 days, apply primer coat of TP-40 and after drying, applying Polydee-11 two component (mixing ratio 2 A : 1 B) ) Antibacterial food grade coating inside drinking water tank in two coats with time interval of minimum 8 hrs. covering 7 years guarantee on Court Fee Stamp Paper of Rs. 100/- etc. complete.
Item No. 44 Providing waterproofing in W.C. and bath including brick bat coba in all position including providing and laying 12mm bedding in cement mortor 1:3 on vergin concrete slab with waterproofing compound @ 1Kilogram/per bag of cement laying brick bat coba of required thickness in cm 1:5 with waterproofing compound 1 Kilogram/bag of cement grouting and finishing the top layer with 20mm thick brick bedding in cm mortor 1:3 with waterproofing compound 1 Kilogram/per bag of cement and testing the treated portion for 48 hours by pond test and covering ten years' guarantee on requisite stamp paper including curing etc. complete.
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Item No. 45 Providing waterproof plaster in W.C. and bath 20 mm thick for dado in cement mortar 1:3 with neat finishing, floating using waterproofing compound at the rate of 1 kg. per bag of cement of approved make and manufacturer and curing (and filling joints of Nahani trap and any outlet by properly) etc. complete.
Ground floor
1st floor
2nd floor
3rd floor
4th floor
5th floor
6th floor
7th floor
8th floor
9th floor
10th floor
11th floor
12th floor
Item No. 46 Providing cement based water proofing treatment to terraces (Indian water proofing or alike) with brick bats laid in required slope to drain the water for any span after cleaning the base surface. Applying a coat of cement slurry admixed with approved water proofing compound and laying the brick bats on bottom layer in C.M.1:5 admixed with approved water proofing compound filling up to half depth of brick bats, curing this layer for 3 days, applying cement slurry over this layer joints of brick bats with C.M.1:3 admixed with approved water proofing compound and finally top finishing with average 20 mm. thick layers of same mortar added with jute fiber at 1 Kg per bag including finishing the surface smooth with cement slurry admixed with approved water proofing compound. Marking finished surface with false squares of 300mm x 300 mm. making the junctions at the parapet rounded and tapered top for required height, with drip mould at the junction of plaster and parapet and curing and covering 10 years Guarantee against leakproofness on Court fee stamp paper of Rs. 500/- including ponding test etc. complete.
For Ground Floor
12 Floor
Terrace
Item No. 47 Providing and laying in situ M-20 cement concrete of trap / granite / quartzite / gneiss metal with 15% plum of trap stones for foundation and bedding of retaining walls and jetty etc. including necessary formwork, compacting, curing, bailing out water manually in tidal range etc. complete.
Item No. 48 Dewatering on BHP basis by using water pump including diversion of stream, providing cofferdams, earthern bunds etc. as may be necessary for foundation and other parts of the the works and pumping out water during and after excavation as may be required by using 10.0 to 19.0 BHP pump etc. complete. (prior approval of Superintending Engineer will be necessary)
Item No. 49 Providng Grouting by specially prepared grout of approved make chemical with cement in proportion 1:3.5 (1 part chemical & 3.5 part cement by weight) along wih 50 ml super plasticizer non cracking antiwash high strength polymer cement grout P C grout available in bags or equivalent with proper water for injectable consistency and applying it in the body of structure like slab, beam, column, pillars, deckslab, retaining wall, basement, underground and elevated water storage reservoir concrete and brick wall, crack portion of structure etc. by injectng method, to achieve its original strength including drilling of suitable diameter drills holes at 2 to 4 Nos. per sqm. using caps and nozzle grouting machinery necessary, scaffolding, finishing and covering gurantee of 10 years on court stamp paper of Rs. 100/- and necessary testing etc. complete. (Prior permission of S.E. in writing is necessary before inclusion of this item in estimate)
Item No. 50 Providing Autoclaved Aerated Concrete Block masonary of Ecolite or equivalent make conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in superstructure including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972)
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Item No. 51 Providing Autoclaved Aerated Concrete Block masonary of Ecolite or equivalent make conforming to IS:2185 (Part 3) - 1984 in extra fine jointing mortar of fixoblock of UltraTech or equivalent in Half brick thick wall including striking joints, raking out joints and scaffolding etc. Complete. (The test shall be carried out conforming to IS:6441 (Part I) - 1972)
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Item No. 52 Providing and applying gypsum plaster ( with Gypsum material of Gypsum India / Mega Sign or equivalent make ) with finishing with gypsum material in 10 to 13 millimeter thickness to previously plastered surface / or on newly brick surface ( Excluding rough cast plaster ) in all position including preparing and Finishing the surface scaffolding etc.complete.
a) Location : Walls
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Item No. 53 Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etc complete.
a) Location : Ceiling
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Above Terrace Floor
Item No. 54 Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete.
Item No. 55 Providing and applying Royale Luxury Emulsion of approved make on internal wall surface as detailed below Scrapping for surface with emery paper and wipe clean for area. wall primer with brush by adding mineral turpentine oil by 8 to 10 % or water by 15 to 20% allowing to dry for 6 to 8 hoursAfter applying Asian / Berger / Nerolac / Dulex Paints or equivalent acrylic wall putty with appropriate prpportion of water of allow to dry for period of 4 to 6 hours of activity. Scrapping with emery paper and wipe clean Applying paints Royale Luxury emulsion 1st coat with brush water content water 40 to 45% or 65 to 70% by role Applying paints Royale luxury emulsion 2nd coat with brush with water content 40 to 45 % or 65 to 70 % by roller. (With prior approval of S.E.)
a) Location : Internal walls & Ceiling
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace Floor
Above Terrace Floor
Item No. 56 Providing and applying two coats of exterior acraylic emulsion paint confirming to corresponding I.S. of approved manufacture and of approved colour to the plastered surfaces including cleaning ,preparing the plaster surface, applying primer coat ,scaffolding if necessary , and watering the surface for two days etc complete.
Item No. 57 Providing and fixing aluminium grill`(5.13 Kg/Sqm) decorative of various sizes as per detail drawing and specification etc. complete. (Prior permission to be obtained from S.E. before execution of this item) ( 5.13 Kg/Sqm)
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
Item No. 58 Providing and fixing 40mm diameter and 1.5 mm thick Stainless steel hand railing in S.S.304 Grade including fabricating ,fixtures, errecting, necessary welding, grinding, finishing, buffing to stainless steel pipe etc. complete
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 59 Providing and fixing 900mm high S.S.304 Grade Stainless steel railing with 40mm diameter and 1.5mm thick at top,40mm diameter and 1.5mm thick vertical supports spaced at 1.5m center to center and 8mm thick toughened glass including fabricating ,fixtures, errecting , necessary welding , grinding , finishing, buffing to stainless steel pipe etc. complete
12 Floor
Item No. 60 Providing and fixing mild steel grill gate with angle iron frame 65mm x 65mm x 10mm with iron bars at 150mm C/C and diagonal flats as per the detailed drawing including hinges, Item No. 59 pivot block locking arrangement, welding riveting and oil painting of three coats of approved shade Weight of gate 35 Kg/Smt.
Item No. 61 Providing and Fixing Processed Stone Cladding on wall surface/plywood surface. RCC pardi/Wall and all type of Interior, Exterior Compound wall and Gate etc. of cladding processed stone with material of Processed clay, Woodenchips, Silicasand, Cement, GFRC admixtures, Colour pigments, Fiber upto thick of 230 mm/ 25 mm including scaffolding, fixing of screw, etc. (As directed by Engineer in Charge)
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 62 Providing and fixing SS-304 strips of size 280mm x 35mm of the approved brand and make inside the building on all floors in corridors, lobbies level differences etc. as per accessibility standards and as per the installation instructions prescribed by the manufacturer, using the necessary adhesive including finishing work up to the satisfaction of the engineer in charge complete.
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 63 Design, supply, fabrication & erection of approved structural glazing using specially designed Vertical Mullion & HorizontalTransoms of Required size & as per architect's approved Grid work with aluminium rectangular sections to be fixed in masonary at interval of eachfloor on concrete slab with 80 mm x 100 mm x 5mm thick galvanized M & Langle fixed on wall side with raw bolt size of 10 mm x 90 mm with necessary bolts & washers / nuts for the plumb the linelevels. the glass panel's shall be fixed on a specially designed architectural sub- frame using Dow Corning 995 strural sealant & GE Silicon (SSG - 4000) sub frame would be fixed on main frame grid in amanner that no aluminium frame is visible from outside & groovesbetween the glass panel shall be filled with weather sealant of Dow corning 789 / GE Sil proof to made it air tight, water proof & dustfree thus giving it a flush look outside. Glass will be of 6 mm thickGlaverbel reflective type with heat strenghthened toughened
Ground
12 Floor
Terrace
Item No. 64 Providing and fixing glazing panels & doors using 12mm thk toughen clear glass (confirming to ASTM Standards C-1048) supported bycchannel (embedded in the floor) at the bottom & side edge and wall connecting profile at the top edge,stainless steel articulated countersunk bolts threaded bolts,chemical fasterners,etc., glass panel size as per design and drawing including applying colourless sealant of joint incl. required edge polish, making glazing water tight etc. Destructive node joint test reports to be submitted forestablishing the safety factor, including operating hardware, SS patch fittings, fabricated long length satin finish SS 304 handles,patchlock, floor springs etc., complete as directed by the architect for frameless patch doors,single or twin leaf shutters with fixed panel on top. Hardware-Droma BTS 80 Floor Spring.
Ground Floor
First Floor
Second Floor
Third Floor
Fourth Floor
Fifth Floor
Sixth Floor
Seventh Floor
Eighth Floor
Nineth Floor
Tenth Floor
Eleventh Floor
Twelve Floor
Terrece
Item No. 65 Providing and fixing sheet glass of 24 oz. for all size including putty etc. complete
Item No. 66 Providng , Supplying & Fixing Spider clamp on Glass Sheet including transportation labour charges, with finishing materials.
Item No. 67 Providing and laying in situ cement concrete M30 with tremix treatment for 200 mm thickness for flooring with groove cutting of 4mm wide and 20mm deep with necessary refilling with bitumen etc. complete.
i) Basement 2 floors
ii) Basement 1 floors
Item No. 68 Providing and fixing factory made Hydraulically pressed Mechanically vibrated and compacted precast inter locking cement concrete paving blocks 100MM thick in M-50 grade of approved size and shape for City streets and roads with high volume/ heavy traffice as specified and as per IS 15658:2006 including cost of all materials, manufacturing, curing, transportation of blocks to work site including loading, unloading and stacking as directed, laying paving blocks in position over prepared bed of VSI crushed sand of 50 mm thickness including necessary excavation in all stratas, spreading blindge of fine sand over the prepared bed, compacting blocks by plate vibrator etc. complete.
Item No. 69 Providing and laying machine cut and mirror polished approved coloured ITALIAN MARBLE SLAB approved size, 20 mm +/- 2 mm thick of approved quality with approved qality, Italian marble inlays for flooring in required pattern on a bed of 1:4 cement mortar 25- 30 mm average thickness including neat cement float, filling joints with neat coloured cement slurry, curing, polishing and cleaning complete. ( Basic rate of ITALIAN marble Rs. 3500/-per Sq.M)
Item No. 70 ITALIAN MARBLE CLADDING Providing and fixing machine cut and mirrorpolished approved coloured ITALIAN MARBLE SLAB with inlays of approvedsize,20mm +2mm thk. Of approved quality for required patternon a bed of 1:4 CM 25mm average thickness including neat cement float,filling joints with neat coloured pigment,curing,polishing andcleaning etc.complete. (Basic rate of ITALIAN marble Rs.3500/-per Sq.M)
Item No. 71 Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace
Item No. 72 Providing and laying ceramic tiles having size 30 cm. x 60 cm. confirming to corresponding I.S. for dado and skirting in required position with readymade adhesive mortar of approved quality on plaster of 1:2 cement mortar including joint filling with white/ colour cement slurry cleaning curing etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 73 Providing and laying vitrified mirror / glossy finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 74 Providing and laying 600 x 600 x 8 mm thk. vitrified tiles as specified below conforming to I.S.15622-2006 with water absorbtion less than 0.08% for flooring of an approved, quality, make and pattern /design for flooring including cement mortar bedding of 25 mm thick in 1:4 proportion, cutting, leveling, jointing, filling the joints by neat cement slurry or approved colour grout, curing, finishing etc complete as directed by Engineer In Charge. Light coloured antiskid / matt vitrified tiles
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace
Item No. 75 Providing and laying machine cut machine polished machine cut Kota stone slabs 20 to 25 mm thick for treads and risers of steps and staircases, with rounded nosing for the treads on a bed of 1:4 cement mortar including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terace
Item No. 76 Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etc. complete.
Item No. 77 Providing and laying chequered tiles of approved quality of size 30 cm x 30 cm, confirming to corresponding I.S. for flooring in required position laid on a bed of 1:4 cement mortar including cement float, filling joint with cement slurry cleaning curing etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terace
Item No. 78 Providing and preparing kitchen otta up to 75 cm width,made up from 30 mm thick and 75 cm high vertical support for kadppa at 1 m. c/c of 25 mm thick both side polished kadappa middle shelf and bottom of 20 mm thick one side polished kadappa with facia patti of 20 x 50 mm kadappa including all material labour cutting fixing with cement mortar and araldite curing polished and cleaning etc. complete.
10 Floor
11 Floor
Item No. 79 Lowering down the debris obtained from breaking and removing the cement plaster/burnt brick masonry of the first floor by any means without causing dust nuisance and damage to structure, stacking the same as and where directed including cleaning the site complete.
Item No. 80 Providing and fixing green marble of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing / moulding the sharp edges wherever necessary, curing, etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 81 Providing and fixing solid core flush door shutter in single leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete.
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Item No. 82 Providing and fixing in position. (as per I.S.1868 / 1982) Aluminium sliding window of two t racks wi th rectangular pipe having overall dimension 63.50 x 38.10 x 1.02 mm at weight 0.547 kg/ Rmt . and window frame bot tom t rack sect ion 61.85 x 31.75 x 1.20 mm at weight 0.695 kg/ Rmt . Top and side t rack sect ion 61.85 x 31.75 x 1.30 mm at weight 0.659 kg/ Rmt . The shut ter should be of bear ing bot tom 40 x 18 x 1.25 mm at weight 0.417 kg/ Rmt . Inter locking sect ion 40 x 18 x 1.10mm at weight 0.469 kg/ Rmt . And handle sect ion 40 x 18 x 1.25 mm at weight 0.417 kg/ Rmt . and top sect ion 40 x 18 x 1.25 mm at weight 0.417 kg/ Rmt . As per detai led drawings and as directed by Engineer in charge wi th all necessary Aluminium sections fixtures and fastenings such as roller bear ing in nylon cast ing and self locking catch fitted in vertical section of shutter including 5 mm thick plain glass with all required screws and nuts etc, complete. With colour Anodising with box.
Item No. 83 Providing and fixing rolling shutter fabricated from steel laths of minimum thickness 0.9 mm with lock plate of 3.15 mm thickness reinforced with 35 x 35 x 5 mm angle section fitted with sliding bolts and handles for both sides, deep M.S. channel section of depth and thickness not less than 65 mm and 3.15 mm respectively with hold fast arrangements, M.S. Bracket plate 300 x 300 x 3.15 mm minimum size and shape with square bar, suspension shaft of minimum 32 mm diameter, hood cover of M.S. sheet not less than 0.9 mm thickness and of any size at top and safety devices including mechanical gear operation arrangement consisting of worm gear wheels and worms of high grade cast iron or mild steel and one coat of red lead primer etc. complete. (I.S. 62481979) (With mechanical gear)
Item No. 84 Providing and fixing steel ventilator fully glazed partly fixed as per detailed drawing with hot dip zinc coating including fabricating glazing with plain / obscured glass panes 5 mm thick and approved type quality and iron oxidized fixtures and fastening with guard square bars 12 mm 10 cm c/c and oil painting 2 coats etc. complete.
Item No. 85 Providing and fixing fire doors with 2 hour fire rating conforming to IS: 3614 (Part 2), BS 476 (Parts 20 & 22), ISO 834 ; 45 mm thick fully flush, double skin door shell with lock seam joints at stile edges made from 1.25 mm thick galvanized steel sheet including door frames made from 1.6 mm thick galvanized steel sheet formed to double rebate profile of size 143 mm x 57mm as per manufacturer's instructions, door frames and shutter primed with Zinc Phosphate stoving Primer and finished with Polyurethane Aliphatic grade or epoxy paint including ironmongery consisting of stainless steel ball bearing butt hinges 3 mm thick fixed flush to the frame and shutter, full width horizontal handles (panic bar), concealed flush bolts, door closers, other standards fixtures and fasteners, etc. complete for the following clear opening sizes:
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace
Item No. 86 Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150Kilogramcapacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length aluminium tower bolts, 150mm dia. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.complete
Basement 2
Basement 1
Ground
1 Floor
2 Floor
3 Floor
4 Floor
5 Floor
6 Floor
7 Floor
8 Floor
9 Floor
10 Floor
11 Floor
12 Floor
Terrace
Item No. 87 Providing and Fixing Fully Glazed double shutter automatic Door Opening having following features Slim line modern Design Australian Made Designed for new standards Compact modular motor DesignHigh security electric locking No exposed wiring Energy Efficient Electronics Lock 600 VA UPS
Item No. 88 Road Marking with Hot Applied Thermoplastic Compound with Reflectorizing Glass Beads on Bituminous Surface- Providing and laying of hot applied thermoplastic compound 2.5 mm thick including reflectorizing glass beads @ 250 gms per Square Meter area, thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC:35 .The finished surface to be level, uniform and free from streaks and holes.complete.
Item No. 89 Providing and Laying of Rumble strips with Plastirib 2K, or equivalent 2 component cold plastic profiled material to give total width of 500 mm and height of 10 mm. Ramp provided to give width of 145 mm, width of ribs to be 55mm laid at centre to centre distance of 35 mm, with reflective glass beads @ 350 gm / Square Meter. The finished surface to be levelled, uniform and free from streaks and holes, to be applied on the edge lines, including surface cleaning and cost of all materials etc. complete.
Item No. 90 Supply, fixing, testing of glow sign board of station name board as per enclosed Annexure-"A". Made up of 26 SWG GI sheet and frame with hollow square pipe with backlight white flex sheet duly stretched in front with printed station name in tri language (Marathi, Hindi and English) in white with blue background. The illumination of board to be done with required 18/20-watt LED batten light fitting. The fixing of boards to be done with all required supply of masonry work and supply of all materials such as cement, sand, chips etc
Item No. 91 Supply & Installation of VRV or VRF OODU / IDU and Other Accessories VRV or VRF Out-Door Units SITC of Capacity (R-410A /R-407c or eco-friendly Refrigerant) Air Cooled type OUTDOOR UNITS of VRF system having hermetically sealed scroll inverter compressor, condenser coil fabricated from Seamless Copper tube & Plate type Al. Fins of Multi Row, Axial Flow, upward throw condenser fan, Condenser fan - motor unit, insulated refrigeration piping, power / control wiring, and earthing, external wiring between Indoor & Outdoor units, all system controls-safety. Each Outdoor units with High Pressure switch, Fan driver overload protector, Over current relay, Inverter Overload Protector & Fusible Plug. The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply, and IP 55 protection. The out door unit shall be installed on M.S. platform duly painted, as per specifications. Note: Anti corrosive resistance paint on all Out Door Unit and In Door Unit with also 100% on Copper pipe.
30 HP VRV (18 HP +12 HP ) clubed system
c) VRF Indoor Units : Ceiling suspended concealed type air condtioning unit
d) Remote control Supply & Installation of Remote control Corded Remote control for (Ductable)
Centralise Remote control
Item No. 92 Supply, Installation, Testing and Commissioning of Central remote controller must be integrable with the VRV/VRF system Complete operation & monitoring of VRV air conditioning system shall be possible through the control system.Following functions shall be possible i.) Controlling indoor units ii.) Zone control iii.) Malfunction code display iv.) All the functions available with wired remote controller v.) It should be possible to wire the remote to 1000m vi.) Remote start / stop of indoor units vii.) Mal function report. viii.) Colour LCD touch panel icon display ix.) Fault History up to 100 actions. x.) Simple Interlock Function xi.) Fire Alarm System interface Required hardware shall be suitable for operation between -10 Deg C to 50 Dg C & humidity range, of 0% to 98%, without condensation.
REFNET Joints
Item No. 93 Supply, Installation, Testing and Commissioning of Refnets as specified of pipe sizes from 1/4 " to 2"
Item No. 94 REFRIGERANT PIPING SITC of Seamless heavy gauge REFRIGERATION COPPER PIPING for VRF/ VRV system in 18 gauge, duly insulated with 13 mm/19 mm thickness. Nitrile Rubber Insulation. Refrigeration piping will have to be taken in the piping rack / Support individually connecting to Indoor units, including necessary supports, fittings, valves, Cable tray for exposed piping where ever required will be included.. The pipe sizes from 1/4 " to 1".(13 mm insulation) and 1-1/8 " to 2"(19 mm insulation) shall be used.( considered suction and liquid length quantities)
Item No. 95 Refrigerant Charging Supply, Installation,Testing and Commissioning charges along with Topping-up of Refrigerant
Item No. 96 Trey for Refrigerant Piping, Size as per requirted for said work(consider 175 Meters-01 lot)
Item No. 97 FRAME WORK Supply, fabrication and installation, Testing and Commissioning of MS base frame for outdoor units complete with epoxy painting, vibration isolation pads, supports, hangers, railing, brackets etc. Note: For constructions approved by Architect/ Engineer Incharge. Apply 2 coats of epoxy primer and 2 coats of finish painting (black paint) as approved by Architect. Stand to be made as per site conditions.
a) For 18 HP
b) For 12 HP
Item No. 98 DRAIN PIPING PVC Drain Condensate Drain Water piping constructed out of PVC / HDPE hard pipes, fitting, accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors. The pipes to be duly insulated with 10 mm Nitrile rubber insulation .
a) 32 mm Dia
b) 25 mm Dia
Item No. 99 SHEET METAL WORK GI Duct GSS Ducting:- Supplying fabrication installation testing and commissioning of GI. Sheet metal ducting. Zinc coated. Complete with all Standard Accessories, G.I.. Hardware, Self Adhesive elastomeric foam gasket, support etc as per SMACNA specification Prefered makes : (Tata, Jindal).
a) 22 G Ducting (above 750mm upto 1500mm anyside)
b) 24 G Ducting (upto 750mm any side)
Item No. 100 Continous Linear Grills Providing aluminium supply air diffusers & return air grills with volume control dampers 150mm wide
Item No. 101 Volume Control Dampers for Duct Supply and installation of volume control dampers, by pass dampers.
Item No. 102 Canvass Connections Supply, installation, testing and commissioning of Flexible double Canvass Connections for DUCTABLE, FCU & FAN.
Item No. 103 THERMAL & ACOUSTIC INSULATION Thermal Insulation for Duct : Providing thermal insulation to supply air ducting with 19mm.thickness nitrile rubber
Item No. 104 Accoustic Insulation for Duct Supply, installation, testing and commissioning of Acoustic lining of duct work with following type Providing acoustic lining to the initial portion of supply air duct from inside of the ducting using fiber glass crown 300*25mm thick rigid board or equivalent insulation material covered with 24 gauge perforated aluminium foil.
Item No. 105 POWER CABLES FOR ODU : Supply, laying, dressing, termination, testing & commissioning 1100 V grade, aluminium/copper conductor, PVC insulated, steel wire/strip armoured, PVC sheathed power and control cables as per specs. Of following sizes, to be laid on trays including clamping, as per specs.
4c x 6 sqmm cable (for 8 HP TO 12 HP ODU)
4c x 10 sqmm cable (for 18 HP TO above)
Item No. 106 POWER CABLES FOR IDU Supply, laying, dressing, termination, testing & commissioning 1100 V grade, aluminium/copper conductor, PVC insulated, steel wire/strip armoured, PVC sheathed power and control cables as per specs. Of following sizes, to be laid on trays including clamping, as per specs. 4c x 4 sqmm cable (for 1 HP TO 10 HP IDU)
Item No. 107 CONTROL CABLES FOR BETWEEN ODU AND IDU Supply & Installation of All control cables between indoor and outdoor unit and between ODU & ODU laid in PVC pipe and clamped . 2c x 1.5 sqmm shielded cable (Control cable)
Item No. 108 CONTROL CABLES FOR BETWEEN IDU AND THEIR REMOTE Supply & Installation of All control cables between indoor and their Remote laid in PVC pipe and clamped . 2c x 1.5 sqmm YRY cable
Item No. 109 EXHAUST FANS Axial Exhaust Fan: (AS SMOKE EXTRACTION FAN) Supply, installation,testing and commissioning of axial exhaust air fan are required to be in compliance with the requirements of Class B performance, as defined in clause 9 of BS 7346:Part 2:1990. This requires the fan to be subjected to a rated temperature of 250C for a rated duration of 120 minutes. with M.S floating foundations, motors, and all other accessories whether specifically mentioned or not. Note: Fan motor rpm not to exceed 600. Preferred Makes : Kruger/Flaktwood/Airovent
a) Air Qty : 15000 CFM (For BASEMENT 2 & Basement 1) Static Pressure : 25 mm Wg , Motor :10 kW,Mounting : Ceiling Suspended
b) Air Qty : 2000 CFM (For PUMP ROOM) Static Pressure : 15 mm Wg , Motor :1.5kW,Mounting : Ceiling Suspended
c) Air Qty : 6000 CFM (For common Toilet) Static Pressure : 32 mm Wg , Motor :2.8 kW,Mounting : Ceiling Suspended
Item No. 110 In line exhaust fan-The inline fans shall be complete with Centrifugal fan, unit casing access door, electrical connections canopy fan shall be suitable for outdoor installation A/C contractor to include all accessories for installation of inline fan. Fresh air to have 6mm thick pad filter with frame.
a) 800CFM @30 MM Static (OWC )
b) 800 CFM @30 MM Static ( Substation)
c) 100CFM @15 MM Static ( pantry)
Item No. 111 FRESH AIR FANS Axial Fresh Air Fan: Supply, installation,testing and commissioning of Axial exhaust air fan with motors, and all other accessories whether specifically mentioned or not. Fans for ventilation duty shall include pre-filters on M.S.framework mounted on the wall opening for fresh air intake. Filters shall be 50mm thick, and pre-filters and shall be easily removable for cleaning. Filter area shall be suitable for 107 M.P.M. air velocity. Note: Fan motor rpm not to exceed 600. Preferred Makes : Kruger / Flaktwoods /Airovent
a) Air Qty : 24000 CFM (For BASEMENT 2) Static Pressure : 25 mm Wg ,Motor:13 kW, Mounting : Ceiling Suspended
b) Air Qty : 8000 CFM (For BASEMENT 1) Static Pressure :25mm Wg,Motor : 4 kW, Mounting : Ceiling Suspended
c) Air Qty : 15000 CFM (For LIFT WELL PRESSURIZATION & Mechanical Ventilation) Static Pressure : 25 mm Wg ,Motor : 7.5 kW,Mounting : Ceiling Suspended
Item No. 112 Jet Fans: Supply, installation,testing and commissioning of Jet Fans with motors, and all other accessories whether specifically mentioned or not. Preferred Makes : Kruger / Dynair/Flaktwood a) Air Qty: 4804 CFM (Normal Mode) (For Basement) Air Qty :2,650 CFM (Fire Mode),Motor : 0.11 KW / 0.75 kW, Air Throuhg : 20 Meter Max, Mounting : Ceiling Suspended
b) CO sensors -Supply, installation,testing and commissioning of CO sensors with cabling and all other accessories whether specifically mentioned or not.
c) Logical Control system for Basement Ventilation: Supply, installation,testing and commissioning of Logical Control system should be BMS Compatible.
d) Logical Control system for lift lobby Ventilation: Supply, installation,testing and commissioning of Logical Control system should be BMS Compatible.
e) CFD analyses for Basement Ventilation: complete
Item No. 113 SHEET METAL WORKS GI Duct-Fabrication, supply, installation, testing & commissioning of Galvanised Iron ( GI )shall conform IS: 227 – 1977 Sheet ducting complete with splitter dampers, turning vanes, access doors, supports etc. as per drawings and specifications. Supports for ducts at 2.4m distance apart upto 2250/1.2m distance part for larger ducts. Each support shall have minimum 2 vertical rods of 10mm/12mm diameter with 40 x 40 x 6 or 50 x 50 x 6 angles as approved by Consultant. Note : 1) All exposed ventilation duct work should be painted with 2 coats of epoxy primer and 2 coats of epoxy paint.All the supports of the duct will be painted to match the ducting. Please note that the supports for ducting have to be taken from the ceiling slab only. 2) Duct Should be Factory made Prefered makes : (Tata, Jindal, ).
a) 22 G Ducting (above 750mm upto 1500mm anyside)
b) 24 G Ducting (upto 750mm any side)
Item No. 114 Continous Linear Grills Supply, installation,testing and commissioning of following sizes of Aluminium extruded powder coated continous grilles with 4 side flanges. Note : If required Contractor should blank off the extra portion of grille without additional cost and provide deflection of 0 deg to 45 deg without extra cost Prefered makes : (Dynacraft, Cosmos, Airproducts).
a) Exhuast air grill
b) Fresh air grill
c) Gravity louvers-Supply, installation, testing and commissioning of Gravity louvers
Item No. 115 Canvass Connections- Supply, installation, testing and commissioning of Flexible double Canvass Connections for FAN
Item No. 116 Starter Panels-Supply, Installation, Testing and Commissioning of cubicle type fullycompartmentalized totally sheet steel enclosed LT panel suitable for 415V, 50 Hz, 3 phase and 4 wire AC power supply with TPN tinned copper busbars and suitable for top cable entry, front access, dead back type and complete with feeders, metering and indications as per single line diagram and specifications enclosed:
a) For Axial Exhaust Fan (AS SMOKE EXTRACTION FAN) 15000 CFM
b) For SISW Exhaust Fan (AS SMOKE EXTRACTION FAN) 6000 CFM
c) For Axial Fresh Fan 24000 CFM
d) For Axial Fresh Fan 8000 CFM
Item No. 117 Starter Panels as Control Panel For Jet Fan Panels with Supply, installation,testing and commissioning of Starter Electrical and PLC Panel with Modbus and should be BMS Compatible.1325 to 2650 CFM Jet Fan with 1.0 HP motor
Item No. 118 Socket For In line exhaust fan-Supply, installation, testing & commissioning of Socket for Propeller with provision for terminating of incoming and outgoing 5 A, 415V
Item No. 119 Power Cable For All Fan Supply, laying, dressing, testing and commissioning of 1100V grade, aluminum/copper conductor, galvanized steel wire/strip armoured, PVC sheathed power and control cables of following sizes to be laid on trays/ wall/racks including clamping as per specifications.
a) 4c x 6 sqmm cable (for 15 hp to 20 hp or 11 kW to 15 kW)
b) 4c x 4 sqmm cable (for 10 hp to 12.5 hp or 7.5 kW to 9.3kW)
c) 4c x 2.5 sqmm cable (for 7.5 hp or 5.5 kW)
d) 4c x 1.5 sqmm cable (for 0.5 hp to 5.0 hp or 0.37 kW to 3.7kW)
Item No. 120 Control Cables For Jet Fan Supply & Installation of All control cables between Jet Fan unit laid in PVC pipe and clamped . 3c x 1.5 sqmm cable. (AVERAGE 38 FANS PER LOT.) Complete.
PLUMBING WORK
Item No. 121 INTERNAL WATER SUPPLY SYSTEM: Providing and fixing CPVC (Chlorinated Poly Vinyl Chloride) water supply pipes . Pipes shall be joined using solvent welded CPVC fittings i.e. Tees, Elbows, Couplers, Unions, Reducers, brushings etc. including transition fittings (connection between CPVC & metal pipe/GI) i.e. Brass Adaptors (both Male & Female threaded) conforming to ASTM D-2846. ASTM F441 with only CPVC solvent cement conforming to ASTM F-493. All termination points for installation of faucets shall have brass termination fittings. Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. Cost shall be inclusive of insulation for hot water pipe. and also Cost shall be inclusive of pipe length whether Geyser installed in Shower area or in plumbing shaft.Cost shall be inclusive of Making maximum of 7.5 x 7.5 cm chase in wall and floors for the pipe, making good the same by using 1:2 cement mortar over the wire mesh and providing protection to embedded pipes and fittings (in wall chase) by wrapping two layers of 400 micron polythene sheet including proper overlaps on joints complete as required.(in toilet area / conceled)
a) 40 mm dia GR FLOOR
1st to 4th
b) 32 mm dia GR FLOOR
1st to 4th
c) 25 mm dia GR FLOOR
1st to 4th
d) 20 mm dia GR FLOOR
1st to 4th
e) 15 mm dia - GR FLOOR
1st to 4th
Item No. 122 uPVC (unplasticized Polyvinyl Chloride) (SCHEDULE 80)Cost shall be inclusive of Fixing/supporting the pipes (& fittings) at wall/ceiling level supported by galvanized clamps, hangers etc, as per specification. Exposed pipes to be painted of legends with direction arrow. GI pipe sleeves suitable higher size shall be provided wherever the pipes are crossing the fire rated walls / floors slab and sealing the sleeves with glass wool in between and fire sealant compound at either end all as per Project Manager's / Consultant requirement. All termination points for installation of faucets shall have brass termination fittings. Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. (in shaft /Terrace lvl.)
a) 80 mm dia (Terrace Flu header)
b) 65 mm dia (Terrace Dom header)
c) 50 mm dia (O..H.Tank feed line) BS TO GR FLOOR
1st to 4th
c) 50 mm dia Gr
1st to 4th
d) 40 mm dia Gr to 4th
e) 32 mm dia GR TO 4TH
f) 25 mm dia GR TO 4TH
Item No. 123 Ball Valve -Providing and fixing ball valve including flanges / union, etc. complete as required.Tested pressure = 15 Kg / Sqcm. Material : Brass
a) 25 mm n.b
b) 32 mm n.b
c) 40 mm n.b
d) 50 mm n.b
Item No. 124 Butterfly Valve (Terrace Floor)-Providing & fixing butterfly valve (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required. Tested pressure = 15 Kg / Sqcm. Material : Cast Iron
a) 65 mm n.b
b) 80 mm n.b
Item No. 125 Air Vent valve (Terrace Floor PIPE LOOP) Providing & fixing Auto Air vent for cold water supply risers.Tested pressure = 15 Kg / Sqcm Material : Cast Iron
Item No. 126 P.R.V.Providing and fixing Pressure Reducing valves complete as directed by engineer-in-charge. Contractor to set pressure as per instructions from consultant during execution. Note: Set of P.R.V. of including 5 nos. x Ball / Butterfly Valve + 2 nos. x P.R.V. Tested pressure = 25 Kg / Sqcm Material : Forged Brass / Bronze
a) 40 mm n.b
b) 50 mm n.b
c) 65 mm n.b
Item No. 127 Providing & fixing heat insulation by wrapping the pipes with glass wool/asbestos fibre rope or tape/videoflex 15 mm as directed by Engineer in charge (for Hot water Pipe within Bathroom) 15 mm n.b
Item No. 128 Providing and fixing ball cock heavy duty with copper float all complete. 50 mm n.b
INTERNALSEWERAGE SYSTEM
Item No. 129 Providing and fixing UPVC pipes of I.S.13592- 1992 (type - B, SWR quality) to correct grade, length and alignment including jointing with solvent cement, testing, fixing to G.I. brackets/clamps complete as per specifications and directions of the Engineer-in-charge, including all kinds of fittings of UPVC type A SWR - quality, Note :- all UPVC pipes should have density in the range of 1.44 to 1.48 gm/cu.cm (in shaft/ceiling suspended)
a) 210mm O. D.
b) 160mm O.D.
c) 110mm O.D.
d) 80mm O.D (AC drain)
e) 80mm O.D (vent) (upvc type A)
Item No. 130 Providing and fixing UPVC pipes of I.S.13592- 1992 (type - B, SWR quality) to correct grade, length and alignment including jointing with solvent cement, testing, fixing to G.I. brackets/clamps complete as per specifications and directions of the Engineer-in-charge, including all kinds of fittings of UPVC type A SWR - quality, Note :- all UPVC pipes should have density in the range of 1.44 to 1.48 gm/cu.cm (in toilet conceled/ sunk)
a) 32mm dia.
b) 40mm dia.
c) 50mm dia.
d) 80mm dia.
e) 100mm dia.
Item No. 131 Providing and fixing vent cowls including fixing the same with ring fittings joint complete as per specifications and directions of the Engineer-in-charge.
a) 110mm dia
b) 80mm dia
Item No. 132 Providing and fixing PVC Pan connectors with or without vent holes straight/bend including providing & jointing with ring fittigns, joints.
Item No. 133 Providing and fixing UPVC. heavy approved Nahani Traps with grating & minimum 50mm seal including fixing the same with the solvent cement joints complete to the satisfaction and direction of the Engineer-in-charge.
150mm round/square ( Gr Floor )
1st to 4th
Item No. 134 Supply, installation, testing, commissioning of UPVC "P" Trap in joint all complete. 100mm dia.
Item No. 135 Providing and fixing clean outs consisting of G.I. coupling & brass plug soldered to G.I. pipe and caulked to C.I.pipe all complete to the satisfaction and direction of the of the Engineer-in-charge. 210mm dia.
EXTERNAL STORM DRAINAGE SYSTEM:
Item No. 136 Rain Water Chamber -Designing and constructing brick masonry inspection chamber of the following sizes in brick work of class 75 in cement mortar 1:5 (1 cement:5 fine sand), R.C.C. at top level with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm. nominal size) embeded with frame for manhole, RCC foundation slab. 1:2:4 mix (1 cement : 2 coarse sand:4 graded stone aggregate 40 mm nominal size) both inside and outside of plastering 12 mm thick with cement motar 1:3 (1 cement : 3 coarse sand) with a floating coat of neat cement on inside face, proper water proofing to ensure no ground water seepage in the manhole, Poly propylene (conforming to ASTMD - 4101) foot rests (meeting the 224 kg load requirement as per IS 5455) at 300 mm spacing, benching and making channels with 1:2:4 cement concrete neatly finished, including necessary centering and shuttering, reinforcement, excavation, in all kind of soil, dewatering, refilling, watering, ramming and removing the surplus excavated earth, making good the same complete as required. Contractor shall submit the structural design and drawings for the approval of Engineer In Charge prior to execution.
a) 600 X 900 X Upto a depth of 1.2 m
b) 600 x 600 x upto a depth of 1.2 m
Frame and cover for Rain Water Chamber Frame and cover with locking arrangement etc. complete as specified.
c) 600 x 900 mm, Heavy Duty
d) 600 x 600 mm, Heavy Duty
STORM DRAINAGE CHANNEL
Item No. 139 Providing & constructing stormwater CHANNEL of 230 mm thick brick masonry work in 1:5 cement mortar, plastering smooth inside & rough outside in 1:3 cement sand mortar, 150 mm thick PCC bed in 1:3:6 PCC, including excavations, dewatering, shoring and strutting, backfilling & 230 mm wide PCC curb in 1:2:4 PCC at top of channel for fixing the Heavy Duty MS / RCC grating etc. complete. 300mm WIDE upto maximum depth of 1.2 m.
CHANNEL Grating complete as specified. DI 300mm WIDE mm (Medium Duty)
Item No. 141 Providing, installation, testing and commissioning of PVC armoured/ sheathed/insulated copper cables of the required ratings (as approved) with terminations, installation, accessories, cable trays, saddles, clamps, complete in all respects to all Plumbing Equipment from the above Power Panel located in the Pump room. Cost shall be inclusive of Supporting angle for Submersible pump.
a) Domestic Water Transfer Pump 1 Set = 2 Nos. Pump (1 Working + 1 Standby) TYPE OF PUMP SUBMERSSIBLE Pump Capacity / Discharge = 170 lpm outlet Head = 100 mwc
b) Flushing Water Transfer Pump 1 Set = 2 Nos. Pump (1 Working + 1 Standby) TYPE OF PUMP SUBMERSSIBLE Pump Capacity / Discharge = 250 lpm outlet Head = 100 mwc
c) Rain Water Transfer Pump (For Rain Water Harvesting Tank) 1 Set = 2 Nos. Pump (1 Working + 1 Standby) TYPE OF PUMP SUBMERSSIBLE Pump Capacity / Discharge = 100 lpm outlet Head = 100 mwc
Item No. 143 Providing, installation, testing and commissioning of PVC armoured/ sheathed/insulated copper cables of the required ratings (as approved) with terminations, installation, accessories, cable trays, saddles, clamps, complete in all respects to all Plumbing Equipment from the above Power Panel located in the Pump room. Cost shall be inclusive of Supporting angle for Submersible pump.
Item No. 144 Sump Pump ( For Storm Water Drainage ) (1 working + 1standby) Pump Capacity / Discharge =500 lpm outlet Head = 20 mwc
Item No. 145 Organic Waste Composter Supply, Installation, Testing and Commissioning of Organic Waste Composter (OWC) and complete as directed with all accessories. a. 100 KG
Item No. 146 Approval of Plumbing System From Local Authority Complete Lioasning
Item No. 146 Approval of Plumbing System From Local Authority Complete Lioasning
INTERNAL RAIN DRAINAGE SYSTEM:
Item No. 147 Providing and fixing UPVC - IS:4985 with push fit rubber ring sockets for easy installation, to correct grade, length and alignment including jointing with all kinds ofring fittings, testing, fixing to G.I. brackets/clamps, complete as per specifications and directions of the Engineer-in-charge.(Down takes)
a) 200mm O.D.
b) 80mm O.D.
Item No. 148 Providing and fixing C.P. Brass heavy quality gratings (3mm thick/SS) for floor drains including making necessary recessment grouting with neat cement all complete to the satisfaction and direction of the of the Engineer-in-charge.
a) 300mm round/square (for terrace RWP)
b) 150mm round/square (for 12th RWP)
Item No. 149 Providing and fixing lead sheet flashing sheet of size 450mm x 450mm to suit the following dia pipes/rain water outlet using lead sheets weighing not less than 27.5 Kg.per sq.m.including moulding to proper shape and grade including cutting of R.C.C. roof slab or wall as required and providing and fixing with cement mortar 1:2 with water proof compound etc. all complete as per specifications and directions of the Engineer-in-charge. Size 300 round inlet x 150 / 100 mm.outlet (Roof drain)
Item No. 150 Providing and fixing Cast Bronze Square Clean Out Flow Drain with 100mm thick body & cover frame for Storm water of size 300 x 300mm including making proper recessment, grouting with cement mortar 1:1 Anti corrosive painting as approval all complete as per specifications all complete (for Basement-1 lvl.)
External Water Supply:
Item No. 151 Providing and fixing on walls/ ceiling/ floors, 80 mm dia.heavy grade having embossed as ISI Mark galvanised iron pipes weight of 10.15 Kilogram/meter with necessary fittings. and remaking good the demolished portion and applying primer of anti-corrosive oil paint 2 coats Including necessary scaffolding and removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete. Work within Muncipal Main Line to UG Tank
Item No. 152 Water Meter -Providing and fixing 100mm diameter water meter with non-return valve including strainer, sockets/ union nut and including water meter box making locking arrangements and lock. [Without chamber].
Item No. 153 Water Meter chamber Providing and constructing Brick Masonry Inspection Chamber 90cm x 45cm x 90cm including 1:4:8cement concrete foundation 1:2:4 cement concrete channels half round G.S.W.pipes, Brick Masonry,plastering from inside and C.I. lid cover of 75 Kilogramwith lid and frame fixed in cement concrete.
EXTERNAL SEWAGE DRAINAGE SYSTEM:
Item No. 155 SW gully trap -Providing and fixing stoneware Ceiling suspended gully trap at ceiling level. Making necessary connections & providing water tight D.I. cover with frame of suitable size. Cost shall be inclusive of Fixing/supporting the pipes (& fittings) at wall/ceiling level supported by galvanized clamps, hangers etc, as per specification. Exposed pipes to be painted of legends with direction arrow. GI pipe sleeves suitable higher size shall be provided wherever the pipes are crossing the fire rated walls / floors slab and sealing the sleeves with glass wool in between and fire sealant compound at either end all as per Project Manager's / Consultant requirement. All termination points for installation of faucets shall have brass termination fittings. Installation shall be to as per Technical Manual of manufacturer of pipes & fittings. 450 x 450mm chamber with 150 x 100mm size `P' trap
Item No. 156 IC Chamber / Inspection Chamber -Providing and constructing Brick Masonry inspection Chamber 90cm x 45cm including 1:4:8 C.C foundation, 1:2:4 C.C.channels/half round glazed stoneware pipe channel, salt glazed stone-ware intercepting trap with rodding pipe set in 1:4:8 cement concrete block, brick masonry plastering inside and Outside, with C.I. lead cover of 75 kg with frame fixed in cement concrete. Contractor shall submit the structural design and drawings for the approval of Engineer In Charge prior to execution.
Item No. 157 U.G. TANK G.I. Puddle flanges Supplying & fixing in position galvanised iron puddle flanges of approx. 60 cm length with flange on one end and welded to mild steel plate (8mm thick) in the centre etc. complete as directed by engineer-in-charge
a. 150 mm dia
b. 65 mm dia
c. 50 mm dia
Item No. 158 Manhole Covers (for domestic, Flushing & Fire Tank) Providing and fixing Circular type Manhole Covers with frame of approved make of 525 mm dia including all necessary supports, grouting of the frame in RCC, etc. complete as directed by engineer-in-charge. 600 mm, Heavy Duty
Item No. 159 Vapour vent pipes (for Domestic & Flushing Tank) Supply & installation of vapour vent pipes with Tee, Elbow, Pvc Mosquito proof jali including required jointing material etc. complete. (1 set = 2'' pipe + 1 Tee + 2 Elbow + 2 mosquito jali) 50 mm n.b.
Item No. 160 G.I. Puddle flanges Supplying & fixing in position galvanised iron puddle flanges of approx. 60 cm length with flange on one end and welded to mild steel plate (8mm thick) in the centre etc. complete as directed by engineer-in-charge
a) 150 mm dia
b) 80 mm dia
c) 65 mm dia
d) 50 mm dia
Item No. 161 Manhole Covers (for domestic, Flushing & Fire Tank) Providing and fixing Circular type Manhole Covers with frame of approved make of 525 mm dia including all necessary supports, grouting of the frame in RCC, etc. complete as directed by engineer-in-charge. 600 mm, Heavy Duty
Item No. 162 Y-Strainer (For OH Tank outlet) Providing & fixing Y-Strainer complete as required. Tested pressure = 15 Kg / Sqcm Material : Cast Iron
a) 80 mm dia.
b) 65 mm dia.
Item No. 163 Overflow and Drain pipes ("C" class G.I. pipe ) (for Domestic & Flushing Tank) Supply & installation of overflow and drain pipes of 50mm with Elbow, Plug, Pvc Mosquito proof jali including required jointing material etc. complete. for under ground and over head water tanks 80 mm n.b
Item No. 164 Butterfly Valve (OH Tank outlet & Drain) Providing & fixing butterfly valve (Body : Grey Cast Iron, Shaft : SS, Disc : SG Iron (Rilson coated), Liner : HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required. Tested pressure = 15 Kg / Sqcm Material : Cast Iron
a) 65 mm n.b
b) 80 mm n.b
Item No. 165 Providing and fixing 45 cm wide mild steel ladder of 40mm x 6 mm mild steel flat stringers and steps of 18 mm dia. mild steel bar for water tank including fixing it in (1:2:4) M-15 cement concrete block 60cm x 30cm x 30cm and painting the ladder complete. (Anti Corossive Paint)
SANITARY FIXTURES & FITTINGS
Item No. 166 Providing and fixing white vitreous china extended wall mounting water closet of size 780x370x690 mm of approved shape including providing & fixing white vitreous china cistern with dual flush fitting, of flushing capacity 3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover, and cistern fittings, nuts, bolts and gasket etc complete. Jacquar Make
Item No. 167 Providing & fixing in position `Jacquar Continental' make CP Jet Spray with flexible CP supply pipe, and all other accessories, complete
Item No. 168 Providing and fixing white vitreous china water closet squatting pan (Indian type)
Item No. 169 Providing and fixing Oval Type Under Counter Wash Hand Basin of 420 x 590 x 195mm size with pillar cock, C.P.Angular stop cock, long thread of approved make continental including SS bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 mm thick fixed on Black Kadappa Framework, Making necessary inlet/outlet connection all complet etc. Complete as directed by Engineer in charge.
Gr (ground)
1st to 4th
Item No. 170 Supply & fixing stainless steel sink of size 600 X 510 X 200mm (19 gauge) single bowl without drain board of Nirali make or equivalent including 40mm dia. Waste coupling, CP bottle trap, waste flexible pipe upto nahani trap and making inlet/outlet connections all complete as per specifications and directions of the Engineer-in-charge. ( Gr Floor)
1st to 4th
Item No. 171 Supply & fixing 15mm dia. approved quality CP sink cocks (wall mounted Swivel type swan neck) including fixing the same with CP wall flanges, angle stop cock all complete.. ( Gr Floor)
1st to 4th
Item No. 172 Supply & fixing in position concealed type single lever operated Hot & Cold bath mixture divertor with shower arm, shower head, bucket filler for complete installation. ( 12th Floor )
Item No. 173 Providing and fixing white glazed urinal of size 710x460x300mm with sensotronic concealed type flushing valve for urinal with complete kit having fittings, inlet pipe with stop tap, brackets for fixing the cistern, 32mm diameter P.V.C. flush pipe with fitting and flushing arrangement including lead soil pipe, lead trap & soil pipe connection upto the outside face of wall etc complete
Ground Floor
1st to 4th
Item No. 174 Supply & fixing 50 LTR geyser (3 KW Rating) with angle stop cock, CP connector, PRV, NRV all complete.
Item No. 175 Supply & fixing Aquaguard unit with all inlet/outlet with connections all complete. (for Drinking points)
Item No. 176 Supply & fixing C.P. open type toilet paper holder recessed type 200 x 150mm, including fixing the same with C.P. screws complete. (FOR WC) ( Gr Floor )
1st to 4th
Item No. 177 Supply & fixing CP approved quality angle stop cock for miscellaneous areas.
Item No. 178 Stainless Steel Silver Hand DryerUnit Size : 11.2"Lx6.7"Bx9.6"H Material : S/S 304 (Non Magnetic) Power : 2000(W) Drying Time(sec) : 10-15 Sec. Noise Level(dB) : 65dB. Detective Distance(mm) : 50-200mm. Wind Speed(m/sec) : >>90m/Sec. Auto Stop : 10 Sec.
ELECTRICAL WORK
Item No. 179 1600 KVA,11/0.433 kv OCTC Transformer Make: voltamp Supplying, installing, testing & commissioning 3 phase, 11/0.433 kV, 50 Hz., 1600 kVA, oil immersed and naturally cooled outdoor type, copper wound transformer, delta/star connected additional neutral brought out on load side, temperature rise should not exceed 40oC by thermometer in oil and 45oC by the resistance in winding at full load rating, with HV tapping (with off load tap changer) off load +5 to -10 in steps of 2.5%, with standard accessories complete with test certificate with losses below 1860 Watts at 50% load, 5300 Watts at 100% load as per IS:1180 - 2014 energy efficiency level II with necessary permissions of Electrical Inspector, as per specification no SS- TR.
Item No. 180 MAIN LT PANEL Panel Supply, installation, testing and commissioning of cubicle type panels as specified and shown on drawing. i) Note: Main Aluminium busbars with bar type feeder connections & all internal wiring and connections. Earthing all components,frame etc. to a common internal earth bar. Painting all sheet metal works. All accessories & supporting structure. Brass glands and crimping lugs for sending and receiving ends. All ammeters with C.T's and voltmeter and energy meters with necessary fuses. All Load Managers to have parameters like KW, KVA, A, V, PF,KVAR, Active & Reactive component of power, RS 485 port to have BMS compatibility as required & desired to complete the system. Panel components as specified. MS base frame. All switch gear to have short circuit levels as specified.
A) LT PANEL (INDOOR TYPE) (IP‐42) (IEC‐60439)
B) MAIN DISTRIBUTION PANEL (INDOOR TYPE) (IP‐42) (IEC‐60439)
C) BASEMENT VENTILATION PANEL (INDOOR TYPE) (IP‐42) (IEC‐60439)
D)BASEMENT VENTILATION PANEL 1 (INDOOR TYPE) (IP‐42) (IEC‐60439)
E) BASEMENT VENTILATION PANEL 2 (INDOOR TYPE) (IP‐42) (IEC‐60439)
F) TERRACE PANEL (OUTDOOR TYPE) (IP‐55) (IEC‐60439) (WALL MOUNTED)
G) GROUND FLOOR PANEL (INDOOR TYPE) (IP‐42) (IEC‐60439)
H) PUMP PANEL (INDOOR TYPE) (IP‐42) (IEC‐60439)
Item No. 181 DB ( Distribution Boards) General Specifications: Supply, installation, testing & commissioning of 500V Distribution Boards as specified & shown on drawing with necessary blankplates(if require), interconnection and accessories Note: Copper busbars together with tapped neutral bar for individual phases. Copper earth strip with tapping for EEC. Busbar mounting mcb's individually lockable in off position. Interconnections and earthing. Sheet steel enclosure suitable for recessed or surface mounting with hinged lockable doors interlocked with the incomer switch. Phase to phase barriers in case of 3Ph boards. Necessary support frame & painting, labelling, phase indicating lamps with fuses etc. complete. DOUBLE DOOR Prefarably standard DB's of specified makes as per list of materials shall be used CSR Base Specifications
Item No. 182 DB - (12 WAY) - Supplying & erecting triple pole and neutral distribution board (TPNDB) with door surface/ flush mounted SPMCB of 12 ways/phase (36 Poles) on iron/ G.I frame/wooden board. (Horizontal Busbar type). as per specification no. SW-SWR/MCBDB IP Protection: IP 20 / IP 43 / IP 54
Item No. 183 LT CABLING Supplying, erecting & terminating XLPE armoured cable 3 core 2.5 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Item No. 184 Supplying, erecting & terminating XLPE armoured cable 4 core 4 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Item No. 185 Supplying, erecting & terminating XLPE armoured cable 4 core 6 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Item No. 186 Supplying, erecting & terminating XLPE armoured cable 4 core 10 sq. mm. copper conductor continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Item No. 187 Supplying, erecting & terminating XPLE armoured cable 4 core 16 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 188 Supplying, erecting & terminating XLPE armoured cable 3½ core 25 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 189 Supplying, erecting & terminating XLPE armoured cable 3½ core 35 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 190 Supplying, erecting & terminating XLPE armoured cable 3½ core 50 sq. mm. aluminium conductor with continuous 5.48 sq. mm. (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 191 Supplying, erecting & terminating XLPE armoured cable 3½ core 70 sq. mm. aluminium conductor with continuous 8.35 sq. mm. (10 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 192 Supplying, erecting & terminating XLPE armoured cable 1100 V. 3½ core 185 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 192 Supplying, erecting & terminating XLPE armoured cable 3½ core 300 sq. mm. aluminium conductor with continuous 12.97 sq. mm. (8 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Electrical Work From Meter Room to Office
Electrical Meter
Item No. 193 Supply & installations of Meter, Breakers / Isolators after Meter General Specifications Supply, installation, testing & comissioning of MCB's / Isolators in Metal boards in IP42 enclosure, as follows: 3 Phase CSR Base Specifications Supplying, erecting & marking TPMCB 40A to 63A in provided distribution board as per specification No. SW-SWR/MCB
Item No. 194 Providing & erecting 4 Pole MCCB of 800A, 415V capacity with short circuit rating 50 kA ,(Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, in provided enclosure on iron /GI frame as per specification no. SW-SWR/MCCB Note 1: 1) For use of 4pole MCCB in place of 3pole MCCB add 20% in overall rate of 3 pole MCCB
ISOLATOR- 3 Phase 63A, TPN ISOLATOR
CABLE TRAY / CONDUITS / HUME PIPE
Item No. 195 Cable Trays- Providing & erecting Hot dipped galvanized ladder type cable tray manufactured from 16 swg (1.6 mm thick) GI sheet of & 100 mm height comprising all required standard accessories.
a) 500 mm width
b) 300mm wide
c) 150mm wide
Item No. 196 Supplying & laying HMS PVC conduit 32 mm dia. with necessary accessories in RCC work/false ceiling/false flooring as per specification No. WG-MA/CC.
a) 32mm HMS FRLS PVC Conduit
b) 25mm HMS FRLS PVC Conduit
c) 20mm HMS FRLS PVC Conduit
Item No. 197 Supply, laying of Pipe complete with excavation, laying of pipes, proper jointing,back filling with soft soil, installing cable markers, etc
A) RCC Hume Pipe
a) 200mm dia
b) 250mm dia
c) 300mm dia
B) HDPE Pipe
a) 150mm dia
b) 200mm dia
IC chamber
Item No. 198 Providing and constructing Brick Masonry Inspection Chamber including 1:4:8cement concrete foundation 1:2:4 cement concrete channels half round G.S.W.pipes, Brick Masonry,plastering from inside and C.I. lid cover of 75Kilogramwith lid and frame fixed in cement concrete
a) Inspection chamber of internal size 0.9 mtr x 0.9 mtr x Depth(as required on site)
b) Inspection chamber of internal size 0.6 mtr x 0.6 mtr x Depth(as required on site)
c) Inspection chamber of internal size 0.45 mtr x 0.45 mtr x Depth(as required on site)
d) Inspection chamber of internal size 0.3 mtr x 0.3mtr x Depth(as required on site)
Item No. 199 Trench : Constructing 750mm wide & 600mm height trench in 230 thick brick masonry in 1:5 cement mortar complete with:150 thick foundation with 1:4:8 cement concrete with bottom cement concrete with bottom channel.20mm plaster inside and outside with 1:3 cement mortar.Running grating of 40 x 5 flat 25mm cc welded vertically in a 40 x 40 x 5 around frame, 50 x 50 x 6 angle runners on either side embedded in masonry with holdfasts.generally meeting the intents of the specifications and drgs. RCC covers of Suitable size to be provided on top in series for maintenance purpose
POINT WIRING
Notes :
1) Rates for point wiring shall include
A) Supply & installation of conduits, wires, junction boxes & accessories.
B) Supply & installation of Switches & sockets .
C) Rate shall include cost of GI switch Box, Modular Front Plate, Modular Switches, ceiling rose & holder, connectors etc.
D) The rate shall include cost of 10mm MS hook mounted in ceiling slab. Rate to include cost of dimmer & switch for Chandelier point and Ceiling Fan point
E) Circuit wiring from MCB DBs to the first switch boards OR looping to other switch boxes shall be included as part of primary, points for the `Rate'.
2) Rates for point wiring shall not included
A) Payments for light fixtures will be made separately as per the items given in 'Light Fixtures & Accessories'.
Cost of MCB for DB not to be included.
3) General note:
A) Unless otherwise specified, all wires in point wiring shall be 2.5 Sq. mm Stranded copper conductor 1.1 KV grade, I.S.I. marked (P+N+E), Fire Retardant Low Smoke (FRLs) insulated.
B)The Contractor can take more than one circuit in the same conduit provided they are of the same phase.
C) The size of conduit shall be decided according to the number of wires in it as per ISI & as specified. (Conduits size not less than 20 mm dia)
D) Wires shall be colour coded (Red, Yellow and Blue for Phases, Black for Neutral & Green for earth).
The point wiring shall be terminated in a terminal block inside the junction box.
E) Looping of wires shall be in fittings and switch boxes only
F) External lighting shall be done with armoured cables.
G) Location of switches/sockets/ DBs shown on the drawings shall be confirmed with the Architect/ Consultant/ Project Manager before installation.
H) Type & location of light fixtures shown in the drawings are tentative and subject to revision as per the recommendation of Architect/ Consultant.
I) The quantities of point wiring will be revised as actual installed on account of such revisions in the layouts.
FOR COMMON AREA
Light Point Wiring
Light Point Wiring with Switch Operated
Item No. 200 Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size (Run): 3 Run of 1.5 sqmm Type: Flexible wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Voltage Grade: 1100 volts Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all accessories (as per IS 9537 part 3) CSR Based Specifications Point wiring for light/fan/bell concealed type in min 20 mm PVC conduit with 1.5 sq.mm. (2+1E) FR grade copper wires, moduler type switch, earthing and required accessaries as per specification No: WG-PW/CW
a) 1-Way Primary Light Point controlled by 6A 1-way Switch
b) 1-Way Secondary Light Point controlled without Switch
c) 2-Way Primary Light Point controlled by 2 Nos. x 2-way Switches
d) 2-Way Secondary Light Point controlled without Switch
Item No. 201 Light Point Wiring with MCB Operated (For Car Park, Basement Lighting and Staircase Lighting.) Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size (Run): 3 Run of 1.5 sqmm Type: Flexible wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Voltage Grade: 1100 volts Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all accessories (as per IS 9537 part 3) Note: MCB Control Cost of MCB/Isolator not to be included.
a) Primary Light Point controlled by MCB
b) Secondary Light Point. i.e. looped from the above Primary Point.
Item No. 202 Power Point : Power Point (6A Switch+Socket) Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size (Run): 3 Run of 1.5 sqmm Type: Flexible wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Voltage Grade: 1100 volts Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all accessories (as per IS 9537 part 3) Switch+Socket: Switch- 6 Amp. Socket - 6 Amp. 2/3 pin Switch+socket flush mounted in 1.6 mm thick GI box Power Point (6 / 16 A Switch+ 16 Socket ) etc Complete
Item No. 203 Power Point (6A Switch+Socket) Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size (Run): 3 Run of 2.5 sqmm Type: Flexible wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Voltage Grade: 1100 volts Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all accessories (as per IS 9537 part 3) Switch+Socket: Switch- 16 Amp. Socket - 6 Amp/16 Amp . 3 pin Switch+socket flush mounted in 1.6 mm thick GI box Power Point etc CompleteSwitch+socket flush mounted in 1.6 mm thick GI box
Item No. 204 FOR OUT DOOR LIGHT POINT Point Wiring for Landscape Lighting Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size: 3 Core 2.5 sq. mm Type: Armoured cable. Material of conductor: Copper With insulated: XLPE PVC / FR / FRLS/ HFFR / HR / HRFR Colors :Grey & Black Voltage Grade: 1100 volts Conduit: NA MCB Control Including the outlet points with connector, Junction boxes & sockets.
a) Primary Landscape Light Point
b) Secondary Landscape Light Point
Item No. 205 Primary Facade Light Point Secondary Facade Light Point Supply, laying, testing & commissioning of point wiring asper specification; Wires: Size: 3 Core 2.5 sq. mm Type: Armoured cable. Material of conductor: Copper With insulated: XLPE PVC / FR / FRLS/ HFFR / HR / HRFR Colors :Grey & Black Voltage Grade: 1100 volts Conduit: NA MCB Control :Including the outlet points with connector, Junction boxes & sockets.
a) Primary Facade Lighting
b) Secondary Façade Lighting
Item No. 206 Providing temporary illumination Consisting of LED light fitting 100w to 115w Metal Halide flood light fitting 250watt complete erected with lamp, holders, mains, switchgears with continuous earth wire erected and dismantled with using scaffolding upto three days
Item No. 207 Supplying and erecting 2 x 36 / 40W FTL corrosion proof Capsule type in non corrosive polycarbonate housing and prismatic polycarbonate cover with individual high power electronic ballast saving Power factor >0.9 and working voltage range of 170 - 270V ACIP 65 protection suitable for cold storage areas to be fixed in false ceiling or at ceiling or on wall complete.
Item No. 208 Supplying and erecting LED square / circular 16 to 20W downlighter having pressure diecast aluminimum housing, opal translucent cover, mounting arrangement with board for surface type or spring loaded mounting clips for flush type complete.
LIFT ELECTRICAL WORK
Item No. 209 Inside the Lift Shaft Power Point (6 / 16 A Switch+ 16 Socket ) for Lift Shaft Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size: 3 Core 2.5 sq. mm Type: Armoured cable. Material of conductor: Copper With insulated: XLPE PVC / FR / FRLS/ HFFR / HR / HRFR Colors :Grey & Black Voltage Grade: 1100 volts Conduit: NA Switch+Socket: Switch- 16 Amp. Socket - 6 / 16 Amp. 3 pin
Item No. 210 Switch+socket surface mounted in 1.6 mm thick GI box Power Point (6 / 16 A Switch+ 16 Socket ) Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size: 3 Core 2.5 sq. mm Type: Armoured cable. Material of conductor: Copper With insulated: XLPE PVC / FR / FRLS/ HFFR / HR / HRFR Colors :Grey & Black Voltage Grade: 1100 volts Conduit: NA Switch+Socket: Switch- 16 Amp. Socket - 6 / 16 Amp. 3 pin
Item No. 211 Switch+socket surface mounted in 1.6 mm thick GI box DBs Type: SPN DB - (12 WAY) Supplying and erecting single pole and neutral distribution board (SPNDB) surface/flush mounted with 2 ways for incoming and 10 ways for outgoing SP MCB’s on iron/ G.I. frame/wooden board as per specification No. SW-SWR/MCBDB IP Protection: IP 20 / IP 43 / IP 54
Item No. 212 distribution board as per specification No. SWSWR/MCB Breakers / Isolators Starters in Enclosure Supply, installation, testing & comissioning of MCB's / ELCB in Metal boards, as follows: IP Protection: IP 20 / IP 43 / IP 54 Inside application: 63A MCB in Metal boards in IP42 enclosure
EARTHING SYSTEM
Item No. 213 Earth Pit : Supply, Installation, Testing and commissioning of maintenance free earthing comprising of Electrode of 17.2 mm diameter Low Carbon Steel with 250 micron molecular copper bonded earthing rod of Length 3m along with 25 kg Carbon based environment friendly back fill ground enhancing compound required to fill up the excavated earth with required quantity complete. Specification no. EA-MOBI
Item No. 214 Earthing conductor a) Earthing Strip Providing and laying earthing conductors of GI/Cu. strip including necessary accessories, clamping to walls, cables etc. as required and interconnection between lengths as per specifications and as per good installation practice. The rate shall include all supports, accessories and hardware necessary for proper installation.
Item No. Note: Joints shall be lap welded/souldered & coated with bitumen CU. Strip
b) 25 mm x 3 mm Cu. Strip
c) 50 mm x 3 mm Cu. Strip
d) 25 mm x 6 mm Cu. Strip
e) 50 mm x 6 mm Cu. Strip
f) 75mm x 6 mm Cu.strip
Item No. 215 Earthing Wires : a) Supply & laying of Al / Copper conductor through PVC conduits of suitable sizes thro' ducts,trays etc. The rates shall include cost of all materials & accessories including termination. CU wires
Item No. 216 Earthing Cable : Supply & laying of single core flexible PVC insulated Copper conductor through PVC conduits of suitable sizes thro' ducts,trays etc. The rates shall include cost of all materials & accessories including termination.
Single Core 2.5 Sqmm Copper Flexible cable without Conduit
Single Core 4 Sqmm Copper Flexible cable without Conduit
Item No. 217 LIGHTNING PROTECTION EARLY STREAMER SYSTEM Lightning arrester type Controlled Early Streamer Emission system. NFC17-102 Compliant. The unit should be equipped with a central pick up rod made of tin plated copper ensuring full electrical continuity between the tip and the earth point. The unit shall be fully autonomous, collect energy from ambient electric field with a lower series of electrodes, detect lightning strikes and emit a steamer at the right time (controlled emission). A tester or remote testing facility should be available for maintenance purpose. Performances of the unit should have been tested in High Voltage Laboratory (CPRI) as well as in Real Lightning Conditions
Item No. 218 Elevation pole made of GI with a dia. Of 35mm to 50mm with a thread at the top to fix the unit. Base plate, mounting bracket, clamps and all required fixing accessories should also be supplied.
Item No. 219 Down Conductor a) Down conductor made of Copper (Cable or strip) for tower impedance and temperature rise. It should have a minimum cross section area of 50 Sq.mm to withstand 250kA lighning current and comply with IEC 62305 standard. Note: for multistranded copper cable, the dia. For each strand should be 1.7mm minimum as per IEC.
b) A test clamp should be installed in order to disconnect the down conductor from the earth termination for regular checks of the earth termination resistance value.
c) The base of the down conductor should be protected from accidental knocks and other damage by means of a 2meters stainless-steel or PVC protection sheath fixed to the structure.
Item No. 220 Performance Recording Equipment Lightning Flash counter recording any lightning current comprises between 1000A to 100kA for a 8/20 micro second peak current. The item shall have been tested in a High Voltage Laboratory (CPRI).
Item No. 221 Earthing System Equipotential Bonding a) The earth termination should be connected to the electrical earth of the building and other earth terminations with a copper cable or strip of 16 Sq.mm minimum, in order to achieve an equipotential network as per IEC 62305 standard (Surge Arrester might be added).
b) Copper Earth Clamp, installed in the inspection pit, to connect equipotential cable/strip with the earthing system
Item No. 222 AVIATION LIGHT a) Supply of GVK approved make , High Intensity Type A, 360° divergence Aviation Warning Light (AWL) with 3 mtr height Mounting Stand Conforming to regulations from ICAO, FAA, DGCA. Medium Intensity AWL LED White light output for day & night operations. Luminous Intensity of light as per ICAO/DGCA will be as below: Day : 20,000 Cd ±25% (White), Night 2000Cd ±25% (White). AWL to IP 65 compliant and made up of Full alluminium body LM6 Alloy for better heat dissipation. Borosillicate glass used for reduced sand blasting effect. UL certified 8 Bit Micro controller based Digital flasher card with LCD display for status monitoring. LDR used for intensity changover as per day & night time. Metal Core PCbs for total heat dissipation Step change in intensity through micro controller PWM technique. All nut, bolt, screws to be of Stainless steel. Aviation light supplied with IP 65 Rittal make or equivalent control panel having LED driver, LCD display, controller, LDR, LED light having life of 100k burning hours. Operating on Single Phase 230V AC power supply 2.5 Sq mm 3 core flexible cable upto 5 Mtrs to connect Light Head and Control Panel to be included.with Complete Installation.
Item No. 223 Point Wiring for AVIATION LIGHT Supply, laying, testing & commissioning of point wiring as perspecification; Wires: Size: 3 Core 2.5 sq. mm Type: Armoured cable. Material of conductor: Copper With insulated: XLPE PVC / FR / FRLS/ HFFR / HR / HRFR Colors :Grey & Black Voltage Grade: 1100 volts Conduit: NA Primary AVIATION LIGHT controlled by MCB (From Meter Room to Terrace)
Item No. 224 DATA / WIFI Supply,Installation,testing & commissioning of RJ 45 socket outlet complete with back box + Face Plate & other required accessories RJ-45 Socket (For CAT-6)
Item No. 225 Cable Supply, Installation,testing & commissioning of CAT cables wiring through condiuts. Note: 1) The rate shall include cost of condiuts. Supplying & installing UTP networking Cat-6 cable suitable for LAN / WAN Computer networking as per specification No. WG-COC/NC As per per Mtrs. CAT-6 UTP cable
Item No. 226 Wifi Router Supply, Installation,testing & commissioning of Wifi Router 5G 500m range as per specification In Port: Data utility access point cum wireless router 03 Anteena router/ Higher Range etc Complete.
Item No. 227 Network Switch Supplying, fixing, and configuring Web Smart Power over Ethernet Switch of 24 Ports on provided rack or as directed as per specification No. WG-NWC/ENS
Item No. 228 TELEPHONE Telephone / Intercom Point Wiring Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size (Run): 2-Pair of 0.5 sqmm Type: Telephone wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all accessories (as per IS 9537 part 3) RJ-11 Socket RJ-11 the channel socket outlet point. Switch Box RJ 11 mounted in 1.6 mm thick GI box & Modular Front Plate. a) Telephone Point Wiring
b) Intercom Point Wiring
Telephone Cable a) Supply, Installation,testing & commissioning of cables for telephone / hook-up wire through PVC conduit with pull box/ junction box & all accessories . Inside the Shaft Cable Supplying & erecting Jelly filled armoured telephone cable 10 pair with 0.5 mm dia. laid in provided trench as per specification No. WGTW
b) Conduit 20mm.dia. (MMS) FRLS PVC Conduit
c) From Shaft to LV DB Cable 1 Supplying & erecting telephone copper cable 2 pair with 0.5 mm dia. laid in provided PVC casing capping/ conduit as per specification No. WG-TW
d) Conduit 20mm.dia. (MMS) PVC
e) MDF (Main Distribution Frames) Supply, Installation,testing & commissioning of MDF as per following specification 10 Pair
f) crone module
g) kye phone
Item No. 229 Supplying, erecting & commissioning MDF Box 100 pairs as per specification No. WGTW
Item No. 230 EPABX Supply, Installation,testing & commissioning of EPABX as per following specification Supplying and installing, testing & commissioning of Digital (Hybrid) type EPABX of 8 x 20 (4 Digital+ 16 analog) extensions suitable upto 120 extentions 48 - Hybrids / Analog Extensions Expandable up to 48 Trunk & 128 Extensions by adding cabinets
Item No. 231 TV SYSTEM TV Point Wiring Supply, laying, testing & commissioning of point wiring as per specification; Wires: Size : RG-6 coaxial cable Type: TV wire Material of conductor: Copper With insulated: PVC / FR / FRLS/ HFFR / HR / HRFR Conduit: Size: 20 mm / 25 mm Dia. Mechanical Srength: (LMS ) for Brack Wall, (MMS) for RCC Wall, (HMS) for RCC Slab Material: PVC / FRLS PVC / GI (For Open) Colors :Grey & Black with all acce ssories (as per IS 9537 part 3) RTV Socket TV the channel socket outlet point. Switch Box TV Socket mounted in 1.6 mm thick GI box & Modular Front Plate.
a) TV Point Wiring
b) Cable- Supply and laying of RG 6 / 11 U tinned copper co-axial cable with polythene insulation with PVC Conduits 25mm/32 mm fixed to walls/Ceiling with Spacers & saddles Inside the Shaft RG-11 coaxial cable
c) From Shaft to LV DB RG-6 coaxial cable
d) Splitters Supply and installation of splitters in die cast Aluminium casing. Inside the Shaft 3-way splitters
e) Antenna (TATA SKY or Other ) Supply and installation of Antenna.
f) Set TOP Box- Supply and installation of Set TOP Box
SOLAR SYSTEM
Item No. 232 Supply installation of the Solar sytem with required all the accessories solar panels, structure, cable, converter etc.Panel Specifications. Quotation for the 11KW,Mono crystalline silicon Cells,Have less shade tollerant, More temprature Sensitive Mono crystalline silicon Cells Batteries with complete Battery Backup Installation.
MISCELLENOUS WORK
Item No. 233 Rubber Mats Supply & Installation of 1.1KV Grade Rubber Mats in front of all the Panels.
Item No. 234 Danger Notice Board Supply & Installation of Danger Notice Board etc (Danger Board 440 V / Shock treatment instruction charts in Hindi & English in good quality frame & glass cover.)
First aid boxes-First aid boxes with all standard contents.
Item No. 235 Electrical liasoning work -Lump sump fees of Electrical liasoning work necessary approval from Electricity board / local authority / PWD Complete.
Item No. 236 Diesel Generator- Supplying, Erecting and Commissioning of Diesel generating set with alternator of 750 kVA output continuous rating, 3 Phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, alongwith standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722- 2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising of meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite Acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel etc. and obtaining necessary approval from Electrical Inspector as per specification no. GEN-DG Each 3405391 16017 3421408
Item No. 237 Providing and Fabricating Structural steel work required framing with all material fixtures and fastening and Laboursd etc. complete Note:- 1) DG Set rating for altitudes more than 150 m above mean sea level shall be de-rated at 3.5 % for every 300 m above 150 m mean sea level. 2) In case of new DG set, if AMF/SYNC panel is to be used in lieu of standard panel, reduce rate by 10% of the cost of material of new AMF panel/SYNC panel. 3) For all the Engines, the emission standards/norms shall meet applicable polution control board norms as amended by Government.
Item No. 238 AMF panel Supplying, erecting, testing and commissioning of Microprocessor based AMF panel suitable for Diesel Generating Set of upto 750 kVA capacity Single/Three phase, 230/415 Volts, 50Hz A.C. with all standard features, safeties etc as per specification no. GEN-AMF.
Item No. 239 Sychronizing Panel -Supplying, erecting, testing and commissioning of Microprocessor based Generator Control Unit (Synchronization panel) panel suitable for Diesel Generating Set of 1500 kVA capacity Three phase, 415 Volts, 50Hz A.C. with all standard features and safeties etc as per specification no. GEN-SYNC.
Item No. 240 Providing, Laying and Jointing of 160mm dia (OD) HDPE pipe (PN 6 Class-PE 80 grade: IS 14333) to correct grade and alingnment upto 2.1m depth including boring, Pilot inclined dilling from exisitng ground level upto required depth (invert level) on rig side of proposed gravity sewer line (i.e. entry side) using Horizontal Directional Drilling method in any type of ground including soft soil, mixed ground and soft/hard rock. Length of gravity sewer line i.e. actual pipe laid will be considered for measurement
Item No. 241 FIRE FIGHTING PUMP ELECTRICALLY DRIVEN FIRE HYDRANT PUMP Supply Installation, testing and commissioning of electrically driven high pressurefire hydrant pump, suitable for automatic operation consisting of the following: a. Horizontal positive end suction / high pressure multistage, centrifugal pump or Submersible pump as per CFO NOC ) , suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and C.S. (304) Shaft with mechanical seal, ensure a minimum pressure of 3.5 Kg/Sqcm at the farthest or topmost hydrant / sprinkler. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should be tested for bench mark at factory and shall be gotten approved by the Local fire Authority). b. Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head.
c. Squirrel cage induction motor, TEFC type suitable for operation on 415 volts, 3 phase 50 HZ A.C supply, for the above pump with synchronous speed of 2900 RPM, conforming to IP 55 protection & class F insulation. The motor shall conform to IS 325-1978 (up to date) with flexible coupling and coupling guard, complete as required. d. Common base plate for (a) and (b) from M.S. Channel for required size. e. Suitable cement concrete foundation with cement concrete plaster (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with anti vibration arrangement of cushy foot mountings. a. TYPE OF PUMP = Centrifugal Pump Capacity / Discharge = 2400 lpm outlet Head = 100 mwc
Item No. 242 ELECTRICALLY DRIVEN FIRE SPRINKLER PUMP Supply Installation, testing and commissioning of electrically driven high pressurefire sprinkler pump, suitable for automatic operation consisting of the following: a. ( Horizontal positive end suction / high pressure multistage, centrifugal pump or Submersible pump as per CFO NOC ) , suitable for operation on 415 volts ± 6%, 3 phase, 50 HZ A.C supply. The installation shall be complete with flexible coupling and coupling guard as required. Fire pump shall have C.I. casing, CS diffusers, bronze impeller (hard finished and dynamically balanced) and C.S. (304) Shaft with mechanical seal, ensure a minimum pressure of 3.5 Kg/Sqcm at the farthest or topmost hydrant / sprinkler. The installation shall be complete with necessary pressure gauge with gun metal shut off cock on delivery side. (The pump should be tested for bench mark at factory and shall be gotten approved by the Local fire Authority). b. Pump shall be capable of furnishing not less than 150% of rated capacity at a head of not less than 65% of the rated head. The shut off head shall not exceed 120% of rated head.
c. Squirrel cage induction motor, TEFC type suitable for operation on 415 volts, 3 phase 50 HZ A.C supply, for the above pump with synchronous speed of 2900 RPM, conforming to IP 55 protection & class F insulation. The motor shall conform to IS 325-1978 (up to date) with flexible coupling and coupling guard, complete as required. d. Common base plate for (a) and (b) from M.S. Channel for required size. e. Suitable cement concrete foundation with cement concrete plaster (design and drawing to be provided by the Contractor while the foundation will be done by others) complete with anti vibration arrangement of cushy foot mountings. a. TYPE OF PUMP = Centrifugal Pump Capacity / Discharge = 2400 lpm outlet Head = 100 mwc
Item No. 243 JOCKEY PUMP Supplying of Jockey pump centrifugal horizontal type end suction top discharge back pullout type of 2900 RPM CI body with bronze impeller, bronze working parts, SS shaft and coupled to 2900 RPM motor F class motor (TEFC) insulation squirrel cage induction motor mounted on common base plate, nut, bolts with matching suction and discharge side flanges coupling guards and anti vibration rubber pads etc., complete Pump Capacity / Discharge = 180 lpm outlet Head = 100 mwc
Item No. 244 BOOSTER PUMP Supply, Installation, testing and commissioning of Booster pump centrifugal horizontal type. The pump shall be of negative end suction top discharge type running at 2900 RPM, with CI body, bronze impeller, bronze working parts SS shaft, directly coupled to totally enclosed Fan cooled (TEFC) squirrel cage AC induction motor of capacity to operator on 3 Ph , 415 V 50 cycle AC with B/F class insulation both the pump and motor are to be erected on common MS base plate of required size with foundation bolts with matching suction and discharge side flanges, coupling guards and anti vibration rubber pads etc., complete Pump Capacity / Discharge = 900 lpm outlet Head = 32 mwc
FIRE PUMPS PANEL & ELECTRICAL WORK
Fire Pumps Panel
Fire Main Pumps Panel
OUTGOING Feeder for Main Hydrant pumps - (1 Nos.) Capacity: xxx A C-Curve, TP MCCB / MCB Type of starters: Star Delta starter / Soft starter With: over load relay, single phase preventor and indicating lamps with ON / OFF push buttons. Feeder for Stanby Hydrant pumps - (1 Nos.) Capacity: xxx A C-Curve, TP MCCB / MCB Type of starters: Star Delta starter / Soft starter With: over load relay, single phase preventor and indicating lamps with ON / OFF push buttons. Feeder for Sprinklar pumps - (1 Nos.) Capacity: xxx A C-Curve, TP MCCB / MCB Type of starters: Star Delta starter / Soft starter With: over load relay, single phase preventor and indicating lamps with ON / OFF push buttons. Feeder for Jockey pump (2 nos.) Capacity: xxx A TP MCB / MCCB Type of starters: Star Delta starter /DOL starter With: over load relay, single phase preventor and indicating lamps with ON / OFF push buttons. Feeder for Booster pumps (1 nos.) Type of starters: Star Delta starter /DOL starter Type of starters: Star Delta starter /DOL starter All above works
Item No. 246 Start / Stop Push Button for Booster pump Supply Installation, testing and commissioning of Emergency Start / Stop Push Button station weather proof type for Booster pump at all Floor and terrace level.
Item No. 247 LT Cable (Power Cabling ) Supply and laying of 1.1kV Voltage grade, aluminium / copper conductor, XLPE insulated, steel armoured, power / control cables. The cables shall be laid in tray / hume pipe / in ready made trenches, with nylon cable ties / MS Clamps @ 600mm interval etc., as required.
a) Supplying, erecting & terminating PVC armoured cable 3 core 2.5 sq mm copper conductor continuous 5.48 sq mm (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
b) Supplying, erecting & terminating PVC armoured cable armoured cable 4 core 4 sq mm copper continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
c) Supplying, erecting & terminating PVC armoured cable armoured cable 4 core 6 sq mm copperconductor continuous 5.48 sq mm (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
d) Supplying, erecting & terminating PVC armoured cable armoured cable 4 core 10 sq mm copper copper conductor continuous 5.48 sq mm (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Aluminium Cable
a) Supplying, erecting & terminating PVC armoured cable 4 core 16 sq mm aluminium continuous 5.48 sq mm (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
b) Supplying, erecting & terminating PVC armoured cable 3½ core 25 sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
C) Supplying, erecting & terminating PVC armoured cable 3½ core 35 sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
C) Supplying, erecting & terminating PVC armoured cable 3½ core 50sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
D) Supplying, erecting & terminating PVC armoured cable 3½ core 70sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
E) Supplying, erecting & terminating PVC armoured cable 3½ core 185sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
f) Supplying, erecting & terminating PVC armoured cable 3½ core 300sq mm continues (12 SWG) G.I. earth wire complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Item No. 248 Cable Termination of the above cables with Heavy
ii. Qty. For Control Panel of Diesel Engine Pump a. 2C x 2.5 Sqmm. Armoured Copper cable for Diesel engines b. 2C x 2.5 Sqmm Armoured Copper cable. .for Instrumentation iii. Qty. For Start / Stop Push Button for Booster pump a. 3C x 2.5 Sqmm. Armoured Copper cable. iv. Qty. For Control Cable of Pressures switches 2C x 1.5 Sqmm Armoured Copper cable. v. All Cables Terminations works as per above i to iv
Item No. 249 Cable Trays ( Perforated Type) Supply & installations of Pre Galvanised 60 microns, 2.mm Thick, 50mm height, readymade Perforated Type cable trays complete with couplers, bends etc. The rate to include supports of 25x25mmx3mm of angle with 10mm verticle rods fixed with 6mm Anchor fasteners. The vertical support shall be placed at interval of not more than 1.5 Metrs & at all bends. a. 200mm wide x 50mm height b. 150mm wide x 50mm height c. All Cable Trays works as per above i to iii
Item No. 250 Earthing G.I. Earthing strips of 50mm x 6mm thick, strip shall run on floor / ceiling / walls, from the equipment to the nearest Earth pit with neccessory accessories as required.(Scope of M/s. Elect Vendor Scope) NOTE: Incoming cable to the panel will be in the scope of the Electrical Contractor, but the termination of it in the panel will be in the scope of the Fire Contractor
Item No. 251 PUMP ROOM & TERRACE (PIPING + VALVE) "C" class G.I Pipes Providing & Laying "C" class G.I Pipes as per IS 1239 with screwed ends including ' all necessary heavy quality fitting such as bends,tees,elbows,coupling reducers, unions,checkneuts etc., joining with Teflon tapes structural supports incluiding cutting welding ,threading as required etc., all complete. The pipes shall be painted with 2 coats of primer & 2 coats of finishing paints as per painting procedure mentioned in technical specifications.
a. 80 mm dia.
b. 100 mm dia.
c. 150 mm dia.
d. 200 mm dia. (Header)
Item No. 252 Butterfly valve Supply, installation, testing and commissioning of Butterfly valve with flanges, nut bolts, gaskets and necessary pad locking arrangement complete required. Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar/10 kg/sq.cm/100 m of H2O / 145 psi)
a. 80 mm dia.
b. 100 mm dia.
c. 150 mm dia.
d. 200 mm dia.
Item No. 253 Non Return Valves -Supply, installation, testing and commissioning of C.I. double flanged NRV with matching flanges of following sizes complete in all respect as per spec. Note: Suitable for test pressure of 1.5 time of rated pressure.i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
a. 80 mm dia.
b. 100 mm dia.
c. 150 mm dia.
d. 200 mm dia.
Item No. 254 Y-Strainer- Supplying, installing and commissioning C.I.flanged "Y" type Strainer with SS mesh,suitable flanges, nuts, bolts, gaskets etc. complete. Note: Suitable for test pressure of 1.5 time of rated pressure i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
a. 80 mm dia.
b. 100 mm dia.
c. 150 mm dia.
Item No. 255 Flanged flexicon rubber expansion joint (Below) Providing & fixing double flanged flexicon rubber expansion joint (suitable for system test pressure) of standard length as per manufacturers specs including rubber gaskets, flanges, nuts, bolts and washers complete as required. Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
a. 80 mm dia.
b. 100 mm dia.
c. 150 mm dia.
Item No. 256 Pressure Gauge Dial type (100 mm) pressure gauge, glycerin filled with S.S. bourdon tube with isolation ball valve suitable for working pressure of 250 PSI. Cost shall be inclusive of providing any short pieces, nipples, elbows etc as required. Note: Suitable for test pressure of 1.5 time of rated pressure i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
Item No. 257 Pressure Switch Supply, installation, testing and commissioning of pressure switch complete in all respect as per spec. no. complete in all respect as per spec. . Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
Item No. 258 Inspectors test assembly complete with test valve Providing and fixing inspectors test assembly complete with test valve, sight glass sectional drain valve, union with corrosion resistant orifice all complete strictly as per drawing. (1 no. for hydrant + 1 no. for sprinkler) Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
Item No. 259 Control Valve with turbine type automatic Alarm Gong (for Sprinklers system)
Providing & Fixing of Installation Control Valve with turbine type automatic Alarm Gong to be connected with control valve, drain & test valve and all other necessary components as per manufacturer's specifications complete as required.
a. 150 mm dia
Precharged air Vessel (Air Vessle) at Terrace Level
Item No. 260 Providing, fixing, testing and commissioning of precharged air vessel (size 450 mm dia & 2000 mm height) for pressurization of hydrant / sprinkler system complete with adequate pressure switches (as per design / requirement) with valves to operate as per operating sequences including 25 mm dia drain valve, air release valve with stop cock on the top, 25 mm dia inlet with isolating valve duly painted from inside and outside complete as required.
Priming Tank (For -ve section)
Float Level Switches
Item No. 261 Providing / Fixing Providing, fixing, jointing and testing in position the following Top Mounted Guided Float Level Switches and Electronic Control Switches including all necessary fittings required for installation etc.( Make : Mahalaxmi Instruments) e Project Manager complete with probes & all control wiring etc. Note : Contractor shall include in his rates for providing level controllers, pressure switches, wiring, cabling from level controller / pressure switch to panel etc. complete as required to operate the system automatic/manual. Pump shall be protected against running dry.
HYDRANT, PIPING & ACCESSORIES
Item No. 262 GI `C' Heavy class pipe (Non Trenches ) Providing, laying, jointing, testing and commissioning of following sizes of GI `C' Heavy class pipe conforming to IS- 1239 with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with clamps, hangers (using anchor fastners) as per specification. G.I. pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s / Consultants requirements including cutting holes and chases in brick, R.C.C work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwire and then supply of the same shall also be included for rates under this head.. Welding of any kind on the galvanized support / hanger shall not be permitted.
Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Engineer In charge. For wet riser System - GI `C' Heavy class pipe
a. 80 mm dia
b. 150 mm dia
Item No. 263 GI `C' Heavy class pipe (In Trenches ) Providing, laying, jointing and testing in trenches the following sizes of GI class `C' (heavy class) pipes conforming to IS:1239 with accessories like fittings including tees, elbows, reducers, flanges, rubber gaskets, G.I. nuts, bolts and washers including excavation in all kind of soil, refilling, ramming, shoring, removing the excavated surplus material, providing adequate support to the pipe and making good the same complete as required. Rate shall include for dewatering necessary to execute the work. The pipe shall not be less than 1.0 m below ground level at any point. Providing protection to embedded GI pipes and fittings by applying protective primer (@ 100 gm/sqm) thereafter wrapping 4 mm thick protection coating by thermo fusion process. Overlap shall be maintained at 15 mm. The application process shall be strictly according to manufacturer’s specification.150 mm dia
Item No. 264 Brass Ball Valve Providing and fixing forged brass ball valve with forged brass ball(Cost shall be inclusive of providing necessary union / flangeconnection). Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi) a. 25 mm dia b. 32 mm dia c. 40 mm dia d. 50 mm dia ii. PN 16 (16 Bar / 16 kg/sq.cm / 160 m of H2O / 232 psi) a. 25 mm dia b. 32 mm dia c. 40 mm dia d. 50 mm dia
Item No. 265 Orifice plate / Pressure reducing disc Supplying and erecting one no. brass orifice plate having 6 mm. thickness, 160 mm outer dia and required/proper diameter of inner hole at every double outlet hydrant valve as per specification a. 160 mm dia outer
Item No. 266 External Fire hydrant landing valve Providing & fixing gun metal / SS fire hydrant single / Double landing valve with 80 mm N.B. flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. G.M. / SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS:5290. Single landing Valve b. SS Material
Item No. 267 FIRE HOSE cabinet Providing and fixing weather proof lockable cabinet of size not less than 0.75 x 0.60 x 0.25 mtr made out of MS sheet of 16 gauge thickness having central opening and 4 mm thick glazed glass doors two nos.( 4mm thick glass with rubber beeding) suitably marked on the outside with the letters "FIRE HOSE" including necessary locking arrangement and shall be painted with one coat of primer and two coats of synthetic enamel paint of approved shade. The cabinet shall be suitable to accommodate 2 nos. or 4 nos 15 mtr long Hose pipe & 1 nos or 2 nos branch pipe nozzle. It shall be mounted on raised Brick platform complete as required. (Cost shall be inclusive of providing break glass box containing key for the cabinet along with hammer).
Double Door a. 750 x 600 x 250 (L X W X D)
Single Door b. 450 x 450 x 250 (L X W X D)
Item No. 268 Coupling for Hose Pipe Providing and Fixing ISI marked brass male & female coupling (IS:903) bound & riveted to hose pipe with copper rivets & 1.5 mm copper wire, complete as required. a. with ss Material
Item No. 269 Branch pipe Nozzle Providing and Fixing rising Branch pipe Nozzle with completeas required. a. with ss Material
Item No. 270 Internal Fire hydrant landing valve Providing & fixing gun metal / SS fire hydrant single / Double landing valve with 80 mm N.B. flanged inlet, brass spindle controlled 63 mm dia female instantaneous outlet type. G.M. / SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS:5290. Single landing Valve a. SS Material
Item No. 271 "FIRE DUCT DOOR" (If Fire Shaft/Duct in project) Providing and fixing 5 mm thick glass door (with M.S. frame) of size 1.5 m x 0.9 m with center opening for fire hose cabinet. Suitably marked on the outside with the letters "FIRE HOSE" including locking arrangement. All M.S. work to be in Red P.O. colour over appropriate primer. The above item is only for masonary fire station. Double Door a. Size 1200mm x 900 mm (H x L)
Item No. 272 Fire Canvas hose pipe Providing & fixing controlled percolation fire hose pipe (as per IS:8423) of 63 mm dia and 15 meter length rated for brust pressure of 35.7 Kg/sqcm. The hose shall be tested for flame resistance test in accordance to IS:8423. a. 63 mm dia and 15 meter lengthx 1 no.
Item No. 273 Coupling for Hose Pipe Providing and Fixing ISI marked brass male & female coupling (IS:903) bound & riveted to hose pipe with copper rivets & 1.5 mm copper wire, complete as required. a. with ss Material
Item No. 274 Branch pipe Nozzle Providing and Fixing rising Branch pipe Nozzle with complete as required. a. with ss Material
Item No. 275 Swinging type First hose reel Drum with Assemble Providing & fixing swinging type First Aid hose reel in red colour drum with 30 mts long and 20 mm dia heavy duty rubber water hose, 20 mm dia globe valve stop cock, terminating with G.M. coupling & nozzle of 6mm outlet with shut off valve confirming to IS 8090 - 1976 complete with MS socket for tap-off, drum and brackets (including painting) for fixing on wall with anchor fastner, bolts & nuts conforming to IS:884-1969 complete as required. with ss coupling & nozzle
Item No. 276 way fire brigade connection - Providing & fixing gun-metal fire brigade connection (suction collecting head) consisting of 4 Nos. 63 mm dia instantaneous type male couplings with built-in check valves, 1 No. 150 mm dia Butterfly valve, 1 No. 150 mm dia non-return valve and 150 mm dia flanged outlet complete with bolts, nuts and rubber insertions as required and as per IS:904-1963. a. with Stainless Steel
Item No. 277 WAY Fire brigade suction hose Providing & fixing gun-metal fire brigade suction hose coupling (draw-out connection) with nut for female coupling as per IS: 902-1974 complete with 100 mm dia GI suction pipe and 100 mm dia foot valve (to be connected to static tank). Provision of GI drop pipe and foot valve shall be made in all the fire water static storage tanks (4 Nos) (GI pipe to be paid separately through appropriate item while cost of foot valve to be included). a. with Stainless Steel
Item No. 278 GI `C' Heavy class pipe (Non Trenches ) Providing, laying, jointing and testing of following sizes of GI `C' Heavy class pipe conforming to IS-1239 with all accessories like all fittings ( all pipes & fittings shall be forged steel with welded joint shall be used) including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer including supporting/fixing the pipe on floor / wall /ceiling with clamps, hangers (using anchor fastners) as per specification. G.I. pipe sleeve of suitable higher size shall be provided wherever the pipes are crossing the walls/floors and sealing the sleeves with glass wool in between & fire sealent compound at either end all as per Project Manager’s requirements including cutting holes and chases in brick, R.C.C work and making good the same to original conditions complete in all respects. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and the supply of the same shall also be included in rates under this head. Welding of any kind on the galvanized support / hanger shall not be permitted.
Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Engineer In charge
a. 25 mm dia
b. 32 mm dia
c. 40 mm dia
d. 50 mm dia
e. 65 mm dia
f. 80 mm dia
g. 100 mm dia
h. 150 mm dia
Item No. 279 GI `C' Heavy class pipe (for drainage purpose ) Providing, fixing, jointing and testing in position the for drainage purpose following heavy class (Class C) G.I. pipes conforming to IS:1239 cut to required lengths including all necessary fittings (All fittings shall confirm to IS:1879 (part 1 to 10) and specials such as bends, tees, unions, Reducers, flanges & plugs etc. fixing at wall / ceiling level supported by clamps, hangers (using anchor fastners) etc, as per specification. Threading, jointing, and making proper connections, cutting hole in wall / floor / slab and making good the same. GI pipe sleeves suitable higher size shall be provided wherever the pipes are crossing the fire rated walls / floors slab and sealing the sleeves with glass wool in between and fire sealent compound at either end all as per Project Manager's / Consultant requirement. All hangers, clamps, brackets etc. shall be of galvanized iron unless specified otherwise and the supply of the same shall also be included in rates under this head. (Fire sealent shall be provided to the contractor free of cost). Welding of any kind on the galvanized support / hanger shall not be permitted.
Providing two coats of synthetic enamel paint of approved shade over a coat of primer. Prior to application of primer the surface should be cleaned for any dirt, rusts, rough substance etc. Including painting of legends both direction arrow as per the approval of the Project Manager
a. 25 mm dia
b. 80 mm dia
Item No. 280 Brass ball valve (for Sprinkler & drainage) Providing and fixing forged brass ball valve with forged brass ball of the following size including providing necessary union / flange. Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi) a. 25 mm dia
Item No. 281 Butterfly valve (for Sprinkler & drainage) Providing & fixing of butterfly valve with flanges, nut bolts & gaskets complete required. Butterfly valve shall be with pad locking arrangement. Note: Suitable for test pressure of 1.5 time of rated pressure.i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
a. 65 mm dia
b. 80 mm dia
c. 100 mm dia
Item No. 282 Orifice plate / Pressure reducing disc Supplying and erecting one no. brass orifice plate having 6 mm. thickness, 160 mm outer dia and required/proper diameter of inner hole at every double outlet hydrant valve as per specification a. 160 mm dia outer
Item No. 283 Water flow switches-Providing and Fixing electrically operated water flow switches (Vane type) including tamper switch and accessories, complete with tap off socket arrangement as required, with potential free contact with 2 Nos. NONC. Note: Suitable for test pressure of 1.5 time of rated pressure. i. PN 10 (10 Bar / 10 kg/sq.cm / 100 m of H2O / 145 psi)
a. 63 mm dia
b. 80 mm dia
c. 100 mm dia
Item No. 284 Sprinklers Providing & fixing brass quartzoid sprinklers (UL approved) of 15 mm dia size, suitable for sustaining the pressure on the seat & water hammer effect. The type & temperature rating shall be as follows. Note -i. All sprinkler shall be chrome finish coated except for the concealed ones. The concealed sprinkler shall be of brass finish. The cover plates of the concealed sprinkler shall be factory painted at manufacturer’s work and the shade shall be confirmed prior to application on the cover plate. ii. The sprinkler shall be either pendent OR upright type and shall not be universal style / nature. iii. Contractor shall ensure provision of sprinkler guard at no additional cost, as required by the Project Manager. iv. Shop drawing for multi spray sprinkler system shall be submitted for comment / approval to the owner / project manager /consultant. v. quartzoid bulb type UL/FM Approved and as per IS 9972
a. 15 mm dia. @ 68 Deg.C ( Pendent Type)
b. 15 mm dia. @ 68 Deg.C ( Side wall Type)
c. 15 mm dia. @ 68 Deg.C ( Upright Type)
Item No. 285 Flexible Sprinkler drop assembly Providing & fixing of Flexible Sprinkler drop assembly consist of S.S. braided hose, sprinkler reducer, nipple, bracket, clamps & adaptor etc. complete. a. 700 mm long ( FOR ENTRANCE LOBBY ONLY )
Item No. 286 Providing and fixing inspectors test assembly complete with a corrosion resistant bronze quarter turn ball test valve,cast iron body with dual glass lenses mounted in plated steel sight glass sectional drain valve, union with a chrome plated, corrosion resistant bronze quarter turn ball valve with a 5.6K smooth bore test orifice. All of the pipe thread connections are assembled with a Teflon based pipe joint sealant and each assembly tested to 350 psi (24,1 bar). (For sprinkler branch pipe) a. 25mm dia
Item No. 287 FIRE EXTINGUISHERS Supply, installation, testing and commissioning of following types of extinguisher with provision of wall bracket (fixed with anchor fastner). Dry Chemical Power Type (ABC) Portable Dry Chemical Power Type Fire Extinguisher with Gun Metal cap and nozzle and complete in all respects including initial fill and wall suspension bracket a. ISI marked (IS:2171) Gas Cartridge Type i. Capacity 9 Kg Make: SAFEX / CEASEFIRE
Item No. 288 Fire Buckets-Supplying and installing at approved location approved make fire buckets of 24 gauge galvanized steel sheet, standard 9 litre capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letters “FIRE” in black and gold. Cost shall be inclusive of providing MS stand duly painted over a coat of primer.
Item No. 289 FIRE SAFETY SIGNS Fire Safety Signs- Supply, installation, testing and commissioning of Fire Safety Signs as per spec. no. complete in all respect as per spec. . i. Self Glow base Sticker 3mm Rigid Plastic & Self Adhesive Vinyl
a. Fire Hose Reel
b. Fire Extinguisher
c. Fire Call Point
d. Lift not use
e. Refuge Area
f. Assembly Point
Item No. 290 Escape Route Signs- Supply, installation, testing and commissioning of Escape Route Signs as per spec. no. complete in all respect as per spec. . i. Self Glow base Sticker 3mm Rigid Plastic & Self Adhesive Vinyl
a. EXIT
b. Emergency Exit
APPROVAL OF FIRE SYSTEM FROM LOCAL FIRE AUTHORITY
Item No. 291 Liasoning work with Approval of fire hydrant & sprinkler system from local fire authority and any other relevant statutory authority at initial & various other stages of works, including preparation of report / drawings as per fire authority. Contractor shall include cost of all liaison works which are not explicitly mentioned above but are mandatory to have fire authority approval
Item No. 292 FIRE ALARM SYSTEM: Make :A : Bosch / Notifier (Honeywell) / Edwards (United Technologies ) / FireFinder (Siemens) / Metasys (Johnson Controls) / Simplex (Tyco) B : Morley (Honeywell) / Honeywell / GST (United Technologies ) /COOPER / Cerberus (Siemens) / FIRE CLASS (Tyco) 5.1 Main Fire Alarm Panel a. Conventional / Analog Fire Panel SITC of Conventional / Analog Fire Alarm Panel, as per below, with a built-in 32 bit microprocessor Approvals: UL / EN / FM Battery: Battery of 15 min /48 hrs backup in normal condition,+ 15 min / 1 hr backup with 25% Loop under fire condition. No of zones in Panel : 4 / 6 / 8 / 12 No. of devices / modules connected to each zone : NA Max No. of devices / modules connected to Panel: 150 / 300/500/1000 / 1500 Max + with 20% spare capacit Display: Min 60 / 80 character LCD display Digital Voice Evacuation System : NO Integrate : NO or b. Addressable Fire Alarm Panel SITC of Addressable Fire Alarm Panel, as per below, Approvals: UL / EN / FM "Shall support minimum Four access levels, 400
event historical logging, flash EPROM, 4 Nos. of programmable relay controls. Complete with 240 volts AC PSU, automatic battery charger, 24 volts SMF batteries Programmed: Panel shall support to programmed as a node on a peer to peer network with other Panels. Battery: Battery of 15 min /48 hrs backup in normal condition,+ 15 min / 1 hr backup with 25% Loop under fire condition. No of loop in Panel : 4 / 6 / 8 / 12
Item No. 293 No. of devices / modules connected to each zone : maximum loading of 125 detectors and 125 devices in one loop. No. of devices / modules connected to Panel: 150 / 300/500/1000 / 1500 Max + with 20% spare capacity Display: Min 60 / 80 character LCD display Fire Alarm Graphic software : NO Printer Interface : NO Firefighter Telephone Channels : NO Networkable : YES Digital Voice Evacuation System : YES Integrate : : YES
Item No. 294 Repeater Panel SITC of Addressable Fire Alarm Repeater Panel, as per below. Approvals: UL / EN / FM Active Repeater Panel with Microprocessor based LCD minimum160 character display for monitoring & controlling other Panels on the network loop with Power supply. Peer To Peer Networked with all main panels, such that the status of the entire system shall be available on individual Annunciator.
Item No. 295 Accessories
b. Fire Fighting's Addressable Telephone Handset
c. Digital Voice Evacuation System
Integrated 8 channel Digital Voice Evacuation System capable to supervise all the speaker circuits, with minimum 20 zone control and accessories required to complete the system. The equipment shall be of same make as panel.
d. PC Fire Alarm Graphic PC as per Technical Specifications for monitoring fire detection systems
e. Printer Alarm Printer A4 Size lasejet paper for Alarm printing
Item No. 296 Smoke Detector -SITC of Analogue Addressable Photoelectric type Smoke Detector, sensitivity range of 0.5% to 2.35% /ft with Detector base, complete with MS Powder coated Junction Box for Approvals: UL / EN / FM
a i. Mounting on Surface / Below False Ceiling
a ii. Mounting on on above False Ceiling
B) Photoelectric + thermal Multi-sensor Detector Approvals: UL / EN / FM SITC of Analogue Addressable Photoelectric + thermal Multi- sensor Detector with Detector base, complete with MS Powder coated Junction Box for mounting on Surface / on False Ceiling / Below False Floor.
C) Reflective Type Beam detector Approvals: UL / EN / FM SITC of Reflective Type Beam detector,black powder coated 70mtrx5mtr
Item No. 297 Monitor Modules -Approvals: UL / EN / FM SITC of Addressable Monitor Modules with MS Powder coated Housing and mounting accessories.
Item No. 298 Hooter Approvals: UL / EN / FM Supply installation Testing & commissioning of Ceiling / Wall mounted Hooter cum Strobes. The Hooter cum Strobes shall be made of ABS plastic and have the Db level of 90dbs at 10ft and a multi tone facility, Strobes intensity should be 15 to 120 Candela. a. Ceiling mounted Hooter
Item No. 299 Fault Isolator Modules Approvals: UL / EN / FM SITC of Fault Isolator Modules with MS Powder coated Housing and mounting accessories.
Item No. 300 Panic Bar Approvals: UL / EN / FM Supply installation Testing & commissioning of Panic Bar, push to open type with auxiliary PF contact, PF contact shall be connected to Annunciater panel & Local Hooter at Door.
Item No. 301 Cable Make : Polycab / Finolex / Vinay "Supply installation of 2 Core x 1.5 mm2, Twisted Pair , Multistranded AT Copper, FRLS Armoured cable, RED in Colour. The cable shall be laid on surface with GI saddle-spacers every 0.3 meters. Complete with GI Junction Box, lugs, cable compression glands, cable tags and Ferruling."
a. 2 Core x 1.5 mm2, Twisted Pair
b. 2 Core x 1.5 mm2, Twisted Pair
C.C.T.V. SURVEILLANCE SYSTEM :
A. Analog Base CCTV System
Item No. 302 Box Camera -Hikvision/CP Plus Supply & Installation Testing ,commissioning of item with Accessories, power conjuction box and various mounting brackets, Pole Mounting , Weather protection as per following a. Aplication : Outdoor Base: Analog Resolution: HD1080P- 2 Megapixel 30M DISTANCE With: POE (for no need of power cable) With: Infrared IR (Day/ Night Camera) With:Analytical software control for intrusion alarm With: Color
Item No. 303 Dome Cameras-Hikvision/CP Plus Supply & Installation Testing ,commissioning of item with Accessories, power conjuction box and various mounting brackets, Pole Mounting , Weather protection as per following b. Aplication : Indoor Base: Analog Resolution: HD 720P - 1 Megapixel ,FULL HD - 4 Megapixel With: POE (for no need of power cable) With: Color
Item No. 304 NVR (Network Video Recorder )-Hikvision/CP Plus Supply & Installation Testing ,commissioning of item with Recoding: CIF, 2CIF, 4CIF, Up to 5 Megapixels 1 Sata port support upto 1 TB HDD, lanport for LAN/WAN connectivty. Mobile device suppor: No Remote alarm notification: No Remote alarm notification: No Network function for remote viewing: No Analog video Input:
Item No. 305 Hard Disk- Seagate/WD Supply & Installation Testing ,commissioning of item with Hard Disk: (For 45 Days) 4 tb
Item No. 306 C.C.T.V. System Softwares.
Item No. 307 Monitors A. 32" LCD-LG/Samsung
Item No. 308 Personal computer ( Desktop) Processor- core i7, ram-16 GB, Graphic card-04 GB, 2TB SSD drive) including UPS Backup etc complete.
Item No. 309 HDMI CABLE
Item No. 310 Equipment Rack with with proper ventilated and openable doors from all sides, with casters and with cooling fans as above complete with necessary mounting hardware &
Item No. 311 Cables a. Video Transfer Cable + Power Cable Cat 6 -Dlink i. Cat - 6 /4 Pair cables (UTP).
Item No. 312 Miscellaneous components, accessories, connectors, jacks etc. not indicated here. but required for a complete CCTV Surveillance, Video Recording and Remote Monitoring Systems.
SECURITY SYSTEM:
Vehicle Access Control:
Item No. 313 AUTO SLIDING GATES- Supply & Installation Testing ,commissioning of item with Accessories as per following features. i) Type of Gate: Motorised Telescopic Sliding Gates Gates Opening; 8 m Gates weighing; 1200 kg With Features: Manual operation in case of power failure Incomplete gate closing operation warning light Obstacle detection causes the gate movement to stop if an obstacle is detected with Remote Controls Note; Door Design by Architect, Door construct not in SECURITY SYSTEM Vendor scope.
Item No. 314 AUTO SWING GATES -Supply & Installation Testing ,commissioning of item with Accessories as per following features. Type of Gate: Motorised Actuators Gates Opening; 8 m Gates weighing; 1500 kg With Features: Manual operation in case of power failure Incomplete gate closing operation warning light an obstacle is detected Obstacle detection causes the gate movement to stop if with Remote Controls Note; Door Design by Architect, Door construct not in SECURITY SYSTEM Vendor scope.
Item No. 315 BOOM BARRIERS Supply & Installation Testing ,commissioning of item with Accessories as per following features. Boom length : 2 up to 8.4 m Opening / Closing times max. : 4.0 sec Hydraulic System / Electro : Mechanical Protection Class : IP54 Manual override in case of power failure Adjustable: opening /closing times Without: Boom skirt (For additional barrage below the barrier boom when the barrier is closed) Without: Articulated Boom (For low height) With: LED lighting (For visibility of the barrier boom) With: Obstacle detection causes theBoom movement to stop if an obstacle is detected With: Remote Controls
Item No. 316 ARM BARRIER K4 Rating Supply & Installation Testing ,commissioning of item with Accessories as per following features. ARM length : 2 up to 8.4 m Opening / Closing times max. : 4.0 sec Hydraulic System / Electro : Mechanical Protection Class : IP54 Rating : K4 Manual override in case of power failure Adjustable: opening /closing times Without: Boom skirt (For additional barrage below the barrier boom when the barrier is closed) Without: Articulated Boom (For low height) With: LED lighting (For visibility of the barrier boom) With: Obstacle detection causes theBoom movement to stop if an obstacle is detected With: Remote Controls
Item No. 317 e. Tyre Killer Supply & Installation Testing ,commissioning of item with Accessories as per following features. Tyre Killer length : 8 m Blocking Width: from 2.00 m to 6.00 m Blocking Height: 475 mm high Note: The Tyre Killer should be integrated with sliding gate. (In case boom barrier provision is not suitable as per design intent. If boom barrier option is possible then bollard should be integrated with boom barrier & manual gate option can be looked into).
Item No. 318 Bollards Supply & Installation Testing ,commissioning of item with Accessories as per following features. Rising: Hydraulic / Pneumatic Diameter: 250mm Post length: 600mm or 900mm Underground length: 900mm Operation time: 3~5 seconds (adjustable) Working voltage: AC220V Note: The bollard should be integrated with sliding gate. (In case boom barrier provision is not suitable as per design intent. If boom barrier option is possible then bollard should be integrated with boom barrier & manual gate option can be looked into).
Item No. 319 Car SCANNER : Supply & Installation Testing ,commissioning of item with Accessories as per following features. Maximum Vehicle Speed:10mph / 16kmh Tunnel Inside Dimensions: 2895mm (W) x 2504mm (H) Safety Radiation:5 µRem per scan typical / ANSI N43.17 compliant
Item No. 320 RFID Technology for Car Access Supply & Installation Testing ,commissioning of item with Accessories as per following features. with :RFID Tag + UHF Reader + Software + PC 3.2 Pedestrian Access Control
Item No. 321 X-Ray Hand Bag Scanner Supply & Installation Testing ,commissioning of item with Accessories as per following features. Tunnel Dimensions: 530mm (width) x 350 (height). Conveyor belt speed : Atleast 0.23 meters per second Conveyor Max Load: atleast 165 kg. Monitor: 17 inch High resolution low radiation ergonomic LCD color monitor Color Format: 5 colors or more Image max Resolution: 1280 x1024 pixel Image storage: 50000 image storage capacity in real time Zoom: Atleast 32X Auto Center Positioning: The image should automatically center itself on the screen wherever the bag is placed on the conveyor Backup: Uninterruptable Power supply (20 mins) Central Monitoring: Images from all the baggage scanners should be viewable in the IBMS room on a video wall.
Item No. 323 i. METAL DETECTORS FRAME TYPE / Walk-Through Supply & Installation Testing ,commissioning of item with Accessories as per following features. Environmental protection:IS-200W IP 55 (EN 60529) Alarm :Audible and 6-zone visual alarm. 2 X 4 LED alphanumeric traffic and alarm counters: Multi- zone with LED lightbar display. Sensitivity: 100 sensitivity steps in separate floor level adjustment. SAFETY : International standards for human safety to electromagnetic fields. It is safe for pregnant women, people using medical implanted devices like heart pacemakers.Safety Standards: Confirms to the applicable international standards CE, FCC for electrical safety and EMC.
Item No. 324 ii. HANDLE TYPES METAL DETECTORS Supply & Installation Testing ,commissioning of item with Accessories as per following features.Environmental protection:Dimensions (in mm): 362(L) x 55(W) x 30(H)Environmental protection: IP64No risk to persons with pacemakers: Yes Non-interference to magnetic media: Yes Battery: 9 volt block battery can be either replaceable 9 Volt 550mA hours or optional rechargeable NiCad 180mA hours.Tests & approvals: EEC EN5008-1 Table 1:1:1. 2.0 Access Control System:Make : HID / Siemens / VIRDI / Honeywell , Lenel , Cardax, DDS, ZICOM, G4S 2.1 Readers
Item No. 325 Card readers Supply, installation, testing & commissioning of card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories. External control: audio/visual indication and internal LED and buzzer Type: HID Proximity / HID Smart card (Mifare) / HID i-Class Readers Read Range: 3"
Item No. 326 Card + Pin readers Supply, installation, testing & commissioning of card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories External control: audio/visual indication and internal LED and buzzer Type: HID Proximity / H ID Smart card (Mifare) / HID i-Class Readers Read Range: 3"
Item No. 327 Biometric + Card readers Supply, installation, testing & commissioning of Biometric + Card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories External control: audio/visual indication and internal LED and buzzer Type: HID Proximity / HID Smart card (Mifare) / HID i-Class Readers Read Range 3"
Item No. 328 Biometric + Pin + Card readers Supply, installation, testing & commissioning of Biometric + Pin + Card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories External control: audio/visual indication and internal LED and buzzer Type: HID Proximity / HID Smart card (Mifare) / HID i-Class Readers Read Range 3"
Item No. 329 Face Detection + Biometric + Card readers Supply, installation, testing & commissioning of Biometric + Pin + Card readers as per specification suitable for mounting on metal surface/metal frames or wooden frames wall or as required based on site conditions including all accessories External control: audio/visual indication and internal LED and buzzer Type: HID Proximity / HID Smart card (Mifare) / HID i-Class Readers Read Range 3"
Item No. 330 Exit Device a i) Panic Bar Supply installation, testing, commissioning of Panic Bar for fire Escape Door with local alarm
b ii) Door Ajar Sensor /Buzzer. Supply installation, testing, commissioning of Door Ajar Buzzer.
c. SS Push Button for Exit. Supply , installation, testing and commissioning of SS Push Button for Exit.
d. Emergency Break Glass Units. Supply installation, testing, commissioning of Green ABS plastic Emergency Break Glass Units.
Item No. 331 Door Lock
i. Electromagnetic Lock Supply, installation, testing and commissioning of electromagnetic Lock (fail safe type) of 600lb holding force for the following type doors : a. Double leaf Door b. Single leaf Door
ii. Electromagnetic Lock / Door Strike Supply installation, testing, commissioning of Magnetic Contact
Item No. 332 Smart Cards 5. Supply of ISO Thickness, Mifare 2K Smart Cards with the possibility of printing the company details on its facia using sublimation method. Type: HID Proximity / HID Smart card (Mifare) / HID i-Class
Item No. 333 Controller i. Reader / Door Controller Supply installation, Testing & Commissioning of 2/4 Reader Microprocessor based intelligent Access door controller with TCP/IP connectivity and required accessories, power supply unit with Battery Charger & battery back up. a. 4 Reader
b. 8 Reader
ii. Master controller controller (not rq. In IP) Master controller suitable for minimum 64 Card Readers having capability of upto 128 readers linked to four Reader controller on 1 Bus, with battery backed RTC with Dual communication capability over Network
Item No. 334 2.6 Access & Time Attendance Reader, Controller and Software with Features: Standard Version Single User supports Basic Time & Attendance: NO Digital Video Management System : NO Anti passback : NO All standard access control, audit trails: Yes Time & attendance: NO Alarm reports: Yes User handing capacity: 2000 2.6 Visitor Management System
Item No. 335 Supply installation, testing, commissioning of Visitor Management System with including all accessories with Features: Registration Process most visitors in 20 seconds or less Capture visitor’s photo and/or signature Scan arriving visitor’s photo ID or business card Send invites and notifications Video badging : Yes Print visitor passes: Print professional color visitor passes with expiration date, visit area, host, and purpose of visit Issue Pro-Watch® access control raids
Item No. 336 2.7 Access Control Database SQL Sever Access Control Database SQL Sever with Redundant Access Control Database SQL Sever for Automatic Change over in case failure of Main server and automatic synchronization of database ( Vendor to consider cost of redudant software , server along with all necessary hardwares, only if ACS panel has lesser memory on board for no of user & events ie 90000 card holder capacity and 90000 Transaction events)
Item No. 337 2.8 Access Control software license Access Control software license suitable for total number of card reader indicated above with a provision of 30 % spare and future expansion capacity Software license: 2000 readers
Item No. 338 Printer Alarm Printer A4 Size Laser jet paper for Alarm printing
Cable i. Armored AB Copper flexible Cable
Item No. 339 Supply & Installation Testing ,commissioning of Armored AB Copper flexible Cable,PVC insulated, shielded PVC Sheathed layed with fittings & G.I Supports at 0.3mtr
a. 6 c x 0.75 Sq.mm
b. 4c x 0.75 Sq.mm
c. 2c x 0.75 Sq.mm
Item No. 340 d. Cat-6 cable a. Cat-6 cable, laid on Surface with GI Saddle- Spacers , or in cable trays, or in GI Conduits as per site requirements, with required terminations as required with Cable tie`s & Tags.
Item No. 341 Shoe Polisher : Stainless steel shoe shining M/C with sole cleaner, Material : Stainless Steel, Voltage : 220V/50Hz ,Rated Power : 40W , RPM : 1400 ,Time Protection : 15 seconds auto cut off, Polish Capacity : 200ml.
Item No. 342 Linear Surface Mounted Fixture Is an IP66 ultra-slim, multi-pixel, LED linear module, whose aluminium body fitted either with with opaline or clear diffuser hosts 48 RGB LEDs.This module features an independent 8-pixel configuration per Meter, whereas each pixel is made up of 6 LEDs. must always be purchased with L5250 Address setting DMX driver to set the DMX address. More fixture units can be addressed with one L5250.Dimensions: 1000 x 28 x 32 mm / 39.37 x 1.1 x 1.26 in Weight: 0.68 Kg / 1.499 lb Control: DMX mode Pixel pitch (6 LEDs): 125 mm / 49.21 in (minimum) Resolution: 280 pixels/m2 (maximum) Separate IP67 electronic driver Power supply: 100-277VAC / 50-60 Hz Main unit: 24VDC Power consumption: 12W/m. 21 units max per line Impact resistance rating: IK08. Electrical class: III. Operating temperature: -20°C to 50°C (-4°F to 122°F). Approvaed Makes for Proposed light fixture - 1. Griven Lighting 2. Plus Light Tech Lighting 3. Archion Lighting.
Item No. 342 Power Supply - Install with every 5 fixture IP67 Approvaed Makes for Proposed light fixture - 1. Griven Lighting 2. Plus Light Tech Lighting 3. Archion Lighting.
Item No. 343 DMX Controller System Approvaed Makes for Proposed light fixture - 1. Griven Lighting 2. Plus Light Tech Lighting 3. Archion Lighting.
Item No. 344 Mixing garden soil/silt & manure thoroughly well, watering previous night. Planting required plant species, lawn grass as directed etc. complete. (1/10 of Semi-skilled labour)(DSR 2015-16-P-229/ Sr.No.-23)
Item No. 345 GARDEN SOIL: Supplying on site garden soil well sieved 90% to pass through I.S. sieve of 10mm size free from stones rubbish like dried grass roots and other such materials.The soil should be fresh from quarry. The colour of the soil generally be red.The soil will be measured by measuring box. (Farma) (Item includes Royalty charges, octroi, corporation Tax Transporting, loading unloading etc.) (lead charges per 5km considered)
Item No .346 FARM YARD MANURE: Supplying on site well decayed, well dried, well powdered, without clods and free from stones, dried grass and other rubbish material. The colour of the manure generally be black. The manure will be measured by measuring box.(Farma) (Item includes Transporting, loading unloading etc.)(lead charges per 5km considered)
Item No .347 Preparing Shrubbery:-Excavating the ground to a required depth of 30cms. Removing rubbish & conveying unwanted stuff to a required distance as directed. Filling fresh garden soil & manure in excavated area in 3:1 proportion to a height of 30cms. Mixing garden soil and manure thoroughly well, leveling, watering on previous night. Planting well developed shrubs plants, 0.50mtr apart as dircted and maintaining till well established by watering, weedings, Stirring, replacing casualatie etc. complete.
Item No .348 Planting Clipped Hedge:-. Filling fresh garden soil & manure in excavated area in 3:1 proportion to a height of 30cms. Mixing garden soil and manure thoroughly well, leveling, watering on previous night. Planting hedge plant of required species in two rows. Distance b/w two rows & b/w two cutting will be 25cms. Maintaining till well established by watering, weeding, stirring the soil and clipping if necessary etc. complete.
Item No .349 Preparing Lawn (30cm Depth): . Filling fresh garden soil/ silt & manure in excavted area in 3:1 proportion to a height of 30 cms. Mixing garden soil and manure thoroughly well, levelling, watering on previous night. Planting required variety of lawn grass as directed and maintaining till well established y watering, weeding, clipping, rolling etc complete
Item No. 350 Providing and casting in situ or precast tapering R.C.C. M-20 Barrier type Kerb without gutter ( as per IRC 86 1983) embedded 125mm below ground level over M-10 PCC finished neatly with C.M. 1:2, setting the same in C.M. 1:2, including the required excavation in any strata and removing the excavated stuff any where in city and redoing the surface as specified and directed by Engineering In-charge. Using Concrete Batching and Mixing Plant
Item No. 351 Providing , fixing and Installing Garden Interior: Sculpture
Item No. 352 Providing , fixing and Installing Garden Interior : Water Fountain
Item No. 353 Supplying & Installing EV Charging , 60 KW DC fast Charger , with overcharging protection , shortcircuit protection, overcurrent, overvoltage, undervoltage , surge protection , ground fault, overtemprature , overheating protection and voltage stabilization Operating on 415V AC.Plug CC S2 connector ,display with TFT Touch screen , network/sim connectivity.
Item No. 354 Supplying & Installing EV Charging , 3.3 KW DC fast Charger , with overcharging protection , shortcircuit protection, overcurrent, overvoltage, undervoltage , surge protection , ground fault, overtemprature , overheating protection and voltage stabilization Operating on 230V AC. connector ,display with TFT Touch screen , network/sim connectivity.
Item No. 355 Supplying and installing Façade cleaning boom / track mounted with suspended platform of 3.00 x 1.15 x 1.15m , height of wire rope upto 150m size including all machineries , equipments , accessories , materials and labour charges complete.
Item No. 356 SITC of Passenger Lift MMR Gearless for (15 pass) of required speed as per technical specification Including required scaffolding & structural steel brackets for erecting lift as per above specification obtaining required all necessary permissions of Lift inspector (IE & L Dept.) to erect and complete the elevator work, Laisons to operate the elevators including all necessary charges, payments for the same etc complete. (Belt or rope driven) Make :- Schindler/kone/Jhonson/Otis/ Mitsubishi/Hitachi
Item No. 357 Stack Parking TECHNICAL DATA Parklift411/440 Hold to run operations Dependent / independent / indoor /powder coated /galvenized WOHR std colour pebble grey 2.0 ton Electromagentic locks lockers from top to bottom at every 1000mm to ensure maximum safety Emergency stop switch & hydraulic non return valve
WOHR standard corrugated design in galvenised Wohr parlift 411 Ground level Galvenized
Wohr parlift 440 Basement 2 level Powder coated
Total Part-A
PART-B: CHARGES
Item No. 358 Compressive Strength OF C.C. Cube (Set of 3 cubes).
Item No. 359 Rubble:- Crushing Value/Compressive Strength, Water Absorption & Specific Gravity,
Item No. 360 Murum (Liquid Limit & plastic Limit)
Item No. 361 Murum (Compaction test (Proctor density))
Item No. 362 STEEL BAR TESTING Upto 16 mm (Set of 3 Bars)
Item No. 363 STEEL BAR TESTING above 16 mm (Set of 3 Bars)
Item No. 364 To carry out Density test (set of 3 blocks), compressive strength (set of 8 blocks), water absorption test (set of 3 blocks) on concrete blocks in approved laboratory and submiting test results
Item No. 365 To carry out Core cutting in concrete pavement.
Item No. 366 CERAMIC TILES / VITRIFIED TILES Water Absorption, Modulus of Rupture (Set of 6 Tiles)
Item No. 367 Royalty Charges for Rubble
Item No. 368 Royalty Charges for Murum
Relcon Infraprojects Ltd
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid