| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.8 LAccepted-AOC 13 218 MASJID EXTEN SADAR BAZAR | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹17.2 L+₹2.4 L (16.0%)Rejected-Finance | L2 | Rejected-Finance Not Lowest Bidder | |
| 3 | L3₹17.2 L+₹2.4 L (16.0%)Rejected-Finance | L3 | Rejected-Finance Not Lowest Bidder | |
| 4 | L4₹17.3 L+₹2.5 L (16.6%)Rejected-Finance NIVADA TIVAYA ROAD TIVYA MUST BUS STOP VILLAGE KHATAULI SAHARANPUR UP 247001 | SAHARANPUR | SAHARANPUR | UP | 247001 | L4 | Rejected-Finance Not Lowest Bidder | |
| 5 | L5₹19.0 L+₹4.2 L (28.3%)Rejected-Finance | L5 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
21 Dec 2023, 6:00 pmClosed
GE South Delhi Cantt-10
GE South Delhi Cantt-10
REPAIR/REPLACEMENT OF DBs, SUBMAIN WIRINGS, REWIRING, SUMMER AND COOLING APPLIANCES AT KHANPUR ARMY CAMP, MANESAR ARMY CAMP INDU BINOLA UNIVERSITY AND DUNDAHERA MIL STN UNDER AGE E/M OF GE (SOUTH) DELHI CANTT-10
2023_MES_629568_1
GE/DS-72/2023-24
Open Tender
Civil Works
Item Rate
270 days
GE South Delhi Cantt
Please refer Tender documents.
11 documents required · 11 mandatory
₹500
GE South Delhi Cantt
₹70,000
Yes
4 Jan 2024
23 Nov 2023
23 Dec 2023
23 Nov 2023
21 Dec 2023
7 Dec 2023
Amount
Attending complaints for checking and replacing the existing defective electrical items for continuous electric supply including carrying out minor repair as required to make the item functional and replacing fuse, small pieces of copper wire, copper cable as of suitable size at site, insulation tape roll etc., Attending minor repair(s) such as testing, connections, fittings, nut, bolts screws etc to ceiling fan, exhaust fan (without taking down) etc, emergent complaints i.e. no light, earth leakage, short circuit, neutral break in mains/sub mains/ internal circuits of existing electrical system of main building/block and making continuous electric supply including carrying out minor repairs etc. required to make the system in order/functional with insulation tape roll, copper thimbles, glands, earthing wire as required at site complete all as specified and as directed.
Notes :- This item is applicable only where no store is required. (i) Three electrician shall be provided by the contractor for attending daily complaints on working days including holidays/sunday and shall report to MES complaint cell at 8:30 hrs. (ii) Contractor shall ensure the security passes for his staff, to be obtained from concern authority for attending complaints. (iii) The MES Department is not responsible for the payment of electrician, as all the items of CA are to be supply and fixed by the contractor. (iv) The Contractor will ensure that the team of electricians with necessory tools bag shall always remain present at complaint cell to attend the complaints. (v) A recovery of Rs 500/- per complaint shall be recovered from the contractor for non deploying of electrician on any day. (vi) All the complaint slip,register & other connected document will be provided by the contractor without any extra cost.
S&F in repairs switch piano flush type 6 Amps SP one way complete all as specified and as directed.
S&F in repairs switch piano flush type 6 Amps SP 2-way complete all as specified and as directed.
S&F in repairs bell push, flush type 6 Amps complete all as specified and as directed.
S&F in repairs socket outlet 6 Amps flush mounted piano type 5 pin multi purpose complete all as specified and as directed.
S&F in repairs switch piano type 16 Amps SP one way complete all as specified and as directed.
S&F in repairs socket outlet 2 in 1 (multipurpose) 6 pin 6 and 16 Amps flush mounted type complete all as specified and as directed.
S&F in repairs lamp holder bakelite insulated body with back plate suitable for batten fitting complete all as specified and as directed.
S&F in repairs bell Ding dong type 230 volts single phase complete all as specified and as directed.
S&F in repairs ceiling rose surface Bakelite 65x25 mm two to three terminals complete all as specified and as directed.
S&F in repairs of fan regulator electronic, stepped type, Switch type, suitable for ceiling fan 1200/1400mm sweep complete all as specified and as directed.
S&F in repairs of fan condenser 2.5 Mfd complete all as specified and as directed. Make :- Epcos/Tibcon/Havells
S&F in repairs of fan condenser 3.15 Mfd complete all as specified and as directed. Make:- Epcos/Tibcon/Havells
S&F in repairs LED Glass Bulb 9 Watt B-22 Cap, AC 230V, 50 Hz, suitable for Batten Holder/Bulk head/wall light fittings complete all as specified and as directed.
S&F in repairs Decorative wall light made up of high grade engineering plastic material suitable for 9 W LED lamp B22 base complete all as specified and as directed.
S&F in repairs LED Bulk head 10 watt integrated type complete with LED and 3 core flexible connecting wires complete all as specified and as directed.
S&F in repairs LED Batten T-5 fitting 20 watt LED White, indoor decorative aluminum extruded T5 LED battern -integrated type environmental friendly complete all as specified and as directed.
S&F in repairs of LED Integrated Batten T5 10 watt - 2FT White, indoor decorative polycarbonate extruded T5 LED battern --integrated type environmental friendly complete all as specified and as directed.
S&F in repairs of LED Building security light fitting 45W energy saving and environmental friendly LED street light made up of pressure diecast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection complete all as specified and as directed.
S&F in repairs Circuler Hylam/PVC Sheet upto 10 Cm dia of 3 mm thick (for using as Junction box Cover) including screws and cup washer complete all as specified and as directed.
S&F in repairs of PVC casing caping of size 25mm with suitable size of nails for fixing PVC casing caping, in repairs of batten/surface wiring complete all as specified and as directed.
M&L for submain wiring of two runs of 4 Sqmm size for main cable and one run of 4 Sqmm size earth continuity conductor of single core PVC insulated but unsheathed FRLS cable of specified size multistranded copper conductor 1100 volts grade IS-694 marked , drawn through existing steel/PVC conceiled conduit of size 25mm dia with all fittings accessories complete all as specified and as directed.
M&L for submain wiring of two runs of 6 Sqmm size for main cable and one run of 6 Sqmm size earth continuity conductor of single core PVC insulated but unsheathed FRLS cable of specified size multistranded copper conductor 1100 volts grade IS-694 marked , drawn through existing steel/PVC conceiled conduit of size 25mm dia with all fittings accessories.all as directed
M&L for submain wiring of two runs of 10 Sqmm size for main cable and one run of 10 Sqmm size earth continuity conductor of single core PVC insulated but unsheathed FRLS cable of specified size multistranded copper conductor 1100 volts grade IS-694 marked , drawn through existing steel/PVC conceiled conduit of size 25mm dia with all fittings accessories complete all as specified and as directed. Notes for Srl item Nos.22 to 24 :- (i) New conduit of suitable size with connected fitting will be laid if there is a burnt/blockage/damage to the existing conduit including bends/elbows/tees/Junction boxes including making good to disturbed surface finished with the adjoining surface of disturbed area and the rates are inclusive of quoted rates. (ii) The rate for taking down existing submain wiring is including under respective items.
Taking down of ceiling fan/ exhaust fan/ wall fan dismantling of blades, transportation to work shop and carrying out rewinding, transportation to site, reinstallation and testing complete all as specified and as directed. Note:- Rewinding will be measured and paid under respective item of this Schedule.
M&L for Rewinding of ceiling fan 1200/1400 mm sweep by dismantling of fan motor cutting and removing of burnt windings, cleaning, winding with supper enameled copper wire of superior quality, same gauge of wire, same Nos of turns, provn of insulation paper applying of varnish drying of varnish and assembling of fan including replacement gun metal bush, shaft and ball bearing where ever required complete all as specified and as directed. Note:- The rate quoted by the tenderer are deemed to be included for taking down of old unserviceable part and refixing new parts. However these parts shall be measured and paid seperately as "Supply ony".
All as per Srl item No.26 above, but exhaust fan/wall fan upto 450 mm sweep.
Supply only Gun metal bush for fans complete all as specified and as directed.
Supply only Ball bearing of suitable size & model for ceiling/Exhaust fan complete all as specified and as directed.
Supply only Exhaust fan iron blades for size 225/300/450 mm sweep as per sample complete all as specified and as directed.
Supply only motor of exhaust/fresh air fans of 225/300 mm swipe size, heavy duty, duly painted with one coat of paint of suitable colour complete all as specified and as directed.
Supply only motor of exhaust/fresh air fans of 450 mm swipe size, heavy duty, duly painted with one coat of paint of suitable colour complete all as specified and as directed.
Supply only metal frame of exhaust/fresh air fans of 225/300/450 mm swipe size, heavy duty duly painted with one coat of synthetic enamel paint of suitable colour complete all as specified and as directed.
S&F in repairs Exhaust fan Louvers 225/300/450 mm Size, MS, including taking out old louvers complete all as specified and as directed.
S&F in repairs ceiling fan holder hook with rubber real suitable for size 1200/1400 mm ceiling fan as per sample complete all as specified and as directed.
S&F in repairs PVC canopy for ceiling fan of size 1200/1400 mm as per sample complete all as specified and as directed.
S&F in repairs plug top 20 Amps complete all as specified and as directed.
S&F in repairs single pole and neutral metal clad sheet steel enclosures with 2 pin and earth plug and socket complete with one no MCB SP upto 20 Amps as per site requirement of existing type complete all as specified and as directed.
S&F in repairs MCB DB SPN 4 Way double door type,(IP 43 Protection) flush mounting complete all as specified and as directed.
S&F in repairs MCB DB SPN 8 Way double door type,(IP 43 Protection) flush mounting complete all as specified and as directed.
S&F in repairs MCCB 3 Pole 415V, Adjustable type, 100 Amps with breaking capacity 16 KA complete all as specified and as directed.
S&F in repairs MCCB 3 pole, 415V, Adjustable type,125 amps with breaking capacity 16 KA complete all as specified and as directed.
S&F in repairs MCCB 3 pole 250 Amps 36 KA 415 Volts with breaking capacity 36 KA, in replacement complete all as specified and as directed.
S&F in repairs Recessed mounting 36 Watt 2'x2' flat LED panel fitting luminaire to enhance the delight of occupants with comfortable experience through its classic design and glare & flicker free illumination. White powder coated CRCA housing with seamless front frame with flat non-yellowish diffuser to fix in existing POP including cutting/grouting of existing POP and get electrically connected the fitting with switch board for suitable size of PVC copper wire complete all as specified and as directed.
S&F in repairs for MCB SP 06 to 32 Amps 240 Volts, 10 KA, `C' curve, all as per site requirement and complete all as specified and as directed.
S&F in repairs for MCB SPN 40 Amps, 240 Volts, 10 KA, `C' curve all as per site requirement and complete all as specified and as directed.
S&F in repairs for MCB SPN 63 Amps, 240 Volts, 10 KA, `C' curve all as per site requirement and complete all as specified and as directed.
S&F in repairs MCB TPN/ Isolator 4P from 63 Amps 415 volts, 'C' Series 10 KA as per site requirement and complete all as specified and as directed.
S&F in repairs MCB TP 3 Pole from 40 Amps 415 volts, 'C' Series 10 KA as per site requirement and complete all as specified and as directed.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors etc. complete all as specified and as directed.
M&L for point wiring complete, stranded copper conductor 1.5 Sqmm nominal area PVC insulated FRLS 1100 volts grade electrical cable in but with through existing concealed PVC/ MS conduit and including replacement of unserviceable pressed steel terminal boxes of required size with top cover 3 mm thick plastic/laminated sheet of required color with screwed and cup washer with all accessories including 1.5 sqmm stranded copper conductor PVC unsheathed cable earth wire to common earth and connected to earth dolly complete all as specified for One light/Fan/Bell point controlled by one switch 5 Amps one way using cable (1.5 Sq mm for phase and neutral and 1.5 sqmm for earthing) and making good to disturbed surface of walls including necessary touch up with adjoining surface of disturbed area i.e with OBD/colour work/white wash as existing finishes complete all as specified and as directed. Note :- In existing conduit wiring new conduit will be added where there is a burnt/blokage/damage to the existing conduit including bends/elbows/tees/Junction boxes.
All as per Srl item No. 51 above, but One light / fan/bell point controlled by one switch SP, one way, 230 volts.
All as per Srl item No. 51 above, but One 3 pin socket outlet 5/6 Amps on same board.
All as per Srl item No. 51 above, but One socket outlet 5/6 Amps on independent board.
All as per Srl item No. 51 above, but One power socket 15/16 Amp but with cable 2.5 Sqmm for phase & neutral and for earth 2.5 sqmm.
S&F distribution board vertical triple pole and neutral 4 way, double door for fixing MCCB upto 125 Amps as incommer and MCBs as out goings with metal door and IP 43 Protections and connecting in replacement complete all as specified and as directed.
S&F in repairs MS fastner bolt 8mm dia and 100mm (Min.) for fixing Exhaust fan/Bldg security light etc. with nut and washer complete all as specified and as directed.
Taking down geyser 25/50 ltrs capacity of any make, opening up complete for inspection descalling by chemical treatment of internal tank, themrostate pipe, base plate assembly carrying out minor repairs including replacement of gaskets testing and refixing in position including making electrical and water connection complete all as specified and as directed. Note : Old defective spare parts shall be replaced with new one and measured and paid seperately here-in-after under respective item & catered as "Supply only".
Supply only heating element 1.5 KW for any make of geyser of 25 litres capacity as per sample complete all as specified and as directed. Make:- Micronking/Theeta/Standard
Supply only heating element 2 KW for any make of geyser of 50 litres capacity as per sample complete all as specified and as directed. Make:- Micronking/Theeta/Standard
Supply only thermostat for 25/50 ltrs capacity geysers complete all as specified and as directed. Make:- Micronking/Theeta/Standard
Supply only indicating lamp round / flat type as required in replacement for geyser 25/ 50 litres capacity as per sample complete all as specified and as directed.
Supply only safety valve ISI marked for geyser 25/50 litres capacity in replacement as per sample complete all as specified and as directed.
Supply only safety plug for geyser 25/50 litres capacity in replacement as per sample complete all as specified and as directed.
Supply only PVC connection with brass nipple 15 mm x 450 mm long in replacement for geyser 25/50 ltrs capacity as per sample complete all as specified and as directed.
Supply only base plate geyser syphon assembly set complete with inlet, outlet and thermostat pipe including rubber gasket in replacement for any make of geyser of 25 litres cap as per sample complete all as specified and as directed.
Supply only base plate geyser syphon assembly set complete with inlet, outlet and thermostat pipe including rubber gasket in replacement for any make of geyser of 50 litres cap as per sample complete all as specified and as directed.
Supply only 25 Ltr inner stainless steel tank suitable for 25 Ltr storage water heater complete all as specified and as directed.
Supply only 50 Ltr inner stainless steel tank suitable for 50 Ltr storage water heater complete all as specified and as directed.
M&L for welding/brazing the inner shell made out of stainless steel /copper sheet for geyser 25/50 ltrs capacity of any make and make the shell water tight including testing complete all as specified and as directed. Note:-Taking down, de-scaling, replacement of rubber gasket and any minior repair involved will be mesured and paid seperatly.
Supply only rubber gasket for water heater storage type of any capacity fixed and suitable as per the existing complete all as specified and as directed.
Supply only Top & Bottom cover body suitable for 25 Ltrs storage water storage heater made of MS sheet as per site requirement complete all as specified and as directed.
Supply only Top & Bottom cover body suitable for 50 Ltrs storage water storage heater made of MS sheet as per site requirement complete all as specified and as directed.
Comprehensive maintenance of desert cooler of any type and any make, fixed at different location at Dundahera mil stn and manesar army camp including taking down, cleaning all dirt, dust, oiling of motor and pump, checking of parts, including replacement of nuts bolt, screw etc and preparation of the desert cooler body and tank by scrubbing the old paint and spray painting with two coats of synthetic enamel paint complete all as specified and as directed. Note : Old unserviceable parts shall be replaced with new one and these parts shall be measured and paid seperately under respective item catered here-in-after as "S&F in repairs".
S&F in repairs 18 inch mounting frame including 3 sets of side Panels made with 2mm thick MS sheet as per existing size/Model and as per sample for desert cooler complete all as specified and as directed.
S&F in repairs blade of 18 inch sweep suitable for desert coolers complete all as specified and as directed.
S&F in repairs operating kit for 18 inch desert cooler complete all as specified and as directed.
S&F in repairs fan mounting bracket set as required for desert cooler complete all as specified and as directed.
S&F in repairs water lifting pump,single phase suitable for desert coolers complete all as specified and as directed.
S&F in repairs cooler fan motor 1/7 HP or any Hp as per site requirement 230 volt,50Hz cycles AC complete all as specified and as directed.
S&F in repairs capacitor, 4 mfd rating complete all as specified and as directed.
S&F in repairs wood wool pad (set of 3) suitable for 18 inch sweep desert cooler of good quality complete all as specified and as directed.
M&L for refilling of gas in 1.5 Ton AC including necessary arrangement for gas filling.R-22 complete all as specified and as directed.
M&L for refilling of gas in 320 ltr capacity Deep Frzeer including necessary arrangement for gas filling. R-134A complete all as specified and as directed.
S&F in repairs compressor for deep freezer of capacity 320 ltr complete all as specified and as directed. Make:-Godrej/LG/Tecumseh.
Note :- The contract sum shall be after deducting the amount of credit shown in Sch of Credit of this tender
Vijeta Solutions
P R Constructions
Chaudhary Constructions
NAVYUG VYAPARI
MOHIT ENTERPRISES
DHAIRYAE ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .