Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹91.3 LAccepted-AOC 13 29 304 3RD FLOOR EAST PATEL NAGAR OPP SIDDHARTHA HOTEL NEW DELHI 08 | NEW DELHI | NEW DELHI | DELHI | 110008 | L1 | Accepted-AOC L1 | |
| 2 | L2₹94.9 L+₹3.6 L (3.98%)Rejected-Finance CONGRESS BAZAR PATHANKOT 145 001 PUNJAB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance NOT BEING LOWEST BIDDER | |
| 3 | L3₹1.0 Cr+₹10.0 L (10.9%)Rejected-Finance 67 A HAFIZALI BAHADUR KHAN MARG SURAJI COMPOUND BEHIND KHATAU MILL BYCULLA W MUMBAI 400011 BRITE INDUSTRIES 67 A HAFIZALI BAHADUR KHAN MARG SURYAJI COMPOUND BEHIND KHATAU MILL MUMBAI | MUMBAI | MAHARASHTRA | 400011 | L3 | Rejected-Finance NOT BEING LOWEST BIDDER | |
| 4 | L4₹1.0 Cr+₹12.1 L (13.3%)Rejected-Finance 12 BHARTI AARTIST COLONY VIKAS MARG NEW DELHI 110092 | EAST | DELHI | 110092 | L4 | Rejected-Finance NOT BEING LOWEST BIDDER | |
| 5 | L5₹1.1 Cr+₹18.6 L (20.4%)Rejected-Finance 131 SANGAM NAGAR OPP NATIONAL SCHOOL SANGHVI PUNE 411027 | PUNE | MAHARASHTRA | 411027 | L5 | Rejected-Finance NOT BEING LOWEST BIDDER |
Tender Value
₹84.6 L
EMD Value
₹1.5 L
Closing Date
9 Nov 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CHIEF ENGINEER RND SECUNDERABAD
CHIEF ENGINEER RND SECUNDERABAD PICKET OPP JUBILEE BUS STATION SECUNDERABAD 500003
UPGRADATION AND PROVISION OF STANDBY ELECTRIC POWER SUPPLY TO MEMS FACILITY AT RCI HYDERABAD
2023_MES_621426_1
84004
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
RCI HYDERABAD
Class C category b (ii)
7 documents required · 7 mandatory
₹1,000
GARRISON ENGINEER RND RCI HYDERABAD
₹1.5 L
Yes
6 Dec 2023
3 Oct 2023
16 Nov 2023
3 Oct 2023
9 Nov 2023
25 Oct 2023
Amount
Supply installation testing and commissioning of Outdoor silent Diesel Engine driven generating set 415 volts, 625 KVA / 500 KW 3 phase 0.8 power factor 50Hz, 1500 RPM, Liquid Cooled, With all complete connected accessories in all respects for commissioning of the DG Set, with CPCB approved Accoustic enclosure IP 23, self excited, self regulated brushless AC generator installed including accoustic enclosure suitable for ambient condition at Hyderabad including AMF panel and confirming to condition under IS 4722/1460, BS 5514/2613/5000 ISO 8526/3046 with the following . Note: Emission Standards for DG Set (a) The Emission limits of DG Sets upto 800 KW/1000 KVA shall be incorporated as per the latest CPCB norms as published by the Gazette of India New Delhi dated 03 Nov 2022 vide S No 716 Extraordinary Part II Section 3-sub section (i) and emission limits shall come into force from 01 Jul 2023. (b) The emission limits shall be tested through one of the five CPCB approved/recognized labs as mentioned below:- (i) Automotive Research Association of India, Pune (Maharashtra). (ii) International Centre for Automotive Technology, Manesar (Haryana) (iii) Indian Oil Corporation, Research and Development Centre, Faridabad (Haryana). (iv) Indian Institute of Petroleum, Dehradun (Uttarakhand). (v) Vehicle Research Development Establishment, Ahmednagar (Maharashtra). (c) The cost for incorporation of Emission Standards and testing is included in unit rate quoted by the contractor. (d) DG set manufactured prior to 01 Jul 2023 shall not be allowed / acceptable.
Alternator - Standard design alternator, Power Rating 625 KVA/ 500 KW, 3 Phase 4 wire, 415 Volts, 50 HZ, Power factor 0.8(lagging) Current 875 Amps, net output at site after considering derating for per site conditions at 0.8 (lagging) power factor, 1500 RPM, Cooling Liquid cooled, Aspiration Turbo charged, air cooled self regulated screen protected drip proof IP 23 enclosure brushless design with widing in pole faces, insulating class 'H' and voltage regulation of +1% at rated voltage from no load to full load, A1 The alternator shall be conforming to BS 2613/5000 and shall be in position to generate supply with frequency regulation with in +1% tolerance. The alternator will be suitable for tropical climate and shall generally confirm to BS-2613/5000/IS-4722.
Diesel Engine : Adequate capacity Diesel Engine suitable for 625 KVA coupled with alternator and after considering derating as per site conditions after generating and reducing power consumed by accessories, directly coupled through flexible coupling, multi cylinder, multi stroke direct injection, cold starting 1500 RPM, as per relevant ISO 3046 /BS-5514 with an overload capacity of 10% for one hour in 12 hours continous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessoires shall be as under :
Insulation class - 'H' , Temperature rise class - 'H' ,Excitation- Self excited Regulation performance - The voltage is kept constant with + 1%, manual voltage adjustment with in + 5%. , Frequency Regulation + 1% Suitable size & suitable number of runs of UG copper cable (Control cable) from Alternator to AMF & RAW Power to AMF Panel is deemed to be included in quoted rate. (i) Flywheel with housing (ii) Cooling System : Mounted radiator with fan and belts and corrosion inhibitor coolant etc (iii) Cooling Water Pump : Centrifugal type belt driven (iv) Exhaust System : As per CPC-II norms as amended upto date or 3.5M above the adjacent building complete with stacking arrangement by providing steel structure. (v) Starting System :- Electric Self Starter with maintenance free batteries including battery charging alternative belt driven. (vi) Electronic governer type (vii) Electric self starter with reputed make.
(viii) Batteries :- 2x12 Volts DC electrical batteries of suitable 180AH rating, complete connected with copper cable PVC sheathed conductor multistranded leads of suitbale length from self starter to the battery terminals complete with initial charge and initial fill of electrolite all as specified and directed. (ix) Fuel tank of adequate capacity :- As per OEM norms and specifications designed for above capacity of DG Set.
Hooter. Voltage sensing relay. Six window annunciator for fault indications.
Acoustic Enclosure : Enclosure is free standing floor mounted factory built and modular in construction to facilitate easy assembly at work site and will be drop over housing type. It will consist of acoustically treated panel housed in sheet metal will provide easy access for maintenance, repairs and operation. The enclosure is custom to suit conditions, with the following features :- (i) Custom built product for various equipments, will ensure the optimum performance without duration. (ii) 16SWG (1.6mm) thick CRCA sheet to be used for enclosure panel to ensure longer life against weathering action. High quality acoustic insulation materials to be used as per IS 8183 for maximum sound absorption. Acoustic layers are supported by perforated sheets. (iii) Sheet metal component of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action. (iv) Special paint treatment with pure polyster powder/epoxy to be provided for better weather resistance. (v) Well designed ventilation system to be provided to put out the heat from the chamber efficiently. (vi) For effective acoustic/weather sealing a special type weather sealing gaskets, new frame rubber gaskets to be used. (vii) Working space is to be provided around the equipment for easy maintenance/repairs. (viii) Necessary cut out provision for entry and exist of fuel lines cable to be incorported in the enclosure as per the requirement.
(ix) See through transparent window(glass or acrylic) in front of engine panel to be provided for monitoring the operation. (x) Ducting if required, bellows, mechanical hardware like locks, hinge, fasteners etc to be provided. (xi) Deliverables 75DB @ 1 meter at 75% load under free field conditions. The temp inside the enclosure will be with in limit and as per manufacturer's recommendations above ambient temp. (xii) The enclsoure shall be provided with bulk head light fitting for inside illumination. (xiii) The exhaust pipe along with proper aluminium cladding, shall be laid to a height of above the roof level. The rates for the same are to be included in the quoted rate. (xiv) The batteries should be placed inside the enclosure inside the DG Set on a suitable insulated platform. (xv) The DG set should be provided with external emergency stop push button. (xvi) Provn of 2 Nos 11 Watts LED lamp fitting of approved Make including wiring inside canopy with single switch controlled. (xvii) Fuel gauge to be provided with the neck of fuel tank. (xviii) Tools as per manufacturer's with the box. (xix) Invents of suitable company manufacturer. (xix) The acoustic enclosure parts shall be of powder coated after pre treatment process.
(e) Civil Work : All civil works including RCC/ PCC platform 1:3:6 type C2 using 40mm graded stone aggregate and related to foundations and commissioning of Gen Set, The depth of the foundation shall be minimum 300mm with anti vibration pads or as recommended by the manufacturer. The foundation drawing for DG Set shall got be approved by GE before laying of foundation. The Contractor has to obtain approval for RCC/PCC foundation for the DG Set with the manufactures. Rates shall be quoted accordingly with written certificate from the manufacturers for the same.
Supplying, laying, jointing, testing and commissioning 3.5 core 300 sqmm 1100 volts grade, LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 with latest amendments, galvanized steel strip heavy duty, electric cables, with multistranded aluminium conductor laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., all as specified and directed for AMF Panel to main panel Note: Earthwork Excavation, sand cushioning, GI pipe and cable protection will be measured and paid separately.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting out in hard/dense sol complete all as specified and directed.
Returning, filling in , including spreading, levelling, watering and well ramming in layers not exceeding 25cms thick complete all as specified and directed.
Removal of excavated soil to a distance not exceeding 50 mtrs and deposited where directed at a level not exceeding 1.5mtrs above the starting point all as directed.
Supply and spread natural dry river sand for cable cushioning in trenches and punned down all as specified and directed. Note : Punned thickness will be measured for payment.
Supply and lay un reinforced pre cast concrete cable cover class LV type I flat size 250X150mmX40mm all as specified and directed.
M&L for earthing complete with Galvanised steel earth plate electrode 60cm x 60cm x 6mm, buried directly in ground( earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including GI strip 32X6 mm protected with GI light grade pipe 40mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less by means of bolts, nuts, check nuts and washers all shown in electrical plate No 3 (of SSR part-I) connected to earthing test point all as specified or indicated including provision of necessary excavation and earth work of any type of soil, PCC pit , RCC cover, 50mm thick with 8mm dia TMT bar @ 100cm c/c both way , 20mm bore medium grade watering pipe, water funnel, common salt, charcoal dust, returning filling, in of soil, removal of soil to a distance of not exceeding of 50 mtr etc, including testing on completion complete
Supply, installation, testing and commissioning of 11 KV, 630 Amps, extensible, outdoor type (IP-54), fixed type, SF6 insulated RMU (Ring Main Unit) 3 way comprising 01No as incomer and 2 Nos Vaccume circuit breaker as out going inside robotically welded stainless steel 304 (Non Ferrite Non Magnetic grade) tank having minimum thickness 3mm with IP 67 degree of protection and impulse withstand voltage 75 KV, rated power - frequency withstand voltage 28 KV/minute, rated frequency 50 Hz and rated peak current 52.5 KA, rated short time breaking current 21 KA/3 Sec. RMU should be provided with internal bus bars, as well as earthing bus bars of electrolytic grade copper, padlock provisions, inbuilt spring charging handle & complete with all accessories. The RMU shall be type tested for internal arc as per IEC 62271-200. RMU shall have onsite repairability features such as site replaceable bushing / coupling / mechanism and gas filling at site. The earthing bus bar shall be provided inside each cable compartment for solid earthing of cable sheilds. The outer hinged main door should cover entire front of switch gear including cable doors for providing fall safe protection. The unit shall include the following with all necessary standard fittings as required at site complete with PCC foundation work as per manufacturer's instructions / design (Incoming-01 No and outgoing -2 Nos for MEMS and Ground System). Location : Near MEMS 6 pole structure
(A) Incomer : SF6 insulated motorized Breaker module consisting of following accessories : (i) 11 KV, 630 Amps fixed type Vacuum Circuit Breaker module for making and breaking of fault current alongwith disconnector + Earth switch and interlocking facility. (ii) Short time current - 21 KA / 3 Sec, breaking capacity - 50 kA (iii) Auxiliary contacts - 1 NO + 2 NC & Auxilary contact on earth switch is 1 NO+1 NC (iv) Stored energy mechanism with manual / motorized spring charging, associated closing / tripping coils, integrated non removable spring charging operating handle and ON/OFF push buttons mechanically latched to the mechanism. (v) Interlocked, arc proof cable box for front termination of the cable suitable upto 1 R x 3 Core 150 Sqmm, 11 KV XLPE cable with double door arrangement (IP 54 + IP3X & IP 2X) safety interlocked to prevent access to cable termination in live condition.
(vi) Numerical based self powered OC + EF Protection Relay, providing over current (Min setting 20%), Earth Fault (Min setting 10%) (vii) Resin cast, Ring core CTs of suitable capacity for protection (Acc.CI.5P10), 2.5 VA, incomer 400/1 & outgonig with 75/1, installed away from bushings to prevent saturation of core - 1 No. (viii) Potential Transformers with HT fuse on primary side and MCB on secondary side for protection and primary voltage 11000 V3v & secondary voltage 110 V3v with burden windings 5 VA, class of winding 1:10 (ix) Digital multi function meter with Rs-485 port (A, V, kw, KVA, KWh, PF) etc. (x) Suitable site replaceable cable bushings situated not beyond 300mm from cable cover to allow ease of access for installation /testing / replacement purpose. (xi) self interlocking mechanism between doors, earth switch, disconnector and VCB. (xii) Capacitive voltage indication fixed type system. (xiii) Mechanical indications for breaker ON, OFF, EARTH, Spring charged-Discharged (xiv) Mechanical interlock between incomers. (xv) Battery 2 x 12 volts alongwith battery chargers
(B) Outgoing : SF6 insulated motorized Breaker module consisting of following accessories : (i) 11 KV, 630 Amps fixed type Vacuum Circuit Breaker module for making and breaking of fault current alongwith disconnector + Earth switch and interlocking facility. (ii) Short time current - 21 KA / 3 Sec, breaking capacity - 52 kAp (iii) Auxiliary contacts - 1 NO + 1 NC (iv) Stored energy mechanism with manual / motorized spring charging, associated closing / tripping coils, integrated non removable spring charging operating handle and ON/OFF push buttons mechanically latched to the mechanism. (v) Interlocked, arc proof cable box for front termination of the cable suitable upto 1 R x 3 Core 120 Sqmm, 11 KV XLPE cable with double door arrangement (IP 54 + IP3X) safety interlocked to prevent access to cable termination in live condition. (vi) Emergency trip push Button
Supplying, laying, jointing, testing and commissioning 11000 volts grade, Earthed, HT XLPE insulated, insulation screened with extruded semi-conducting compound in combination with copper tape (0.3 KA for one second), cores laid up, PVC inner sheath with fillers, galvanized steel flat strip armoured, heavy duty, electric cables, with multistranded aluminium conductor, conductor screen with extruded semi conducting compound and overall PVC sheathed cable as per IS-7098 (Part-2) 1988 with latest amendments, laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., complete all as specified and directed for the 3 Core 150 Sqmm Note : Earthwork Excavation, sand cushioning, GI pipe and cable protection will be measured and paid separately.
Supply and fix cable jointing kit for 11 KV (Earthed) grade Out door cable for heat shrink type End Joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 150 Sqmm complete all as specified and directed.
Disconnecting the electrical supply and removing the incoming and outgoing cables from the existing 4 Pole structure and connected to the proposed RMU within the same yard complete all as specified and directed.
Shekhar Enterprises
BRITE INDUSTRIES
Vijaypower Generators Limited
LEO ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .