Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹17.4 Cr
EMD Value
₹17.4 L
Closing Date
11 Mar 2024, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Package No. GAJ-002-PM-ABHIM Construction of Critical Care Block (CCB) at DHH Gajapati, Odisha
NBCC/ODISHA/SBG/NHM/NIT/23-24/66
NBCC/ODISHA/SBG/NHM/NIT/23-24/66
Open Tender-Domestic
Civil Works General
Gajapati, Odisha
₹11,800
₹17.4 L
11 Mar 2024
22 Feb 2024
11 Mar 2024
11 Mar 2024
3 Apr 2024
Providing and laying plain cement concrete of proportion (1:3:6) in
foundation and floors using 4 cm. size black hard crusher broken granite
stone metal and screened and washed sharp sand for mortar of approved
quality and from approved quarry including hoisting, lowering, laying
concrete, ramming, watering and curing etc. complete to required levels
laid in layers not exceeding 15 cm. thick in each layer including cost,
conveyance, royalties of all materials and cost of all labours,labour cess,
T&P etc complete as per the direction of the Engineer-in-charge.
13 6 Anti-termite Treatment 0 0.00 0.00 0.00
Supplying diluting and preparing chemical emulsion like imidacloprid 30.5%
SC or other chemicals approved by central insecticides Board or as directed
by the manufacturer and spraying the mixture uniformly by sprayer as per-
constructional Anti-termite Treatment confirming to IS 6313 (PART-II) and
creating a chemical barrier under and around the column pits, wall
tranches, basement excavation top surface of plinth filling juction of wall
14 0 and floors along with external perimeter of the building expansion joints. sqm 1122.79 123.36 1,38,504.23
surrounding the pipes and conduits etc. at the rate of 7.5liter per sqm on
vertical surface and 5.0 liter per sqm on horizontal surfaces, 50% of the
emulsion to be filled in the holes made in trenches at 150mm center to
center (or as directed by the manufacturer) including the cost of all
materials. cost of all labour, conveyance, loading, unloading, T&P, Etc. all
complete as per the direction of Engineer-in-Charge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Fly Ash brick masonry in cement mortar (1:6) in Substructure using Fly
Ash bricks of 25 cm. x 11 cm. x 8cm size having a crushing strength of not
less than 75 kg./sqcm with dimensional tolerance ± 2% including splays
cutting circular moulding chamfering and corbelling and similar such type of
16 0 works with all necessary projections watering and curing after immersing 0 0.00 0.00 0.00
the bricks in water at least for six hours before use including cost,
conveyance, royalties and taxes of all materials with all labour,labour cess
and T & P required for the work complete in all respect as per direction of
Engineer-in-Charge.
Providing, lifting, hoisting and laying Reinforced cement concrete of M-25
grade as per approved designs and drawings having a minimum
compressive strength (in work test) 250 Kg. / Square cm. in 15 cm. cubes
at 28 days after mixing and test conducted in accordance with I.S. 516
using 12 mm. to 20 mm. size black hard crushed broken granite stone
chips and screened and washed sharp sand for mortar of approved quality
from approved quarry, washed and cleaned ( 20mm. size chips not to
exceeds 25 %) to be mixed in concrete mixture with Portland slag cement
(PSC) including hoisting, lowering, laying and compaction concrete by using
vibrators, watering and curing for 28 days, centering and shuttering then
after dismantling and removing debris from the work site and finishing the
exposed surface smooth providing grooves or beads wherever necessary
including cost, conveyance, loading, unloading, royalties and taxes of all
materials and cost of all labours, sundries, T & P required of the work
etc.complete in all respect as directed by the Engineer-in-Charge. But
excluding cost and conveyance of M.S. rods or Tor steel and binding wires
and labour charges for straightening, cutting, bending etc. of M.S. rods or
tor steel tying the grills and placing in proper position.
20 0 Foundation and plinth 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
68 9 Reinforcement 0 0.00 0.00 0.00
Supplying Cutting, straightening coiled or bent up M.S. Rod or tor steel of
primary steel producers such as SAIL / Tiscon / RINL / JINDAL STEEL /
SHYAM STEEL (grade Fe-500D) etc. including bending, binding, welding
and jointing if necessary and tying the grills and placing in position as
required for R.C.C. Work and for providing fan hooks as required, hoisting,
69 0 lowering, laying including cost, conveyances, taxes of M.S. Rod or tor steel 0 0.00 0.00 0.00
and binding wires of 18 to 20 gauge and labour required for the work for
bending, binding and tying the grills in all floors with labour cess etc.
(payment will be made on standard weight of B.I.S. for M.S. Rods or tor
steel only) etc. complete as per specification & direction of Engineer-in-
70 0 Foundation and plinth qtl 457.58 10462.95 47,87,638.40
Fly Ash brick masonry in cement mortar (1:6) in super structure using Fly
Ash bricks of 25 cm. x 11 cm. x 8 cm size having a crushing strength of
not less than 75 kg./sqcm with dimensional tolerance ± 2% including
splays cutting circular moulding chamfering and corbelling and similar such
79 0 type of works with all necessary projections watering and curing after 0 0.00 0.00 0.00
immersing the bricks in water at least for six hours before use including
cost, conveyance, royalties and taxes of all materials with all labour,labour
cess and T & P required for the work complete in all respect as per
direction of Engineer-in-Charge.
Providing Fly ash bricks masonry work using 12.5 cm. x 11 cm. x 8 cm
having crushing strength not less than 75Kg/Sqcm in cement mortar
(1:4). Immersing the bricks in water before use in all necessary projection
87 0 splays cutting, circular moulding, corbelling etc. Including cost of 0 0.00 0.00 0.00
conveyance ,taxes & royalties, loading and unloading of all materials &
cost of all labour, scaffolding ,watering & curing, sundries, T & P etc.
complete as per the direction of Engineer-in-charge .
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing 16 mm thick cement plaster with cement mortar of mix (1:6)
with screened and washed sharp sand for mortar and finished smooth to
the rough surface of walls in all heights after racking out joints including
94 0 watering and curing, rounding of corners, providing grooves where ever 0 0.00 0.00 0.00
necessary with cost, conveyance, royalties of all materials with cost of all
labour,labour cess, T&P, and scaffolding required for the work etc.
complete in all respect as directed by the Engineer in charge.
Providing 12 mm thick cement plaster with cement mortar of mix (1:6)
with screened and washed sharp sand for mortar and finished smooth to
the rough surface of walls in all heights after racking out joints including
102 0 watering and curing, rounding of corners, providing grooves where ever 0 0.00 0.00 0.00
necessary with cost, conveyance, royalties of all materials with cost of all
labour,labour cess, T&P, and scaffolding required for the work etc.
complete in all respect as directed by the Engineer in charge.
Providing 6 mm thick cement plaster with cement mortar of mix (1:4) with
screened and washed sharp sand for mortar and finished smooth to R.C.C.
work after closed deep chipping & slurry treatment including watering and
110 0 curing, rounding of corners, providing grooves where ever necessary with 0 0.00 0.00 0.00
cost, conveyance, royalties of all materials with cost of all labour, T&P, and
scaffolding required for the work etc. complete in all respect as directed by
the Engineer in charge.
Providing and installing two component acrylic modified cementitious
waterproofing coating with masterseal 551/ Equivalent over roof slab after
carring out pond test on roof slab filling all defects. Saturating the surface
118 0 mixing the products and then application in 2.0 mm thickness (1.8kg/ sqm 0 0.00 0.00 0.00
coverage rate for 1.0mm thickness) in suitable layers complete in all
respect all material, tools, plant & labour complete in all respect. Density
1850kg/m3, mix ratio (Powder to liquid ) 3.1 by weight water.
122 16 Grading Plaster 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing 2.5cm thick Grading Concrete over roof slab with cement
concrete (1:2:2) using 6mm size black hard granite crusher broken chips
and screened & washed sharp sand for mortar and finished smooth to the
123 0 rough surface of slab including watering and curing with cost, conveyance, 0 0.00 0.00 0.00
royalties of all materials with cost of all labour, labour cess and T&P
required for the work etc. complete in all respect as directed by the
Engineer in charge.
127 17 Vitrified Floor Tiles 0 0.00 0.00 0.00
Supplying, fitting and fixing Double charge vetrified tiles of premium grade
having thickness 8mm to 10mm confirming to IS 13756 of size 600mm x
1200mm plain (Ivory) stain free & Germs free of approved make
(JOHNSON / SOMANY/ KAJARIA or equivalent ) in floors on 20mm thick
bed of C.M. (1:4) (1cement:4course sand) and filling the joint with white
cement mixed with pigment to match the shades of the tileincluding cost of
all materials, labour, labour cess, T&P etc. required for the work complete
in all respect as directed by the Engineer in charge.
134 18 Vitrified Floor Skirting 0 0.00 0.00 0.00
Providing, fitting, fixing Double charge vitrified tiles of premium grade
having thickness 8mm to 10mm confirming to IS 13756 of size 600mm x
600mm plain (Ivory) of approved make (JOHNSON / SOMANY/ KAJARIA
or equivalent ) as directed by Engineer-in-charge in dados skirting and
risers of steps on 12mm thick cement plaster (1:3) jointed with neat
cement slurry mixed with pigment to match the shades of the tiles
including rubbing and polishing etc. complete with cost, conveyance,
royalties of all materials all labour,labour cess complete in all respects.
141 19 Conductive Flooring 0 0.00 0.00 0.00
Providing and installation of Primo SD Vinyl Sheet Flooring manufactured
by Tarkett with a nominal thickness of 2mm as per ISO 24340 - EN 429
and width of 2m as per ISO 24341 - EN 426. Primo SD shall conform to
requirement of ISO 10581 - EN 649. Primo SD shall have binder content of
Type I as per ISO 10581, Fire resistance of 8kW/m2 as per ISO 9239-1
and Class Bfl-S1 as per EN 13501-1, Indentation of less than .03mm as
per ISO 24343-1 and EN 433, Slip Resistance of R9 as per DIN 51130,
greater than 0.3 as per EN 13893. The static electrical discharge shall be
142 0 less than 2kV as per EN 1815. The electrical resistance of the product shall 0 0.00 0.00 0.00
be less than 10^8 Ω as per EN 1081. The product does not contain
Pthalate based plasticizer and emission rate of VOC is very low, measured
after 28 days as per EN 16516. TVOC and formaldehyde emissions are
below 10µg/m3. It is 100% REACH compliant. The product is fit to be
used in Class 34 in Commercial and Class 43 in Industrial as per EN ISO
10874. The product is installed using multi coloured welding rods to ensure
seamless finish. The average seam strength shall be more than
240N/50mm as per EN 684
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
146 20 Stainless Steel Ceiling 0 0.00 0.00 0.00
Providing and fixing Knauf Ceiling Solutions SS 304 grade , one side
polished to ground, 0.5 mm thick stainless steel Clip In ceiling for operation
theatre ceiling required GI substructure at all levels including, making panel
surface free of projection and cavity, with all materials and labour
complete. The rate shall include trap doors, making cut outs for tube lights,
spotlights, duct doors, for specified size, grills etc., providing additional
trimming around cut outs for light fittings, grills, etc., providing additional
supports from ceiling where main / cross members are cut. Installation to
be done with All Clip in Accessories including DP 12 Hanger, C Channel,
Wall angle anchor fastner Butterfly clip and 2.5mm dia GI wire
149 21 Amstrong False Ceiling 0 0.00 0.00 0.00
Providing & Fixing horizontal level suspended ceiling comprising of Knauf GI
Bioguard Clip-in Plain Tile 600x600mm (Nominal Size) tiles of 120 gsm
galvanized steel as per IS 277 (2003) suitable for architectural finishes in
0.5mm thickness as per in IS:513 (1994) in Global white color with
concealed suspension system having a bevelled edge of 3x3mm and height
of 33mm on one side and 18mm on the other side. Tiles shall be flattened
by precision leveller to minimize sag to less than 1/400mm. The tiles shall
have double round pip of ɸ 2mm and ɸ 6mm for secure engagement and
levelling respectively, along with swing down feature and special tabs to
allow removal of tile to enable plenum access. The coated surface of the
tile shall exhibit anti-microbial properties (eradication and inhibition of
growth) and shall achieve up to 99.99% reduction in bacterial activity as
per ISO22196:2011 when tested for organisms: Escherichia Coli, Bacillus
Subtilis, Pseudomonas Aeruginosa, Clostridium Perfringens, Enterococcus
Faecalis, Staphylococcus Aureus, Salmonella Enterica, Streptococcus
Faecalis and MRSA. The coated surface of the tile shall also exhibit fungal
resistance properties and shall achieve a “Rating 0” (No fungal growth
observed) as per ASTM G-21 when tested for Aspergillus Brasilliensis,
Penicillium Pinophilum and Candida Albicans. The tile shall be
electrostatically polyester powder coated using RoHS compliant powder
having coating thickness ranging from 60-80 microns. The powder coating
shall pass Salt Spray Test for 750 Hours as per ASTM B117, QUV –A Test
for 1000hours as per ASTM G-154 – (Cycle – 1) and Humidity test for
1000hours as per DIN 50017.
The powder coating shall have an adhesion of GT0 as per EN ISO 2409.
The shade variation across batches shall be delta E<1 using Excite/BYK
Gardner instrument and gloss level of 25±5% at 60˚ as per ASTM D523.
151 0 The tile shall have scratch, mar & abrasive resistance properties. The tile 0 0.00 0.00 0.00
shall have a Light Reflectance of ≥ 63% in accordance with ASTM 1477-98
and Fire Performance of class 0/1 as per BS 476 Part 6 & 7 in module size
154 22 Granite Flooring 0 0.00 0.00 0.00
Fixing granite tiles of approved dimension area above 0.4 sqm (20mm
thick) in floor, treads of steps and landing on 20mm thick bed of cement
mortar (1:4) jointed with neat cement slurry mixed with pigment to match
the shades of the tiles including rubbing and polishing etc. complete with
cost, conveyance, royalties of all materials complete in all respects as per
direction of Engineer-in-Charge.
161 23 Granite Skirting 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Fixing granite tiles of approved dimension area above 0.4 sqm (20mm
thick) in Dados, treads of steps and landing on 12mm thick cement mortar
(1:3) jointed with neat cement slurry mixed with pigment to match the
shades of the tiles including rubbing and polishing etc. complete with cost,
conveyance, royalties and taxes of all materials complete in all respects as
per direction of Engineer-in-Charge.
168 24 Industrial vitrified floors tiles 0 0.00 0.00 0.00
Supplying, fitting & fixing of Industrial vitrified tiles (30x30)cm in floors of
approved make laid on 20 mm thick cement mortar (1:4) (1 cement : 4
169 0 course sand) and filling joints with slurry including cost of all materials, 0 0.00 0.00 0.00
labour T&P etc required for the work all complete as per direction of the
Engineer-in-charge.
175 25 Industrial vitrified dadoes tiles 0 0.00 0.00 0.00
Supplying, fitting & fixing of Industrial vitrified tiles (30x30)cm in dadoes of
approved make laid on 12 mm thick cement mortar (1:3) (1 cement : 3
course sand) and filling joints with slurry including cost of all materials,
labour T&P etc required for the work all complete as per direction of the
cost of all materials, labour T&P etc required for the work all complete as
per direction of the Engineer-in-charge.
Supplying and Fixing of M.S. Grills, M.S.Doors, M.S. Gate etc including
183 0 cost,conveyance of all materials,priming,and labour for fitting fixing 0 0.00 0.00 0.00
etc.complete as per the instruction of Engineer-in-Charge
Supplying , fitting and fixing of openable UPVC doors with door frame of
approved make with 6mm thick glass of approved quality complete with
frame, shutters and all fitting and fixtures. .( SOR 2022: Page No 235,
Supplying , fitting and fixing of two track two pannel UPVC sliding window
with Fly proof Netlon Fibre mesh (Two nos. of Glazed and One nos. of Wire
200 0 mesh pannels) made of (small series) frame 62*52mm and sash 42*68mm 0 0.00 0.00 0.00
both having wall thickness of 2.5(+/- 0.2 mm) and single glazing bead of
appropriate dimension (are of window above 1.75sqm)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
208 29 UPVC VENTILATORS 0 0.00 0.00 0.00
Supplying and fixing-Fixing of Un-plasticised poly vinyl chloride (UPVC)
(FENESTA/NCL VEKA LTD.) Ventilators Top Hung-60-Series duly
manufactured using UPVC reinforced profiles of 60mm x 50mm x 2.5mm
for outer frames, 75mm for outer frames. 75mm x 60mm x 2.5mm for
casement window sash profile capable of mounting single glazing system,
structurally reinforced with hhot dip galvanised up to 50 microns of
minimum thickness of 1.5 mm prefabricated & welded through fusion
welding the window sash shall be fitted with EPDM weathering seal
resistant accessories like clipping locking system made of aluminium 1 No.
per set of sashes and th esystem isto be installed at the site using anchor
fasteners, silicon rubber sealant,easy glazing/deglazing at site etc.
including cost and conveyance of all material, accessories, labour charges,
materials and product conforming to ASTM D 638-14,EN-447-95 and other
applicable codes and standards.
Providing and fixing of NAVAIR make insulated fire rated GI Sheet doors
conforming to FD 120-I 30 classification of IS 3614 :2021 with fire rating
of 120 minutes integrity and 30 minutes insulation. The factory
manufactured door frame and shutter assembly shall be made out of
minimum 1.20 mm thick GI Sheet with minimum 120 GSM coating as per
Door and frame should be finished with powder coating in standard RAL
shade finish having DFT of minimum 30 microns. The door should carry a
minimum 500 Hrs of salt spray test. All accressesories like hardware, vision
panel, fire & smoke seal etc to be supplied by Fire door manufacturer only
as per the guidelines laid down in IS 3614:2021.Every door must carry a
215 30 label confirming to type of door & its fire rating. 0 0.00 0.00 0.00
The door must carry a 5years valid test evidence from CBRI-Roorkee /
NTH-Kolkata/ NABL accrediated lab which operates in accordance with
The Door frame shall be single rebate grooved profile of size minimum
100mm x 57mm made out of 1.20mm (18gauge) minimum thick
galvanized steel sheet. Frames shall be butt / mitered joint and field
assembeled with bolting system. Frames to have inbuilt grooved to
accomodate Intumuscent fire seal strip . The frame should also be provided
with fire rated EPDM smoke seal 20x4 mm conforming to IS: 3614:2021 or
as per test evidence. It shall be fixed in grooves, specifically cut in rebate
on all the 3 sides of the frame.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
All provisions should be mortised & provided with necessary inbuilt
reinforcement to receieve appropriate hardware.
Door leaf should be minimum 46mm thick fully flush double skin door. Door
leaf must be manufactured from 1.2mm(18gauge) thick galvanised steel
sheet. The infill material shall be mineral wool of minimum density 48
kg/cum. All doors shall be factory prepped for receiving appropriate
hardware and provided with necessary reinforcement for hinges, locks, and
door closers. The edges should be interlocked with a bending radius of
216 0 1.4mm. For double leaf doors integrated astragals has to be provided on 0 0.00 0.00 0.00
the meeting stile for both active and inactive leaf.
Double leaf insulated fire rated door of FD 120 classification IS 3614:2021
with 120 minutes integrity and 30 minutes insulation - For staircase/exit
pathway application / Refuge area. - Door frame fixed to exit opening with
12 nos. fasteners and door assembly must be provided with 1 no. single
point panic bar and external trim with key cylinder to active door shutter, 1
no. 2 point panic bar on inactive door leaf, 2 no. door closers with spring,
1 no. coordinator for sequencing.
Fully Glazed door having frame of (62 X 58 mm) size and sash having (62
X 102mm) with Glass of 8mm clear display reinforced with 1.5mm G.I.
Sheet fixing with 3D hing having load capacity of 150 kg, having a locking
system 1800mm Espegalod with multipoint locking system.
227 32 STRUCTURAL GLAZING 0 0.00 0.00 0.00
Designing, fabrication, testing, protection, installation and fixing in position
228 0 semi(grid) unitized system of structural glazing (with open joints) for linear 0 0.00 0.00 0.00
as well as curvilinear positions of the building for all heights and all levels
Supplying, fitting and fixing of Stainless steel of 304 grade in hand railing
using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x
32mm x 2mm @ 0.90mtr. C/C and stainless square pipe bracing of size
234 0 32mm x 32mm x 2mm in 3 rows in stair case as per approved design and 0 0.00 0.00 0.00
specification, buffing, polishing etc with cost, conveyance, taxes of all
materials, cost of all labour,labour cess, T&P etc. required for the work
complete in all respect as per direction of the Engineer-in-charge.
Painting two coats to new Iron work with approved enamel paints of
approved colour, shade over a coat of primer including sand papering,
242 0 polishing the surface, cost, conveyances, taxes of all materials and cost of 0 0.00 0.00 0.00
all labour, labour cess with T&P etc, complete as per specification &
direction of Engineer-in-charge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
250 35 Red oxide Primer 0 0.00 0.00 0.00
Painting one coat with approved Red oxide primer including cost,
conveyances, royalties, taxes of all materials and cost of all labour with
T&P required for the work etc. complete as per specification & direction of
Engineer in charge.
257 0 Terrace Floor sqm 14.48 92.85 1,344.53
Wall painting two coats with Weather coat paint (1st quality) exterior grade
of approved make & approved shade over a coat of primer to make an
even finished surface in all floors and heights with all scaffolding and
staging charges including cost, conveyance, cost of all labours, T & P,
sundries etc. as required for the work complete in all respect as per the
direction of the Engineer-in-Charge.
268 37 Primer Outside Walls 0 0.00 0.00 0.00
Priming one coat with wall cement primer (water bound) to make an even
finished surface in all floors and heights to wall surface of approved make
and shade including sand papering, applying putty wherever necessary &
cost of scaffolding, staging charges with cost, conveyance, cost of all
labour,labour cess T&P etc. complete as per the direction of the Engineer-in-
275 Terrace Floor sqm 642.20 98.60 63,321.43
276 38 Primer Inside Walls 0 0.00 0.00 0.00
Priming one coat with wall cement primer (water bound) to make an even
finished surface in all floors and heights to wall surface of approved make
and shade including sand papering, applying putty wherever necessary &
cost of scaffolding, staging charges with cost, conveyance, cost of all
labour,labour cess T&P etc. complete as per the direction of the Engineer-in-
283 Terrace Floor sqm 266.84 92.17 24,594.59
Finishing plastered surfaces of walls with cement based wall putty (Water
based) of approved make and finishing the surface smooth and even by
sand papering to receive painting in walls, at all heights with staging
wherever necessary with cost, conveyance, cost of all labour, labourcess,
all T&P etc. required for the work complete in all respect as per the
direction of the Engineer-in-charge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
291 Terrace Floor sqm 266.84 90.68 24,197.85
292 40 Plastic emulsion paint 0 0.00 0.00 0.00
Painting two coats with plastic emulsion paint over a coat of water bond
cement primer to make an even finished surface in all floors and heights to
wall surface of approved make and shade including sand papering, applying
293 0 putty wherever necessary & cost of scaffolding, staging charges with cost, 0 0.00 0.00 0.00
conveyance, cost of all labour,labour cess, T&P etc. complete as per the
direction of the Engineer-in-charge.
299 Terrace Floor sqm 266.84 109.07 29,103.55
300 41 Expansion Joint 0 0.00 0.00 0.00
Supplying and fixing of Elastomeric Membrane of 200mm x 2mm size for
301 0 expansion joint sealing from approved manuefacturer, fixing with epoxy 0 0.00 0.00 0.00
adhesive of approved quality complete.( SOR: Page No 234, Item No: 11)
302 0 Ground Floor mtr 17.91 0.00 0.00
303 0 First Floor mtr 17.91 0.00 0.00
304 0 Second Floor mtr 17.91 0.00 0.00
305 0 Third Floor mtr 17.91 0.00 0.00
307 42 Demolition Work 0 0.00 0.00 0.00
Demolishing cement concrete manually/ by mechanical means including
308 0 disposal of material within 50 metres lead as per directionof Engineer - in - cum 683.23 744.33 5,08,545.25
11 0 Sub-Total of Civil Works 0 0.00 0.00 11,90,25,168.64
12 0 Electrical Works 0 0.00 0.00 0.00
Internal Electrification
13 A. Circuit Cum Wiring 0 0.00 0.00 0.00
Supplying & Wiring for light point/ fan/ exhaust fan point/ call bell point
with 1.5 sqmm FR PVC insulated copper conductor single core cable in
surface / recessed 1.6 mm thick PVC conduit with modular switch and
earthing the point with 1.5 sqmm FR PVC insulated copper conductor single
core cable including providing modular box with cover of requisite number
of modules including providing cover plates as required. (Make of Switches:
Legrand/ Schneider/ Crabtree/ ABB/ Reckoner),(Make of wire:- Finolex/
Polycab/ Anchor/ Havells) )
Single light point controlled by one 6A switch or first light point of group
control.(Primary Point Group-C)
16 b) Subsequent point of group control (Secondary Point) Each 387.00 565.22 2,18,740.14
Supplying & Wiring for twin control light point with 1.5 Sqm.m FR PVC
insulated copper condutor single core cable in surface / recessed PVC
conduit 2 way modular switch,modular plate,suitable GI box and earthing
17 2 the point with 1.5 Sqm.m .FR PVC insulated copper conductor single core Each 12.00 1126.90 13,522.80
cable etc as required. (Make of Switches: Legrand/ Schneider/ Crabtree/
ABB/ Reckoner).(Make of wire:-Finolex/ Polycab/ Anchor/ Havells/
Supplying and fixing two module steeped type electronic fan regulator with
18 3 proper modular plate switch box including connections etc. as Nos 99.00 579.38 57,358.62
required.(Make : Legrand/ Schneider/ Crabtree/ ABB/ Reckoner)
Supplying and fixing 6 Amp plug with 6 Amp switch (Modular Type) on
existing board.(Make: Legrand/ Schneider/ Crabtree/ ABB/ Reckoner)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying & fixing suitable size GI Box with modular plate and cover in
front on surface or in recess, including providing and fixing 3pin 5/6 amps
modular socket outlet and 5/6 amps modular switch etc. as
required.(Make: Legrand/ Schneider/ Crabtree/ ABB/ Reckoner)
Supplying & fixing suitable size GI Box with modular plate and cover in
front on surface or in recess, including providing and fixing 2nos 3pin 5/6
amps modular socket outlet and 2nos 5/6 amps modular switch etc. as
required.(Make : Legrand/ Schneider/ Crabtree/ ABB/ Reckoner)
Supply & fixing of 6 / 16 Amp Plug Boards consisting of a 16 Amp clip-in
type modular switch with indicator and a 6/16 Amp clip-in type modular
shuttered plug socket fixed on metallic concealed box including
interconnections and making good the damages caused complete as
required and as per direction of Engineer-in-charge.(Make : Legrand/
Schneider/ Crabtree/ ABB/ Reckoner)
Supply & fixing of 6 / 16 Amp Plug Boards consisting of 2nos 16 Amp clip-
in type modular switch with indicator and 2nos 6/16 Amp clip-in type
modular shuttered plug socket fixed on metallic concealed box including
interconnections and making good the damages caused complete as
required and as per direction of Engineer-in-charge.(Make : Legrand/
Schneider/ Crabtree/ ABB/ Reckoner)
Supplying, installation, testing & commissioning of 25 Amp AC starter
switch with 25 Amp modular socket outlet with 25 Amp Plug on surface or
24 9 in recess, on 2 Nos two module GI box with plate etc. complete with Each 30.00 667.88 20,036.40
direction of Engineer-in-charge. Starter-Crabtree(cat no-ACT0202504) or
equivalent.(Make : Legrand/ Schneider/ Crabtree/ ABB/ Reckoner)
Supply and Wiring for circuit/ submain wiring along with earth wire of
following size of FR heavy gauge PVC insulated copper conductor single
25 10 core cable in heavy duty PVC conduit laid in surface/ recess as required. 0 0.00 0.00 0.00
(Make of wire:-Finolex/ Polycab/ Anchor/ Havells)(Make:- NORPACK/ AKG/
BEC/ PRECISION)
33 B. Fan & indoor Fixtures 0 0.00 0.00 0.00
Supply, delivery and fixing of Ceiling fan hook box made out of 18 swg GI
sheet and containing 10 mm dia round ms bar projecting atleast 150mm
on either side & duly bent to accommodate ceiling fan down rod bolt &
having earthing arrangement as per direction of Engineer-in-charge.
Supplying, installation, testing and commissioning following type of light
fixtures with dummy box for surface mounted fixtures only, fans and
35 12 exhaust fans with all accessories, as required.(The colour temprature for 0 0.00 0.00 0.00
fixtures shall be above 4000 deg K, CRI Min 80 & white in colour as per
Fully diffussed Recess mounted, enegry efficient, bottom opening panel,
36 a) duly powder coated CRCA Alminum l sheet housing 2'X2' LED fitting (3600 Each 32.00 5279.32 1,68,938.24
Lumen/36W) Similar to Halonix /Philips/ Wipro/Orient.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Fully diffussed Recess mounted,slim flat 1'X1' LED panel (2000 Lumen/
37 b) 20W) made of die cast aluminum housing with high efficient led similar to Each 61.00 3285.12 2,00,392.32
Halonix/ Philips/ Wipro/Orient.
Fully diffussed Recess mounted (1800 Lumen/ 18W) LED backlit round
38 c) Downlighter made of PDC aluminum with high efficeint LED similar to Each 38.00 2580.66 98,065.08
Halonix / Philips/ Wipro/Orient.
Fully diffussed Surface mounted, enegry efficient, bottom opening panel,
39 a) duly powder coated CRCA Alminum l sheet housing 2'X2' LED fitting (3600 Each 53.00 5279.32 2,79,803.96
Lumen/36W) Similar to Halonix / Philips/ Wipro/Orient.
Fully diffussed Surface mounted,slim flat 1'X1' LED panel (2000 Lumen/
40 d) 20W) made of die cast aluminum housing with high efficient led similar to Each 41.00 3695.76 1,51,526.16
Halonix / Philips/ Wipro/Orient.
Fully diffussed Surface mounted (1800 Lumen/ 18W) LED backlit round
41 e) Downlighter made of PDC aluminum with high efficeint LED similar to Each 248.00 2580.66 6,40,003.68
Halonix/ Philips/ Wipro/Orient.
Aluminium extrusion Housing Batten type Surface/Wall mounted 4' LED
fitting (2100 Lumen/ 18W) similar to Halonix /Philips/ Wipro/Orient.
Aluminium extrusion Housing Batten type Surface/Wall mounted 2' LED
43 g) fitting for mirror light(1000 Lumen/ 10W) similar to Halonix / PHILIPS/ Each 23.00 1032.50 23,747.50
Fully diffussed Surface mounted (900 Lumen/ 9 W) LED Edgelit round
44 h) Downlighter made of PDC aluminum with high efficeint LED similar to Each 66.00 1090.32 71,961.12
Halonix / Philips/ Wipro/Orient.
Dia cast Aluminum with Polycarbonate cover IP65 type 1000 Lumen/10W
LED Bulkhead wall fitting Halonix / Philips/ Wipro/ Orient.
Supplying and fixing call bell/ buzzer suitable for single phase,230 V,
complete as required.
Supplying, installation, testing and commissioning of ceiling fan ISI Marked
47 13 including wiring the down rod, earthing etc as required (Make : Halonix/ 0 0.00 0.00 0.00
Crompton/ Orient/ Khaitan/ Havells).
Supplying, installation, testing and commissioning of wall mounted fan ISI
49 14 Marked including earthing etc as required (Make : Halonix/ Crompton/ 0 0.00 0.00 0.00
Orient/ Khaitan/ Havells).
Supplying, installation, testing and commissioning of Exhaust fan Marked
51 15 including louvres, Ceiling Rose & Electric Connection as required. (Make - 0 0.00 0.00 0.00
Halonix/ Crompton/ Orient/ Khaitan/ Havells)
53 C. Panels, MDBs, DBs. MCBs 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply, installation, testing and commissioning of cubicle type
sectionalised, front operated top entry dust and vermin proof M.V. Panel
Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution
system fabricated out of 2.0 mm (14 SWG) thick at outer and 1.6mm for
inner partition CRCA sheet for frame work and covers, 3mm thick for gland
plated i/c cleaning & finishing complete with 7 tank process for powder
coating in approved shade, having suitable capacity extensible type FP
Aluminium alloy Bus bars of high conductivity with heat shrienkable PVC
sleeve, DMC.SMC bus bar supports, with short circuit withstand capacity of
70 KA for 1 sec. bottom base channel of MS section not less than 100mm x
50mm x 5mm thick, fabrication shall be done in transportable sections,
wiring with space heater, thermostat and control MCBs shall be provided
for all vertical sections of main LT Panel, all hinged door shall be earthed
through 2.5 sq mm tinned braided.
The incoming and outgoing feeders shall be accommodated in a modular
arrangement, detachable gland plates, adequate size cable alley, Sign
writing, Painting, Earthing entire panel shall have a common earth bar of
suitable size at the rear with 2 Nos earth solid connections from main bus
bar to switch gears with required 1.5 sq.mm. zero halogen fire retardant
low smoke insulated copper conductor s/c cable, cable alleys, cable gland
plate in two half, Numbering, Danger plate, including PVC insulated copper
FRLS wires of minimum 1.5 sq.mm & 2.5 sq.mm for CT's etc. with all
accessories including interconnections, earth bus, Surge protection
Device(SPD) etc. as required.
56 16 LT Panel (To be installed inside the Electrical Room at Ground Floor) 0 0.00 0.00 0.00
Busbar - 800 Amp Al busbar with SC rating of 36 KA suitable for operation
at 415 Volt, 50 Hz, 3 Phase supply.
58 0 One (1) No Incomer from EB Source each comprising of 0 0.00 0.00 0.00
One (1) - 800 Amp FP, 36 KA, LSIG Microprocesser based released
Electrical interlocking MCCB with 3 Nos Phase indicating lamps with control
fuse/ MCB, 3 Nos 800/5 A 10VA Cl 1.0 CTs, Digital Voltmeter, Ammeter
One set - Indicating lamp for ON/OFF/Trip and Phase indication with control
61 0 One(1)- Trip Push Button 0 0.00 0.00 0.00
62 0 One(1) Set- Trip Circuit Healty Test Push Button with Indicating Lamp. 0 0.00 0.00 0.00
63 0 One (1) No Incomer from DG Source each comprising of 0 0.00 0.00 0.00
One (1) - 400 Amp FP, 36 KA, LSIG Microprocesser based released
Electrical interlocking with adjustable overload MCCB with 3 Nos Phase
indicating lamps with control fuse/ MCB, 3 Nos 400/5 A 10VA Cl 1.0 CTs,
Digital Voltmeter, Ammeter With S/S. With inbuilt 400A
One set - Indicating lamp for ON/OFF/Trip and Phase indication with control
66 0 One(1)- Trip Push Button 0 0.00 0.00 0.00
67 0 One(1) Set- Trip Circuit Healty Test Push Button with Indicating Lamp. 0 0.00 0.00 0.00
Bus coupler (with electromechanical castle key interlocking provision)
One set - Indicating lamp for ON/OFF/Trip and Phase indication with control
Three (3) - Outgoing Feeders (for 1 nos Fire Panel, 1 HVAC Panel, 1 spares
each comprising of
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
74 0 One (1) - 3 Ph Digital Ammeter. 0 0.00 0.00 0.00
75 0 One Set ON/OFF Indicating lamp with control fuse/ MCB. 0 0.00 0.00 0.00
Ten (10) - Outgoing Feeders (For 5nos Floor Distribution Panel, 1no MGPS
Panel, 1no x-Ray DB, and 3 spares each comprising of
79 0 One (1) - 3 Ph Digital Ammeter. 0 0.00 0.00 0.00
80 0 One Set ON/OFF Indicating lamp with control fuse/ MCB. 0 0.00 0.00 0.00
Nine (9) - Outgoing Feeders (for 2 no. UPS I/C Breaker, 3nos Lift Panel,
1no STP panel, 1no WTP panel & 2nos spare each comprising of
84 0 One (1) - 3 Ph Digital Ammeter. 0 0.00 0.00 0.00
85 0 One Set ON/OFF Indicating lamp with control fuse/ MCB. 0 0.00 0.00 0.00
86 0 Four (4) - Outgoing Feeders spare each comprising of 0 0.00 0.00 0.00
88 0 Four (4) - Outgoing Feeders spare each comprising of 0 0.00 0.00 0.00
90 0 Four(4) - Outgoing Feeder for spare comprising of 0 0.00 0.00 0.00
92 0 PANEL AS ABOVE (Make of switch gears: L&T/ Siemens/ ABB/ Schneider) Set 1.00 1154276.00 11,54,276.00
94 17 FLOOR DISTRIBUTION PANEL 0 0.00 0.00 0.00
One (1) no Incomer- 160 Amp FP ,16 KA MCCB with 3 Nos Phase indicating
95 0 lamps with control fuse/ MCB Digital Voltmeter and Ammeter with selector 0 0.00 0.00 0.00
switch with required other accesories.
Busbar - 200 Amp,16KA AL TPN busbar suitable for operation at 415 Volt,
50 Hz, 3 Phase supply
Eight(8) - Outgoing Feeders for (2nos of PDB, 2nos ACDB & 4 spares) each
Four(4) - Outgoing Feeders for (2nos of LDB & Two spares) each
101 0 Four(4) - Outgoing Feeders for ( Four spares) each Comprising of 0 0.00 0.00 0.00
103 0 PANEL AS ABOVE(Make of switch gears: L&T/ Siemens/ ABB/ Schneider) Set 5.00 92158.00 4,60,790.00
Two (2) Incomer comprising of - 63 Amp, 25 KA, FP MCCB , One(1) set of
– 63/5A , 15VA , CL 1.0, CT with 3 Nos Phase indicating lamps with
control fuse/ MCB Digital Voltmeter and Ammeter with selector switch
.(with required other accesories.)
Busbar - 160 Amp, 25KA Cu TP2N busbar suitable for operation at 415
Volt, 50 Hz, 3 Phase supply
108 0 Ten(10) - Outgoing Feeders for (Floor UPS DB) each Comprising of 0 0.00 0.00 0.00
110 0 Six(6) - Outgoing Feeders for (Floor UPS DB) each Comprising of 0 0.00 0.00 0.00
112 0 Six(6) - Outgoing Feeders for (Floor UPS DB) each Comprising of 0 0.00 0.00 0.00
114 0 Six(6) - Outgoing Feeders for (Floor UPS DB) each Comprising of 0 0.00 0.00 0.00
116 0 PANEL AS ABOVE (Make of switch gears: OEM of L&T/ ABB/ Schneider) Set 1.00 142780.00 1,42,780.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
119 0 Lift Panels to be installed in respective lift rooms, each comprising of 0 0.00 0.00 0.00
One (1) Incomer - 63 Amp, 25 KA, MCCB with 3 Nos Phase indicating
lamps with control fuse/ MCB Digital Voltmeter and selector switch
Busbar - 100 Amp Al busbar with SC rating of 25 KA suitable for operation
at 415 Volt, 50 Hz, 3 Phase supply
122 0 One (1) - Outgoing Feeder with 63 Amp 4P MCB for lift supply 0 0.00 0.00 0.00
Four (4) - Outgoing feeder with 32A,2P, 10KA MCB for ARD battery
charger,Liftwell lighting & one nos spare
124 0 PANEL AS ABOVE (Make of switch gears: L&T/ Schneider/ ABB) No 3.00 50386.00 1,51,158.00
One (1) no 63 Amp TPN ,25 KA MCCB with required other accessories &
127 0 suitable metal enclosure concealed in wall for power supply to 10KVA Set 2.00 15340.00 30,680.00
UPS.(Make of switch gears: OEM of L&T/ ABB/ Schneider)
Supplying and fixing following way, horizontal type three pole and neutral,
sheet steel, MCB distribution board, 415 V, on surface/ recess, complete
with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But
without MCB/RCCB/Isolator). (For all Floors LDBs, PDBs, ACDBs &
UDBs)(Make: L&T/ ABB/ Legrand/ Schneider/ Siemens )
Supplying and fixing following way, horizontal type SPN, sheet steel, MCB
distribution board, 230 V, on surface/ recess, complete with tinned copper
bus bar, neutral bus bar, earth bar, din bar, interconnections, powder
painted including earthing etc. as required. (But without
MCB/RCCB/Isolator). (For all OTDBS)(Make: L&T/ ABB/ Legrand/
Supplying and fixing following way, Vertical type double door three pole
and neutral, sheet steel, MCCB distribution board, 415 V, on surface/
recess, complete with tinned 250A copper bus bar, neutral bus bar, earth
bar, din bar, interconnections, powder painted including earthing etc. as
required. (But without MCCB/MCB/RCCB/Isolator).(Make: L&T/ ABB/
Legrand/ Schneider)
Supplying and fixing following rating MCBs/ Isolator in the existing MCB DB
137 24 complete with connections,testing and commissioning etc. as 0 0.00 0.00 0.00
required(Make: L&T/ABB/Legrand/ Schneider)
138 a) 32 Amps, TP 10 KA MCB (C-Curve) Each 4.00 529.82 2,119.28
139 b) 6 Amp to 32 Amp, 10 KA SP MCB (C-Curve) Each 576.00 158.12 91,077.12
Supplying and fixing following rating MCCBs/ Isolator in the existing MCB
141 25 DB complete with connections,testing and commissioning etc. as required 0 0.00 0.00 0.00
(Make: Legrand/ L&T/ Schneider/ ABB )
Supplying and fixing following rating RCCB/ELCB in the existing MCB DB
143 26 complete with connections,testing and commissioning etc. as required 0 0.00 0.00 0.00
(Make: Legrand/ L&T/ Schneider/ABB )
149 D. Cables, Cable Laying & Termination 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying & Testing of 1.1 KV grade Aluminium XLPE power cable of
150 27 following size suitable for 415 Volt, 3Ph, 50 c/s supply. (Make:- Polycab/ 0 0.00 0.00 0.00
Supplying & Testing of 1.1 KV grade Cu XLPE Un Armoured(Flexible) power
cable of following size suitable for 415 Volt, 3Ph, 50 c/s supply.
Laying of one number PVC insulated and PVC sheathed/XLPE power cable
of 1.1KV grade of following size direct in ground including excavation (75
cm),sand cushioning,protective covering and refilling the trench etc as
166 b) Above 25 sq. mm and upto 120 sq. mm Mtr 30.00 177.00 5,310.00
167 c) Above 120 sq. mm and upto 400 sq. mm Mtr 120.00 195.88 23,505.60
Laying of One No. PVC insulated and PVC sheathed/XLPE power cable of
1.1 KV grade of following size in the existing RCC/HUME/MASONERY
TRENCH/HDPE Pipe/Metal Pipe/On Wall Surface(Clamped with saddle/PVC
& UPVC Pipe)/ CableTray as required.
171 b) Above 25 sq. mm and upto 400 sq. mm Mtr 345.00 55.46 19,133.70
173 31 TERMINATION OF CABLES 0 0.00 0.00 0.00
Supply & Making end Termination with brass compression gland and
174 0 Cu/aluminium lugs for PVC insulated and PVC sheathed cable of 1.1 kv 0 0.00 0.00 0.00
grade (without cost of Cable)(Make: Raychem/M-seal/3M)
Supply & making of Sigle Compression cable glands and crimping type Cu.
181 32 cable lugs with required tools and equipments as per IS. The glands and 0 0.00 0.00 0.00
lugs shall be suitable for 2XY cables.
Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in
ground complete with fitting incl. trenching(75 mm depth)and refilling as
per direction of Engg.-in-Charge. Ncessary test report & Warrnaty
certificate to be submitted to the department for genuinity of product & to
avail free after sales service within warranty period for acceptance of
materials.(Make: Duraline, Oriplast, Shaksa Polymer)
187 a) 63 mm dia (for Gate crossing) Mtr 50.00 291.46 14,573.00
188 b) 200 mm dia (for Road crossing) Mtr 30.00 802.40 24,072.00
Supply, fabricating and installing following size of hot dip G.I. perforated
type cables trays including suspending from ceiling with angle, rods
191 0 connection pieces, horizontal vertical bends, reducers, tees, cross 0 0.00 0.00 0.00
members,G.I. nut bolts, G.I. washers, fasteners etc. complete as required
per specifications & approved by the Engineer Incharge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
192 a) 150 mm (W) X 50 mm depth X 1.6 mm thickness Mtr 40.00 512.12 20,484.80
193 b) 300 mm (W) X 50 mm depth X 1.6 mm thickness Mtr 150.00 779.98 1,16,997.00
194 c) 450 mm (W) X 50 mm depth X 1.6 mm thickness Mtr 30.00 1172.92 35,187.60
Supply, Installation, Testing & Comissioning of 20KVA /20KW true online
double conversion UPS system (3Ph-3Ph) with inbuilt ISolation transformer
, with phase sequence correctior, built in BMS, with IEC62040-1,2,3
197 35 certification, DC cable 7meters interlink,SFU and SMF batteries back up of
30miniutes with each UPS and MS rack for battery Housing wit 2years
warrenty on both UPS and Battery.(Make: Legrand/ Numeric/ APC/
Emersion/ Riello or equivalent)
Supply, delivery and laying of following sizes of 2mm thick PVC Conduit
concealed in wall/ column/ roof slab of the building alongwith other
200 36 accessories and 18 swg GI wire complete for Electrical Wiring/Telephone / 0 0.00 0.00 0.00
TV & Data cable wiring as required and as per direction of Engineer-in-
charge. (Make:- NORPACK/ AKG/ BEC/ PRECISION)
203 191 Exteranal Electrification 0 0.00 0.00 0.00
204 A. 250 KVA Silent type DG Sets & Other Accessories 0 0.00 0.00 0.00
Supplying, Installation, Testing and Commissioning of AMF starts Silent
Diesel Generating Set having prime power rating of 250 KVA, 1500 RPM at
0.8 pf at NTP conditions (Alternator directly coupled with Diesel Engine)
suitable for automatic operation on mains failure Panel complete in all
respect and comprising of following enclosed specification, suitable for
indoor installation and as per direction of Engineer-in-charge.
A. Alternator : Self excited, self regulated, brush less type 415 Volt 3
phase 50 Hz synchronous generator delivering 200 at 0.8 PF (lag) at NTP
condition Conforming to IS/ IEC 60034- 1, screen protected self regulated
+ 1% regulation, IP 23 protection with insulation Class-H, AC alternator
complete with, 400 Amp 25KA FP MCCB and outgoing terminals taken out
for connecting through Cable along with all accessories.
B. Engine : Four(4) stroke, Multi-cylinder Turbo charged Radiator Cooled
Diesel Engine of suitabe BHP (to give prescribed output excluding power
consumption for running Auxiliary Accessories) operating at 1500 rpm,
daily fuel tank of 500 ltr capacity duly calibrated including medium class MS
208 0 piping for fuel piping from day tank to Engine and back, residential type 0 0.00 0.00 0.00
silencer, SS flexible below for exhaust pipe and 24 V DC starting
arrangement with 1 Nos 12 V battery having 180Ampere- Hr rating as
prescribed by the manufacturer of Engine along with battery charger, as
C. Base Plate : Common base plate of required size for mounting of engine
alternator set fabricated from MS channel and vibration damping
arrangement with cushy foot mounting i/c painting as per standard practice
of manufacturer etc. required.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
D. Acoustic Enclosur: The acoustic enclosure is made of 14/16 gauge CRCA
sheet. The salient features of acoustic enclosure are:- The enclosure is of
modular construction with the provision to assemble and dismantle easily
at site finished with powder coat painting of approved colour.
a)The Sheet metal components are Seven Tank pre treated before powder
b)The door are gasketed with high quality EPDM gaskets to prevent
leakage of sound as well as door handles are lockable type.
c) Specially designed attenuators to control sound at air entry and exit
214 0 d) Adequate ventilation to meet total air requirements. 0 0.00 0.00 0.00
e) Temprature of enclosure should not exceed beyond 5-7°C of ambient
216 0 f) Emegency shut down button from outside the enclouser. 0 0.00 0.00 0.00
217 0 g) Noise level; <75 DB (A) at 1 mtr Distance. 0 0.00 0.00 0.00
218 0 h) Automatic voltage regulator (AVR). 0 0.00 0.00 0.00
219 0 i) Proper Anti Vibration Pads(AVP) 0 0.00 0.00 0.00
j) The cost of initial charge of lubricants, coolant & first filling of fuel etc.
shall be included .
221 0 DG set as above (Make:-Kirloskar/ Cummins/ Sterling&wilson) Set 1.00 2367080.00 23,67,080.00
Supplying and laying MS pipe for horizontal and vertical run of Exhaust
piping with asbestos lagging and Al sheet cladding along with clamps, MS
Supports & all arrangments supports above 3 mtr etc from the roof of DG
Set as required.
225 B. Metering for DG Set 0 0.00 0.00 0.00
Supplying, installation, testing & Commissioning of LTTV 3ph 4wire
226 3 3x240V,-/5A,0.5S Class DLMS-C complied static meter with SMC Box with No 1.00 9168.60 9,168.60
400/5A LTCT Arrangement.
Supplying, laying, testing & Commissioning of 2Core 2.5Sq MM Cu Control
Cable (un-armoured)
Supplying, laying, testing & Commissioning of 4Core 2.5Sq MM Cu Control
Cable (un-armoured)
Supply of material & Construction of LT Cable trench from Distribution Box
at S/S to LT panel Board for laying of LT Cable with covering RCC Slab.
Supply & Fixing of Copper plate Earthing (600x600x3mm thick) including
accessories, and providing masnory enclosure with cover plate having
locking arrangement and watering pipe of 2.7 meter long etc. with
charcoal/coke and salt as required.
Supply of materials and installation of pipe earth electrode made out of
50mm dia class B G.I. pipe of 3.0 metre long with arrangements for fitting/
termination of G.I. flat / wire with G. I. nut bolts & washers including
cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements,
brick masonary enclosure on top with removable RCC cover complete with
labour for excavation of pit in all kinds of soil & rock as required and as per
direction of Engineer-in-charge.The entire earthing system should be
Replacement Warranty will be 5 years
Providing and fixing 25 mm X 5 mm dia copper strip on wall/surface or in
recess for connection etc. as required.
Providing and fixing 50 mm X 5 mm dia G.I strip on wall/surface With
required DMC insulator and nut bolt connection etc. as required.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing and fixing 25 mm X 5 mm dia G.I strip on wall/surface With
required DMC insulator and nut bolt connection etc. as required.
Providing and fixing 4 mm dia copper wire on surface or in recess for loop
earthing as required as per direction of Engg.-in-Charge.
240 E. LIGHTING ARRESTER 0 0.00 0.00 0.00
Providing and fixing of lightning conductor finial made of 25 mm dia 300
mm long, G.I tube,having single prong at top, with 85 mm dia 3 mm thick
241 13 G.I base plate including holes etc complete as required with as per Nos 10.00 467.28 4,672.80
direction of Engg.-in-Charge.(RATE REFERING OSR 2018 SOR NO-4.2) .The
entire LA system should be Replacement Warranty will be 5 years.
Reveting, sweating and soldering of copper / G.I. tape ( with another
copper / G.I. tape, base of the finial or any other metallic object) as
242 14 required .as per direction of Engg.-in-Charge. (RATE REFERING OSR 2018 Nos 60.00 174.64 10,478.40
SOR NO-4.4) The entire LA system should be Replacement Warranty will
Providing and fixing of G.I. tape 20 mm x 3 mm thick on parapet or
surface of wall for lightning conductor complete as required. (For horizontal
243 15 run) as per direction of Engg.-in-Charge.(RATE REFERING OSR 2018 SOR Mtrs 250.00 71.98 17,995.00
NO-4.7) The entire LA system should be Replacement Warranty will be 5
Providing and fixing of G.I. tape 20 mm x 3 mm thick on parapet or
surface of wall for lightning conductor complete as required. (For virtical
244 16 run) as per direction of Engg.-in-Charge. (RATE REFERING OSR 2018 SOR Mtrs 100.00 119.18 11,918.00
NO-4.8) The entire LA system should be Replacement Warranty will be 5
Providing and fixing of testing joint, made of 20 mm x 3 mm thick G.I.
strip, 125 long with 4 nos of G.I. bolts, check nuts and spring washer etc
245 17 complete as required as per direction of Engg.-in-Charge. (RATE REFERING Each 20.00 76.70 1,534.00
OSR 2018 SOR NO-4.12) The entire LA system should be Replacement
Warranty will be 5 years.
Providing and laying of G.I. tape 32 mm x 6 mm from earth electrode
directly in ground as required as per direction of Engg.-in-Charge. .(RATE
REFERING OSR 2018 SOR NO-4.14) The entire LA system should be
Replacement Warranty will be 5 years.
Maintenance free Safe Earthing Electrodes with ISI G.I. pipe dia 75mm as
Secondary electrode with wall thickness of 2.6 mm and the Primary
Earthing Electrode will be 50mm X 6mm X 1no M.S. hot dipped galvanized
strip filled with a highly conductive & non-corrosive compound in between
the Primary Earthing and the secondary Earthing, the Surface Area in will
be 7,06,500sqmm for 3mtrs length and Cross Sectional Primary conducting
247 19 area is 300 sq.mm. An Solid G.I. Base plat seals the unit at the bottom. Set 4.00 16531.80 66,127.20
as per direction of Engg.-in-Charge. (MES-GFC ground Filling compound
will be provided in 25 kgs Bags.)(MES-GFC ground Filling compound will be
provided in 25 kgs Bags.)(2 bags required for each earthing
electrode.)(FOR lightening protection & Building Electrification).The entire
earthing system should be Replacement Warranty will be 5 years.Make-
OBO/ Star-x/ ABB or equievalant reputed make & model A catogory.
22 0 Sub-Total of Electrical Works 0 0.00 0.00 1,22,97,685.06
Supply of 1.5 ton 3 star rated high wall split AC machine.(Make-
Carrier/LG/Voltas)
Supply of 2 ton 3 star rated high wall split AC machine.(Make-
Carrier/LG/Voltas)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
S/F of 4KVA Voltage stabilizer (90V - 300V) ISI Marked. (Make:- V-
Guard/MICRO-TECH/Eq.).
S/F of 5KVA Voltage stabilizer (90V - 300V) ISI Marked. (Make:- V-
Guard/MICRO-TECH/Eq.).
Supply and fixing of copper pipe with Nitrile rubber tube insulation along
with drain pipe & supply and wiring of 3 core 1.5 sqmm wire.
Supply and Fixing of Angle frame for installation of AC machine outdoor
30 7 Installtion charges of AC machine Nos 27.00 1770.00 47,790.00
SITC of Laminar Air Flow Systems : 6X6 Alluminium Powder coated
33 9 Housing with 13 mm Insulation - Plenum with H- 14 HEPA Filter Nos 2.00 254880.00 5,09,760.00
(610X610X75 mm ) with Aluminium diffuser with Aluminium Housing Grill.
SITC of Return Air Grill : Aluminium Return Airgrill supply -Coller size -
SITC of Air Handelling Unit : 2200 CFM ,25 ACPH , 100 SP-120 SP ,
3.0/4.75 kW Motor,5.5 Tr X 1 ( Twin Face Ckt) -AHU as per Given
Specification.6 Rowcooling Coil , SS drain Tray , EC fan ( VTS - Eurovent
Standard ) , VFD integrated , 43 mm Skin Thickness with Thermal Brake ,
5 Micron and 10 micron Filter to be given , AHU should be inbuil heater for
SITC of Out Door Unit : SITC of Condensing unit 5.5TR - DX ODU - R410-
Green Gas . (Make-Carrier/LG/Voltas)
SITC of Copper refrigerant pipe inbetween AHU & DX Unit with Nitril tube
insulation , Control Cable connectionn , Drain Piping etc with all types of
37 13 ancillariy items . The price ar eincluding the all systems Nitrozen pressure Lot 2.00 147500.00 2,95,000.00
hold , Vaccum sysyems , R410a Refrigerant Charging for Final Testing and
commissioning of the systems .
SITC of frire retardent types Flexible Connection for AHU Mouth connection
SITC of 22 Gauge Alluminium Ducting with 13 MM thik Nitril rubber thermal
insulation - Class O types including the all required supporting & ancillary
items upto final installation & testing at site for Supply air duct & Return air
SITC of Electrical Control Panel (o/d -WP) -Interlock with AHU- Temp & Rh
40 16 Controller.( Ph Reversal , MCCB , DOL starter , Actuator , VFD Set 2.00 171100.00 3,42,200.00
communication ,Heater control , BMS communication with OT )
33 0 Sub-Total of HVAC Works 0 0.00 0.00 47,53,412.88
34 0 Firefighting Works 0 0.00 0.00 0.00
35 A. PART - I : FIRE FIGHTING PUMPS, PIPING, VALVE & ACCESSORIES : 0 0.00 0.00 0.00
36 1 Electric Motor Driven Hydrant Pump Location - Pump Room : 0 0.00 0.00 0.00
Supplying, installing, testing and commissioning of Fire authority approved
37 0 Electrical driven fire pump suitable for automatic/ manual operation 0 0.00 0.00 0.00
consisting of the following:
i) Horizontal split casing, high pressure, single/ multistage centrifugal type
fire pump having cast iron body, bronze impeller,stainless steel shaft &
capable of delivering 2280 LPM against a total head of 70 M while running
at 1500 RPM complete with proper connection to suction and delivery line,
and including bypass arrangement for testing of pumps as per the
requirement. Suitable mechanical seal with mounting aggangement shall be
included, having a name plate indicating suction, delivery, head, discharge,
stages, RPM and direction of rotation.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Pump shall be capable of furnishing not less than 150% of rated capacity
39 0 at a head not less than 65% of rated head. The shut off head shall not 0 0.00 0.00 0.00
exceed 120% of rated head.
ii) Squirrel cage, induction motor, TEFC type suitable for 415 + 10%V, 3
phase, 50 Hz, AC supply, of suitable HP rating for the above pump with
40 0 synchronous speed of 1500 RPM conforming to IP55 protection & class 'F' 0 0.00 0.00 0.00
insulation. The motor shall conform to IS 325 1978(up to date) with
flexible coupling and coupling guard .
iii) Common base plate for mounting pump and motor fabricated of mild
41 0 steel channel as per manufacturer's recommendation with heavy duty Anti 0 0.00 0.00 0.00
Vibration pads (4 Nos., heavy duty).
iv) Suitable reinforced cement concrete pump foundation as per
manufacturer's design including foundation bolts, washers as required.
v) Flexible Coupling and coupling guard for direct coupling of pump and
44 0 Main Fire Hydran Pump 0 0.00 0.00 0.00
vii) Rate should included interconnection cables, foundation and foundation
48 0 PUMP AS ABOVE (Make:- Kirloskar/ Wilo/ Grandfos/ Xylem) Set 1.00 380587.76 3,80,587.76
49 2 Diesel operated Fire Pump for Hydrant System Location - Pump Room : 0 0.00 0.00 0.00
Supplying, installing, testing & commissioning of fire authority approved
50 0 Diesel Engine driven fire pump suitable for automatic/manual operations 0 0.00 0.00 0.00
consisting of the following :
i) Horizontal split casing, high pressure single/ multistage centrifugal type
fire pump having cast iron body, bronze impeller,stainless steel shaft &
capable of delivering 2280 LPM against a total head of 70 M while running
at 2200 RPM complete with proper connection to suction and delivery line,
and including bypass arrangement for testing of pumps as per the
requirement. Mechanical seal shall be included, having a name plate
indicating suction, delivery, head, discharge, stages, RPM and direction of
Pump shall be capable of furnishing not less than 150% of rated capacity
52 0 at a head not less than 65% of the rated head. The shut off head shall not 0 0.00 0.00 0.00
exceed 120% of rated head.
ii) Water cooled heat exchanger type diesel engine of required BHP or as
53 0 per manufacturer at 1500 RPM for the above pump complete with standard 0 0.00 0.00 0.00
accessories & suitable cooling system as described in specifications.
iii) Common base plate for mounting pump & engine of required strength
54 0 manufactured out of M.S. channels as per manufacture's recommendation 0 0.00 0.00 0.00
with heavy duty Anti Vibration pads. (Cushy foot) (6 nos., heavy duty).
55 0 iv) Flexible Coupling & coupling guard for direct coupling of engine & pump. 0 0.00 0.00 0.00
v) Suitable reinforced cement concrete pump foundations as per
manufacturer design including foundation bolts, washer as required.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
vi) 1 No. 200 Lits capacity day oil storage tank fabricated from 4 mm thick
M.S. sheet. Tank shall be provided with inlet, outlet, overflow, vent drain
connections, manhole cover (300 mm I.D.) & level indicators. Tank shall
57 0 be mounted on 2 m high steel structural supports with access ladder 0 0.00 0.00 0.00
(Painted with 2 coats of red oxide paint). Tank shall be provided with
epoxy coat from inside and one coat of red oxide & two or more coats of
synthetic enamel paint of approved colour on out side.
vii) 24 volts 180 AH lead acid battery (12 volts - 2 Nos) with boost/Trickle
charger for starting the engine automatically complete as required.
59 0 Diesel Engine driven pump of: 0 0.00 0.00 0.00
viii) Rate should include inter connecting cables, foundation & foundation
63 0 PUMP AS ABOVE (Make:- Kirloskar/ Wilo/ Grandfos/ Xylem) Set 1.00 634519.04 6,34,519.04
64 3 Electrical Motor Driven Jockey Pump Location - Pump Room : 0 0.00 0.00 0.00
Supplying, installing, testing & commissioning of fire authority approved
65 0 electrically driven Jockey pump suitable for automatic/manual operation 0 0.00 0.00 0.00
consisting of the following:
i) Horizontal / Vertical mounted multistage jockey pump having cast iron
body, S.S. impeller, stainless shaft with mechanical seal capable of
delivering 180 LPM against total head of 70 M while running at 2920 RPM
complete. The system shall be complete with necessary pressure gauge
with gun metal shut off cock on delivery side including bypass arrangement
for testing of working of the pumping set as required. The pump should
meet the requirement of IS 15105:2002 and must be approved by the
local fire authority.
ii) Squirrel cage induction motor suitable for 415 + 10%V, 3 phase, 50 Hz,
AC supply of suitable HP rating for the above pump with synchronous
speed of 2920 RPM T.E.F.C type connected to pump with flexible coupling
and coupling guard .
iii) Common base plate for mounting pump and motor fabricated of mild
68 0 steel channel as per manufacturer's recommendation with heavy duty 4 0 0.00 0.00 0.00
Nos. Anti Vibration pads.(Cushy foot)
iv) Suitable reinforced cement concrete pump foundations as per
manufacturer's design including foundation bolts, washers as required.
vii) Rate shall include inter connecting cables, foundation & foundation
74 0 PUMP AS ABOVE (Make:- Kirloskar/ Wilo/ Grandfos/ Xylem) Set 1.00 105421.20 1,05,421.20
75 4 FIRE PUMP ELECTRICAL PANEL (FPP) 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Fabrication, Supplying, Installation, Testing & Commissioning of Electrical
Fire Motor Control Panel of cubical construction, floor mounted type,
fabricated out of 2mm. thick CRCA sheet, compartmentalized with hinged
lockable doors, dust and vermin proof, powder coated of approved shade
after 7 tank treatment process, cable alley, interconnection with solid
aluminium strip / single core PVC insulated FRLS copper conductor cable,
having suitable mountings for switchgears and accessories and internal
control & power wiring with suitable rating PVC insulated FRLS copper
conductor, earth terminals, numbering etc. complete in all respects,
suitable for operation on 415 V, 3 phase 50 HZ AC supply with enclosure
protection class IP 42 with 400 Amp aluminium bus bar etc complete as
a) MCCB, TPN 250 A, 36ka with adjustable thermal magnetic release and
rotary handle (ICS= ICU= 25Ka) - 1 set.
b) Digital Ammeter (0 - 250 A), 96 mm. sq. CT operated with inbuilt
79 0 selector switch with 3 Nos. CT's of ratio 250/5 A, 10 VA burden and 0 0.00 0.00 0.00
accuracy of class 1.0 - 1 Sets
c) Digital Volt Meter (0-500 V) 96 mm. sq. with inbuilt selector switch and
control MCBs - 1 Sets
81 0 d) Phase Indicating coloured LED (RYB) with control MCBs - 1 Sets 0 0.00 0.00 0.00
Electrolytic high conductivity aluminium three phase and neutral bus bars
83 0 rated at 415V, 300 amps, 50Hz, AC, insulated with heat shrinkable 0 0.00 0.00 0.00
coloured PVC sleeves & clip on shrouds for joints.
84 0 Outgoing for Fire Pumps 0 0.00 0.00 0.00
a) MCCB TPN, 125A (with adjustable thermal magnetic release and
(Ics=Icu=25KA), with CT operated digital Ammeter (0 - 125 A), with 3
CT's of 125/5 A, 10 VA, ccuracy 1.0, ASS and coloured LED for on (Red)
indication - 1Set
b) Fully Automatic Star Delta Starter suitable for fire Pumps motor of
minimum 60 HP / (as per the recommendation of pump manufacturer)
complete with over load protection, current sensing type single phase
preventer complete with contactors, push button, indicators LED type
Auto/manual selector switches all accessories and FRLS copper conductor
wiring etc. as required - 1 Set
c) MCCB TPN, 63 A, 25 KA with CT operated digital Ammeter (0 - 63A),
87 0 with 3 CT's of 40/5 A, 10 VA, accuracy 1.0, ASS and coloured LED for on 0 0.00 0.00 0.00
(Red) indication with adjustable thermal magnetic release -2 Set
d) Fully Automatic DOL Starter suitable for Jockey Pumps motor of
minimum 5.0 HP / (as per the recommendation of pump manufacturer)
complete with over load protection, current sensing type single phase
preventer complete with contactors, push button, indicators LED type
Auto/manual selector switches all accessories and FRLS copper conductor
wiring etc. as required - 2 Set
e) MCCB TPN, 63 A, 25 KA with adjustable thermal magnetic release - 1
h) MCCB, TPN isolator 40 A, 16ka with adjustable thermal magnetic release
92 0 and rotary handle (ICS= ICU= 16Ka) - 1 set with suitable mounted in 0 0.00 0.00 0.00
CRCA enclosure of 2mm thick IP-65 rated near terrace pump. (1 Nos.)
93 0 Diesel Engine Control 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
i) Auto / Manual selector switch and 3 attempt Starting device, Electronic
timer, Relays, Auxiliary switches, Rotary switches, Tripping relays,
Contactors, Push button for manual Start / Stop etc. to make the
equipment automatic as per functional requirement.
j) Battery charging unit suitable for 24 V DC with boost and trickle charger,
selector switch, with suitable rating transformer, rectifier, RC filter network,
fuses on AC and DC protection, 0 - 30 V DC Digital Volt meter, 0 - 20 A DC
Digital Ammeter, the charger should be cut off when the engine is started
and the batteries shall be charged from battery charging alternator
provided in the engine.
k) Suitable rating & type standard relays, contactors and other accessories
for automatic operation of diesel engine
l) Indication LED's for high / low lub, oil pressure, water temperature,
engine on indicator, with suitable alarms, acknowledgement button etc.
98 0 System Controller 0 0.00 0.00 0.00
m) Designing, Supply, Installation, Testing and Commissioning of system
controller to control operation of Main Electric Fire Pumps, Diesel Engine
99 0 Pump, Jockey Pumps, Terrace Pump in sequence as per specification 0 0.00 0.00 0.00
consisting of relays, timers, sensors, annunciation window for fault
indication, complete as per specification.
n) First Jockey pump will start than hydrant start, in case of failure of
power diesel pump will start.
o) Colour coded internal wiring and connections etc. with suitable size Fire
Retardant Low Smoke PVC insulated copper cable / solid aluminium strip /
101 0 bus bar from incoming to bus bar and from bus bar to switch gears / 0 0.00 0.00 0.00
MCCB, starters, meters, selector switches, indicating LED's, interlocking
and sequence operation arrangements.
p) Terminal facility for repeat indicator of various audio and visual
103 0 Fire panel as above (Switch gear Make: Schneider/ L&T/ ABB/ C&S) Set 1.00 284169.96 2,84,169.96
Supply and installing of following size of perforated hotdip G.I. cable trays
including horizontal and vertical bends, reducers, tees, cross members and
other accessories as required and duly suspended from the ceiling with full
threaded GI suspenders, along the wall with supports and including
painting etc. as required & approved by thye Engineer Incharge. (Make:
Saimetal/ Indeana/ Profab)
105 a) 300 mm width x 50 mm depth x 1.6 mm thickness RM 10.00 779.98 7,799.80
106 b) 150 mm width x 50 mm depth x 1.6 mm thickness RM 10.00 512.12 5,121.20
Supply, laying, connecting, testing & commissioning of following size of 1.1
kv grade multicore aluminium/ copper conductor XLPE insulated PVC
sheathed armoured cable as per IS: 7098:1988 (Part-I) with upto date
107 6 amendments etc. complete as required. Tagging on both the ends will be 0 0.00 0.00 0.00
done with aluminium tags etc. complete as required.(Quantities as per site
requirement shall be finally estimated & executed accordingly with prior
approval.) (Make:- Polycab/ Havells/ KEI)
3.5 core x 70 sqmm Al. Ar. XLPE Cable (From Fire Fighting Panel to Main
3 core x 10 sqmm Al. Ar. XLPE Cable (Fire Fighting Panel to Jocky Pump
7 Core x 2.5 Sqrmm Copper Armoured Cable (for Pressure Switchs &
Control cables)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying and making indoor end termination with brass compression
gland (Heavy duty) and suitable copper / aluminium lugs for following size
111 7 of XLPE insulated PVC sheathed copper/ aluminium conductor armoured/ 0 0.00 0.00 0.00
unarmoured cable of 1.1 KV grade including cost of ferrules, cable sockets,
insulation tape & other accessories etc. complete as required.
113 b) 3 core x 10 sqmm Al. Lugs Set 2.00 215.94 431.88
114 c) 3 core x 2.5 Sq mm Copper Lugs Set 1.00 113.28 113.28
Providing and fixing following size of GI strips/ GI wire etc. on surface or in
recess for connections, including GI clamps etc. as required.
Note : Contractor shall include in his rate for providing level controller,
pressure switches, wiring, cabling from level controller/pressure switch to
panel etc. complete as required to operate the system automatic/manual.
Pump shall be protected against running dry.
Providing, fixing, testing & commissioning of M.S. class 'C' diesel pump
exhaust pipe including all fittings like bends, tee, clamps/structural steel
support of suitable dia for the engine . The pipe shall be insulated with 100
mm thick mineral wool insulation wrapped in chicken mesh with clad with
24 gauge aluminium sheet as per the instruction of EIC. (Make-SAIL/
Providing, fixing, testing and commissioning of precharged Air vessel (size
250 mm dia & 1500 mm height) fabricated shell from 6 mm thick & dished
end 8 mm thick M.S. Plate for pressurization of hydrant system complete
121 10 with adequate pressure switches (as per design / requirement) with valve No 1.00 37170.00 37,170.00
to operate as per operating sequences including 25 mm dia drain valve, air
release valve with ball cock on top, 25 mm dia inlet with isolating valve
duly painted from inside and out side complete as required.
Supply,Installation,Testing & Commissioning of 'C' Class heavy duty MS
pipe (as per IS 1239 upto 150 mm NB and IS 3589 for above 150 mm
6.33mm thick) with flanges and fitting such as bends, tees, reducers,
rubber insertions and galvanized nuts and bolts of following size on surface
122 11 along wall / shaft with MS bracket, suspended from ceiling/ beam with 0 0.00 0.00 0.00
suspenders duly painted with two coats of primer and finished with enamel
paint of approved colour laid through pipe or in trench after wrapping with
hassen cloth after applying coal tar primer as required as per direction of
Engineer-in- charge. (Make-SAIL/ JINDAL/ TATA)
Supplying, installation testing and commissioning Cast Iron Body Sluice
127 12 valve PN 1.6 Non-rising stem type conforming to IS:14846, with flanged 0 0.00 0.00 0.00
ends. (Make- ZOLOTO/ KARTAR / SANT)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing, fitting & fixing of following size cast iron double flanged slim seal
wafer type Butterfly valves with EPDM rubber lined with lever operated as
per IS-13095 with ISI mark of pressure ratting PN-1.60 including
131 13 fixing the same with supply of required jointing materials like rubber 0 0.00 0.00 0.00
insertion, MS nuts & bolts, paint etc. and testing the joints with required
water pressure for all floors etc. all complete as per specification &
direction of E.I.C.(Make- ZOLOTO/ KARTAR / SANT)
Providing, fitting & fixing of following size cast iron double flanged Y type
strainer with SS 304 perforated screen confirming to IS 1538 with ISI
mark of pressure rating PN-1.60 including fixing the same with supply of
136 14 required jointing materials like rubber insertion, MS nuts & bolts, paint etc. 0 0.00 0.00 0.00
and testing the joints with required water pressure & all complete as per
specification & direction of E.I.C. .(Make- ZOLOTO/
Providing, fixing, testing & commissioning of C.I. dual plate Non-return
valve [PN 1.6 Rating (10kg/cm2] conforming to IS 778 and test pressure
138 15 not less than 15 kg/cm2, complete 2 nos. matching flanges, rubber 0 0.00 0.00 0.00
insertion, with nuts, bolts and washers etc of following sizes as per the
instruction of EIC . (Make- ZOLOTO/ KARTAR / SANT)
The pressure switches shall be employed for starting and shutting down
operation of pumps automatically, dictated by line pressure. The Pressure
Switch shall be diaphragm type. The housing shall be die cast aluminium,
with SS 316 movement, pressure element and socket. The set pressure
shall be suitably adjustable as per instruction of EIC. (Make- Danfoss/ Abb/
Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16
Kgf/sq.cm. range with cut-off bronze ball valves below of suitable size with
all accessories as per direction of Engineer-in-charge. (Make:- Danfoss/
Fiebig/ H.Guru)
Supply,Installation,Testing & Commissioning of 150NB Alarm Valve , C/w
Sprinkler Water Motor Gong Retarded Chamber, Flange to:- ANSI B 16. 1
Class 125/ANSI B16.5 Class 100, All Components are UL Listed/FM
Approved , Rated pressure 17.50 kg/cm2, Test pressure 500PSI confirming
to IS :15105:2002 with ISI mark as per direction of Engineer-in-charge.
(Make:- Tyco/ NEWAGE/ HD )
PART - II : WET RISER CUM DOWN COMER & FIRE HYDRANT SYSTEM
Supply,Installation,Testing & Commissioning of 'C' Class heavy duty MS
pipe (as per IS 1239 upto 150 mm NB and IS 3589 for above 150 mm
6.33mm thick) with flanges and fitting such as bends, tees, reducers,
rubber insertions and galvanized nuts and bolts of following size on surface
145 19 along wall / shaft with MS bracket, suspended from ceiling/ beam with 0 0.00 0.00 0.00
suspenders duly painted with two coats of primer and finished with enamel
paint of approved colour laid through pipe or in trench after wrapping with
hassen cloth after applying coal tar primer as required as per direction of
Engineer-in- charge. (Make-SAIL/ JINDAL/ TATA)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply,Testing & Commissioning of 'C' Class heavy duty MS pipe (as per IS
1239 upto 150 mm NB and IS 3589 for above 150 mm 6mm thick) with
flanges and fitting such as bends, tees, reducers, rubber insertions and
150 20 galvanized nuts and bolts of following size including laying in ground after 0 0.00 0.00 0.00
excavation and refilling of trench along with providing 4mm thick pipecoat
for underground pipe after applying wrapping coating primer as required as
per direction of Engineer-in- charge. (Make-SAIL/ JINDAL/ TATA)
Providing, fitting & fixing of following size cast iron double flanged slim seal
wafer type Butterfly valves with EPDM rubber lined with lever operated as
per IS-13095 with ISI mark of pressure ratting PN-1.60 including
152 21 fixing the same with supply of required jointing materials like rubber 0 0.00 0.00 0.00
insertion, MS nuts & bolts, paint etc. and testing the joints with required
water pressure for all floors etc. all complete as per specification &
direction of E.I.C. (Make- ZOLOTO/ KARTAR / SANT)
Providing, fixing, testing & commissioning of Stainless steel single headed
ISI marked oblique pattern hydrant landing valves with 80mm dia flanged
inlet & 63 mm dia instantaneous type female outlet complete with stainless
156 22 steel cap and GI chain, twist release type plugh and all accessories as per Each 14.00 7906.00 1,10,684.00
IS : 5290 -1993 (Type 'A') including fixing with anchor fasteners and
flanged tapping from wet riser all complete as per specification & direction
of EIC. (Make: ARMOR/ Newage Mumbai/ PADMINI)
Providing, fixing, testing & commissioning of 15 m long non-perlocating,
rubber reinforced lined fire hose pipe (as per IS : 636-1979, Type A) of 63
mm dia and length as described below. The hose shall be rated for brust
157 23 pressure of 35.7 Kg/sqcm. Hose shall be complete with ISI marked SS Each 28.00 6755.50 1,89,154.00
male & female coupling (IS:903) bound & rivetted to hose pipe with copper
rivets & 1.5 mm copper wire as per the instruction of EIC. (Internal fire
hydrant) (Make: ARMOR/ Newage Mumbai/ PADMINI)
Providing, fixing, testing & commissioning of 63 mm dia Instantaneous
Pattern (male) Stainless Steel short size branch pipe with nozzle of 20 mm
158 24 nominal bore outlet as per IS:903 : 1993 suitable to fit with standard Each 14.00 3009.00 42,126.00
instantaneous type 63mm dia coupling ISI marked (IS:903:1993)
complete. (Make: ARMOR/ Newage Mumbai/ PADMINI)
Providing and fixing standard fireman's axe with heavy insulated rubber
handle tested for 20 Kilowatts.(Make: ARMOR/ Newage Mumbai/ PADMINI)
Supply,Installation,Testing & Commissioning of Swinging pattern wall fixing
first aid hose reel made from MS sheet ,spray painted in Post office Red,
confirming IS: 884 and moving parts complete with:(Make: ARMOR/
Newage Mumbai/ PADMINI)
a) MS fabricated hose reel drum to accommodate 20 mm dia 36 mtr long
hose with fixing bracket.
b) 20 mm dia X 30 Mtr long water hose with ABS(Plastic) shut-off nozzle as
per IS: 444/IS: 12585 Type-I.
163 0 c) 25 mm dia GM Ball Valve at inlet side of the hose reel drum as required. Each 10.00 9322.00 93,220.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing supply & fixing of MS Hose Box for of suitable
size(750X600X250mm) to accomodate 2 nos. of 15/ 1 no of 30 mtr long
fire hose and a branch pipe, wall mounted type as per direction of Engineer-
in-charge. (Make: ARMOR/ Newage Mumbai/ PADMINI)
Supplying and fixing 4 Way Fire Brigade inlet 63MM dia of CI body with 4
No. Gun Metal male instantaneous inlet couplings complete with cap and
chain as required. For 150 mm dia M.S. Pipe connection conforming to lS :
165 28 904 as required With brick platform & duly painted with Post office red Each 1.00 12080.25 12,080.25
externally and white internally with synthetic enamel paint cornplete in all
respect, for external hydrant, as required direction of Engineer-in-charge.
(Make: ARMOR/ Newage Mumbai/ PADMINI)
Providing, fitting and fixing of C.I. 25 MM single air relief valve with stop
cock confirming to IS:14845/2000 with ISI mark for water works purpose
166 29 including fixing the same with hydrant riser including testing & Each 4.00 2741.10 10,964.42
commissioning the system etc. all complete as per approved specification &
direction of Engineer-in-charge. (Make:KARTAR / ZOLOTO/ SANT)
Supply,Installation,Testing & Commissioning of Pressure gauge of 0-16
Kgf/sq.cm. range with cut-off bronze ball valves below of suitable size with
all accessories as per direction of Engineer-in-charge. (Make:- Danfoss/
Fiebig/ H.Guru)
Providing, fixing, testing & commissioning of Ball valve with SS ball
suitable for test pressure of not less than 15 kg / sq.cm of the following
size with nuts, bolts, gaskets, necessary accessories, etc as required.
(Make- SANT/ Zoloto / KARTAR)
170 III) PART - III : SPRINKLER SYSTEM : 0 0.00 0.00 0.00
Supply,Installation,Testing & Commissioning of Pendent / Upright type
Standrd Sprinkler with QB of 68 /79 deg. C temperature rating and 1/2"
171 32 end connection confirming to IS: 15105 with ISI mark for all floors etc. all Nos 396.00 413.00 1,63,548.00
complete as per direction of Engineer-in-charge. (Make:- KARTAR /HD /
Supply,Installation,Testing & Commissioning of 1.5Mtr Sprinkler flexible
pipe (UL Listed) of stainless steel complete with 15NTP on reducer thread
with maximum working pressure of 175PSI test pressure of 875 PSI
(Burst) with branch line (inlet) 25mm NPT male thread to sprinkler head
(Outlet) 15mm NPT female tread with reducer , nipple , 2 side bracket ,
center bracket, stockbar. (Make:- KARTAR /HD / FIRESHIELD)
Supply,Installation,Testing & Commissioning of 'C' Class heavy duty MS
pipe (as per IS 1239 upto 150 mm NB and IS 3589 for above 150 mm
6.33mm thick) with flanges and fitting such as bends, tees, reducers,
rubber insertions and galvanized nuts and bolts of following size on surface
173 34 along wall / shaft with MS bracket, suspended from ceiling/ beam with 0 0.00 0.00 0.00
suspenders duly painted with two coats of primer and finished with enamel
paint of approved colour laid through pipe or in trench after wrapping with
hassen cloth after applying coal tar primer as required as per direction of
Engineer-in- charge. (Make-SAIL/ JINDAL/ TATA)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Providing, fitting & fixing of following size cast iron double flanged slim seal
wafer type Butterfly valves with EPDM rubber lined with lever operated as
per IS-13095 with ISI mark of pressure ratting PN-1.60 including
180 35 fixing the same with supply of required jointing materials like rubber 0 0.00 0.00 0.00
insertion, MS nuts & bolts, paint etc. and testing the joints with required
water pressure for all floors etc. all complete as per specification &
direction of E.I.C. (Make-SANT/ ZOLOTO/ KARTAR)
Providing, fixing, testing & commissioning of C.I. dual plate Non-return
valve [PN 1.6 Rating (10kg/cm2] conforming to IS 778 and test pressure
182 36 not less than 15 kg/cm2, complete 2 nos. matching flanges, rubber 0 0.00 0.00 0.00
insertion, with nuts, bolts and washers etc of following sizes as per the
instruction of EIC . (Make-SANT/ ZOLOTO/ KARTAR)
Supply,Installation,Testing & Commissioning of C. I. Sight glass with 25 NB
Gunmetal Globe Valve with CI hand wheel ISI Mark for all floors etc. all
complete as per direction of Engineer-in-charge. (Make-ZOLOTO / KARTAR
185 IV) PART - IV: FIRE EXTINGUISHER : 0 0.00 0.00 0.00
Note : [1] All Fire Extinguisher shall be HCFC, CFC and Halons free. [2] The
186 0 Fire Extinguisher Manufacturer/Supplier shall provide declaration, Technical 0 0.00 0.00 0.00
Data Sheet/cutsheet of All type of Fire extinguisher to be installed.
Providing and fixing Carbon-di-oxide fire extinguishers consisting of welded
M.S cylindrical body,squeeze lever discharge valve fitted with internal
discharge tube, ISI marked high pressure discharge hose, discharge
187 38 nozzle, suspension bracket, confirming to IS : 15683 finished externally 0 0.00 0.00 0.00
with red enamel paint and fixed to wall with brackets with rawl
plug/dash fasteners complete with internal charge with CO2 gas
conforming to IS : 307-1996.(Make- SAFEPRO / OMAXE / FIRESHIELD)
Providing and fixing ABC stored pressure dry chemical powder (mono
ammonium phosphate) Fire Extinguisher IS : 15683 latest revision
manufacturer and of CRCA sheet in welded construction, finish with High
quality epoxy polyster powder coated complete with brass forged ball
valve, gun metal cap and nozzle, including initial filled and wall suspension
bracket (suitable for fighting in class 'A', B & 'C' that is wood, textile,
flammable liquid, electric and gases). (Make- SAFEPRO / OMAXE /
Supplying, installation, testing and commissioning of Mechanical Foam type
9 litre capacity Fire Extinguisher, ISI marked, IS: 10204, containing 540
ml AFFF liquid ISI marked, IS: 4989 Part II and a polyurethane coated
191 40 CO2 Gas Cartridge, ISI marked, IS: 4947 complete with gunmetal union Each 2.00 4430.46 8,860.93
cap, nylon hose with plastic foam making branch and wall mounting
bracket as per direction of Engineer-in-charge. (Make- SAFEPRO / OMAXE /
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying and installing at approved location approved make fire buckets
at 24 gauge galvanized steel sheet, standard 9 liters capacity and of round
bottom shape, painted white inside and red outside and black on the
bottom, inscribed with letter "FIRE" in black and gold. Cost shall be
inclusive of Providing MS stand duly painted over a coat of primer (one
stand shall be suitable for hanging 5 buckets.
193 V) PART - V : AUTOMATIC FIRE ALARMING AND DETECTION SYSTEM: 0 0.00 0.00 0.00
Supply, Installation, Testing & commissioning of of Addressable fire alarm
Panel which consists of display board which will have 160 Character Display
with Touch key pad, Mother board which will have ARM CORTEX M3 32 Bit
Processor, Inbuilt RS-485 Networking Circuit for peer to peer networking,
Inbuilt USB 2.0 Port for upload and download the Configuration tools, Two
inbuilt programmable inputs, Two inbuilt NAC's, and Three Programmable
194 42 Relays, and 4 Loop Card circuits. power Supply Board which will have No 1.00 281910.26 2,81,910.26
SMPS fully protected board, which its operates on 120 to 220V AC ± 10%
with 50/60 Hz, battery backup 24V DC with built-in charger. the panel
have IP-50 rating Optional: for BMS integration thru MODBUS converter,
Graphical Software, Software for TCP/IP Module, provision for GSM based
Auto dialler,provision for printer thru compatible module, Approval UL
Listed, (Make: Ravel/ GST/ Morley/ Siemens.)
Supply, Installation, Testing & commissioning of of Loop Card which will
have 254 devices of both detectors and modules in a single line circuit on
195 43 any combination, SLC should supports both Class A and Class B No 2.00 41300.00 82,600.00
wiring.Shall have an LED indication for FIRE,Normal and Redundancy
conditions Approval: UL Listed, (Make: Ravel/ GST/ Morley/ Siemens).
Supply, Installation, Testing & commissioning of Analog Addressable
196 44 smoke cum heat detector or heat detector sensor with status indicator . Nos 210.00 5192.00 10,90,320.00
(Make: Ravel/ GST/ Morley/ Siemens).
Supply, Installation, Testing & commissioning of of Response Indicator
Alarm status is indicated By Red colour LED, Operates on 12 VDC, Dual
197 45 LED’s for 360deg visibility, Flush / Ceiling wall mount, Operating Voltage : Nos 70.00 200.60 14,042.00
12 VD.C, Operating Current : 10mA, Alarm Indication : RED LED with
required accessories. (Make: Ravel/ GST/ Morley/ Siemens.)
Supply, Installation, Testing & commissioning of of Manual Pull Station -
Single Action/Dual action - with back box andBreak Glass Rod,shall be
resettable by Align key to avoid unauthenticated restorations - Approval:
UL Listed - (Make: Ravel/ GST/ Morley/ Siemens.)
Supply, Installation, Testing & commissioning of of Conventional Sounder
cum strobe with 24V DC, Audiable Sound 85 db @ 1 mtr range (16 V DC).
It is used for Fire, Burglar & Emergency Alarm System, Low current
consume @ 47 -73 mA Candela: flashing every second, 4 candela
settings:15/30/75/110cd output and 2 different tone audiable sound.
(Make: Ravel/ GST/ Morley/ Siemens.) - UL Listed.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply, Installation, Testing & commissioning of of power supply unit
operting on 120-220VAC,60/50HZ + 10%, Battery backup with built in
charging and up to 14 Ah batteries.Output 30VDC@ 5A Max, shall provide
200 48 the supplies to Beam detector/Conventional Sounders/Strobe,etc. Shall Nos 1.00 41890.00 41,890.00
have LED indications for Power supply ON, battery Fail, Battery Charging
etc.,IP -50,Dimension (350 W x 400 H x 100 D (mm),IP -50. (Make:
Ravel/ GST/ Morley/ Siemens.)
Supply &Laying of 2 core 1.5 sq.mm, multi strand, copper conductor, FRLS
201 49 (Fire Retardent Low Smoke)-PVC insulated GI Screened Armoured cable Mtr. 1800.00 153.40 2,76,120.00
with saddle and required accessories.& Power Cable.
Supply, Installation, Testing & Commissioning of High Power PA
Amplifier,his is a rugged and highly reliable product, ideally suited for a
wide variety of music and public address applications.6 Mic & 2 Aux Inputs.
Built-in MP3 player with LCD display, remote control, for USB, SD/MMC
cards.Preamplifier and Line Output for connecting to a Booster Amplifier
and for recording the programme. Line Input for connecting the output
from any external mixer or permitting UBA-500DP to be used as a Booster
Power Amplifier Resettable circuit breaker for protection against overload
and short circuit.Instant transfer to DC power (2Ã- 12C Car Battery) if AC
power fails. Box Speaker/Driver Unit selector switch. Bass boost defeated
at Driver Unit position for safer operation of driver units. if AC power fails.
with booster amplifier. Make-AHUJA
Supply ,Installation,Testing and Commissioing of High quality fulsh mount
ceiling / wall speaker with stylish grill and frame, which integrates
wonderfully well with all interiors. Clear and clean sound for speech and
205 51 music. 5" full range speaker 6W/100V. Beautiful powder coated aluminium Nos. 25.00 4363.55 1,09,088.64
mesh grille and moulded plastic frame , 100 V line operation with easy
power tap selection through a terminal block, etc. as per direction of
Engineer-in-charge Make-AHUJA / Equivalent
Supply, Installation Testing & Commissioninf of General PA Applications (PA
Microphones) a robust and reliable microphone , ideal for addressing an
audience. Frequency Response : 50-15,000Hz, including stand, quick
datachable holder with 3-pin professional XLR connector & 6 Mtr . twin core
shield low noise cable etc. as per direction of Engineer-in-charge Make-
AHUJA / Equivalent
Providing and laying of a pair of 1 sq.mm single core flexible copper cable
(2X 1) to be laid within Existing PVC conduit of suitable size to be erected
207 53 above the wall or concealed, as the case may be, with all accessories for all Mtr. 1200.00 109.74 1,31,688.00
floors etc. as per direction of Engineer-in-charge. Make- POLYCAB/
HAVELLS/ RR KABLE
208 C MISCELLANEOUS WORK : 0 0.00 0.00 0.00
209 54 Supply and installation in Position the "FIRE EXIT" Sign with luminicent Each 30.00 1411.75 42,352.56
colour having size: 300 mm x 150 mm
44 0 Sub-Total of Firefighting Works 0 0.00 0.00 82,24,098.45
46 1 Data Network and CCTV 0 0.00 0.00 0.00
Supply,installation, testing and commissioning of 4 P&T & 14 Extensions
Hybrid EPABX System
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply,installation, testing and commissioning of RJ11 Modular Complete in
concealed manner including termination of cable
Supply & Laying of 2 Core 0.5mm telephone cable using Rigid PVC Pipe in
concealed manner per running metre of cable laid.
Supply,installation, testing and commissioning of Electronic Push Button
Telephone with Caller ID
52 5 Supply,installation, testing and commissioning of GSM FCT Terminal Nos 2.00 4130.00 8,260.00
Supply,installation, testing and commissioning of Lightening Protector for
Supply,installation, testing and commissioning of 12v 7 Ah Battery
including termination
Supply,installation, testing and commissioning of RJ45 Modular Complete in
concealed manner including termination of cable
Supply & Laying of Cat 6 cable using Rigid PVC Pipe in concealed manner
per running metre of cable laid.
Supply,installation, testing and commissioning of Patch Panel, 6U Rack,
Cable Manager, Cooling Fan x 2 Nos., Earthing Kit, Power Manager
60 11 Supply,installation, testing and commissionining of 1 Mtr Patch Cord Nos 40.00 224.20 8,968.00
61 12 Supply,installation, testing and commissionining of 3 Mtr Patch Cord Nos 35.00 283.20 9,912.00
Supply,installation, testing and commissioning of 10 Channel DVR with 2
Supply,installation, testing and commissioning of 4 MP Dome / Bullet
Camera with 25 Mtrs IR Range
Supply & Laying of RG59+ 3 Core cable using Rigid PVC Pipe in concealed
manner per running metre of cable laid.
66 16 Supply,installation, testing and commissioning of BNC & DC Connectors Nos 19.00 88.50 1,681.50
Supply,installation, testing and commissionining of 4 TB CCTV Surveillance
68 18 Supply,installation, testing and commissionining of 10 Amps Power Supply Nos 2.00 5310.00 10,620.00
69 19 Supply,installation, testing and commissioning of Smart 32" LED Monitor Nos 2.00 29500.00 59,000.00
70 20 Supply,installation, testing and commissioning of 10 Mtrs HDMI Cable Nos 2.00 14160.00 28,320.00
71 21 Supply,installation, testing and commissioning of Bird Canopy Nos 19.00 885.00 16,815.00
72 22 Supply,installation, testing and commissioning of Wireless Mouse Nos 2.00 885.00 1,770.00
SITC of Oxygen Outlets as Per standards, Terminal units shall be capable of
single-handed insertion and removal of the medical gas probe. The wall
mounted first fix assembly shall consist of brass pipeline termination block
75 a with copper stub pipe secured between a back plate and a gas specific Nos. 88.00 3327.60 2,92,828.80
plate to allow limited radial movement of the copper stub to align with the
pipeline. The gas specific plate shall be permanently fixed to the backplate
etc. complete as required. (Make:-Meditek/ Classic/ ASmedico/ GHL)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
SITC of oxygen manifold of Size (8 working + 8 Standby) for Indian type
bulk cylinders, high pressure copper annealed tail pipes complete with
middle frame, chains for individual bulk oxygen cylinder, NRV's and 16 nos.
pig tail pipes. it should be suitable to withstand a working pressure of 145
kg/cm2 and should be tested at 300 kg/cm2. etc. complete as
required.(Make:-Meditek/ Classic/ AS Medico/ GHL)
SITC of oxygen manifold of Size (4 working + 4 Standby) for Indian type
bulk cylinders, high pressure copper annealed tail pipes complete with
middle frame, chains for individual bulk oxygen cylinder, NRV's and 8 nos.
pig tail pipes. it should be suitable to withstand a working pressure of 130
kg/cm2 and should be tested at 300 kg/cm2. etc. complete as
required.(Make:-Meditek/ Classic/ AS Medico/ GHL)
SITC of Semi Automatic pneumatically operated oxygen control panel.
Visual indication of the manifold is provided by 3 guages within control
panel, Indicating Pressure of the right & Left hand bank and the supply
pressure from control panel to distribution system with sensing faciliteies to
provide visual signals na other anciliary services such as heaters. Pannel
78 d should be fitted with audio alarm indication for changeover of empty Nos 1.00 159300.00 1,59,300.00
cylinder. The entire manifold will be hydraulically tested at 130 Kg/Cm2
pressure, duly degreased foroxygen Service, and supplied in sealed cover,
ready for assembly at site etc. complete as required.
(Note : Excluding Supply of cylinder). (Make:-Meditek/ Classic/ AS Medico/
SITC of Oxygen flowmeter complete with humidifier bottle, The flow meter
must be constructed with chromium plated brass body, extremely robust,
to take care of the day to day usage demand. Flow meter cartridge type
knob : easy to maintain, offers optimum adjustment quality and superior
designing and engineering to provide high level of accuracy, with no
significant affect from restrictions caused by down-stream equipments. The
flow meters should be 0-15 LPM range for oxygen. etc complete as
required. (Make:-Meditek/ Classic/ AS Medico/ GHL)
80 f SITC of Oxygen Adopter (Make:-Meditek/ Classic/ AS Medico/ GHL) Nos 88.00 606.52 53,373.76
SITC of Vacuum outlets as per standards, Terminal units shall be capable
of single-handed insertion and removal of the medical gas probe. The wall
mounted first fix assembly shall consist of brass pipeline termination block
82 a with copper stub pipe secured between a back plate and a gas specific Nos. 57.00 3327.60 1,89,673.20
plate to allow limited radial movement of the copper stub to align with the
pipeline. The gas specific plate shall be permanently fixed to the backplate,
etc. complete as required. (Make:-Meditek/ Classic/ AS Medico/ GHL)
83 b SITC of Vaccum Adopter . (Make:-Meditek/ Classic/ AS Medico/ GHL) Nos 57.00 606.52 34,571.64
SITC of Ward Vaccum Regulator with 600ml jar. (Make:-Meditek/ Classic/
AS Medico/ GHL)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
SITC of The vacuum Pumps 02 Nos having shall fully meets and complied
with NHS Health Technical memorandum (HTM02-01)/. Vacuum System
shall ensure the minimum pipeline vacuum level of 745mmHg is maintained
at the plant service connection point at the rated volumetric ‘free air’ flow
rate with two pumps in standby. Vacuum Pumps- CFM -60,Motor power -
3.7 Kw (5 HP) Oil Lubricated Reciprocating vacuum pumps with filtration
(Make :- Anest Iwata/ IR)
SITC of Vacuum Receiver’s- 1 x 500Liters(01 No) capacity vertical vacuum
receiver. Vacuum receiver(s) shall be supplied with relevant test certificates
86 e and have a total volume of at least 100% of the plant output in 1 minute in Nos 1.00 159300.00 1,59,300.00
terms of free air aspired at normal working pressure. (Make:-Meditek/
Classic/ AS Medico/ GHL)
87 3 COMPRESSED AIR SYSTEM 0 0.00 0.00 0.00
SITC of Compressed M.Air- 4 Bar outlets as Per standards , Terminal units
shall be capable of single-handed insertion and removal of the medical gas
probe. The wall mounted first fix assembly shall consist of brass pipeline
termination block with copper stub pipe secured between a back plate and
a gas specific plate to allow limited radial movement of the copper stub to
align with the pipeline. The gas specific plate shall be permanently fixed to
the backplate, etc. complete as required. (Make:-Meditek/ Classic/ AS
SITC of Compressed S.Air- 7 Bar outlets as Per standards , Terminal units
shall be capable of single-handed insertion and removal of the medical gas
probe. The wall mounted first fix assembly shall consist of brass pipeline
termination block with copper stub pipe secured between a back plate and
a gas specific plate to allow limited radial movement of the copper stub to
align with the pipeline. The gas specific plate shall be permanently fixed to
the backplate, etc. complete as required. (Make:-Meditek/ Classic/ AS
90 c SITC of Air Adopter(4 Bar) (Make:-Meditek/ Classic/ AS Medico/ GHL) Nos 31.00 606.52 18,802.12
91 d SITC of Air Adopter(7 Bar) (Make:-Meditek/ Classic/ AS Medico/ GHL) Nos 4.00 606.52 2,426.08
92 e Air Pressure Regulator Nos. 4.00 21181.00 84,724.00
SITC of Oil Free Air Compressor , Cap:- 7.5 Hp, 24.4 CFM . Make:- Anest
Iwata/IR ,& Accessories
•Two stage two cylinder single acting reciprocating type air-cooled air
• ASSC. 7.5 HP electric motor foot mounted with starter,
• To remove maximum contamination and minimum pressure drop. (Make
:- Anest Iwata /IR)
SITC of Air Reciver,Cap-500Ltr, The reviver assembly are be fitted with a
pressure safety valve. (Make:-Meditek/ Classic/ AS Medico/ GHL)
SITC of Desicant Air Dryer,Cap-40 CFM
Dryer type-regenerative dessicant dryer,design pressure -13.2 bar g.
Maximum air inlate temp.-65 degree C ,maximum pressure- 25
bar,pressure dew point -40 degree C.
96 4 Nitrous Oxide System 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
SITC of Nitrous Oxide outlets as Per standards, Terminal units shall be
capable of single-handed insertion and removal of the medical gas probe.
The wall mounted first fix assembly shall consist of brass pipeline
termination block with copper stub pipe secured between a back plate and
a gas specific plate to allow limited radial movement of the copper stub to
align with the pipeline. The gas specific plate shall be permanently fixed to
the backplate, etc. complete as required. (Make:-Meditek/ Classic/ AS
SITC of (2 working + 2 Standby) size of N2O manifold complete with
middle frame, chains, NRV's 4 nos. pig tail pipes, Manifold should have
high pressure copper annealed tail pipes with one end having brass bull
98 b nose suitable for Nitrous Oxide cylinders and other end suitable for Nos 1.00 47908.00 47,908.00
Manifold non- return Valves. Each manifold will have one terminal header
and a NPT connection for the Automatic Control Panel. etc. complete as
required.(Make:-Meditek/ Classic/ AS Medico/ GHL)
SITC of Emergency Nitrous Oxide Manifold comprising of 1 N2O manifold
99 c with tail pipe , Regulator and stand (Make:-Meditek/ Classic/ AS Medico/ Set 1.00 16829.16 16,829.16
SITC of Semi Automatic pneumatically operated N2O control panel. With
heater, The entire manifold will be hydraulically tested at 250 Kg/Cm2
pressure, duly degreased , etc complete as required. (Make:-Meditek/
Classic/ AS Medico/ GHL)
101 0 Distribution system 0 0.00 0.00 0.00
SITC for Medical Grade copper pipe with required copper fittings, All pipes
shall be drawn half hard temp., solid drawn, seamless, phosphorous
deoxidised, non-arsenic and degreased copper pipe conforming to EN BS:
13348:2008/ASTM B819 standard ,EN 1057:1996 (originally BS 2871-
1971 Part 1 (Table X) and chemical composition as per BS-6017 of 1981
102 5 table 2, The supplies of copper pipe would be accompanied with 0 0.00 0.00 0.00
manufacturers test certificate for the physical properties of copper pipes
and their Chemical composition. The supply of pipes be further
substantiated with inspection certificate from the third party like
SGS/Lloyds Register. etc. complete as required. (MAKE:-Rajco Metals/
Janya Extrusion/ Mandev tube/ Maxflow)
103 a 12mm outer dia x 0.7 mm thick Mtr 356.00 796.50 2,83,554.00
104 b 15mm outer dia x 0.9mm thick Mtr 246.00 1162.30 2,85,925.80
106 d 28mm outer dia x 0.9mm thick Mtr 596.00 1516.30 9,03,714.80
107 e 42 mm outer dia x 1.2 mm thick Mtr 60.00 2843.80 1,70,628.00
Supply Installation Testing and Commissioning of following sizes ball type
isolation valve with PTFE seat Brass body with Nickel plating valves having
quarter turn handle opening of size suitable for 12mm copper pipe to
54mm OD copper pipe and shall have brass adopter suitable for copper
pipe. The valves are designed for a working pressure of 27” Hg vacuum to
300 psi.(Make:-Meditek, Classic,ASmedico,GHL)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply Installation Testing and Commissioning of Valve Box , Area valve
service units module should consist of three gas service. It should
incorporate a valve with NIST connection at either side. The valve boxes
would be made of Zinc coated Mild Steel and shall be powder coated for
114 7 housing area/zonal valves. The valve box would be lockable having glass 0 0.00 0.00 0.00
cover, the valve will be complete with stub pipes that extend to the outside
of the box to enable easy connection to the MGPS. The valve box should be
equipped with gauge for the gases.(Make:-Meditek/ Classic/ ASmedico/
Supply Installation Testing and Commissioning of the Medical Gas alarm
system should be capable of monitoring upto 5 medical gas services by
mean of pressure sensors which detect deviation from the normal
118 8 operating limits of either pressure or medical vacuum. All parameters of 0 0.00 0.00 0.00
Alarm System should be displayed in Analogue form. Signals should be
auditory, visual and indicate color. Auditory signals can be silenced by
operator.(Make:-Meditek/ Classic/ AS Medico/ GHL)
Supply installation and providing wiring and piping connctions for bed head
wall panels. The panel shall be fabricated out of high strengths extruded
alluminium sections with inbuild single rolling and powder coated to color as
per the owners choice. the panel shall have facility to accomodate: Max. 5
nos of Gas outlets, 5/15 A multi pin switched socket outlets -2 nos, 1 nos
Nurse call switch panel with wired remote. , 1 no infusion pump rail mount
pole with adapter, and holder for vacuum collection jar. ( 6/16 Amp)(Make:-
Meditek/ Classic/ AS Medico/ GHL)
Design Supply, Installation, Testing & Commissioning and putting into
operation with compelete inspection by concerned electrical inspector,
Director Factory and Boilers, Odisha with proper testing certificate and
final testing of Automatic Lift complete with all standard equipments
accessories and control equipments as per Manufacturer's Design with lift
control panel including BMS facility and as per BIS and fulfilling following
requirements.It includes supply,laying of power cable and fixing of
124 1 glands,lugs etc.( Machine room less, Gearless Type). Design and as per 0 0.00 0.00 0.00
CPWD /OPWD specification (Part - III Lifts) 1981 with valid lisence for
installation and fulfilling following requirements on turnkey basis as per
direction of Engg.-in-Charge. LIFT OF machineroom less type (Make-Kone/
Johnson/ OTIS/ Schindler/ Levitar/ Thysenkrup/ or equievalant reputed
make & model A catogory, ISI marked as approved ) Warrentee period of
accessories & system must be 5 years & compelete test certificate must be
submitted along with Lift including component list .
125 0 Type: HOSPITAL Strecher cum 15 Pax LIFT 0 0.00 0.00 0.00
127 0 Speed: 1.0 Meter Per Second. 0 0.00 0.00 0.00
128 0 Control: Variable voltage with variable frequency 0 0.00 0.00 0.00
Operation: Microsprocessor based simplex collective selective with /
without Lift Attendant.
130 0 Total Rise: About 0-16.8 Meters. 0 0.00 0.00 0.00
131 0 Landings: For All on same side. 0 0.00 0.00 0.00
132 0 Floors Served: GF,1F,2F,3F,4F 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Signals: Digital Car Position Indicator, Car Travel direction Indicator in Car
& at all Landings.
134 0 Lift Shaft Size: About as 15 passenger lift standard, finished with Plaster. 0 0.00 0.00 0.00
135 0 Lift Car Size: About lift standard. 0 0.00 0.00 0.00
136 0 Car Entrance: Clear Opening lift standard high Protected with Car Door. 0 0.00 0.00 0.00
Landing Entrance: Clear Opening lift standard high Protected with Landing
Car Door: Stainless with Hairline finish Two Panel Center opening flush
139 0 Landing Door: Mild Steel Two Panel Center opening flush type. 0 0.00 0.00 0.00
Door Operation: Automatic Electric Power operated Door with in infrared
141 0 Car Interior: Stainless Steel Panel with Hair line finish on all sides. 0 0.00 0.00 0.00
142 0 Car Floor: Hard Wood covered with PVC / Marblex Tiles. 0 0.00 0.00 0.00
Car Ceiling & Lighting: LED Lighting Concealed by suspended false ceiling
143 0 with plain acrylic diffiuser. The frame of suspended false ceiling shall be of 0 0.00 0.00 0.00
powder coated Aluminum.
144 0 Car Ventilation: Pressure Fan with anodized Aluminum Grill. 0 0.00 0.00 0.00
Emergencing Lighting in Car: Battery operated Emergencing Lighting in the
Intercom System: Battery operated intercom system in Lift Car and Control
Emergencing Alarm: Battery operated Alarm Bell System in Lift Car and
148 0 Position of Machine Room: Directly above the Lift Shaft. 0 0.00 0.00 0.00
Electric Power Supply: AC 415 Volt 3 Phase 50 Hz terminated in control
149 0 room along with control panel with facility of BMS connectivity system .The 0 0.00 0.00 0.00
scope of lift control panel is inclussive with lift vender scope.
150 0 OTHER SPECIAL PROVISIONS 0 0.00 0.00 0.00
151 0 • VVVF CONTROLLER 0 0.00 0.00 0.00
152 0 • AUTOMATICE RESCUE DEVICE (ARD) 0 0.00 0.00 0.00
153 0 • EMERGENCY LIGHT AND BATARY OPERATED ALARAM BELL 0 0.00 0.00 0.00
154 0 • DOT MATRICKX SEVEN SIGMENT DIGITAL POSITION INDICATORS 0 0.00 0.00 0.00
155 0 • FIRE RATED DOOR FOR 1 HOUR 0 0.00 0.00 0.00
156 0 • 3 WAY INTER COM/PRESS AND SPEAK BUTTON WITH HAND SET 0 0.00 0.00 0.00
157 0 • FLOOR ANNUNCIATOR WITH MUSIC 0 0.00 0.00 0.00
159 0 • OVER LOAD WARNING INDICATOR 0 0.00 0.00 0.00
160 0 • BRAILLE BUTTONS 0 0.00 0.00 0.00
161 0 • FREE SERVICE FOR 5 YEARS 0 0.00 0.00 0.00
163 0 • FULL CAR HEIGH CAR FIXTURE ARRIVAL CHIME 0 0.00 0.00 0.00
164 0 • PROVISION FOR CC CEMARA WITH INSTRUEMENT 0 0.00 0.00 0.00
165 0 Fire Man Switch: Fire Man Switch at Main Landing Terminal. Job 3.00 1899800.00 56,99,400.00
55 0 Sub-Total of Other Works 0 0.00 0.00 1,50,98,553.12
56 0 Plumbing Works 0 0.00 0.00 0.00
57 1 Internal PH Work 0 0.00 0.00 0.00
Supplying all materials, labour, T&P and providing and fixing to wall or
ceiling and floor CPVC pipes conforming to IS:15778 having thermal
stability for hot and cold water supply, including all CPVC plain and brass
58 1 threaded fittings including fixing the pipe with clamps at 1.00. spacing. This 0 0.00 0.00 0.00
includes Jointing of pipes & fittings with one step CPVC solvent cement and
testing of Joints all complete as per specification and direction of the
Engineer in charge.
59 a In Ground Floor 0 0.00 0.00 0.00
61 ii 25mm dia CPVC pipe Mtr 100.00 446.51 44,651.20
62 b In First floor 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
64 ii 25mm dia CPVC pipe Mtr 90.00 456.78 41,110.02
65 c In Second floor 0 0.00 0.00 0.00
66 i 20mm dia CPVC pipe Mtr 95.00 347.27 32,991.03
67 ii 25mm dia CPVC pipe Mtr 70.00 467.04 32,693.08
68 d. In Third floor 0 0.00 0.00 0.00
69 i 20mm dia CPVC pipe Mtr 95.00 357.54 33,966.30
70 ii 25mm dia CPVC pipe Mtr 70.00 477.31 33,411.70
71 e. In Fourth floor 0 0.00 0.00 0.00
72 i 20mm dia CPVC pipe Mtr 90.00 367.81 33,102.54
73 ii 25mm dia CPVC pipe Mtr 50.00 487.58 24,378.80
Supplying all materials, labour, T&P and providing and fixing to wall or
ceiling and floor U-PVC pipes conforming to pipe fittings of the following
nominal bore with clamps including making good the wall, ceiling and floor
for Distribution of water supply and return in between floors and Ringline
over terrace floor all complete as per specification and direction of the
Engineer in charge .
76 i 32mm dia U-PVC pipe (Ashirbad/Supreme) Mtr 140.00 596.84 83,558.16
77 ii 40mm dia U-PVC pipe (Ashirbad/Supreme) Mtr 110.00 933.14 1,02,645.84
78 iii 50mm dia U-PVC pipe (Ashirbad/Supreme) Mtr 40.00 764.05 30,562.00
79 iv 65mm dia U-PVC pipe (Ashirbad/Supreme) Mtr 1.00 982.59 982.59
Supplying all materials, labour, T&P and cutting holes through existing brick
work including making good the damages in cement mortar (1:4) for
80 3 taking GI pipes and fittings/ PVC pipes and fittings etc all complete as per 0 0.00 0.00 0.00
PH specification and direction of the Engineer in charge.
82 i In Ground Floor Each 30.00 60.42 1,812.48
83 ii In First floor Each 30.00 61.48 1,844.34
84 iii In Second floor Each 10.00 62.66 626.58
85 iv. In Third floor Each 10.00 63.84 638.38
86 v. In Fourth Floor Each 10.00 65.02 650.18
Supplying all materials, labour, T&P and cutting hole in R.C.C floors, roofs,
etc upto 19 cm thick for passing GI pipes / PVC pipes and fittings etc and
repairing the holes after insertion of pipes etc with cement concrete
(1:2:4) including finishing complete so as to make it leak proof as per
direction of the Engineer in charge.
89 i In Ground Floor Each 25.00 192.22 4,805.55
90 ii In First floor Each 25.00 193.05 4,826.20
91 iii In Second floor Each 10.00 194.11 1,941.10
92 iv. In Third floor Each 10.00 195.29 1,952.90
93 v. In Fourth Floor Each 10.00 196.71 1,967.06
Supplying all materials, labour, T&P and cutting grooves in pucca floors
and walls for taking GI/ PVC pipes and making good the damages as per
the direction of the Engineer in charge.
96 i In Ground Floor Mtr 30.00 212.40 6,372.00
97 ii In First floor Mtr 30.00 218.30 6,549.00
98 iii In Second floor Mtr 10.00 225.26 2,252.62
99 iv. In Third floor Mtr 10.00 233.05 2,330.50
100 v. In Fourth Floor Mtr 10.00 241.78 2,417.82
Supplying all materials , labour, T&P and cutting holes through existing
brick or laterite masonry wall for taking U-PVC pipes and fittings including
102 6 making good the damages etc. all complete as per P.H. specification and 0 0.00 0.00 0.00
direction of Engineer-in-charge.
103 i In Ground Floor Mtr 25.00 230.93 5,773.15
104 ii In First floor Mtr 25.00 237.42 5,935.40
105 iii In Second floor Mtr 10.00 244.61 2,446.14
106 iv In Third floor Mtr 10.00 252.52 2,525.20
107 v In Fourth Floor Mtr 10.00 260.43 2,604.26
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials , labour, T&P and cutting of RCC chajja for taking
HCI or U-PVC pipe and fittings including making good the damages etc. all
complete as per P.H. specification and direction of Engineer-in-charge.
Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil
waste ventilating pipes and fittings of the following outside diameter
conforming to ISI No 13592/1992 to walls with nails, bobbins and wooden
plugs or laying in trenches including jointing with supply of approved
rubber lubricant by non-heat application method/as per manufacturer's
specification, testing, earthwork in excavation in all kinds of soil and
refilling of trenches , cost & conveyance of all materials to worksite,
payment of taxes etc. all complete as per P.H specification and direction
of the Engineer-in-charge.
112 i 75mm dia U-PVC SWR pipes (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Mtr 140.00 229.04 32,065.32
113 ii 75mm U-PVC Socket (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 40.00 95.93 3,837.36
114 iii 75mm U-PVC Plain tee (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 35.00 375.71 13,149.92
75mm dia U-PVC Door Bend. (Ori Plast/ Finolex/ Supreme/ Ashirvad
75mm dia U-PVC Plain Bend. (Ori Plast/ Finolex/ Supreme/ Ashirvad
110mm dia U-PVC SWR pipes (Ori Plast/ Finolex/ Supreme/ Ashirvad
118 vii 110mm dia U-PVC Door Tee (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 40.00 455.48 18,219.20
119 viii 110mm U-PVC Plain tee (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 40.00 455.48 18,219.20
120 ix 110mm U-PVC door bend(Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 45.00 346.45 15,590.16
110mm dia U-PVC Plain Bend (Ori Plast/ Finolex/ Supreme/ Ashirvad
122 xi 110mm U-PVC ‘P’ Trap (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 30.00 586.81 17,604.42
110mm U-PVC offset without ear(Ori Plast/ Finolex/ Supreme/ Ashirvad
124 xiii 110mm U-PVC vent Cowl (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 15.00 68.68 1,030.14
125 xiv 110mm U-PVC Socket (Ori Plast/ Finolex/ Supreme/ Ashirvad Make) Each 45.00 188.92 8,501.31
PVC SWR Clamp/clip suitable for 75mm to 110 mm dia pipe (Ori Plast/
Finolex/ Supreme/ Ashirvad Make)
Supply,Providing, fixing, testing and commissioning in position UV
stabilised 110 mm dia UPVC Rain water pipe with Fittings (IS: 13592
127 2 Type - B). In case of ceiling hanging, the supply of Pipe Clamps (Chilly/MS Mtr 225.00 466.45 1,04,952.15
angle) as per engineer in charge. (Ori Plast/ Finolex/ Supreme/ Ashirvad
Supply,Providing and fixing 150 mm x 150 mm.dia CI Grating for Rain
water pipes 110 mm dia.
Providing & fixing rain water `Khurras' size 200x200 mm required depth
129 4 with lead flashing around the pipe with one piece lead sheet of 3 mm thick Each 11.00 531.00 5,841.00
set on a layer of cold bitumen.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials , labour, T&P and fixing rotational moulded
polyethylene cylindrical vertical water storage tanks conforming to
IS:12701/1996 including cutting holes through the tank and fixing mild
steel tubes and fittings and providing extra sockets and jam nuts, fixing
ball valve etc. including hoisting upto a height of 5 metres above ground
level and placing the tank to the required position and providing 5.40 mtr.
lengthx0.25 mtr width KB brickwork in cement mortar (1:6) of 0.46m
height in staging and 0.13mtr thick circular protection wall of 0.46mtr
height to support the tank,12mm thick cement plaster in cement mortar
(1:6) over brick work, RCC slab of size 1.60mX1.60m and 0.10m thick
,RCC beam of 0.25mx0.30m and 3.40m average length in cement concrete
(1:2:4) using 12mm size crusher broken hard black granite chips and
required steel reinforcement including centering and
shuttering,watering,curing ,cost of all materials,conveyance of all materials
to worksite , payment of royalty, all taxes etc.all complete as per
approved drawing , P.H. specification and direction of Engineer-in-charge.
131 i 5000 liters capacity PVC water storage tank roof of fifth floor Each 2.00 82294.31 1,64,588.62
132 76 Ceramic and Sanitary Fittings 0 0.00 0.00 0.00
Supplying all materials, labour, T&P and fixing vitreous china water closet,
squatting pan (Indian type W.C pan/Orissa pattern squatting pan) duly
embedded in cement concrete (1:5:10) using 4cm size hard granite metal
including fixing a pair of vitreous china 250mm x 130mm x30mm footrest,
fixing 100mm dia HCI 'p' or 's' trap (with/without 50mm dia horn) for
133 1 water colset squatting pan including jointing the trap with pan in cement 0 0.00 0.00 0.00
mortar (1:1) cutting the floor and mending good the damages , cost &
conveyance of all materials to worksite, payment of royality , taxes etc.
all complete as per P.H specification and direction of the Engineer-in-
134 i 580mm long Indian water closet (Hindware/ Parryware/ Neycer make) Each 4.00 1877.85 7,511.41
Supplying all materials, labour, T&P and fixing the following vitreous china
Wash Down Water Closet (European type W.C. pan)with integral 'p' or 's'
trap to the floor with wooden plug and chromium plated pedestal screws
including jointing the trap with soil pipe in cement mortar (1:1) fixing
135 2 plastic seat and cover for wash down water closet with chromium plated 0 0.00 0.00 0.00
brass hinges and rubber buffers including polishing , cost & conveyance of
all materials to worksite, payment of royality, taxes etc. all complete as
per P.H specification and direction of the Engineer-in-charge.
European water closet with 'p' trap plain (Hindware/ Parryware/ Neycer
Matrix Set -1 (WB 65 x 35 with one pair mounting brackets, EWC & Cistern
complete with fittings & seat cover, one no hinged rail 76 cm and five nos
of grab rails 60 cm) .
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and fitting and fixing 10 litres capacity
low level flushing cistern with a pair of cast iron or M.S brackets complete
with fittings such as siphonic arrangements 15mm nominal size brass/pvc
ball valve with polythene float CP brass handle, unions and couplings for
connection with inlet, outlet and overflow pipes,32mm dia CP flush
bend,15mm dia pvc inlet connection pipe including cutting holes and
making good the same and connecting the flush bend with cistern and
closet and connecting the inlet pipe with supply main etc all complete as
per specification and direction of the Engineer in charge.
10 litres capacity PVC LL cistern (Slimline-white) with 32mm dia CP long
Supplying all materials,labour,T&P and fixing Flat back lipped wall (Mini stall
urinal -630mmx180mm) urinal of the following sizes including connecting
the urinal with 32mm. dia pvc waste pipe 910mm. long by means of white
lead mixed with chopped hemp, fixing 32mm. dia CP dome waste, 15mm.
dia CP spreader including cutting holes in walls and making good the
damages with supply of wooden plugs, screws and cement etc. all
complete as per specification and direction of the Engineer in charge.
141 i Half stall urinal Each 6.00 2602.14 15,612.82
142 ii Providing marble slab urinal partition wall Each 5.00 977.75 4,888.74
143 iii 20mm dia CP Con. stop cock (CON-CHR-089KN) Each 6.00 1393.82 8,362.90
144 iv 32mm dia CP dome waste Each 6.00 151.63 909.78
Supplying all materials, labour, T&P and fixing glazed earthenware
squatting plate of size 600mmx350mm with integral longitudinal flushing
pipe including embedding the plate in 25mm cement mortar (1:8) laid over
150mm cement concrete (1:5:10) using 40mm hard granite metal all
complete as per specification and direction of the Engineer in charge.
146 i Fixing of squatting urinal Each 2.00 3440.17 6,880.34
Supplying all materials, labour, T&P and fixing wash basins with hole for
pillar taps with cast iron or M S brackets painted white including cutting
holes in walls and making good the damages with supply of wooden plugs,
screws and cement etc, fixing pedestal for wash basin recessed at the back
for the reception of pipes and fittings, fixing PVC waste pipe of 32mm
147 7 nominal diameter for wash basin including brass check nut complete, fixing 0 0.00 0.00 0.00
pillar taps capstan head screw down high pressure lettered ‘Hot’ and ‘Cold’
with long screws, shanks and back nuts of 15mm dia nominal bore, fixing
15mm dia PVC inlet connection pipe and making connection with pillar
cocks and supply mains for wash basin, fixing 32mm dia CP brass waste,
etc all complete as per specification and direction of the Engineer in charge.
Half Pedestal wash basin (550x400 mm) (Hindware/ Parryware/ Neycer
149 ii Under Counter Basin (560x450 mm) Hindware-No.ZEN Each 14.00 2636.59 36,912.29
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and fixing wash kitchen sink/laboratory
sink with outlet at end and weir overflow including fitting and fixing a pair
of cast iron or MS brackets painted white, fixing 50mm/40mm dia CP brass
waste, fixing 50mm/40mm dia PVC waste pipe 910mm long with supply of
wooden plugs, screws and cement etc including cutting holes in walls and
making good the damages etc all complete as per specification and
direction of the Engineer in charge.
550x404x200 mm stainless steel kitchen sink-glossy-IS:13983 - 1994
Providing 15 mm dia Sink Cock with J Shaped (Table Mounted) of Jaquar
having cat no - CON-CHR-359KN as per IS : 13983 and stainless steel plug
152 9 40 mm, including painting of fittings and brackets, cutting and making Nos 12.00 2700.43 32,405.16
good the walls wherever required : all complete as per specification and
direction of the Engineer in charge.
Supplying all materials, labour, T&P and fixing mirror of superior glass
mounted minimum 5mm thick on 6mm thick A.C sheet or plywood sheet
and fixed to wooden plugs with CP screws and washers complete as per
specification an direction of the Engineer in charge.
154 i 600mmx450mm size B.E mirror (swivelled type) Each 27.00 768.42 20,747.23
155 ii Large Size mirror with Frame (37x0.90x0.75)= Sqm 9.45 2105.12 19,893.38
Supplying all materials, labour, T&P and fixing standard sized glass-shelf
with CP brass brackets and guard rails complete fixed to wooden plugs with
CP screws as per specification and direction of the Engineer in charge.
157 i 600x125mm plate glass shelf with CP guard rails Each 57.00 711.89 40,577.96
Supplying all materials, labour, T&P and fixing standard sized CP towel rail
158 12 /ring complete with CP brass brackets fixed to wooden plugs with CP 0 0.00 0.00 0.00
screws as per specification and direction of the Engineer in charge.
159 i 20mmx450mm long CP towel rail Each 4.00 423.38 1,693.54
160 ii C.P. Ring towel ring Each 54.00 306.68 16,560.83
Supplying all materials, labour, T&P and fitting and fixing CP shower with
161 13 15mm or 20mm inlet with CP shower arm including polishing all complete 0 0.00 0.00 0.00
as per specification and direction of the Engineer in charge.
162 i 15mm dia CP revolving shower with arm. Each 4.00 593.19 2,372.74
Supplying all materials, labour, T&P and fixing CP soap holder complete
with CP brass brackets fixed to wooden plugs with CP screws as per
specification and direction of the Engineer in charge.
164 i CP soap holder Each 4.00 215.70 862.82
165 ii CP liquid soap holder Each 55.00 266.09 14,634.95
Supplying all materials, labour, T&P and fixing of Stainless Steel Coat Hook
alongwith all necessary accessories complete including cutting, making
166 15 good the walls, floors, slab wherever complete in all respect as per 0 0.00 0.00 0.00
specification and direction of the Engineer in charge. (Jaquar/ Hindware/
167 i Double coat hook (Jaquar Make) Each 32.00 576.73 18,455.20
Supplying all materials, labour, T&P and fixing of gyeser system for hot
168 16 water provision complete with CP brass brackets fixed to wooden plugs 0 0.00 0.00 0.00
with CP screws as per specification and direction of the Engineer in charge.
Erica manual storage water heater 10 litre capacity vertical Installation
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and fitting and fixing brass/CP fittings
of the following nominal bore with supply of all jointing materials complete
as per specification and direction of the Engineer in charge.(C.P.fittings are
171 i 15mm dia CP Angle stop cock (CON-CHR-053 Jaquar) Each 111.00 725.94 80,578.90
172 ii 15mm dia CP Abulation Cock (CON-CHR-039 Jaquar) Each 32.00 696.91 22,301.06
173 iii 15mm dia CP Two way bib cock (CON-CHR-041 Jaquar) Each 32.00 1161.47 37,167.17
174 iv 15mm dia CP Health faucet (ALD-MCH-563 Jaquar) Each 28.00 1509.93 42,277.98
175 v 15mm dia CP Elbow Op. cock (FLR-CHR-5043N Jaquar) Each 30.00 2700.43 81,012.90
176 vi 15mm dia CP Longbody Bibcock (CON-CHR-107 Jaquar) Each 32.00 1161.47 37,167.17
177 vii 15mm dia CP Pillar cock (CON-CHR-011KN Jaquar) Each 48.00 1364.79 65,509.82
178 viii 20mm dia CP Consealed Stopcock (CON-CHR-089KN Jaquar) Each 6.00 1393.82 8,362.90
179 ix 15mm dia 1" CP extension piece Each 35.00 62.07 2,172.38
180 x 125mm dia CP grating Each 96.00 100.30 9,628.80
181 xi 25mm CPVC Ball valve Each 20.00 397.31 7,946.12
182 xii 25mm dia brass fullway valve(Shakti Make) IS:778 - 1984 class-I) Each 25.00 1096.93 27,423.20
183 xiii 32mm dia brass fullway valve(Shakti Make) IS:778 - 1984 class-I Each 7.00 1605.98 11,241.86
184 xiv 40mm dia brass fullway valve(Shakti Make) IS:778 - 1984 class-I Each 8.00 2038.33 16,306.66
185 xv 50mm dia brass fullway valve(Shakti Make) IS:778 - 1984 class-I Each 5.00 3016.79 15,083.94
Supplying all materials, labour, T&P and providing fitting and fixing (Aqua
guard) Pure Chill 80 PSS UV of size 750x570x1350mm height with water
186 18 storage capacity 80 liters along with 2 nos of faucets 1 for cold water and 1 0 0.00 0.00 0.00
for normal water including a flow of 1.5 ltr per minute etc all complete as
per approved drawing,specification and direction of the Engineer in charge.
187 i Pure Chill 80 PSS UV Make-Aqua guard/ Usha Each 5.00 132445.56 6,62,227.80
Providing 12 mm thick cement plaster with cement mortar of mix (1:6)
with screened and washed sharp sand for mortar and finished smooth to
the rough surface of walls in all heights after racking out joints including
189 1 watering and curing, rounding of corners, providing grooves where ever 0 0.00 0.00 0.00
necessary with cost, conveyance, royalties of all materials with cost of all
labour,labour cess, T&P, and scaffolding required for the work etc.
complete in all respect as directed by the Engineer in charge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and providing and fixing ceramic tiles
of sizes 300x300 mm in floors, treads or steps confirming to (IS-
15622:2017) and landing on 25mm thick bed of cement mortar (1:1) ( 1
cement : 1 sand ) jointed with neat cement slurry mixed with pigment to
match the shades of the tiles including watering, curing,cost of all
materials, conveyance of all materials to work site , payment of royalty, all
taxes etc all complete as per direction of Engineer-in-charge. (Antiskid Tile
flooring size 30cmx30cm approved by the Engineer-in-charge)
Supplying all materials, labaour, T&P and fixing ceramic glazed tiles in
dados skirting on 12mm thick cement plaster (1:3) joined with neat
cement slurry mixed ith pigments to match the shades of the tiles etc.
211 3 complete as per direction of the Engineer-in-charge.(ceramic vitrified 0 0.00 0.00 0.00
Glazed tiles in wall of size 450x300 ) of make
Johnson/Kajaria/Somany/Orient Bell/Rak) plain/printed series to be pre-
approved by the Engineer-in-charge.
Priming one coat with wall cement primer (water bound) to make an even
finished surface in all floors and heights to wall surface of approved make
and shade including sand papering, applying putty wherever necessary &
cost of scaffolding, staging charges with cost, conveyance, cost of all
labour,labour cess T&P etc. complete as per the direction of the Engineer-in-
Painting two coats with plastic emulsion paint over a coat of water bond
cement primer to make an even finished surface in all floors and heights to
wall surface of approved make and shade including sand papering, applying
putty wherever necessary & cost of scaffolding, staging charges with cost,
conveyance, cost of all labour,labour cess, T&P etc. complete as per the
direction of the Engineer-in-charge.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Finishing plastered surfaces of walls with cement based wall putty (Water
based) of approved make and finishing the surface smooth and even by
sand papering to receive painting in walls, at all heights with staging
wherever necessary with cost, conveyance, cost of all labour,labourcess, all
T&P etc. required for the work complete in all respect as per the direction
of the Engineer-in-charge.
Supplying the waterproofing material Pidifin 2K of Dr.fixit on equivalent
water proofing material and appling in two coat over the concrete floor and
265 7 dado upto 1"-6" in wall including cleaning,applying and mending as per 0 0.00 0.00 0.00
specification including all labour charges as per direction of Engineer-in-
269 0 In Fourth floor Sqm 28.13 316.24 8,895.83
Supplying all materials, labour, T&P and filling in foundation and plinth with
sand well watered and rammed including conveyance of all materials to
worksite, payment of royalty, taxes etc all complete as per direction of the
Engineer in charge.
Supplying all materials, labour, T&P and providing cement concrete (1:4:8)
with 4cm size hard granite metal including watering, curing, conveyance of
all materials to worksite, payment of royalty, taxes etc all complete as per
specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing cement concrete (1:2:4)
with 12mm size hard broken granite chips including watering, curing,
conveyance of all materials to worksite, payment of royalty, taxes etc all
complete as per specification and direction of the Engineer in charge.
R.C.C. work M-25 grade with 20mm and down grade black hard granite
(crusher broken) stone chips including centering and shuttering work.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Factory made single leaf Solid WPC (Wood polymer) composite door
shutter of 25mm thickcompacted with wood grain finish structural foam
panel of 29mm thickness and a density of 650kg/cu.mtr shall be used as
core material for fitting the metal fittings such as tower bolts, aldrops,
handles etc shall be provided. A structural adhesive compatible with (EPS)
foam shall be used for bending the core material, The material and
process for manufacturing the door shutters shall conform to RV-TIFAC
composites Design Centre's standards and specifications and the door
shutters Conforming to relevant I.S.specification. The finish of door shutter
will be plain colour white/ Ivory/ Beige/ Light grey/ Mahogany/ Teak wood
or any other colour using high quality pigments. Three heavy whight mild
steel butt hinges type-I (ISI marked) size 100mm are to be fitted on one
side of shutter. of make Rajshri Plastiwood/ Alstone/Aramstrong or
euivalant as per direction of Engineer-in-charge.
Factory made Solid WPC door frame of size 90mmx45mm fabricated .The
door frame consist of four segments which are provided with plug-in-
socket arrangement in-situ in the mould. The segments are plugged in and
are joined together by means of screw. The WPC frame shall be provided
with The material and process for manufacturing the door frames shall
287 10 conform to Relavent I.S.specification. The finish of door frame will be plain 0 0.00
colour white/ Ivory/ Beige/ Light grey/ Golden brown/Mahogany/ Teak
wood/sand stone/Champagne/Pastel blue or any other colour using high
quality pigments complete in all respect as per specification. of make
Rajshri Plastiwood/ Alstone/ Aramstrong or euivalant as per direction of
Engineer-in-charge.
Supplying all materials, labour, T&P and laying in trenches (to level or
slope) unplasticized PVC pipes conforming to IS: 4985/2000 of the
following outside dia for class–3(0.60mpa) including jointing with supply of
approved solvent cement by non-heat application method/as per
290 1 manufacturer’s specification, providing and laying in trench cement 0 0.00 0.00 0.00
concrete (1:4:8) with 40mm size hard granite metal in the Type C-1
standard bedding surrounding or encasing including concrete for bedding
and curing etc all complete as per PH specification and direction of the
Engineer in charge.
291 i 110mm dia U-PVC Alround Concrete Mtr 90.00 1336.35 1,20,271.50
292 ii 160mm dia U-PVC Alround Concrete Mtr 150.00 2206.84 3,31,025.40
Supplying all materials, labour, T&P and constructing gully trap chamber of
the following inside size with 8cm thick R.C.C precast cover slab in cement
concrete (1:2:4) mix using 12mm size h.g chips, foundation concrete
(1:4:8) using 40mm size hard granite metal on bed and around trap, KB
293 2 brickwork in cement mortar (1:6) in F&P and inside 12mm thick cement 0 0.00 0.00 0.00
plastering (1:3) finished with a floating coat of neat cement including fixing
100mmx100mm size HCI gully trap,150mmx150mm size CI grating etc all
complete as per approved drawing, specification and direction of the
Engineer in charge.
294 0 size 250mmx250mm with R.C.C cover slab Each 10.00 1744.87 17,448.66
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and constructing inspection chamber of
the following size with cement concrete(1:3:6) using 40mm size hard
granite metal on bed, Ground class fly ash brickwork in cement
mortar(1:6), moulding and shaping the channel inside and benching with
cement concrete (1:2:4) using 12mm size h.g chips, 12mmthick cement
295 3 plaster (1:3) with punning to inside, cement flush pointing (1:3) to outside, 0 0.00 0.00 0.00
RCC cover slab in (1:1.5:3) using 12mm size h.g chips with RCPC man hole
cover, earthwork in excavation in all kinds of soil and refilling the cavity
around the chamber including watering, curing, conveyance of all materials
to worksite, payment of royalty, taxes etc all complete as per approved
specification and direction of the Engineer in charge.
296 0 Inside size 760mmx760mmx460mm with R.C.C cover slab Each 15.00 10750.63 1,61,259.39
Supplying all materials labor T&P and constructing MH chamber of sizes
earth work in excavation in all kinds of soil CC(1:1:8) with black granite
chips size 46mm brick work with K.B. brick having crossing strength not
less than 75 Kg /CM2 to 90 Kg/CM2s in CM(1:6)12mm C.P(1:8) inside MH
chamber over benching with cement slush pointing (1:3)outside the MH
chamber providing painting MS or CI step iron RCC (roof of slab with
CC(1:2:4)with black granite chips size 12mm bending binding tying the
grills placing of the reinforcement providing RCC color of required size
refilling the cavity around the MH chamber with excavated earth including
channeling the bed of MH etc all complete as per PH specification.
299 i Inside size 910mmx910mmx910mm (18” dia RCC Cover ) Each 15.00 20860.75 3,12,911.22
300 0 ---- do --- addl depth of 0.30m upto 4.50m depth Each 1.00 3013.72 3,013.72
Design, supplying, installing, testing & commissioning of SewageTreatment
302 A plant of capacity 20 KLD (excluding all Civil & construction work) for the 0 0.00 0.00 0.00
following duty:
303 0 Nature of Sewage - Domestic Sewage, 0 0.00 0.00 0.00
304 0 Daily average flow -20 cum/day 0 0.00 0.00 0.00
311 0 Sewage discharge standard after treatment 0 0.00 0.00 0.00
314 0 S. Solids - Less than 20 Mg/L 0 0.00 0.00 0.00
316 0 Coliform – traces 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of Stainless Steel Perforated,
318 1 6mm perforated Bar Screen with suitable lifting arrangement with brackets NO 1.00 23600.00 23,600.00
in the sreen sump of (size 800 mm x 2500mm depth approx), SS-304
Supply, installation, testing & commissioning of electronic type level
indicator, instrumation and controller for automatic operation of the system
with high/low level alarm complete with auxillary NO/NC contacts.
320 2 Contractor shall ensure submission of detailed GA drawings (Plan & NOS 2.00 11800.00 23,600.00
Section), P & I diagram, schematic diagram for the above mentioned
component and additional component if so required for the complete
working of the STP.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply, installation, testing & commissioning of non clogging type Mono
block centrifugal sewage transfer pumps capable of handling solids upto
10 mm having C.I casing & Bronze impeller complete with all
322 3 accessories, motor of required capacity, Pressure gauge on delivery line SET 1.00 53100.00 53,100.00
with isolation cock, level controller (with wiring) to control the level
of sump automatically Capacity 4-5 M3/hr each , 1 set = 2 Nos.(1
working + 1 standby)
325 0 Inlet/outlet Size 40 x 40 mm 0 0.00 0.00 0.00
328 0 Make- KIRLOSKAR/CG/LUBI 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of non clogging type
Mono-block centrifugal sludge transfer pumps capable of handling solids
upto 10 mm having C.I casing & Bronze impeller complete with all
330 4 accessories, motor of required capacity, Pressure gauge on delivery line SET 1.00 53100.00 53,100.00
with isolation cock, level controller (with wiring) to control the level
of sump automatically Capacity 4-5M3/hr each , 1 set = 2 Nos.(1
working + 1 standby)
333 0 Inlet/outlet Size 40 x 40 mm 0 0.00 0.00 0.00
336 0 Make- KIRLOSKAR/CG/LUBI 0 0.00 0.00 0.00
Twin lobe type rotary air blowers with 1450 rpm suitable motor (1W +
1Sb) capable of delivering 35 cum/hr ( 2 nos. ) of free air at 0.3 kg/cm2
driven through “V” belt or directly coupled through flexible coupling to a
338 5 TEFCmotor of suitable 1 HP Suitable for 415 ± 10% volts, 3 phase, 50 SET 1.00 165200.00 1,65,200.00
cycles A/C supply. complete with silensors,filters ,NRV,SV and divert
valaves,Vibration pads etc complete with all acessories 1set=2 Nos (1
working + 1 standby),
339 0 Make-A1 /AIRVAK /AKASH 0 0.00 0.00 0.00
340 0 Motor Make SIEMENS/CROMPTON/KIRLOSKAR 0 0.00 0.00 0.00
Supplying, installing, testing and commissioning, of fine bubble diffuser
along with membrane of silicone membranes, PVC support pipe(10 ksc
pressure rating),PVC fitting, nylon rope braided hose with all accessories to
make it retrievable & to provide clog-free oxygen for Aeration Tanks.
MBBR Media Module as per std specification and detailed drawing and
technical spec, quantity required as designed (approx 3.0-m3 each ) with
support rest etc for the proposed MBBR directed by engineer in charge at
345 0 Make-- MM AQUA/WELCOME MARKETING 0 0.00 0.00 0.00
Hexagonal Tube settler with MSEP rack support and open able bracket
/MH and support frame for clarifier unit of size 750 mm long and with end
locking arrangement ,the inclination of 51’ is required ,end lock sud have
the surface locking arrangement in rack etc (media min approx 3 m3) with
all fittings and fixtures as required for clarifier as directed by engineer in
charge at site.
348 0 Make--MM AQUA/WELCOME MARKETING 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Piping (heavy class) in MS/GI/SS/UPVC/HDPE as per the approval of the
350 9 consultants, to be designed for suitable and corrosion resistance complete LOT 1.00 70800.00 70,800.00
or as directed by engineer in charge at site
351 0 MS PIPE MAKE -JINDAL/TATA 0 0.00 0.00 0.00
352 0 UPVC PIPE AND FITTINGS -- SUPREME/ASTRAL/FINOLEX 0 0.00 0.00 0.00
354 0 TERTIARY TREATMENT PLANT 0 0.00 0.00 0.00
Supplying, installing, testing and commissioning of horizontal
single/multistage centrifugal filter feed pump complete ,impeller CI casing .
Each pump shall have TEFC 2900 RPM three phase electric motor. The
pump shall have cast iron head, base plate SS Shaft/ Impeller/
Intermediate chamber. Pump shall be provided with mechanical seal. The
pump shall be suitable for auto/ manual operation. of capacity 4-5 M3/hr @
35 MWC.(1 W + 1 St by ) MONO-BLOCK PUMP,1 set = 2 Nos.(1 working +
358 0 Inlet/outlet Size 40 x 40 mm 0 0.00 0.00 0.00
361 0 Make- KIRLOSKAR/CG/LUBI 0 0.00 0.00 0.00
Providing, fixing, testing & commissioning of FRP Tertiary filtration plant
MULTI GRADE FILTER (suitable for 3.5 Kg/Sqcm working pressure)
complete with initial charge with Gravels/pebbles/sand /silex media ,
Multiport valves with built in frontal pipe work with back wash system,
pressure gauge at inlet, outlet and back wash (each with isolation cock),
valves, fittings associated works.
364 0 Pr Vessel MOC – FRP COMPOSITE VESSEL 0 0.00 0.00 0.00
366 0 Back Wash Period 12 Hrs. 0 0.00 0.00 0.00
367 0 Operating Pressure 3 Kg. per sq.cm 0 0.00 0.00 0.00
368 0 Test Pressure 7.5 Kg. Sq.cm. 0 0.00 0.00 0.00
370 0 Make- STARLITE/PENTAIR/AQUANOMICS 0 0.00 0.00 0.00
Providing, fixing, testing & commissioning of FRP water filtration plant
ACTIVATED CARBON FILTER (suitable for 3.5 Kg/Sqcm working
pressure) complete with initial charge with Gravels/pebbles/Activated
carbon , Multiport valves with built in frontal pipe work with back wash
system, pressure gauge at inlet, outlet and back wash (each with isolation
cock), valves, fittings associated works.
373 0 Pr Vessel MOC – FRP COMPOSITE VESSEL 0 0.00 0.00 0.00
375 0 Back Wash Period 12 Hrs. 0 0.00 0.00 0.00
376 0 Operating Pressure 3 Kg. per sq.cm 0 0.00 0.00 0.00
377 0 Test Pressure 7.5 Kg. Sq.cm. 0 0.00 0.00 0.00
379 0 Make- STARLITE/PENTAIR/AQUANOMICS 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of Hypochloride dosing
381 13 system for tertiary water treatment with 100 L . HDPE/PVC tank with lid NOS 1.00 17700.00 17,700.00
382 0 Capacity of the dosing Pump - 0-4 LPH 0 0.00 0.00 0.00
384 0 Stroke per minute-55 0 0.00 0.00 0.00
385 0 Make- KANAKDHARA/E-DOSE/UKL 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14 gauge
CRCA sheet steel in form in 3b formation with reinforcement of suitable
size angle iron, channel ‘T’ sections irons and/or flats wherever necessary.
Cable gland plates shall be provided on top as well as at the bottom of the
panels. Panels shall be treated with all anticorrosive process before painting
as per specifications with 2 coats of red oxide primer and final approved
shade of powder coated paint. 2 Nos. earthing terminals shall be provided
for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be
provided in case of large panels. Approval shall be taken for each panel
before fabrication. Cadmium Plated hardware shall be used in fabrication of
panels. Quoted rates shall inclusive of cables (in accordance to
specification) with earthing from panel to each motor /STP Motor Control
388 0 Incoming Distribution panel with bus bar etc as std required. 0 0.00 0.00 0.00
389 0 MCC for GWTP as described above 0 0.00 0.00 0.00
390 0 CABLE & CABLE TRAYS 0 0.00 0.00 0.00
Supplying & laying of following 1100 volt grade PVC sheathed
aluminum/copper conductor armoured cables as per specification in
392 0 existing trenches, cable trays, ducts over bed of sand, clamped to wall with 0 0.00 0.00 0.00
suitable clamps, saddles fixing bolts including connecting testing and
commissioning. as site suitable quantities as per site.
393 0 4 core 4 sq. mm copper cable 0 0.00 0.00 0.00
395 0 Make- L&T/SIEMENS/ABB 0 0.00 0.00 0.00
A. COMPLETE COMMISSIONING OF SEWAGE TREATMENT PLANT WITH
UREA, DAP, COW DUNG, BIO-CULTURE, MAN POWER ALONG-WITH TOOLS
AND TACKLES FOR 20 DAYS.
B. 1 YEAR MAINTAINANCE SERVICE AND REPLACEMENT WARRANTY(BUT
EXCLUDES MAN-POWER,CONSUMABLES ,ELECTRICAL ETC)
C. INLET AND OUTLET PARAMETERS TEST REPORT AFTER SUCCESFUL
COMMISSIONING FROM POLLUTION BOARD APPROVED LABORATORY.
Design, supplying, installing, testing & commissioning of Effluent Treatment
399 A plant of capacity 5 KLD (excluding all Civil & construction work) for the 0 0.00 0.00 0.00
following duty:
400 0 Nature of Sewage - Hospital effluent, 0 0.00 0.00 0.00
401 0 Daily average flow -5cum/day 0 0.00 0.00 0.00
408 0 Sewage discharge standard after treatment 0 0.00 0.00 0.00
411 0 S. Solids - Less than 20 Mg/L 0 0.00 0.00 0.00
413 0 Coliform – traces 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of Stainless Steel Perforated,
415 1 6mm perforated Bar Screen with suitable lifting arrangement with brackets NO 1.00 11800.00 11,800.00
in the sreen sump of (size 600 mm x 1000mm depth approx), SS-304
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supply, installation, testing & commissioning of electronic type level
indicator, instrumation and controller for automatic operation of the system
with high/low level alarm complete with auxillary NO/NC contacts.
417 2 Contractor shall ensure submission of detailed GA drawings (Plan & SET 2.00 5900.00 11,800.00
Section), P & I diagram, schematic diagram for the above mentioned
component and additional component if so required for the complete
working of the STP.
Supply, installation, testing & commissioning of non clogging type Mono
block centrifugal sewage transfer pumps capable of handling solids upto
32 mm having C.I casing & Bronze impeller complete with all
419 3 accessories, motor of required capacity, Pressure gauge on delivery line SET 1.00 35400.00 35,400.00
with isolation cock, level controller (with wiring) to control the level
of sump automatically Capacity 1.0 M3/hr each , 1 set = 2 Nos.(1
working + 1 standby)
423 0 Make- KIRLOSKAR/CG/LUBI/TEXMO 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of non clogging type
Mono-block centrifugal sludge transfer pumps capable of handling solids
upto 25 mm having C.I casing & Bronze impeller complete with all
accessories, motor of required capacity, Pressure gauge on delivery line
with isolation cock, level controller (with wiring) to control the level
of sump automatically Capacity 1.0 M3/hr each ,
429 0 Make- KIRLOSKAR/CG/LUBI/TEXMO 0 0.00 0.00 0.00
Twin lobe type rotary air blowers with 1450 rpm suitable motor (1W +
1Sb) capable of delivering 15 cum/hr ( 2 nos. ) of free air at 0.4 kg/cm2
driven through “V” belt or directly coupled through flexible coupling to a
431 5 TEFCmotor of suitable 1 HP Suitable for 415 ± 10% volts, 3 phase, 50 SET 1.00 118000.00 1,18,000.00
cycles A/C supply. complete with silensors,filters ,NRV,SV and divert
valaves,Vibration pads etc complete with all acessories 1set=2 Nos (1
working + 1 standby),
432 0 Make-A1 /EVEREST / AIRVAK /AKASH 0 0.00 0.00 0.00
433 0 Motor Make SIEMENS/CROMPTON/KIRLOSKAR 0 0.00 0.00 0.00
Piping (heavy class) in MS/GI/SS/UPVC/HDPE as per the approval of the
436 6 consultants, to be designed for suitable and corrosion resistance complete LOT 1.00 53100.00 53,100.00
or as directed by engineer in charge at site
437 0 MS PIPE MAKE -JINDAL/TATA 0 0.00 0.00 0.00
438 0 UPVC PIPE AND FITTINGS -- SUPREME/ASHIRBAD/FINOLEX 0 0.00 0.00 0.00
440 0 TERTIARY TREATMENT PLANT 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying, installing, testing and commissioning of horizontal
single/multistage centrifugal filter feed pump complete ,impeller CI casing .
Each pump shall have TEFC 2900 RPM three phase electric motor. The
pump shall have cast iron head, base plate SS Shaft/ Impeller/
Intermediate chamber. Pump shall be provided with mechanical seal. The
pump shall be suitable for auto/ manual operation. of capacity 1.0 M3/hr @
35 MWC.(1 W + 1 St by ) MONO-BLOCK PUMP,1 set = 2 Nos.(1 working +
445 0 Make- KIRLOSKAR/CG/LUBI/TEXMO 0 0.00 0.00 0.00
Providing, fixing, testing & commissioning of FRP Tertiary filtration plant
MULTI GRADE FILTER (suitable for 3.5 Kg/Sqcm working pressure)
complete with initial charge with Gravels/pebbles/sand /silex media ,
Multiport valves with built in frontal pipe work with back wash system,
pressure gauge at inlet, outlet and back wash (each with isolation cock),
valves, fittings associated works.
448 0 Pr Vessel MOC – FRP COMPOSITE VESSEL 0 0.00 0.00 0.00
450 0 Back Wash Period 12 Hrs. 0 0.00 0.00 0.00
451 0 Operating Pressure 3 Kg. per sq.cm 0 0.00 0.00 0.00
452 0 Test Pressure 7.5 Kg. Sq.cm. 0 0.00 0.00 0.00
454 0 Make- TECHLITE/PENTAIR/AQUANOMICS 0 0.00 0.00 0.00
Providing, fixing, testing & commissioning of FRP water filtration plant
ACTIVATED CARBON FILTER (suitable for 3.5 Kg/Sqcm working
pressure) complete with initial charge with Gravels/pebbles/Activated
carbon , Multiport valves with built in frontal pipe work with back wash
system, pressure gauge at inlet, outlet and back wash (each with isolation
cock), valves, fittings associated works.
457 0 Pr Vessel MOC – FRP COMPOSITE VESSEL 0 0.00 0.00 0.00
459 0 Back Wash Period 12 Hrs. 0 0.00 0.00 0.00
460 0 Operating Pressure 3 Kg. per sq.cm 0 0.00 0.00 0.00
461 0 Test Pressure 7.5 Kg. Sq.cm. 0 0.00 0.00 0.00
463 0 Make- TECHLITE/PENTAIR/AQUANOMICS 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of Hypochloride dosing
465 10 system for tertiary water treatment with 50 L . HDPE/PVC tank with lid NOS 1.00 11800.00 11,800.00
466 0 Capacity of the dosing Pump - 0-4 LPH 0 0.00 0.00 0.00
468 0 Stroke per minute-55 0 0.00 0.00 0.00
469 0 Make- KANAKDHARA/UKL/E-DOSE 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Design, fabrication, assembling, wiring, supply, installation, testing and
commissioning of motor control centre shall be fabricated out of 14 gauge
CRCA sheet steel in form in 3b formation with reinforcement of suitable
size angle iron, channel ‘T’ sections irons and/or flats wherever necessary.
Cable gland plates shall be provided on top as well as at the bottom of the
panels. Panels shall be treated with all anticorrosive process before painting
as per specifications with 2 coats of red oxide primer and final approved
shade of powder coated paint. 2 Nos. earthing terminals shall be provided
for 3 phase, 4 wire, 50 Hz supply system. Lifting hooks shall also be
provided in case of large panels. Approval shall be taken for each panel
before fabrication. Cadmium Plated hardware shall be used in fabrication of
panels. Quoted rates shall inclusive of cables (in accordance to
specification) with earthing from panel to each motor /STP Motor Control
473 0 Incoming Distribution panel with bus bar etc as std required. 0 0.00 0.00 0.00
474 0 MCC for GWTP as described above 0 0.00 0.00 0.00
475 0 CABLE & CABLE TRAYS 0 0.00 0.00 0.00
Supplying & laying of following 1100 volt grade PVC sheathed
aluminum/copper conductor armoured cables as per specification in
477 0 existing trenches, cable trays, ducts over bed of sand, clamped to wall with 0 0.00 0.00 0.00
suitable clamps, saddles fixing bolts including connecting testing and
commissioning. as site suitable quantities as per site.
478 0 4 core 4 sq. mm copper cable 0 0.00 0.00 0.00
A. COMPLETE COMMISSIONING OF SEWAGE TREATMENT PLANT WITH
UREA, DAP, COW DUNG, BIO-CULTURE, MAN POWER ALONG-WITH TOOLS
AND TACKLES FOR 20 DAYS.
B. 1 YEAR MAINTAINANCE SERVICE AND REPLACEMENT WARRANTY(BUT
EXCLUDES MAN-POWER,CONSUMABLES ,ELECTRICAL ETC)
C. INLET AND OUTLET PARAMETERS TEST REPORT AFTER SUCCESFUL
COMMISSIONING FROM POLLUTION BOARD APPROVED LABORATORY.
Supply, installation, testing & commissioning of Flocculation type dosing
484 13 A system comprising of 100 ltrs HDPE/FRP tank with 0-4 LPH metering type SET 1.00 17700.00 17,700.00
485 0 Make- KANAKDHARA/UKL/E-DOSE 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of Coagulation type dosing
486 B system comprising of 100 ltrs HDPE/FRP tank with 0-4 LPH metering SET 1.00 17700.00 17,700.00
487 0 Make- KANAKDHARA/UKL/E-DOSE 0 0.00 0.00 0.00
Supply, installation, testing & commissioning of
489 14 REACTION/AERATION/CLARIFIER/CLARIFIED Tank of 3000 liters capacity Ltr. 12000.00 12.78 1,53,400.00
each . HDPE/PVC tank with lid etc
490 0 Make- SINTEX /SUPREME 0 0.00 0.00 0.00
492 15 Supply, installation, testing & commissioning Static Mixture NO 1.00 23600.00 23,600.00
494 16 Sludge drying Media ( pebbles,gravels.medium sand) LS LS 29500.00 29,500.00
Construction of 20 KLD RCC Over Head Tank of Fire Fighting Tank,
Inside size- 4.40 X 3.70 X1.50m-Terrace Floor
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Supplying all materials, labour, T&P and providing cement concrete
(1:1½:3)with 12mm size hard broken granite chips for R.C.C works
496 1.1 including hoisting, laying, watering, curing, conveyance of all materials to 0 0.00 0.00 0.00
worksite, payment of royalty, taxes etc all complete as per specification
and direction of the Engineer in charge .
Supplying all materials, labour, T&P and providing M.S.Reinforcement for
504 1.2 RCC work including cutting, banding, binding, straightening and trying the 0 0.00 0.00 0.00
grills and placing in position including cost of binding wire 18 to 20 gage.
Supplying all materials, labour, T&P and providing rigid and smooth
506 1.3 centering and shuttering for RCC work including false work and dismantling 0 0.00 0.00 0.00
then after casting including cost of materials complete in ground floor.
507 0 RCC floor roof, chajja etc 0 0.00 0.00 0.00
511 1.4 RCC Beam, Column, wall etc 0 0.00 0.00 0.00
Supplying all materials, labour,T&P and providing 6mm thick cement
519 1.5 plasster (1:4) over CC work including watering curring and conveyance of 0 0.00 0.00 0.00
all materials to site.
Supplying all materials, labour, T&P and providing cement punning
including watering, curring and conveyance of all materials to site.
524 0 Quantity same as item No-4 sqm 78.60 46.02 3,617.17
Supplying and fitting and fixing stainless steel 34 grade in said rail using
5mm dia 2mm thick circular pipe and lalustrade 32mmx32mmx2mm at the
525 1.7 rate of mtr.Center to center and square pipe 32x32x2mm below including Kg 50.00 395.30 19,765.00
welding with stanless steel elect rod and fixing with necessary accessories
etc.complete as per direction of the Engineer-in-charge.
Providing fitting and fixing MS cover made out of MS angle and sheet duly
526 1.8 welding and fixing with frame and hinges along with locking arrangement of Kg 40.00 109.88 4,395.26
size 60cmx60cm etc complete as per direction of Engineer-in-charge.
Construction of 150000 Liters RCC UGR for Fire Fighting of Inside size-
Providing & Constructing RCC underground sump of 150000 ltr. Capacity
including RCC top cover, ladder, airvent, inlet and outlet pipe, water
proofing including pipeline from UG Sump to top over head tank with its
pump and etc. as per the design provided by the engineer in charge.
530 0 For Production well. 0 0.00 0.00 0.00
2 H.P three phase 3 stage head range 30 to 54 metres, discharge 155 to
110 L.P.M with outlet dia of 32mm.
532 1.3 DOL controll pannel Each 1.00 4490.49 4,490.49
534 1.5 32mm dia steel short piece Each 4.00 179.71 718.86
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
535 1.6 Steel rope with cover Mtr 50.00 31.51 1,575.30
537 1.8 50mm size CI bracket Each 1.00 107.73 107.73
538 1.9 20mm dia rigid UPVC pipes Mtr 100.00 8.14 814.20
Construction of 15000 Liters RCC UGR for Domestic Water of Inside size-
Providing & Constructing RCC underground sump of 15000 ltr. Capacity
including RCC top cover, ladder, airvent, inlet and outlet pipe, water
proofing including pipeline from UG Sump to top over head tank with its
pump and etc. as per the design provided by the engineer in charge,
542 0 For Production well. 0 0.00 0.00 0.00
2 H.P three phase 3 stage head range 30 to 54 metres, discharge 155 to
110 L.P.M with outlet dia of 32mm.
544 1.3 DOL controll pannel. Each 1.00 4490.49 4,490.49
546 1.5 32mm dia steel short piece. Each 4.00 179.71 718.86
547 1.6 Steel rope with cover Mtr 130.00 31.51 4,095.78
549 1.8 50mm size CI bracket. Each 2.00 107.73 215.47
550 1.9 20mm dia rigid UPVC pipes. Mtr 100.00 8.14 814.20
Construction of 10000 Liters RCC UGR for Domestic Water of Inside size-
Providing & Constructing RCC underground sump of 10000 ltr. Capacity
including RCC top cover, ladder, airvent, inlet and outlet pipe, water
proofing including pipeline from UG Sump to top over head tank with its
pump and etc. as per the design provided by the engineer in charge,
554 0 For Production well. 0 0.00 0.00 0.00
2 H.P three phase 3 stage head range 30 to 54 metres, discharge 155 to
110 L.P.M with outlet dia of 32mm.
556 1.3 DOL controll pannel. Each 1.00 4490.49 4,490.49
558 1.5 32mm dia steel short piece. Each 4.00 179.71 718.86
559 1.6 Steel rope with cover Mtr 130.00 31.51 4,095.78
561 1.8 50mm size CI bracket. Each 2.00 107.73 215.47
562 1.9 20mm dia rigid UPVC pipes. Mtr 100.00 8.14 814.20
563 507 SOLAR WATER HEATING SYSTEM (1000 LTRS CAPACITY) 0 0.00 0.00 0.00
Supply of Solar flat plate Collectors. of make Supreme Solar/Greentek
India/ Radient Energy or equivalant as per direction of Engineer in charge.
Supply of input 7.5 Kw output 35Kw 250LPD/Hr Air Source Heat Pump of
565 2 make Thermex/Brio/Neo or equivalant as per direction of Engineer-in- 1.00 413000.00 4,13,000.00
Supply of Hot Water insulated pressurized Storage Tank made out of stain
566 3 less steel SS304grade–1 nos. 1000 ltrs capacity of make Parkland/Radient Each 1.00 354000.00 3,54,000.00
or equivalant as per direction of Engineer-in-charge.
Supply of Non return valve and SS fittings., 2 nos of Circulation cum
pressure pump of make WILO/ GROUNDFOUS with 4 nos Electrical Backup
567 4 Heater(5KW) internal Kitech pipes and fittings, 40 nos MS power coated 1.00 94400.00 94,400.00
Stand for fixing of solar plates etc. as per requirement at siteetc complete
as per direction of Engineer-in-charge
Installation of all the above materials on the roof including fitting and fixing
of Insulated tank, circulating pump, back-up heater, piping arrangement Each
etc complete with functioning of solar water heating system etc complete set
as per standard specification and direction of Engineerin-charge
Sinking of 200 mm dia (8") Gravel Packed Production Well including saline
569 513 sealing where necessary through Rotary Drilling Rig 300 Mtrs with PVC/ GI 0 0.00 0.00 0.00
Casing Pipes- 2 No.
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Labour for drilling a perfectly vertical bore hole of specified dia for a
specified depth below ground level through consolidated and
unconsolidated rock with down the hole hammer drilling rig or combination
rig as required to suit the site condition as per the direction of the Engineer
in charge including use of own rig with its accessories, tools and plant and
consumables etc for lowering of 200mm/150mm dia G.I/P.V.C/M.S casing
570 1 pipes for housing fitted with socket and with or without well screen as per 0 0.00 0.00 0.00
the necessity for soft, medium, hard and boulder formation (G.I/ P.V.C/
M.S casing pipes if required to prevent collapse of overburden is to be
provided by the contractor including lowering and withdrawing after
completion of the tube well), 200mm dia to 400mm dia in overburden
portion including packing of gravel supplied by the contractor for 400mm
571 a Drilling of 200mm dia bore 0 0.00 0.00 0.00
574 b Drilling of 150mm dia bore 0 0.00 0.00 0.00
Lowering the following size of G.I/P.V.C/M.S housing pipes with or without
slotted pipes as per the necessity from ground level up to 45.00m depth
and fitted and fixed up in perfectly vertical position including cutting and
threading of pipes and slotted pipes and supplying and fixing all jointing
materials, tools and plant etc all complete and keeping the top of casing
pipe threaded including plugging tube wells to prevent entry of foreign
577 a Lowering of 200mm dia P.V.C casing pipes 0 0.00 0.00 0.00
Supplying polyvinyl chloride pipes as per ASTM-D-1785-89 having threads
in accordance with DIN 2999 part-1/DIN-42225 part-II specification length
of pipe (laying length) will be 3 mtrs. The pipes shall be supplied with both
external and threaded with free socket. The pipe having external thread at
one end i.e female and or belled end. The female end having internal
580 3 thread is to be belled in order to accept the male end while jointing pipes 0 0.00 0.00 0.00
with a bore threading shall be provided with a greave at the roof of the
male thread accomodate flexible PVC/Rubber 'O' ring to make the joint
water tight colour of the pipe shall be blue. The name of the manufacture
along with batch No class of pipe shall be stranded legibly of each pipe
581 i 200mm dia PVC (sch-80) pipe- (2x45.00mtr each=90.00mtr) mtr 90.00 2047.89 1,84,310.10
Supplying all materials, labour, T&P and providing and providing sanitary
sealing by cement concrete grouting of annular space around GI/PVC/MS
housing pipe upto 5m below ground level (as per drawing) to plug the bore
582 4 hole excluding cost of cement all complete as per direction of the Engineer Each 2.00 1190.62 2,381.24
in charge. Minimum one metre of casing pipe to be inserted in the bore into
the rock at the bottom to ensure sanitary sealing (excluding cost of cement
which will be supplied directly by the department)
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
Cleaning and developing the tube well with supply of compressor worked
till clear and adequate discharge is obtained from the tube well including
583 5 supply and use of all necessary equipment and labour as per direction of 0 0.00 0.00 0.00
the Engineer in charge.
Supplying all materials, equipment, labour & conducting reconnaissance
survey, integrated Hydrological and Geophysical (Electrical Resistivity
Method) survey & selection of potential source for exploration of Ground
585 6 Water including selection and recommendation of site for drilling wells in 0 0.00 0.00 0.00
selected locations in any part of Orissa under the following Geological
586 i Rocky terrain with boulder formation for 300m depth 2.00 1324.09 2,648.18
Supplying all materials, labour, T&P and providing, fitting and fixing
submersible pump with squirrel cage induction type submersible type
submersible electric motor to run on 3 phase/1 phase line voltage ranging
from 320 volt to 450 volt conforming to IS: 8034/89 with following
specifications with suitable control panel, jointing with GI/PVC/HDPE pipes,
electrification, testing, commissioning, trial running, conveyance of all
materials to worksite, payment of taxes etc all complete as per
specification and direction of the Engineer in charge (Texmo/Crompton
Greaves/Kirloskar make)
2HP single phase 3 stage vertical / horizontal submersible pump set at
588 a head range 20 to 35 meters discharge 145 to 110 LPM with outlet dia of Each 3.00 26033.99 78,101.96
589 b DOL Control panel Each 3.00 4490.49 13,471.47
590 c 40mm dia steel short piece Each 2.00 179.71 359.43
592 e 50mm size CI bracket Pair 2.00 107.73 215.47
594 g 20mm dia rigid UPVC pipes Mtr 100.00 8.14 814.20
595 i Steel rope with cover Mtr 100.00 31.51 3,150.60
596 j Labour charges for lowering including transportation Each 3.00 2360.00 7,080.00
Supplying all materials, labour, T&P and providing and fixing to wall or
ceiling and floor HDPE pipes and pipe fittings conforming to IS: 4984/2000
(10kgf/sqcm) of the following nominal bore with clamps and jointing by
597 8 Fusion welding method including testing, making good the wall, ceiling and 0 0.00 0.00 0.00
floor all complete as per specification and direction of the Engineer in
598 i 32mm HDPE pipes (Finolex/Supreme make) Mtrs. 200.00 117.76 23,552.80
Supplying all materials,labour,T&P and constructing surface drain of size
100mm top width and 75mm deep with cement concrete (1:3:6) using
40mm size h,g metal on bed, 1st class K.B. brick work in cement morter
(1:3) inside, 12mm thick cement plaster (1:3) finished smooth with
cement punning including watering, curing, conveyance of all materials to
worksite, payment of royality, taxes etc all complate as per specification
and direction of the Engineer in charge.
600 544 Construction of 6.75mx3.60m x 1.40m(h) Rain Water Recharge Pit 0 0.00 0.00 0.00
601 1 Sinking of tube well through D.T.H.Rig. 0 0.00 0.00 0.00
603 2 Lowering of PVC casing pipe inside bore. 0 0.00 0.00 0.00
606 4 Cutting slot in casing pipe for recharge of rain water Mtr. 25.00 417.13 10,428.25
607 5 Labour for packing gravel outside the tube well 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
609 6 Cost of washed gravel. Cum 4.70 1902.63 8,942.37
Earth work in all kinds of soil within 50 mtr initial lead and 1.5mtr initial lift
including rough dressing and breaking clods to maximum 5cm to 7cm and
laying in layers not exceeding 0.3 mtr in depth and as per direction of the
Engineer in charge.
Supplying all materials, labour, T&P and providing cement concrete (1:4:8)
with 4cm size hard granite metal including watering, curing, conveyance of
all materials to worksite, payment of royalty, taxes etc all complete as per
specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing brick work with Fly ash
bricks having crushing strength not less than 75kg/cm² with dimensional
617 9 tolerance ± 8 percent in cement mortar (1:6) including watering, curing, 0 0.00 0.00 0.00
conveyance of all materials to worksite, payment of royalty, taxes etc all
complete as per specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing 12mm thick cement
plaster (1:4) on brickwork including watering, curing, conveyance of all
materials to worksite, payment of royalty, taxes etc all complete as per
specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing cement punning
including watering, curing, conveyance of all materials to worksite,
payment of royalty, taxes etc all complete as per specification and direction
of the Engineer in charge.
Supplying all materials, labour, T&P and providing rigid and smooth
centering and shuttering for R.C.C works including false work and
631 12 dismantling them after casting including conveyance of all materials to 0 0.00 0.00 0.00
worksite, payment of royalty, taxes etc all complete as per specification
and direction of the Engineer in charge.
Earth work in excavation of foundation in all kinds of soil within 50 mtr
initial lead and 1.5mtr initial lift including rough dressing and breaking
clods to maximum 5cm to 7cm and laying in layers not exceeding 0.3 mtr
in depth and as per direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing M.S reinforcement for
R.C.C work including cutting, bending, binding, and tying the grills and
637 14 placing in position including cost of binding wire 18 to 20 gauge, 0 0.00 0.00 0.00
conveyance of all materials to worksite, payment of royalty, taxes etc all
complete as per specification and direction of the Engineer in charge.
639 15 Providing and filling filter media 0 0.00 0.00 0.00
Digitally signed by Rakesh
Description of Item Unit Qnty. Rate Amount
643 18 Providing fitting and fixing M.S.grill,Jalli cover over the harvesty pindi Qntl. 4.00 10988.16 43,952.64
66 0 Sub-Total of Plumbing Works 0 0.00 0.00 1,50,40,854.47
67 Grand Total 17,44,39,772.61
67 Grand Total 17,44,39,772.61
Digitally signed by Rakesh
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT-66.pdf
Tender Document
GCC with upto date amendments.pdf
Tender Document
BOQ CCB.pdf
Tender Document
3b SCC.pdf
Tender Document
14 Scope of Work.pdf
Tender Document
8 Milestone.pdf
Tender Document
Signed IP.pdf
Tender Document
Drawing.pdf
Tender Document
LIST_OF_MAKES.pdf
Tender Document
corrigendum-2322-Corrigendum01.pdf
pdf • 0.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .