| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.8 LAccepted-AOC 601 603 EROS APARTMENT 56 NEHRU PLACE NEW DELHI 110019 | NEW DELHI | NEW DELHI | DELHI | 110019 | ₹31.8 L | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹42.8 L+₹11.0 L (34.6%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | ₹42.8 L+₹11.0 L (34.6%) | L2 | Rejected-Finance Higher quoted amount. |
| 3 | Rejected-Technical | - | - | Rejected-Technical No shortfall documents submitted for fulfilling NIT requirement |
| 4 | Rejected-Technical P 27 1 RASHTRAGURU AVENUE DUM DUM KOLKATA 700028 | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | - | - | Rejected-Technical No shortfall documents submitted for fulfilling NIT requirement |
Tender Value
₹38.8 L
Closing Date
22 Nov 2021, 5:30 pmClosed
SR. Manager (Engg-E)
AAI, Bagdogra Airport
Internal Electrification for Airlines Counter Shifting at Cityside and security offices at Terminal Building at Bagdogra Airport. SH SITC of FADS System in existing area of terminal building.
2021_AAI_94578_1
AAI/BD/CW/2021-22/NIT/02/157
Open Tender
Electrical Works
Item Rate
90 days
Bagdogra Airport
As Per NIT
2 documents required · 2 mandatory
₹1,180
Exempted
11 Jul 2022
12 Nov 2021
23 Nov 2021
13 Nov 2021
22 Nov 2021
13 Nov 2021
13 Nov 2021 - 16 Nov 2021
Amount
Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable multi criteria detector {Smoke + heat } with unique optical sensing chamber, visible LED, fully coated circuit board, superior RF / Transient protection suitable for 2 wires loop connection, complete with plug into common separate base & housing constructed of LEXAN (or polycarbonate) complete with connections etc. as required and to be installed below / above false ceiling roof and concealed space and as per enclosed specifications, compatible for existing installed FAD Panel ,complete as required. (Cost of plug in common base shall deemed to be included in cost of detectors)
Supply, installation, testing and commissioning of UL / EN listed (Latest Version) intelligent Addressable type Heat Detector (Fixed cum-rate of rise type) with max. triggering temperature programable from 58 degree C to 69 degree C complete with all fixing accessories like base, base box, self adhesive sticker indicating loop number and address etc. to be installed below / above false ceiling, roof and concealed space, etc. interconnecting to loop cable, etc. as per specification,compatible for existing installed FAD Panel, complete as required.
Supply, Installation, Testing & commissioning of UL / EN listed (latest version) intelligent addressable Manual call station (Resetable pull / push type) suitable for semi flush mounting, IP 54 for indoor use & IP 65 for outdoor use with double gang outlet box, equipment for key operated test-reset lock, electronic or rotary switches for address setting. Manual pull station shall be connected with two wire to SLC loop of Fire Control Panel. Cover shall be made out of LEXAN (or poly carbonate equivalent) with clear operating instruction and the word Fire appearing on the front complete with connections etc. as required and as per enclosed specifications,compatible for existing installed FAD Panel.
Supply, installation, testing and commissioning of UL / EN listed (latest version) loop powered addressable Hooter-cum- strobe with adjustable sound level in the range of min. 90 db to Max. 120 db at 1M distance complete with termination etc. as required and as per enclosed specification,compatible for existing installed FAD Panel.
Supply installation testing and commissioning of Card cage compatible for expansion in existing FAD system.
Supply, installation, testing and commissioning of UL / EN listed (Latest Version) Response Indicators for getting fire indications of detectors i/c mounting boxes installed above false ceiling area interconnecting to loop cable etc. as per specification complete as required.
Supply, installation, testing and commissioning of UL / EN listed (latest version) Intelligent addressable Control Module/ Relay Module (output module) with inbuilt fault isolator / isolator module for tripping of AHU & Ventilation / pressurisation fans / hooter complete with termination etc. complete as required and as per enclosed specifications.
Supply installation testing and commissioning of UL listed & FM approved LOOP ISOLATOR module suitable for effective fault isolation as applicale to the system.
Providing, installation, testing & commissioning of UL / EN listed (Latest Version) Monitor Module / input module (for monitoring different electrical / mechanical device etc) as per specifications,compatible for existing installed FAD Panel.
Supply, Installation, Testing & Commissioning of Graphic User Interface (GUI) / Operator work station with PC having Intel Pentium I7 Processor/ similar AMD processsor including Serial ports (RS232) and USB ports and following accessories etc. complete with software all as specified),compatible for existing installed FAD Panel: a. 4 Gigabytes of RAM memory b. 2 TB of hard disk space c. DVD ROM d. 32' LED colour Monitor e. Mouse with Mouse Pad f. Standard Key Board g. Latest Windows Operating System h. Compatible Fire Alarm System Control Software i. Laser Printer colour A4- 1 No j. Software for Automatic Fire Detection and Alarm System k. UPS 800 VA or better
Supply installation testing and commissioning of Device Loop Card compatible with existing installed FAD system for expansion.
Supply installation testing and commissioning of network interface card for management stations(/PC) compatible with existing installed FAD system .
Supply installation testing and commissioning of network interface card compatible with existing installed FAD system for expansion.
Supply installation of Detector Mounting 4" x 4" Junction Box
Supplying & laying of 2 x 1.5 sqmm FRLSZH armoured cable, 600 / 1000V rated with annealed copper conductor as per applicable IS standared complete as required.
Supply installation testing and commissioning of Power Supply Unit for Hooter
GLYPTIC
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .