Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.7 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹8.8 L+₹72,250 (8.97%)Rejected-AOC | L2 | Rejected-AOC Rejected |
| Sl No | Description | Qty | Unit | Pacific Enterprises L2 | Hardik Engineers L1 |
|---|---|---|---|---|---|
| 1.00 | M&L for testing of fire hydrant system by checking serviceability of water pressure, hydrant valve, pumps, wheel, spindle assembly, coupling, assembly with lug, canvas hose, MS pipe, brass nozzle, pressure gauge etc at each floor complete all specified and directed of the following building locations:-
Bldg No P-226, P-227, P-228, P-229, P-265, P-231, P-230, Offr Ward bldg, Airmen Mess, P-266, P-267, P-164, P-165, P-166, P167, P-223, P-224 and P-225. Note:-
The contractor shall be responsible to carry out check & serviceability state of each fire fighting / fire alarm system whenever directed to ensure serviceabilty and effectiveness of the complete system for which contractor shall maintain a register of serviceability / maintenance record / certificate duly signed by contractor and concerned JE E/M, Engineer-in-Charge and user. | 6 | Each Job | 7,000 ₹42,000 | 5,500 ₹33,000 Lowest |
| 2.00 | S&F in replacement of electronic motor protection relay having overload, earth fault, locked rotor, single phasing, phase sequence protection of size 16 to 44 A, three phase, 415V, fixed on existing fire pump starter panel and testing complete all as specified and directed. | 5 | Each | 1,200 ₹6,000 Lowest | 2,200 ₹11,000 |
| 3.00 | S&F in repair 8 zone fire alarm panel with audio visual indication suitable for operating on 230 Volt, AC / 24 Volt, DC supply with solid state electric having conventional modular type one zone per card complete with all connections and testing the panel on every zone complete all as specified and directed. | 1 | Each Job | 9,000 ₹9,000 Lowest | 12,500 ₹12,500 |
| 4.00 | S&F in replacement of power contactor, continous current rating 40 amp, 3 phase, 4 Pole, 440 V, on existing fire pump control panel complete all as specified and directed | 5 | Each | 1,400 ₹7,000 Lowest | 1,800 ₹9,000 |
| 5.00 | S&F in replacement of push switch with NO/NC auxilary contacts, rated 230 V, 6 A complete all as specified and directed | 10 | Each | 120 ₹1,200 Lowest | 500 ₹5,000 |
| 6.00 | S&F in replacement of LED indicator rated 230 V, fixed in existing starter panel complete all as specified and directed. | 25 | Each | 100 ₹2,500 Lowest | 150 ₹3,750 |
| 7.00 | S&F in replacement for power supply SMPS of rating 24 V, 5/6.5 Amps for fire alarm panel including connection on existing control panel and testing complete all as specified and directed. | 4 | Each | 2,500 ₹10,000 Lowest | 3,000 ₹12,000 |
| 8.00 | S&F in replacement of rubber gasket for pipe flange/pump connections as per existing size complete all as specified and directed. | 20 | Each | 50 ₹1,000 Lowest | 500 ₹10,000 |
| 9.00 | M&L for rewinding of motor of any make with enameled copper winding wire of suitable gauge, providing insulating materials such as fibre glass, tape, varnishing, heating up the assembling incl replacement of bearings/bushes by using hydraulic press, commissioning complete testing to full load complete all as specified and directed including dismantling & taking to work shop and bring back after repair and re-fixing complete all as specified & directed for the following capacities :- | - | - | - | - |
| 9.01 | 10 HP capacity or above | 4 | Each Job | 9,000 ₹36,000 | 3,500 ₹14,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹20,360
Closing Date
27 Feb 2026, 6:00 pmClosed
GE (AF) BANGALORE
GE (AF) BANGALORE HQTC, IAF CAMPUS HEBBAL BANGALORE - 560 006
REPAIR / MAINT OF FIRE ALARM, FIRE HYDRANT SYSTEM AND CONNECTED WORKS AT CHAFB
2025_MES_742842_3
8440/E8
Open Tender
Civil Works
Item Rate
180 days
CHAFB
AS PER NIT
5 documents required · 5 mandatory
₹500
GE (AF) BANGALORE
₹20,360
27 Mar 2026
12 Feb 2026
2 Mar 2026
12 Feb 2026
27 Feb 2026
19 Feb 2026
M&L for testing of fire hydrant system by checking serviceability of water pressure, hydrant valve, pumps, wheel, spindle assembly, coupling, assembly with lug, canvas hose, MS pipe, brass nozzle, pressure gauge etc at each floor complete all specified and directed of the following building locations:- Bldg No P-226, P-227, P-228, P-229, P-265, P-231, P-230, Offr Ward bldg, Airmen Mess, P-266, P-267, P-164, P-165, P-166, P167, P-223, P-224 and P-225. Note:- The contractor shall be responsible to carry out check & serviceability state of each fire fighting / fire alarm system whenever directed to ensure serviceabilty and effectiveness of the complete system for which contractor shall maintain a register of serviceability / maintenance record / certificate duly signed by contractor and concerned JE E/M, Engineer-in-Charge and user.
S&F in replacement of electronic motor protection relay having overload, earth fault, locked rotor, single phasing, phase sequence protection of size 16 to 44 A, three phase, 415V, fixed on existing fire pump starter panel and testing complete all as specified and directed.
S&F in repair 8 zone fire alarm panel with audio visual indication suitable for operating on 230 Volt, AC / 24 Volt, DC supply with solid state electric having conventional modular type one zone per card complete with all connections and testing the panel on every zone complete all as specified and directed.
S&F in replacement of power contactor, continous current rating 40 amp, 3 phase, 4 Pole, 440 V, on existing fire pump control panel complete all as specified and directed
S&F in replacement of push switch with NO/NC auxilary contacts, rated 230 V, 6 A complete all as specified and directed
S&F in replacement of LED indicator rated 230 V, fixed in existing starter panel complete all as specified and directed.
S&F in replacement for power supply SMPS of rating 24 V, 5/6.5 Amps for fire alarm panel including connection on existing control panel and testing complete all as specified and directed.
S&F in replacement of rubber gasket for pipe flange/pump connections as per existing size complete all as specified and directed.
M&L for rewinding of motor of any make with enameled copper winding wire of suitable gauge, providing insulating materials such as fibre glass, tape, varnishing, heating up the assembling incl replacement of bearings/bushes by using hydraulic press, commissioning complete testing to full load complete all as specified and directed including dismantling & taking to work shop and bring back after repair and re-fixing complete all as specified & directed for the following capacities :-
10 HP capacity or above
Upto capacity of 7.5 HP
M&L for servicing of existing 6/8/10/12 zone fire alarm panel, re-wiring of defective wiring/connection, changing defective minor spare parts such as relays, connectors, electronic components etc and testing the panel on every zone complete all as specified and directed.
M&L for dismantling the existing faulty centrifugal pump set (Terrace pump) from position by disconnecting the electrical connections and taking down the centrifugal pump set complete along with motor of capacity 10/12.5 HP, 3 phase and transporting to workshop for servicing/overhauling and greasing, incl painting with two coats of synthetic enamel paint (Post box Red colour) and replacement of the following worn out parts and re-installation, testing and commissioning etc complete all as specified and directed :- (a) Bearings for Motor – 02 Nos. (b) Bearings for pump – 02 Nos. (c) Gland packing – 01 Set. (d) Bolts, nuts and washers – 01 Set.
S&F in replacement of gun metal single way fire hydrant landing valve of size 63mm dia, ISI marked with instantaneous coupling complete all as specified and directed
All as per Item No 12.00 here-in-before but double way fire hydrant landing valve.
S&F in replacement of hydrant valve wheel of size 63mm dia complete all as specified and directed
S&F in replacement of Gun metal gate valve of size 50 mm dia after dismantling the existing union, nipple and cutting out rusted threaded portion and making new thread for inserting new GM gate valve (heavy duty), ISI marked, complete all as specified and directed.
S&F in replacement of suction strainer valve of size 100 mm dia (heavy duty), ISI marked, after dismantling the existing valve and testing complete all as specified and directed
S&F in replacement of foot valve CI, ISI marked, heavy duty conforming to IS 4038 of rubber ball lock type including all accessories regular little rubber gasket, nut, bolts & washers complete of size 100mm dia complete all as specified and directed
S&F in replacement of butterfly valve, cast copper alloy screwed down high pressure with iron wheel screwed both sides for iron pipe confirming to IS 13095 and complete all as specified & directed for following sizes :-
100 mm dia
80 mm dia
S&F in replacement of NR Valve, cast iron body with brass spindle, class-1 ISI marked, PN-1.6, both end flanged and drilled and fixed with nuts, bolts & washers including providing rubber insertion of suitable thickness complete all as specified and directed for following sizes :-
100 mm dia
80 mm dia
S&F in replacement of MS pipe carefully and supply, laying and connecting heavy grade ERW steel pipe of 100 mm NB, 6 mm thick as per IS 3589 (1981) including cutting / welding / grinding etc and painting with two coats of synthetic enamel paint (post box red colour) over a coat of red oxide primer complete all as specified and directed
S&F in replacement of pipe supports for all types of pipes including hangers / fastners / elbows/ supports / tees including testing complete all as specified and directed
S&F in replacement of manual call point with glass cover and connected items complete all as specified and directed
S&F in replacement of fire alarm hooter, electronic type, horizontal, single stage, continous normal operation for atleast 50 minutes with sound level 65 dB to 120 dB measured at 1.5 m with sound output variation of + 5 dB, 500 mtrs range with connected items complete all as specified and directed
S&F in replacement of automatic star delta starter panel for terrace pump 12.5 HP, 3 phase, 415 V, with MCB, power contactor, OLR, single phase preventer, timer with connected accessories and conecting the incoming and outgoing cables with proper lugs/glands etc & testing complete all as specified and directed
S&F in replacement of pressure gauge of size 4" dia, 0-21 Kg/cm2 rating complete all as specified and directed
S&F in replacement of sealed maintenace free lead acid battery of capacity 12V, 7/7.5 AH battery, including connecting the wire with proper lugs,nuts bolts etc and testing the changing system to ensure the battery get charge complete all as specified and directed
S&F in replacement of 63 mm dia, 15 mtr long rubberized fabric reinforced rubber lined Controlled Percolation (CP) canvas hose conforming to 15636-1988 including gun metal male & female instantaneous coupling hose and coupling conforming to IS 903-1975 complete all as specified and directed
S&F in replacement of 20 mm dia, 30 mtr long rubber hose reel conforming to IS 444-1987 with gun metal nozzle complete all as specified and directed
M&L for fabrication of fire hose cabinet box for keeping 2 No's hose pipe of size 63mm and length 15 meter each including branch pipe nozzle, coupling etc box made up of MS sheet 800mm x 600mm x 250mm and thickness 3 mm with double leafed glazed shutters (glazed with 4mm thick glass) secured with rubber lining and locking arrangements including painting with 2 coats of synthetic enamel paint (post box red colour) over a coat of red oxide primer complete all as specified and directed
S&F hose reel drum suitable for 63 mm.dia and 30 mtr length conforming to IS 884-1985 all as specified and directed
S&F in replacement of brass nozzle 20mm dia with connected items complete all as specified and directed of the following sizes :-
20mm dia
63mm dia
S&F in replacement of MS sheet enclosure of 3.15mm thick for pump set of overall size 2.0m x 1.5m x 1.0m, factory made with opening in both ends for entry exit for pipe with locking arrangements including two coats of synthetic enamel paint (post box red colour) over a coat of red oxide primer complete all as specified and directed
S&F LT UG Cable XLPE insulated, armoured, heavy duty with multistranded aluminium conductor, 1100 volts grade, laid in trenches or fixed to walls/ poles or passing through pipes including lugs/ thimbles/ ferrules and connection & testing including taking down old/unsv cable complete all as directed and specified for the following cross sectional area sizes :-
25 sqmm 4 core
16 sqmm 4 core
S/&F GI tubing, medium grade, 50 mm bore, as in cable protection fixed to poles/walls or laid in trenches / under roads / crossing etc including taking down old/unsv pipe complete all as specified and directed
M&L for Boring of holes under road pavement hard standing by manual boring incl making good the disturbed surfaces complete all as specified and directed
Excavation in trenches n.exc 1.5 m wide and n.exc 1.5 m depth for getting out in hard dense soil for laying of UG cables complete all as specified and directed
Returning filling including spreading levelling watering well ramming in layers no exceeding 25 cm thick all as specified and directed
Removal of excavated material not exceeding 50 mtr and depositing where directed at level not exceeding 1.5m above the starting point all as specified and directed
M&L for sand filling (pulverised stone dust) for sand cushioning incl spreding ,levelling for protection of cable complete all as specified and directed. Note- Punned thickness of sand i.e 18 cm shall be considered for measurement purpose.
Supply and laying un-reinforced precast concrete cable cover Class LV, Type I, flat, size 250 mm x 150mm x 40mm laid in trenches as in protection of UG cables all as specified and as directed.
M&L for cement concrete in foundations, filling and mass concrete PCC 1:3:6 type C2 using 40mm graded stone aggregate complete all as specified and directed
M&L for painting of entire fire hydrant system of a building with two coat of synthetic enamel paint (post box red colour paint chromate) after scrubbing, removing of old painted surface and preparing the surface, including painting of electric panel and all marking with white colors, valve pipeline, hydrants, tank, lid etc complete all as specified and directed
S&F in replacement of PVC FRLSH cable copper conductor complete all as specified and directed of the following sizes :-
1.5 Sqmm 4 core
2.5 Sqmm 4 core
S&F in replacement of Fire Brigade inlet connection adaptor complete all as specified and directed for the following ways :-
Two ways
Four ways
S&F in replacement of Branch pipe, gun metal, 63mm, instantaneous inlet, made threaded outlet, 15mm bore nozzle short including connection and pressure testing complete all as specified and directed
Refilling, servicing and pressure testing of ABC type Fire extinguisher of 04 Kg Capacity complete all as specified and directed
Refilling, servicing and pressure testing of CO2 type Fire extinguisher of 04 Kg Capacity complete all as specified and directed
S&F in replacement of fire hook confirming to IS 927- 1981, hook head made up of forged carbon steel duly painted with anti-corrosive paint, handle shall made of bamboo of length not less then 3 mtr, hook should marked with ISI marked complete all as specified and directed.
S&F in replacement of fire beater confirming to IS 8096-1992, beater blade is made out of steel wire mesh of size 452 x 352 mm with fire resistant frame and handle is made out of bamboo wood of length 1.8 mtr, dia 30 +/- 5 mm complete all as specified and directed
S&F in replacement fire mild steel fire bucket confirming to IS 2546-1974, body made out of minimum 1 mm thickness of capacity min 10 litre and bucket is duly painted with a coat of synthetic enamel paint (post box red colour paint) and marked as per fire standard complete all as specified and directed
M&L for fabricating outdoor fire bucket stand made out of 50mm x 50mm x 6mm angle iron and MS sheet top roof made out of minimum 3mm thickness for hanging 04 Nos of fire bucket and extingusher with proper foundation and placing the stand wherever specified including necessary welding, cutting etc and with a coat of synthetic enamel paint (post box red colour paint) complete all as specified and directed
M&L for De-watering, removing all mosses, algae and dirt from internal walls, floors & mouths of pipes of RCC overhead tanks (Fire tanks) for OH Fire tank upto 5000 litres capacity by using steel wire brush and cleaning with high pressure industrial vacuum cleaner including removing of dirty water completely using sludge pump set and disposing off the same to a safe distance and applying of anti bacterial sterilization spray to internal surfaces using Zero bacterial compound (Sodium hypochlorite) or equivalent approved chemical complete and writing the date of cleaning on outside of tank using synthetic enamel paint of white colour over black background with letters of size 50mm height x 50mm breadth complete all as specified and directed.
Notes for item No 1 to 52.00 :- (a) In case of any breakdown of motor or pumps or any connected items of fire fighting / fire alarm items become faulty, the contractor shall locate the problem / fault at site within 24 hours on intimation by JE / Engineer-In-Charge within 24 hours and ensure that the fault rectification within 24 Hours on locating the fault, failing which an amount Rs 300.00 per hour shall be recovered as penality from contractor dues after expiry of 24 hours. (b) The contractor shall be responsible for all spares / items as applicable.Those has been purchased from original manufacturers / auth distributor / dealer only shall be submitted to department while claiming payments. (c) The contractor shall be responsible to carry out check of all the fire fighting / fire alaram system at least once in month to ensure serviceabilty and effectiveness of the complete system round the clock 24X7 for which a maintenance record duly signed by contractor and JE E/M and Engineer-in-Charge seperately to be maintained.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.28 MB
BOQ_842685.xls
BOQ • 0.74 MB
Tender_8440.pdf
Tender Documents • 0.59 MB
SOC_8440.pdf
Additional Documents • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .