Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.6 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹26.3 L+₹69,561.40 (2.72%)Rejected-Finance BORBHETA JAIL ROAD NEW CHRISTIAN PATTY JAIL ROAD JORHAT ASSAM 785001 | JORHAT | ASSAM | 785001 | L2 | Rejected-Finance NOT THE LOWEST BIDDER | |
| 3 | L3₹30.2 L+₹4.6 L (18.2%)Rejected-Finance ROWRIAH KB ROAD PO CHALIHA JORHAT 785004 ASSAM | JORHAT | JORHAT | ASSAM | 785004 | L3 | Rejected-Finance NOT THE LOWEST BIDDER | |
| 4 | Rejected-Technical | - | Rejected-Technical NOT MEETING THE ELIGIBLE CRITERIA |
Tender Value
₹27 L
EMD Value
₹54,000
Closing Date
27 Feb 2024, 6:00 pmClosed
CWE DINJAN
COMMANDER WORKS ENGINEERS DINJAN
SPL REPAIR TO REPLACEMENT OF BER DG SET UNDER MIL STN JORHAT
2023_MES_633098_2
84243E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
GE JORHAT
AS PER TENDER DETAILS
8 documents required · 8 mandatory
₹500
Yes
GE JORHAT
₹54,000
Yes
22 Mar 2024
8 Feb 2024
5 Mar 2024
8 Feb 2024
27 Feb 2024
15 Feb 2024
Amount
Supplying, installing, testing and commissioning silent diesel engine driven generating set 40 kVA /32 kW (prime power), 415 volt, 50 Hz, 3 phase, 4 wire, at 1500 rpm, 0.8 lagging power factor including diesel engine as per IS 10001/10002, alternator as per IS 13364 complete with relay panel and switch gears for automatic starting on main failure, coupling, common base plate, acoustic enclosure, 12 V DC battery, AMF Panel. Exhaust system, foundation etc., sound proof norms as per CPCB norms complete all as specified and as directed. (Note - The quoted rate shall be inclusive of all T&P required for testing and commissioning and preparing suitable foundation as per direction of EIC.)
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
M&L for cutting the road /hard standing and making good disturbed surface by using PCC type C2 (1:3:6) by using 20 mm graded stone aggregate for the fixing the pipe complete all as directed by Engrr-In-Charge.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Supply & spreading in trenches sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
M & L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
ANIL RAI AND COMPANY
M/S DHAR AND DHAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .