Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹86.9 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹88.4 L+₹1.5 L (1.71%)Rejected-Finance | L2 | Rejected-Finance Higher Quoted Rate. | |
| 3 | L3₹92.8 L+₹5.9 L (6.77%)Rejected-Finance | L3 | Rejected-Finance Higher Quoted Rate. | |
| 4 | L4₹95.0 L+₹8.1 L (9.30%)Rejected-Finance MIA GARAGE BUILDING 1ST FLOOR HILLCART ROAD DIST SILIGURI PIN 734401 | SILIGURI | SILIGURI | WEST BENGAL | 734401 | L4 | Rejected-Finance Higher Quoted Rate. | |
| 5 | L5₹1.0 Cr+₹13.6 L (15.6%)Rejected-Finance 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L5 | Rejected-Finance Higher Quoted Rate. |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
28 Jun 2024, 12:00 pmClosed
SE, PWD, Kolkata Electrical Circle
Kolkata Electrical Circle P-16, India Exchange Place Extn.KIT Building, 2nd Floor, Kolkata-700073
Installation of HV Substation, DG set and allied works at I and C and R.D.T.C centre at PVD, Behala.---- SITC of 2x500KVA substation and its allied electrical works.
2024_WBPWD_689485_1
PWD/SE/KEC/NIT-01/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
R.D.T.C centre at PVD, Behala
Please refer Tender documents.
8 documents required · 8 mandatory
₹1.8 L
Office of the SE, PWD, Kolkata Electrical Circle
13 Dec 2024
5 Jun 2024
1 Jul 2024
5 Jun 2024
28 Jun 2024
14 Jun 2024
12 Jun 2024
Amount
SITC OF SUBSTATION HT PANEL Supply, Installation, testing & Commissoning of 6 KV 800 A, short-circuit capacity of 26.3 KA for 1 sec, 3-panel HT Gear with VCBs as per Specification [Make - SIEMENS/ ABB /Crompton Greaves/Lauritz Knudsen] below : BIL-28KV/75KV. The Vacuum Circuit Breaker should comply as per IS:13118 & IEC:62271-100 for Circuit Breaker & IS:3427 & IEC:62271-200/IEC 694, IEC-61850 for Indoor panel. The HT panel is rated at 6 KV, 3-Phase 800A, Breaking Current/short-circuit capacity of 26.3kA for 1 sec, 50c/s and shall be of floor-mounting, sheet steel clad, free-standing metal enclosed air insulated switchgear cubicle with VCB inside. The Vacuum Circuit Breaker is horizantal isolation & horizantal drawout/Vertical isolation & horizontal drawout with 3 compartments and is made of 2mm CRCA sheet for load bearing members with vermin & moisture proof along with automatic shutter arrangement for complete isolation of bars, cable sockets & other live parts etc. when the removable portion is withdrawn. The breaker is arranged for hand operation through front of the panel push buttons & spring charging mechanism and also electrical motor which will be energizied by 230V AC. Closing and tripping coils are rated for 110V DC to be made available from the station 400 V 3 phase 50 C/s A.C. source with remote operation compatibility. All trip coils shall be of shunt trip type energized from a suitable rectifier condenser source.supply is required. There is a remote operation through multicore arrangement for closing & tripping. The shutter shall be gravity operated.
FRONT DOOR :- The front door of the breaker should not be set as front. High-Voltage door during switching operations, the high-voltage door should remain closed and mechanical interlock should prevent opening of door when the switching device is in service and is switched ON. The position of the withdraw-able section, the CLOSED/OPEN switch position of the switching device, the operating cycle counter and the “spring charged” indication should be visible through pressure-resistant inspection windows in the high-voltage door. The panel front door can be closed with the breaker in isolated position. The degree of protection in the panel is IP-43 as per Indian Standard IS 3427. BUBAR: The spacious bus bar compartment is provided on the top of the cubicle. The main bus bar can carry current upto 1000A and are made of electrolytic grade copper & shall be vertically placed one after another. The bus bars should be air insulated but must be HT PVC sleeved & color coded for R-Y-B. No live parts should be accessible. All joints should be covered with monoplast compound and color coded for easy identification. The feeder connection to the busbars are preffered to be encapsulated. BREAKER: The vacuum circuit breaker is mounted on a truck and is of horizontal isolation and horizontal drawout/Vertical isolation & horizontal drawout type having a robust motorized mechanism. The spring charge cycle duty of mechanism is O-C-O. The vacuum circuit breaker is single break design and have one vacuum interrupter per phase. The vacuum interrupter should not be of pinch tube type design, it should be sealed by brazing in a vacuum oven & all the vacuum interrupters must be segregated in a cast resin housing. The minimum operational life of the vacuum interrupter is 30,000 mechanical, 10,000 electrical at rated current & 100 at rated short circuit. The breaker is having auxiliary switch 6NO+6NC.
EARTHING: A continous copper earth bus runs across the entire length of the switchboard. All doors partitions, covers and non current carrying metallic parts are earthed to achieve earth potential for the entire enclosure. Terminals are provided at each end of the earth bus to connect the grid earthing. If integral earthing facility is not available separate earthing truck shall be provided for earthing. INTERLOCK: The circuit breaker can be operated only in service/test position and not in any intermediate position, beside fully isolated condition.The circuit breaker cannot be inserted into service position in closed condition and cannot be removed from service unless it is in open condition. The circuit breaker cannot be moved from test position to service position unless auxiliary plug is disengaged and vise virsa in service position auxiliary plug should be in engaged condition. If earth switch is provided it shall be mechanically interlocked with the breaker so that both the devices can not be 'ON' simultaneously.
TESTING: The fully assembled switch board shall be offered for routine testing as per provision of IS 3427. The manufacturer should submit closing & tripping time curve after testing on a breaker analyzer. For major boughtout components like CT, PT, meters & relays the routine test certificates of the respective manufacturers need to be submitted.
l) Trip circuit Supervision relay type-VAX31 --- 1 no. (Siemens/ABB/ Crompton Greaves/Lauritz Knudsen/Alstom) m) Auxiliary relay for Transformer (Siemens/ABB/ Crompton Greaves/Lauritz Knudsen/Energypack)- 1 no.] Wdg. temp. A/T indication ---- 1 no. (Make - Alstom or equivalent make) n) Antipumping relay -- 1 no. o) 6/8 Window Annunciator -- 1 set p) Local Remote/T-N-C/Motor On-Off/Heater On-Off Switch- 4 set. q) MCB for control supply-AC/DC -- 2 sets r) HRC control fuse & link as per scheme-- 1 set s) 110V DC Hooter- 1 no. t) Panel space heater with thermostat-- 1 no.
The transformer will be Enviromental class E2 (Minimum ), Climatic Class C2 as defined IEC 60076, Fire Behavior Class F1 as defined in IEC 60076-11. All the above i.e. Environmental Class, Climate Class & Fire Behavior Class must be indicated in rating plate. Enclosure : Sheet steel with protection class IP-43, painting should be eposy / as per latest standard.Basic level Insulation for HV : 75 KV pk. Temperature Scanner : Provided with 3 RTDS for sensing winding temperatures alongwith temperature scanners for display of winding temperature and with Alarm / Trip contacts. Testing : All Routine tests as per relevant IS have to be conducted at manufacturer's works.
Testing & commissioning of total system comprising of different sub-station equipments (HT gear,Transformer,LT ACB panel etc.) including all protective devices and relays with overload and earth fault condition at site by co's own testing equipments and tools & plants by authorized firm of directorate of electricity,Govt of WB and submitting the test reports to DOE. fianlly charging & commissioning the entire system (Up to the level of stability of whole system) (level of stability will be under direction of EIC) after obtaining approval of Directorate of Electricity
CUBICLE TYPE L.T. PANEL Supply and installation of L.T. cubical type fully compartmentalized distribution panel board(Raw Normal Power), having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. (Main LT panel comprised of two nos. 800A, ACB, EDO type as incomer and One no. 800A, ACB EDO type as bus coupler. The incomer ACB's & Bus-coupler are to be elctrically & mechanically interlocked to prevent any malfunction.) [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of this item has to approved by EIC before making of it mentioning all major technical details with specification and Make of each and individual part. All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel by means of busbar, copper multi core cables, to be terminated on bolted type terminals for cable connection or on bush insulators for bus bar connection. Each compartment will be providing with DMC/FRP board at back side. Incoming:- i)415V,50KA,800 A, 4P electrically draw- out type A.C.B. with Microprocessor-based protection release. (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider) -----3 no. ( 2 no as Incomer & 1 no as Buscoupler)
BUS COUPLERs:- Buscoupler arrangement: Manually operated with interlocked doors, automatic safety shutters, mechanical ON / OFF and service / test / isolated position indicators and frame earthing contact, 1 no. independent manual spring closing mechanism, 1 no. shunt trip coil 220 Volts AC, conforming to IS 13947 - 2 - 1993 as amended upto date - 1 set. The interlocking arrangement(both electrical & mechanical) should be such that in case of failure of one transformer the entire panel will be charged by one transformer after adjusting the connected load. Otherwise in normal condition the two different supply from two different transformers should be separated and accordingly load will be distributed to hospital. BUS BARS: 500V, 1000 Amp capacity tinned 4 bar copper bus bar [size of flat- 80 mm x 10 mm ] mounted on non-hygroscopic porcelain insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications. Interlockings:- Electrical through advance contacts in ACBs (incomers & bus coulers) and mechanical (castel key) interlocking should beprovided to ensure that only one supply is available at a time on each section of bus and to eliminate any possibility of accedentally approaching two supplies at one bus section.
Outgoing:- 400 Amp 4pole MCCB (Ics=100%Icu,36kA,415V AC,50Hz) with adjustable built in LSING,microprocessor based trip unit,1no Auxiliary contact of 1N/O & 1N/C,shunt release,spreader link on both side with phase barrier,Extended rotary handle etc - 5nos (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider) 250 Amp 4pole MCCB (Ics=100%Icu,36kA,415V AC,50Hz) with built in LSING,microprocessor based trip unit,1no Auxiliary contact of 1N/O & 1N/C,shunt release,spreader link on both side with phase barrier,Extended rotary handle etc 6nos (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider) 200 Amp 4pole MCCB (Ics=100%Icu,36kA,415V AC,50Hz) with adjustable built in LSING, microprocessor based trip unit,1no Auxiliary contact of 1N/O & 1N/C,shunt release,spreader link on both side with phase barrier,Extended rotary handle etc--- 2no (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider) 100 Amp 4pole MCCB (Ics=100%Icu,36kA,415V AC,50Hz) with adjustable built in LSING , microprocessor based trip unit,1no Auxiliary contact of 1N/O & 1N/C,shunt release,spreader link on both side with phase barrier,Extended rotary handle etc 3no (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider) Multipurpose Meter Digital Type Load Monitor (Make ABB / Siemens / Lauritz Knudsen/ Legrand /Schneider)- 3 Nos. Supply & fixing of 6A FP MCB for Meter protection (Make Legrand/Lauritz Knudsen/ABB/Siemens) for all incoming & outgoing switches control ckt. LED type indicating Lamp (Red/yellow/blue/orange/green/white)----60nos (for incoming & outgoing indication for 3phase , ON,OFF,Trip indication)
All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned Aluminium bars or equivalent flexible pvc insulated multistranded single core Al. cable and the same between busbar to all outgoing mains and also for metering arrangements are to be made by suitable size of Copper wire with proper socketing of the end of each wire leads. Earthing:- A separate continuous Cu earth busbar of size 25mm x 5mm is to be placed at the inside bottom of the panel and run across the full length of the panel board atleast extended for 75 mm at both side end of panel and should have drill hole to fit in 12x50mm GI nut bolt for earth strip connection. The complete panel board is to be spray painted after required surface treatment by 7 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
HT cable:- Supply & laying of following sizes 6.6kV UE grade Al armoured XLPE cable (Gloster/Havells/polycabRR Kabel/KEI) confirming to IS 7098(Part-II):2011 with latest amendment as mentioned below as per choise of EIC through existing masonary trench as per GS. 3 core 240 sqmm XLPE cable from CESC Panel to HT panel and HT Panel to 2 nos Transformer
Jointing of H.T. cable of 6.6 KV grade 3 core 240 sq.mm. XLPE (E) cable incl.supply of necy. jointing materials & compound (Heat shrink cable jointing kit of approved make) for switch gear & transformer terminations on H.T. sides incl. testing
S & drawing 1.1KV grade 7 core 2.5 sqmm. PVC/Ar. copper cable from transformer's WTI relay to VCB WT Relay for power & control supply. (Make - Polycab/Gloster/Havells/KEI/RR KABEL)
S & drawing 1.1KV grade 2 core 2.5 sq.mm. PVC/Ar. copper cable from Power DB to VCB. (Make - Polycab/Gloster/Havells/KEI/RR KABEL)
LT Cable:- Supply & laying of 1.1 KV grade XLPE insulated. PVC sheathed, steel Armoured Al. conductor Cable of the following size, and conforming to IS: 7098(Part-I):1988/1554(Part-I):1988/ 5831:1984/ 3961(Part-I):1967/ 3975:1970/ 10810:1984 / 3975:1970 /8130:1984/ 3961:1967/ 10418:1982 / 10810:1984 as amended upto date, in respect of component materials and tests, and as per the approved makes list attached herewith. (cost includes Supply & Fixing of straight through joint, if required, as per direction of EIC) (Make - Polycab/ Gloster/ Havells/ KEI/ RR KABEL) Note : Material Test certificate of all size of cable to be submitted to dpt. (Make of the Cable KEI/Gloster/Havells/Polycab/RR KABEL) Supply & laying 1.1 KV Grade 2x4 Core 400 sqmm XLPE/A AL.Cable to be laid through masonary / U.G. trench as per G.S. (from Transformer to ACB of sub station L.T.main pannel board)
Supply & laying 1.1 KV Grade 2X4 Core 185 sqmm XLPE/A AL.Cable to be laid through masonary / U.G. trench as per G.S. (from sub station L.T.main pannel board to 250KVA DG SET)
S & F compression type gland complete with brass gland , rubber ring for dust & moisture proof entry of 4 core 400 sqmm XLPE/A Al cable incl finishing the ends by crimping method as per GS.
S & F compression type gland complete with brass gland , rubber ring for dust & moisture proof entry of 4 core 185 sqmm XLPE/A Al cable incl finishing the ends by crimping method as per GS.
Supply and Fixing of 150mm dia medium gauge GI pipe (ISI-medium) protection with necessary fittings and jointing materials as required.
Earthing with 80 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 65 mm x 8 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 80 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts as required as per GS (For Transformers (2nos) each.)
Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 No. 50 mm x 6 mm galvanized (Hot Dip) steel strip (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including finishing both ends by making holes etc. and S & F 65 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36cm X 86.36cm X 46cm deep (below G.L.) compleet with cemented brick work (1:6) of 25cm width duly plastered with cement morter (inisde)C.I. hinged Inspection cover of size 36.56cm X 35.56cm with locking arrangement, G.I. reducer incl.drilling of 46 Nos.12mm dia.holes on the G.I.Pipe
Excavation of soil and filling & ramming as to GS. (For soft soil) (for installation of Earth Electrode)
Extra for treatment of soil by using salt and charcoal/coke for pipe electrode.(for Soft Soil)
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 65 mm x 8 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required.
Connecting the equipments body to earth busbsr incl.S&F 50 X 6mm Hot Dip Galv. MS flat on wall / floor with G.I. shaddles as reqd.& making connection to equipments with bolts,nuts & washers 2 Nos. etc.
Insulating the 65X8 mm GI flat incl. S&F black heat shrink PVC sleeves etc. The PVC tube sleeve to be inserted on the GI flat and heat shrinked by heating apparatus by skilled technician carefully without damaging the PVC sleeve as per direction of the EIC (for transformer neutral earth bus bar)
S& laying 150 sq. mm. single core multistrand XLPE insulated flexible copper cable(Mk.-Gloster/Polycab/KEI/RR Kabel) from neutral earth busbar to transformer point as required through PVC flexible pipe(reinforced) of suitable srze from earth busbar to transformer neutral partly concealed in floor as requrred (for Transformer neutral earthing)
Finishing the cable ends by crimping method incl. S&F solderless cu.socket. insulating tape and jointing malerials etc. as required suitable for single core 150 sq. mm.
S & F special type earth electrode clamp made of 65x8mm GI flat with holes for fixing nuts, bolts,, washer etc.and welding on the surface of 80 mm dia GI pipe earth.
Safety Equipments:- Supplying and Fixing 200mmX300mm EI danger plates for 6kV/415V system as to GS.
Providing and fixing carbon dioxide (CO2) type fire extinguishers conforming to IS 15222-2002 and cylinders fully charged of following capacity(4.5 Kg ) [Make - Fire Shield/ Max well/Ceasefire/Surex]
S/F electric shock treatment chart & pasted on hard board with wooden frame and 5 mm thick glass cover (1.20 sq. mtr.)
S/F 4 nos. 9.5ltr capacity round bottom GI Fire Bucket with iron hooks complete with painting inner side white and outer side red with lettering the work 'FIRE' in black colour complete with dry sand filling
S & F best quality FIRST AID BOX (Al. body) as per PWD specification, complete with all necessary items as required by rule of sub-station on MS bracket incl. damages to original finish approved by Indian Red Cross Society ; conforming to IS 13115-1991.
S & D of rubber mat 2 mtrs Length x 1 m. wide and 12mm thick to withstand 15 KV dielectric strength as per IS 15652-2006.
S/D of 15kV grade rubber/equivalent gloves (ISI marked)
S& fixing MS chequered plate (2mtr X 1 mtr) 8mm thick for covering the cable duct including MS handle of appropiate size as per direction of EIC.
Supply and fixing of foam fire extinguishers conforming to IS4989 -2006, Portable type 9 lit capacity hanged on wall with bracket complete as required. [Make - Fire Shield/ Ceasefire/Apollo]
Supply & fixing 75x45 mm "C" channel having length of 2 mtr. each channel incl. nuts, bolts and washer etc. ( For Transformer wheel support over the trench) with mechanical locking arrangement
Ditribution Wiring OF Substation:- S/Laying 1.1 kv grade 4 core 25 sq.mm XLPE/PVC insulated and sheathed, armoured cable with Al.conductor (HAVELLS/POLYCAB/ GLOSTER/R R KABEL) through wall at an average depth of 75mm.
Supplying & fixing 415V, 6-32A per way ,4 way TPN MCBDB with SS enclosure double door with IP 42/43 protection with 63 A FP isolators as incomer and 12 Nos. 16-32A SPMCBs ( 'C' Curve , 10kA ) as outgoing ,concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make-Legrand/Schneider/Siemens/Lauritz Knudsen)
Supplying & fixing 250V,6-10A per way , SPN MCBDB with SS enclosure double door with IP42/43 protection with DP isolators as incomer and SPMCBs ( 'C' Curve , 10kA ) as outgoing ,concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make-Legrand/Schneider/Siemens ), 2+12 way Enclosure, 607712, 40A DP Isolator,12 Nos. SPMCB
Supply and drawing 1.1KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab/Gloster/RR Kabel/KEI) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. Connection as required as per Direction Of EIC. 2 x 2.5 sqmm + 1 x 1.5 sqmm [ for Power Plug & LED Steet Lights ]
2 x 6 sqmm + 1 x 4 sqmm [ TPN to SPN & TPN to timer DB ]
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools. 19mm dia 3mm thick polythene pipe without earth continuity wire and tackles.
Supply & Fixing 25 mm dia PVC rigid Conduit pipe ( Precision make ) on wall and mending good the damages as to original finish as to GS.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire ((Make - Polycab/Gloster/Havells/KEI/RR KABEL) ) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (make:Legrand Myrius/Siemens/ABB) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish. [only PVC Rigid Conduit on ceiling and remaining portion concealed] Avg run- 9 Mtr
Supplying & fixing of 250 V 2 X 16 A modular type Switch, 2x16A 5 pin plug socket (make:Legrand Myrius/Siemens/ABB) fixed on suitable size 6 M modular type G I switch board with top cover plate flushed in wall incl. mending good damages to original finish
S & F twin LED light fitting (Mk.- Philips,TMC 502 P 2xT-LED 22W P3242/CROMPTON/Wipro) suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) upto 1m long supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length with 2 no18 W LED Polycarbonate body(Philips Mas LEDtube 18W, 2100lm 865 T8 (VE)) lamp as per direction of EIC.
Supplying & Fixing MS fan clam of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991
Supply & Delivery of 1200 mm. Sweep AC, 68Watt Ceiling Fan(Colour approved by EIC) complete with blades, canopy,fork, ruber bush, Safety Wire & P2 Capacitor etc. ( Make : Orient- Quasar Ornamental/ Crompton-AuraPrime antidust)
S&F of 230V, 100W step type 2M electronic fan regulator suitable for existing modular switch board with top cover plate (make:-Approve)
S&F 250V, 50 Hz, 300 mm Sweep 1420 rpm Heavy Duty AC Exhaust Fan (EPC make) after making hole and mending good the damages to original finish incl. S&F GI sheet (20SWG) metal Cowl 12" dia. with MS flat iron frame & GI wire mesh on wall with necy. bolts & nuts (6 mm dia x 62 mm long) as per GS. (Make : EPC heavy duty similar of Usha/Cromton )
Supply & Fixing of 200mm x150mm x100mm GI loop box (door type) with G.I top cover having 4mm thick with rubber gasket terminal with lug etc comprising of one 250V kit-kat fuse unit,one NL on porcelain insulator etc incl. all connection.
Supply & Delivery of 90W street light luminarie IP 66 PDC Street light LED street light made up of pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP66 protection. 10KV SPD included. Efficacy ≥120LPW incl. necy. Screws & Clamps for installation as per direction of EIC. (Cromton Greaves CAT No: Nexus Star CRP-404-90-57-SL-GL-NSG/ Similar Phillips/Wipro)
Fixing only outdoor / Flood light type fluorescent light fitting or MV or LED light fitting complete with all accessories to be fixed /projected on Minipole from the Top floor roof top of the building incl. making CC foundation on foop top of top floor as per GS. S&F 1.5m Minipole (ISI-Medium)strandred quality with 1.5 mts. average length having suitable arm bracket of 40mm dia S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc.
Supply & Installation of 25 A Timer controller in SS double door phosphatised powder coated 2+14 way SPNDB with din rail with IP-43 protection with belectrical accessories & front door locking arrangement with all connection A) 25 A DP MCB (10 kA ,C Curve ) -1 no,MCB housing should be thermostat (fire retardent) B) 25 A 2 Pole Power Contactor -1 nos C) Daily & Weekl programmable basis digital time switch ,min switching time 1 min, 25 ON/OF programs 6 Yrs .Battery backup ,settable DST & key pad lock features D)MS Enclosure of suitable size duly powder coated paint & inbuilt locking facilities -1no E) 25 A DP Modular AC starter with 18-26 A relay setting -1no F)ON/OFF LED Panel lamp -1 set G) 2 Way Bypass toggle switch -1no (make-Lauritz Knudsen/ABB/Crabtree)
THE INDIAN OVERSEAS TRADING COMPANY
JAYBEECO
M/S. N.C. HORE
RASH ELECTRICAL WORKS
CHAKRABORTY ENTERPRISE
C. CHOWDHURY AND CO
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .