Executive Engineer (E), BSNL, Bhubaneswar
O/o the Executive Engineer (E), BSNL, Bhubaneswar Door Sanchar Bhawan, Unit-IX, Bhubaneswar-751022
Attending MV/LT Electrical faults and repairing of EI and Fans and Service connection cables etc. for various TEs/BTS
2024_BSNL_192304_1
152/BSNL-EDB/2023-24
Open Tender
Electrical Works
Item Rate
180 days
Koraput BA
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
A O (Cash), BSNL, O/o GMTD, Bhubaneswar.
₹11,547
Yes
6 Nov 2024
23 Mar 2024
4 Apr 2024
23 Mar 2024
3 Apr 2024
23 Mar 2024
23 Mar 2024 - 1 Apr 2024
Amount
Attending Electrical Faults of LT/MV electrical system comprising of LT/MV Service connection line, Feeder panel, Main Distribution panel, MCB DBs, Riser mains etc. on need basis by deputing qualified and trained/skilled technician having valid Electrical License of appropriate voltage and making arrangements for checking, testing with suitable testing devices, fault finding, replacing faulty MCBs/Isolators/Switches/lamps/holders etc. by new ones (cost of materials are not included in the scope of this item and will be paid separately) and restoration of the Power supply to the Telephone Exchange/Admin Bldg/BTS/Staff Quarters complex within reasonable time period etc. complete as required.
Distance up to 25 Kms from Koraput
Distance above 25 Kms and up to 100 Kms from Koraput
Distance above 100 Kms and up to 200 Kms from Koraput
Replacement of the faulty and burn out MCBs, Isolators etc. by new ones of following ratings MCBs and Isolators ISI marked as per IEC 60947-3 /MCBs 10 kA , C- Curve as per IEC 60947-2 in existing MCBDBs i/c connection testing etc. as required.(Make-Legrand / L&T / Schneider Electric / Siemens/Havells )
100Amps 4 pole Isolator
63Amps 4 pole Isolator
63Amps 4 pole MCB
63 Amps DP MCB
32Amps 3 pole MCB
40Amps DP Isolator
40Amps DP MCB
6-32A SPMCB
Replacement of the faulty and burn out Fuse links by new ones of following ratings i/c connection testing etc. as required.(Make-Legrand / L&T / Schneider Electric / Siemens/Havells )
32 Amps 415V HRC Fuse links- Cylindrical type (L&T/Havells)
63 Amps 415V HRC Fuse links- Cylindrical type (L&T/Havells)
32 Amps 415V HRC Fuse links-Bolted type (L&T/Havells)
63 Amps 415V HRC Fuse links- Bolted type (L&T/Havells)
100 Amps 415V HRC Fuse links- DIN type (L&T/Havells)
125 Amps 415V HRC Fuse links- DIN type (L&T/Havells)
63 Amps 415V Porcelain Fuse unit
100 Amps 415V Porcelain Fuse unit
Replacement of the following burnt out/damaged cable/wires/lugs/sockets etc. by new one of following types, sizes and ratings PVC insulated FRLS copper conductor single core stranded flexible cable i/c laying / drawing in existing conduit/pipe, connection, testing etc. as required.
25sqmm with copper socketing
16sqmm with copper socketing
10sqmm with copper socketing
Replacement of the burnt out cables/wirings by the following sizes PVC insulated & PVC sheathed copper conductor multicore cable i/c fixing/laying on wall/ceiling with C clamps etc. as required.
3 coreX2.5sqmm
4 coreX2.5sqmm
3 coreX4.0 sqmm
Supply of the following sizes PVC insulated & PVC sheathed Aluminium conductor armoured cable 650/1100 V. grade confirming to IS : 7098 (Part-1) 1988 i/c transportation to respective sites etc. as required for replacement of faulty/burnt out cables.
2 core 6 sqmm
4 core 10 sqmm
4 core 16 sqmm
4 core 25 sqmm
3.5 core 50sqmm
Replacement of faulty service connection cables by new one of 2 core X4sqmm PVC insulated and PVC sheathed Aluminium conductor weather proof cable etc. as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Up to 35sqmm
Above 35 sq. mm and up to 95 sq. mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Up to 35sqmm
Above 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Up to 35sqmm
Above 35 sq. mm and up to 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size Up to 35sqmm in the existing Duct/Air as required.
Up to 35sqmm
Above 35 sq. mm and up to 95 sq. mm (clamped with 25x3mm MS flat clamp)
Replacement of damaged MV cable end terminations with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 16 sq. mm (28mm)
4 X 25 sq. mm (28mm)
3½ X 50 sq. mm (35mm)
Replacement of faulty SDFU switches by new ones of following ratings after dismantling the old defective ones, fixing, connection & testing etc. as required.
32 Amps 415 volts TPN SDFU with HRC fuses (open execution type). (Make: L&T FN type, /Havells / Siemens) .
63 Amps 415 volts TPN SDFU with HRC fuses (open execution type).(Make: L&T FN type, /Havells / Siemens) .
100 Amps 415 volts TPN SDFU with DIN type HRC fuses (open execution type). (Make: L&T FN type, /Havells / Siemens) .
125 Amps 415 volts TPN SDFU with DIN type HRC fuses (open execution type). (Make: L&T FN type, /Havells / Siemens) .
Replacement of faulty SDFU switches by new ones of following ratings with specious sheet steel enclosure so that there will be no need of separate cable gland boxes, having terminal shrouds and phase barriers on both sides suitable for Cylindrical/DIN type HRC fuse links, confirming to IEC-60947-3, IS/IEC:60947-3, after dismantling the old defective ones, fixing, connection & testing etc. as required.
63 Amps 415 volts TPN SDFU in Sheet steel enclosure with DIN type HRC fuses.(Make: L&T FN type, /Havells / Siemens) .
100 Amps 415 volts TPN SDFU in Sheet steel enclosure with DIN type HRC fuses. (Make: L&T FN type, /Havells / Siemens) .
Replacement of faulty Change over switches by new ones of following ratings after dismantling the old defective ones, fixing, connection & testing etc. as required.
63Amp 4-pole on load change over switch open execution type (Make: HPL Socomec /Havells / L & T) .
125Amp 4-pole on load change over switch open execution type (Make: HPL Socomec /Havells / L & T) .
63Amp 4-pole on load change over switch in sheet steel enclosure , front handle type (Make: HPL Socomec /Havells / L & T) .
100Amp 4-pole on load change over switch in sheet steel enclosure , front handle type (Make: HPL Socomec /Havells / L & T) .
Replacement of faulty MCCBs by new ones of following ratings Conforming to IS/IEC 60947-2 & IEC 60947-2 after dismantling the old defective ones, fixing, connection & testing etc. as required.
63Amps 25 KA 4 pole 415 volts 50 Hz, with Magnetic Thermal over load release (L&T DN0-100C/Equivalent of Siemens/ABB/Havells)
100Amps 25 KA 4pole 415 volts 50 Hz, with Magnetic Thermal over load release (L&T DN0-100C/Equivalent of Siemens/ABB/Havells)
Replacement of faulty and damaged FTL fittings by new one of following ratings, LED Batten with polycarbonate/Aluminium body suitable for operation on 140 volts to 270 volts AC, 50Hz i/c fixing and connection etc. as required. (Havells /Phillips / Surya / Polycab / Crompton)
22 watt 65000K Decorative ultra slim polycarbonate LED lighting fixture with high lumen output, environmental friendly, energy efficient ready to use pack.
25 watt 65000K Decorative ultra slim polycarbonate LED lighting fixture with high lumen output, environmental friendly, energy efficient ready to use pack.
32 watt 65000K Decorative ultra slim aluminium LED lighting fixture with high lumen output, environmental friendly, energy efficient ready to use pack.
18 watt 6500K LED panel round/square Surface mounted Downlighter with ABS housing & PC Opal diffuser with integral electronic LED driver..
24 watt 6500K LED square sleek surface mounted pressure die-cast aluminium luminaire in powder coated white finish in square profile with optimized heat sink for efficient heat dissipation and independent electronic LED driver.
22W General purpose industrial compact batten suitable for single LED Tube light with integral LED driver with single / double side connection options. (Make-Havells/Phillips/Bajaj/Wipro/Crompton)
22W General purpose industrial compact batten suitable for Double LED Tube light with integral LED driver with single / double side connection options. (Make-Havells/Phillips/Bajaj/Wipro/Crompton)
Supply of the following electrical accessories/components for Electrical Light Fittings i/c testing etc. as required.
36 /40 watt Fluorescent Tube rods
36/40 watt Electronic ballast for Fl. Tube fittings
Starter for Fl. Fittings
Driver with universal connector for LED light fittings (15watt/18watt)
Driver with universal connector for LED light fittings (24watt)
9 /10 watt LED Lamp (B22)
14/15 watt BC LED Lamp (B22/E27)
30 watt (B22/E27) LED lamp
20/22W Ultra bright LED Tube light with very high efficacy >=115 lm/W & THD<10% suitable for installation in existing tube light G13 lamp holders to give glare free light.
Replacement of the lamp holders/ceiling roses etc. by new ones of reputed makes etc. as required.
Angle/batten Holder
36/40 W Fl Tube light holder
36/40 W Fl Tube light starter holder
Ceiling Rose
5/6Amps 250 Volts 3 pin Plug top
15/16Amps 250 Volts 3 pin Plug top
Replacement of the defective switches/sockets/lamp holders/ call Bells etc. by the new one of following ratings etc. as required. (Make- Anchor/Havells/Cona/ISI)
6 /10 Amps 1 way modular type switch
16/20 Amps 1 way modular type switch
6 /10 Amps 1 way piano type switch
20 Amps 1 way piano type switch
6 /10 Amps 3pin modular type socket
16/5 Amps 6 pin modular type socket
6 Amps 3 pin piano type socket
16 Amps 3 pin piano type socket
Carry out repairing of Electrical Light Fittings by arranging qualified and trained man power and tools, tackles, ladders etc. i/c dismantling of defective/faulty components and fixing of new components i.e chokes, lamps, starters, interconnection wires, lamp holders etc. as required.
Inspection of faulty compound light/gate light , checking of all components, power supply cable , loop box, switch board i/c minor repairing works etc complete as required.
Supplying/ Fixing/Replacement of faulty compound lights by new 45 Watt LED street light Fitting on the existing GI bracket/pole i/c connection testing etc complete as required.( Make -Philipss,Model -BRP031 LED45/Havells-ENDURA SUNDOWNSL45W/SS make)
Sypplying and Fixing of 30 Watt LED street light Fitting on the existing GI bracket/pole i/c connection testing etc complete as required.( Make - Havells, Model -ENDURA SUNDOWNSL30W/SS make)
Repairing of Gate light by dismantling from the gate and fixing of new LED bulb & holder in the base i/c replacement of damaged 1.5sq mm Cu wire etc complete as required.
Sypplying and Fixing of 32mm dia 2ft length M-class GI Pipe bracket for fixing of LED street light Fitting i/c connection testing etc complete as required.
Rewinding of 1200mm/1400mm ceiling fan by superior quality super enameled copper conductor i/c heat varnishing, testing etc. as required.
Overhauling of Ceiling Fan i/c dismantling, heat varnishing of windings, greasing of bearings, refitting, testing etc. as required.
Replacement of the defective Capacitors / Fan regulators/ bearings for ceiling fans etc. by the new one of following ratings etc. as required. (Make- Anchor/Havells/Cona/ISI)
Stepped type Electronic Fan Regulator (Switch type)
Modular Fan Regulator (2 Modules)
Modular Fan Regulator (1 Module)
2.25 mfd 440 volts Capacitor for Ceiling Fan
Bearings for Ceiling fans (6201 & 6202) etc. as required. (Make: SKF/SS)
Ceiling Fan clamps heavy duty mild steel zinc golden colour with rubber (Shackle set)
Dismantling of ceiling fan and painting the same with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent, reinstalling the same as required.
S/F of MCB protected Socket outlet 4 module with metal box comprising of 01no. 25Amps socket and 01no. 25Amps Plug and 01no. 25Amps "C" series SPMCB for Split AC units i/c connection, testing etc. as required. (Make- Legrand /Havells/HPL/Standard)
Replacement of burn out Sockets/lugs of cables by new ones of following types and sizes i/c dismantling the burnt out portion of cables/wires, crimping/fixing of new sockets/lugs etc. (Dowell's / Comet / Hex Connect well / SS)
For 4X16sqmm Al Conductor Armoured cable
For 3.5/4X25/35sqmm Al Conductor Armoured cable
For 3.5X50/70sqmm Al Conductor Armoured cable
Attending the faults of free cooling exhaust fans at different Telephone Exchange / Mobile BTS sites on need basis, checking, teting and fault finding, rectification of minor faults (without spares), dismantling the faulty exhaust fans if required and taking it to the repairing shop for repairing, transportation of new/spare exhaust fans to site, re-installation of repaired/spare exhaust fans , connection, testing etc. as required.
Distance up to and including 25Kms
Distance more than 25Kms and up to and including 50 Kms
Distance more than 50 Km and up to and including 100 Kms
Rewinding of the 380mm 1500 rpm 230 volts heavy duty Exhaust fans by superior quality insulated copper winding wire i/c heat varnishing, reassembling, testing and greasing the ball bearings etc. complete as required.(The dismantled winding wires may be retained by the Contractor.The rewound exhaust fans may be fitted at other desired locations or may be kept at Sub Division offices for utilisation as per site requirements).
Replacement of the burnt out Exhaust fan motors only by new one of 380mm /15" heavy duty 1400 RPM, capacitor start and run type, continuously rated, totally enclosed and ruggedly built type motor having pre lubricated double ball bearing with Class "A" and "E" insulation suitable for operation on 230 volts single phase 50 HZ AC supply, connection and testing etc. complete as required. (make: Almonard model – 380/15” H/D). (The dismantled burnt-out motor may be retained by the agency)
Replacement of faulty, burnt out and unserviceable exhaust fans by new one of a complete set 380mm /15" heavy duty 1400 RPM Exhaust Fans having maximum free air delivering capacity not less than 3250 m3/ hour (1910 CFM) and maximum sound level not more than 60-65 db. with a capacitor start and run type, continuously rated, totally enclosed and ruggedly built motor having pre-lubricated double ball bearing with Class "A" and "E" insulation suitable for operation on 230 volts single phase 50 HZ AC supply with features for smooth & silent operation to deliver the maximum output at lower operating cost. The impeller of the Exhaust Fan is to be propeller type and both hub and impeller are to be dynamically balances and frames and arms mounted on rubber bushing so that, vibration are virtually eliminated etc. complete as required.(Make- Almonard HD (ISI) or similar superior)
Supply of Hot pressed molded SMC Junction box, hinged double door type of following sizes suitable for application for fixing Electrical controls /switch gears/meters etc. with provision for cable entry/exit from bottom/side , locking arrangements including supply and fixing of 2nos 4 pole stud connectors, interconnections with suitable size single core PVC insulated copper conductor cable with copper sockets/lugs including fixing on existing pole / existing MS/GI angle stands etc. complete as required.
Size not less than 650mmX350mmX250mm (inside dimensions) (Make-Sintex model: SINTEX JB-6535/SS)
Size not less than 400mmX300mmX190mm (inside dimensions) (Make-Sintex model: SINTEX JB-4030/SS)
Making suitable angle base frame made of 40mmX40mmX5mm MS angle for installation of mentioned SMC junction / meter boxes , cutting, welding, fabricating, grouting the same on ground with required PCC work complete as required.
Supply and fixing of SMC Junction box of size 200mm x 140mm x 95mm (inside dimensions) with hinged door type including supply and fixing of 1no. 4 pole stud connector with nuts and bolts etc. as required. (Sintex GSJB2014/SS)
Liaison with the Electricity DISCOMs for taking shutdown of LT/MV lines for checking, testing and replacement of faulty Service connection cable/Energy Meter/ Meter box/Feeder panel etc. and re energization of power supply after replacement of faulty components as above / removal of faults etc. complete as required.
RAY ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .