Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹20,800
Closing Date
9 Jan 2025, 11:15 amClosed
EE ENM M6
DELHI JAL BOARD MU BLOCK PITAMPURA DELHI-34
Repair Renovation of Standard make APFC Panel at Peeragarhi BPS in AC 15
2025_DJB_267763_17
NIT NO. 22(M-6)
Open Tender
Miscellaneous Works
Item Rate
60 days
EE ENM M 6
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Account No 50448339804
₹20,800
Yes
16 Jan 2025
2 Jan 2025
9 Jan 2025
2 Jan 2025
9 Jan 2025
2 Jan 2025
IMPROVEMENT OF 2 Nos. APFC PANELS Dismantling of defective componentof APFC panels such as capacitors, relays, lights, contactors including dismantling of incoming and outgoing connection etc. as required at site.
Supply of Super Heavy duty Round type capacitors of various capacities rated at 440V, 50 Hz, 3 phase AC , complete with terminal cover and discharge device -make standard
Banking of capacitor units to form banks of suitable capacity by electrical interconnection with multistrand copper wires/Al. bus bars using necessary mountings and hardware , etc. as required at site.
Supply of triple pole capacitor duty contactors to replace defective contactors in APFC panel , suitable for 25 KVAr capacitors , make Standard
Supply of triple pole capacitor duty contactors to replace defective contactors in APFC panel , suitable for 50 KVAr capacitors , make Standard
Supply of triple pole MCB up to 63 A to replace defective MCB in the capacitor panel- make Standard
Supply of triple pole MCB up to 32A to replace defective MCB in the capacitor panel- make Standard
Supply of triple pole MCCB of 125 A capacity for operation and safety of the APFC panel - make Standard
Supply of microprocessor based APFC relay with digital display of power factor and other parameters for sensing power factor and giving phased impulses to contactor coils for switching ON-OFF required no. of capacitors on receiving signals from Control CT in the main line- make Standard
Supply of LED indication light of various colours to replace defective lights in various stages of capacitor panel - Make : FTC/standard
Supply of Volta Meter 0-500A to replacement defective ammeter in the capacitor panel. Make: AE/HPL/Eqv.
Servicing of panels including complete dusting of all components, cleaning of contact point with CTC solution, decarbonising of various joints , tightening of all nut bolts , sleeving of live parts alignment of doors to prevent ingress of moisture and vermins and touching of rusted parts of the panels etc. as required at site.
Installation of all above components in the existing capacitor banks with suitable fabrication work to accommodate new items in the existing enclosure / structure for alignment of components and ease of termination complete with hardware on the mounting structure and termination of existing cables with lugs, tapes etc. complete with earthing of the capacitor banks, touching the rusted parts of the structure with paint for protection from moisture etc. as required at site.
Testing & Commissioning of complete APFC Panel installation including following: 01. Meggering of complete capacitor installation using 500V megger 02. Continuity test for checking continuity of all circuits to ensure that all circuits are properly wired. 03. Checking function and efficiency of various components of APFC panel 04. Charging capacitor panel after conducting above tests.
Monitoring of Power Factor during warranty period including checking of efficiency of capacitors and other equipment to ensure that APFC panel is working to its highest capacity for achieving target power factor
REPAIR OF STATIC CAPACITORS OF TRANSFORMER Checking of capacitors and dismantling of defective capacitors from static capacitor banks including dismantling of terminations, wirings, hardware, as required at site.
Supply of Super Heavy duty capacitors of various capacities rated at 440V, 50 Hz, 3 phase AC complete with terminal cover and discharge device for replacement of defective capacitors of static capacitor banks -make standard
Banking of capacitor units to form banks of suitable capacity by electrical interconnection with multistrand copper wires/Al. bus bars using necessary mountings and hardware, etc. as required at site.
Installation & connection of capacitors as described above using necessary hardware, mounting arrangement and termination with multistrand copper wires, lugs, tapes etc. as required at site.
bhawani electrical system (BID ID -1559666)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .