Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.5 LAccepted-AOC 1 OPP NAGAR NIGAM KATNI MAIN ROAD KATNI MADHYA PRADESH 483501 | KATNI | MADHYA PRADESH | 483501 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹20.3 L+₹2.4 L (13.4%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹28.0 L+₹10.1 L (56.1%)Rejected-Finance | L3 | Rejected-Finance NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
8 Jan 2022, 6:00 pmClosed
CWE (AF) TUGHLAKABAD
HQ CWE (AF) TUGHLAKABAD
REPAIR/MAINT OF DG SET, VOLTAGE STABILIZER, SLIDING DOOR, LIFT ROLLING SHUTTERS AND COMPRESSOR AND OTHER MISC E/M WORKS AT AF STN TUGHLAKABAD UNDER GE (AF) TUGHLAKABAD
2021_MES_489718_2
CA NO. CWE/TKD/TOKEN-53/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) TUGHLAKABAD
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (AF) TUGHLAKABAD
₹60,000
Yes
5 Feb 2022
21 Dec 2021
10 Jan 2022
21 Dec 2021
8 Jan 2022
27 Dec 2021
Amount
Servicing of standby DG Set of capacity upto 50 KVA complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel,draining out engine oil from the sump, cleaning the sump thoroughly and replacement of all unserviceable spare parts complete all as specified in repairing manual of DG set and as directed by Engr-in-charge. Make – Kirloskar/ Crompton Greaves/ Cummins. Note:-(i) Load & record shall be made in respect of RPM , oil pressure, oil temp, Coolant temp,Voltage, frequency , load current ,Battery charging , fuel consumption etc. as directed by the Engr- in- charge. (ii) Fuel filter, lubericating filter, air filter, distill water,Engine oil, brass connector, hose pipe set and other unserviceable spare parts shall be measured and paid Separately. (iii) Coolant for make up shall be measured & paid separately (iv) DHPP will be issued by dept for testing only.
All as per srl item no.1 but of capcity above 50 KVA and upto 100 KVA DG set
All as per srl item no.1 but of capcity above 100 KVA and upto 180 KVA DG set
Supply only Diesel fuel filter suitable for DG set of capacity upto 180 KVA complete all as specified and directed .Make:- Kirloskar / crompton Greaves/ cummins.
Supply only Lubricating filter suitable for DG set of capacity upto 180 KVA complete all as specified and directed.Make:- Kirloskar / crompton Greaves/ cummins.
Supply only air cleaner/ filter catridge suitable for DG set of capacity upto 180 KVA complete all as specified and directed.Make:- Kirloskar / crompton Greaves/ cummins.
Supply only brass terminal for batteries all as specified and directed by Engr-in-charge.
Supply only Hose pipe set suitable for DG set of capacity upto 50KVA complete all as specified and directed by Engr-in-charge.
All as per srl item No.8 here-in-before but of capcity above 50 KVA and upto 100 KVA DG set
All as per srl item No.8 here-in-before but of capcity above 100 KVA and upto 180 KVA DG set
S&F in replacement of door lock of acoustic enclosure suitable for capacity 30 KVA to 180 KVA complete all as specified and directed by Engr-in-charge.
Supply only lubricating oil 20W40 for DG Sets as per manufacturer's recommendation.Make - IOC/ Castrol/Hindustan Petroleum.
Supply and filling coolant for Radiator as per manufacturer's recommendations.
S&F in replacement of unserviceable water pump assembly rating upto 100KVA DG set all as specified and directed by Engr-in-charge.
S&F in replacement of unserviceable water pump assembly rating upto 320KVA DG set all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of Engine safety unit (ESU) for DG set of capacity upto 180 KVA complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of unserviceable VAF meter including taking down unsv complete all as specified and directed by Engr-in-charge. Make:- Nippon or equivalent as approved by GE.
Supply and fixing in replacement of oil sensor including taking down unsv complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of unserviceable water line socket for DG Set capacity upto 180 KVA including taking down unsv complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of unserviceable Turbo charger kit upto 180 KVA DG set complete all as specified and directed by Engr-in-charge.
Servicing of radiator assembly by removing from engine transporting to the workshop and removing the sediments and scales, corrosion etc by means of acid cleaning and high pressure water washing and air cleaning, gas welding / soldering with good quality material for stopping the leakage etc, re-assembling the same with new gaskets testing for leakage again and transporting to the site, fixing to the engine with new clips complete all as required for upto 63 KVA DG Set complete all as specified and directed by Engr-in-charge.
All as per srl item No.21 here in before but capacity above 63 KVA and upto 180 KVA DG set.
Taking down unserviceable RPM Meter & supply & fixing New digital RPM Meter on DG Set complete all as specified and directed by Engr-in-charge Make:- Nippon or equivalent as approved by GE.
Supply & fix in replacement of PVC insulated with standard copper conductor cable 2 mtrs length each soldered with 2 Nos gun metal battery terminals suitable for 180 AH 240 volts DC battery complete all as specified and directed
Supply only distilled water in five litre container
Supply only sulphuric acid for lead acid battary in one litre container.
M&L for servicing of self starter assembly of DG Set 24 volts by disconnecing the self starter from the engine and transport to workshop for carryout servicing by replacing all unserviceable spare parts including pinion, armature, carbon brushes, commutator, field coil, bushes, contacts, copper plates, jumping leads ets and replacing the filled coil and varnishing complete all as directed and specified by Engr-in-charge.
Dismantling existing fuel injection pump of DG set of capacity from 30KVA to 180 KVA, transporting to work shop and servicing complete including replacement of plunger, spring,nozzle assembly ,calibrating and re-fixing the same and testing the DG Set to the entire satisfaction of Engineer-in-charge.
S&F in replacement of old/unserviceable submain wiring of any size and capacity with 4 sqmm FRLS copper conductor sub main wiring with 02 runs of 4 sqmm and 01 one of 4 sqmm copper conductor from push button to boom barrier mechanizm both left and right side complete including steel regid conduit for size 25mm dia medium grade including cutting of road/hardstanding as per site requirement complete all as specified and as directed by Engr-in-charge. Make: Finolex/Havells/Plaza
S&F in replacement of old/unserviceable submain wiring of any size and capacity with 6 sqmm FRLS copper conductor sub main wiring with 02 runs of 6 sqmm and 01 one of 6 sqmm copper conductor from push button to boom barrier mechanizm both left and right side complete including steel regid conduit for size 25mm dia medium grade including cutting of road/hardstanding as per site requirement complete all as specified and as directed by Engr-in-charge. Make: Finolex/Havells/Plaza
Dismantling Old unsv oil pressure gauge of DG set, supply and fixing new oil pressure gauge suitable for DG Set of capacity upto 180 KVA complete all as specified and directed by Engr-in-Charge.
Supply and fxing in replacement of PCB control card suitable for operation of Boom barrier upto 3mtr length complete all as specified and as directed by Engr-in-charge
S&F in replacement of old/unserviceable aluminium/copper conductor of any size and capacity with 2.5 sqmm FRLS copper conductor sub main wiring with 02 runs of 2.5 sqmm and 01 one of 2.5 sqmm copper conductor from Push button to Boom barrier mechanizm both Left and right side complete including steel regid conduit for size 25mm dia medium grade including cutting of road/hardstanding as per site requirement complete all as specified and as directed. Make of cable : Finolex/Kalinga/Havells/Plaza
Supply and fixing in replacement of MCB 4A, single pole ,240V C curve, bearking capacity, Icu 10 KA, degree of protection IP 20, frequancy 50 Hz , including taking down old unsv complete all as specified and directed.Make:- L&T/ C&S/ Schneider/Havells
Supply and fixing in replacement of MCB 4A, Double pole ,240V C curve, bearking capacity, Icu 10 KA, degree of protection IP 20, frequancy 50 Hz , including taking down old unsv complete all as specified and directed by Engr-in-charge.Make:- L&T/ C&S/ Schneider/Havells
Supply and fixing in replacement of MCB 6A, single pole ,240V C curve, bearking capacity, Icu 10 KA, degree of protection IP 20, frequancy 50 Hz , including taking down old unsv complete all as specified and directed. Make:- L&T/ C&S/ Schneider/Havells
Supply and fixing in replacement of MCB 16A, single pole ,240V, C curve, bearking capacity, Icu 10 KA, degree of protection IP 20, frequancy 50 Hz , including taking down old unsv complete all as specified and directed.
Supply and fixing in replacement of MCB 32A, single pole ,240V, C curve, breaking capacity, Icu 10 KA, degree of protection IP 20, frequancy 50 Hz , including taking down old unsv complete all as specified and directed.
S&F in replacement of MCCB 3 pole, 125 Amps with breaking capacity 35/36 KA, 415 volts, adjustable thermal and adjustable magnetic setting, Ics = 75% of Icu, including taking down old unsv MCCB complete all as specified and directed.
S&F in replacement of MCCB 3 pole, 160 Amps with breaking capacity 35/36 KA, 415 volts , adjustable thermal and adjustable magnetic setting, Ics = 75% of Icu, including taking down old unsv MCCB complete all as specified and directed.
S&F in replacement of MCCB 3 pole, 250 Amps with breaking capacity 35/36 KA, 415 volts ,adjustable thermal and fixed magnetic setting, Ics = 100% of ICU, including taking down old unsv MCCB complete all as specified and directed.
S&F in replacement of MCCB 3 pole, 400 Amps with breaking capacity 35/36 KA, 415 volts ,adjustable thermal and fixed magnetic setting, Ics = 100% of Icu, including taking down old unsv MCCB complete all as specified and directed.
Servicing/ reconditioning of 90 AH battery with change electrolyte,cell and all connecting element complete all as specified and directed.
Servicing/ reconditioning of 150/180 AH battery with change electrolyte,cell and all connecting element complete all as specified and directed.
S&F in replacement of on load changeover 4 pole, 200 Amps, 415 volts including taking down old unsv changeover complete all as specified and directed.
S&F in replacement of on load changeover 4 pole, 400 Amps, 415 volts including taking down old unsv changeover complete all as specified and directed.
S&F in replacement of power contactor 4 pole, 150 Amps, 415 volts including taking down old unsv contactor complete all as specified and directed.
S&F in replacement of power contactor 3 pole, 180 Amps, 415 volts including taking down old unsv contactor complete all as specified and directed.
S&F in replacement of power contactor 3 pole, 265 Amps, type MNX, 415 volts including taking down old unsv contactor complete all as specified and directed.
S&F in replacement of Power contactor 3 pole, 650 Amps, type MNX, 415 volts including taking down old unsv contactor complete all as specified and directed.
S&F in replacement of power contactor 3 pole, 9 Amps, type MNX, 415 volts including taking down old unsv contactor complete all as specified and directed.
S&F in replacement of HBC fuse link DIN type of rating 250 Amp 415volt, size 01, breaking capacity 80/100 KA complete all as specified and directed.
S&F in replacement of HBC fuse link DIN type of rating 200 Amp 415volt, size 01, breaking capacity 80/100 KA complete all as specified and directed.
S&F in replacement of HBC fuse link DIN type of rating 400 Amp 415volt, size 02, breaking capacity 80/100 KA complete all as specified and directed.
S&F in replacement of HBC fuse link DIN type of rating 500 Amp 415volt, size 03, breaking capacity 80/100 KA complete all as specified and directed.
S&F in replacement of battery charger in DG set control panel of capacity 24 VDC 10 AMP including taking down old unsv charger complete all as specified and directed.Make:- NHP / Technika or equivalent as approved by GE.
S&F in replacement of battery charger in DG set control panel of capacity 12 VDC 10 AMP including taking down old unsv charger complete all as specified and directed.Make:- NHP or equivalent as approved by GE.
S&F in replacement of Earth leakage relay in DG set of capacity upto 320 KVA control panel including taking down old unsv charger complete all as specified and directed by Engr-in-charger.Make:- Technika or equivalent as approved by GE.
S&F in replacement of under voltage relay in DG set of capacity upto 320 KVA control panel including taking down old unsv charger complete all as specified and directed by Engr-in-charger.Make:- Technika or equivalent as approved by GE.
S&F in replacement of on delay timer in DG set of capacity upto 320 KVA control panel including taking down old unsv charger complete all as specified and directed by Engr-in-charger.Make:- Technika or equivalent as approved by GE.
S&F in replacement of reverse power relay in DG set of capacity upto 320 KVA control panel including taking down old unsv charger complete all as specified and directed by Engr-in-charger.Make:- Technika or equivalent as approved by GE.
Supply, installation, testing and commissioning factory made and tested AMF Panel 82.5/100 KVA with bye pass arrangement for Main & DG both Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system having bus bar chamber with insulated Aluminium bus bars of 200 Amps rating installed on DMC insulators with bus bar chamber. The panel shall be dust and vermin proof, protection class (IP-54) and made of 2.00 mm thick CRCA mild steel sheet and mild steel angle iron frame work (made out of 75 x 6 mm thick), front opening type with aprons for cable entry, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035. The scope of work also comprising of the following:- Make of Panel: Unilac/ L&T/ Tricolite/ Universal Switch Gear Control/ Adlac.
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity upto 10 kVA after disconnecting electrical connections for overall servicing, cleaning of dust and replacement of complete old wiring with FRLS copper conductor of suitable size in proper layout and tight with tie, including replacement of all unserviceable parts i.e Electronic sensing card(PCB), micro processor based panel, potentional meter, RC network with box, 6/12 pin connector, indicator, servo motor or any other parts and fixing complete including testing all as specified and directed by Engr-In-Charge. Note : (a) Replacement of any unserviceable parts will be measured and paid separately under relevant items except replacement of old wiring which are deemed to be includd in the quote rate.
All as per item ser No 63 here-in-above but of capacity above 10 KVA and upto 30 KVA
All as per item ser No 63 here-in-above but of capacity above 30 KVA and upto 50 KVA
All as per item ser No 63 here-in-above but of capacity above 50 KVA and upto 100 KVA
All as per item ser No 63 here-in-above but of capacity above 100 KVA and upto 150 KVA
All as per item ser No 63 here-in-above but of capacity above 150 KVA and upto 200 KVA
All as per item ser No 63 here-in-above but of capacity above 200 KVA and upto 300 KVA
Supply only Electronic sensing/circuit card ( PCB) suitable for servo voltage stabilizers. Make - Vintek Electronics/volina
Supply only servo motor 3 Kg torque suitable for servo voltage stabliser of capacity upto 50 KVA complete all as specified and directed. Make:- Vintec Electronic
Supply only servo motor 10 Kg Torque suitable for servo voltage stablizer of capacity 100 KVA to 300 KVA. Make:- Vintec Electronic/volina
Supply only electronic Sensing / trigger transformer suitable . Make:- Vintec electronic/Volina
Supply only potentiometer suitable for servo voltage stabilizer. Make:- Vintec Electronic/Volina
Supply only voltmeter 0-300V suitable for servo voltage stabilizer. Make AE/L&T
Supply only RC network suitable for 3 kg servo motor complete all as specified and as directed. Make:- Vintec electronic/Volina
Supply only RC network suitable for 10 kg servo motor complete all as specified and as directed. Make Vintec electronic/Volina
Supply only box for RC network complete all as specified and as directed.Make Vintec electronic/Volina
Supply only 6/12 pin as required at site as per capacity of voltage stablilizer complete all as specified and as directed. Make Vintec electronic/Volina
Supply only carbon bush of suitable size upto the capacity of 10 KVA to 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina.
Supply only Indicators of RYB of suitable size upto the capacity of 10 KVA to 300 KVA voltage stabilizer complete all as specified and as directed. Make Vintec electronic/volina
Supply only PCB holder suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Supply only rotary switch 5 Amp for R, Y, B phase suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Supply only Microprocessor based control card suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Supply only push button switch suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Supply only auto manual switch suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed.Make:-Vintec electronic/Volina
Supply only DPDT switch suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Supply only micro switch suitable for servo voltage stabliser upto 300 KVA complete all as specified and as directed. Make Vintec electronic/Volina
Material & labour for rewinding of Main Transformers with existing guage material suitable for servo voltage stabilizers of capacity 10 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of Main Transformers with existing guage material suitable for servo voltage stabilizers of capacity 30 KVA complete all as specified and as directed. Make- Vintek Electronics/volina
Material & labour for rewinding Main Transformers with existing guage material suitable for servo voltage stabilizers of capacity 50 KVA complete all as specified and as directed.Make- Vintek Electronics/Volina
Material & labour for rewinding of main transformers with existing guage material suitable for servo voltage stabilizers of capacity 100 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of main transformers with existing guage material suitable for servo voltage stabilizers of capacity 150 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of main transformers with existing guage material suitable for servo voltage stabilizers of capacity 200 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of Main Transformers with existing guage material suitable for servo voltage stabilizers of capacity 300 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of Dimmer state (Variac) suitable for servo voltage stabilizers of capacity 10 KVA complete all as specified and as directed. Make- Vintek Electronics/Volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 30 KVA complete. Make- Vintek Electronics/volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 50 KVA complete. Make- Vintek Electronics/Volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 100 KVA complete. Make- Vintek Electronics/Volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 150 KVA complete. Make- Vintek Electronics/Volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 200 KVA complete. Make- Vintek Electronics/Volina
Material & labour for rewinding of dimmer state (Variac) suitable for servo voltage stabilizers of capacity 300 KVA complete. Make- Vintek Electronics/Volina Note: for item 63 to 102 (i) The tenderer shall submit original copy of MOU executed / made with OEM such as M/s VINTEK ELECTRONICS/ VOLINA before the commencement of work . (ii) The repair work of Voltage stabliser shall carried out by experienced technician expert provide by OEM.
Supply and filling transformer oil for top up as required suitable for voltage stabilizer complete all as specified and directed . Make : Power oil /Servo
M&L for preparation of old painted surface of Servo Voltage stabiliser by scrapping / removing old paint , dirt etc, and spray painting with two coats of blue synthetic enamel paint over a coat of primer including writing of MES / SM No of capacity UPTO 150KVA complete all as specified and directed.
Supply & fixing in replacement MCCB 400 Amps 3 pole breaking capasity 35 KA,415 V,ICS=75 % of ICU adjustable type with fastening elements including taking down old unsv MCCB complete all as per existing type and directed.Make:- Havells/ Standard/ Legrand
Supply & fixing in replacement MCCB 100 Amps 3 Pole breaking capacity 16 KA,415 V,ICS=75 % of ICU Adjustable type with fastening elements including taking down old unsv mccb, complete all as per existing type and directed.Make:- Havells/ Standard/ Legrand
Dismantling / taking down existing burnt unsv on-load changeover switch from voltage stabliser, supply and fixing on-load changeover by pass switch 100A, 415 Volts, 4 pole with fastening element complete all as specified and directed. Make: Havells/ Standard/L&T.
Dismantling / taking down existing burnt unsv on-load changeover switch from voltage stabliser, supply and fixing on-load changeover by pass switch 320A, 415 Volts, 4 pole with fastening element complete all as specified and directed. Make: Havells/ Standard/L&T.
Dismantling / taking down existing burnt unsv on-load changeover switch from voltage stabliser, supply and fixing on-load changeover by pass switch 800A, 415 Volts, 4 pole with fastening element complete all as specified and directed. Make: Havells/ Standard/L&T.
Dismantling of unserviceable motor of sliding shutter from the base for cleaning the base of sliding shutter and Supply & fixing in replacement three phase motor of sliding gate powerful with a mximum gate weight capacity 2000 kg, 400 V-3 phase, 5 HP electro mechanical gear motor of sliding gates for industrial hangers up to 2000 kg complete with encoder, control unit 400 V- EVO 2000 T, magnatic limits safe and precise for slowing down in opening and closing, 50 HZ,motor speed 52 rpm, rated power output of motor 500 W, output shaft height 58.5 meter, output torque 26 N-m, noise ≤ 60 db, Duty cycle S 2 15 Minutes, limit switches, enviremental temperature -20 degrre C to + 40 Degree C, gate move speed 12 m/min for horizontal rack and pinion including remote transmitter comlete with fixing plate and fixing screws in and including fabrication/welding work for proper alignment of rack and pinion of motor installed complete in every respect completeall as specified and directed. Make telcoma EVO2000 T
M&L for taking out old unserviceable motor and inbuilt gear assy of spike barrier from site and fixing new motor of capacity 750 Watt single phase 230 Volt and inbuilt gear assy and making all electrical connection and spike barrier made serviceable including serviceing , cleaning , greasing of shaft complete and making serviceable condition inlcuiding testing complete all as specified and directed. Note : (i) cost of any unserviceable parts will be measured and paid seprately under the relavent items (ii) Cost of cutting , welding at site for cleaning, greasing of shaft are to be included in the quoted rate. Make:- RUDHAR/GREY/ OR EQUIVALENT AS APPROVED BY GE.
Supply and fixing in replacement of motor having capacity 750 watt single phase, 230 Volt AC and inbuilt gear assy with programing controller suitable to operate the existing system complete for smooth operation of spike barrier complete all as specified and as directed. Make:- RUDHAR/GREY/ OR EQUIVALENT AS APPROVED BY GE.
Supply and fixing in replacement of bearing of size 63/11 2Z complete all as specified and as directed.Make SKF
Supply and fixing in replacement of housing for bearing of size 63/11 2Z complete all as specified and as directed.
Supply and fixing concealed in replacement of key switch for motorised shutter as per sample provided complete including making connection and good distubed surface nearby the key switch complete all as specified and directed.
Supply and fixing in replacement of PCB card and relay compatible with side gear motor of make- ELERO suitable for motoriszed shutter as per sample provided by the department complete including making connection complete all as specified and directed.
Material & labour for locating the fault in goods lift Make : ECE, capapcity - 1088 Kg installed at PW-IV including rectification of defects , checking and rectifying loose connection of control panel, accessories etc including replacement of any unserviceable parts to keep the lift functional and making the free movement of entire unit as directed. Note : (a) Replacement of any unserviceable parts will be measured and paid separatly under relevant items (b) If complaint not attend within 24 hrs , penalty shall be charged @ 4 times of the quoted rate of the contractor
Supply and fixing in replacement of door sensor suitable for existing lift and conforming to relevant IS complete all as specified and directed.Note:- Contractor shall submit test certificate from the manufacturer before execution the same.
Supply and fixing in replacement of PCB card suitable for lift controller as per exisitng complete all as specified and direted.
'Supply and fixing in replacement of step down transformer 415/110V of capacity AC 350 VA for goods lift complete all as specified and direcetd.
Supply and fixing in replacement of limit switch suitable for existing lift complete all as specified and directed.
Supply & fixing in replacement of read switch suitable for existing lift complete all as specified and directed.
M&L for servicing of goods lift Make : ECE, Capapcity - 1088 Kg installed at PW-IV. The following work will be done in servicing :- (a) Cleaning of Lift room , Lift chamber , Lift (Inside and top of the lift) complete. (b) Oiling and greasing of concerned parts of lift with ISI marked oil and grease complete. (c) Checking of complete lift for smooth functioning and maintain the register sign by MES rep complete all as specified and as directed. Note :(a) If the lift is laying unserviceable for more than 24 Hrs due to any major fault the contractor will not claim the same item till the lift are made serviceable. (b) If complaint not attend within 24 hrs , penalty shall be charged @ 4 times of the quoted rate of the contractor
M&L for dismantling of unserviceable electronic boom barrier for carrying out necessary repair of movement mechanism, gear assembly and motor or any other unserviceable parts (i.e control PCB card, inbuilt motor, push button, Boom upto 3mtr length , including cleaning, greasing , painting of booms of 03 mtrs (02 Nos) or 06 Mtr (01 Nos) of existing color with synthetic enamel paint as per site and servicing complete including refixing and testing the same after repair complete all as specified and directed.Make:- RUDHAR/GREY/ or equivalent approved by GE Note : (i) Cost of any unserviceable parts (as mentioned above ) are paid separately under the relevant items (ii) New items shall match with the existing system in any cases for proper fitment. (iii) Any minor adjustment/modification for fixing the item if required at site contractor shall carry out at site without any extra cost (iv) Due to security reason contractor will attend the complaint within 24 Hrs from the date of complaint lodge by user as per their complaint chart or as informed by the works section/MES rep and rectified the same at the earliest.
Supply and fxing in replacement of PCB control card suitable for operation of boom barrier upto 3mtr length complete all as per site requirement and specified. Make:- RUDHAR/GREY/ or equivalent as approved by GE
Supply and fxing in replacement of motor 750W suitable for operation of boom barrier upto 3mtr length complete all as specified and as directed by Engr-in-charge Make:- RUDHAR/GREY/ or equivalent as approved by GE
M&L for taking down old unserviceable side gear motor of motorised shutter from site before diconnecting all incoming and outgoing connection and deposit to MES Store yard complete all as specified and directed.
Supply and fixing side gear motor of ELERO suitable for up and down movement of motorised shutter including other necessary accessories DFM 350 NHK , 3 Phase complete all as specified and directed.Make:-ELERO/ ACM / OR equivalent as approved by GE
Supply and fixing VVF drive of capacity 15 HP, 415 V 50 cycle including taking down old unsv drive complete all as specified and directed.
Supply and fixing in replacement of door lift master ( for 4 panel 1500 mm center opening car door mechanism with motor drive, with a door sill) complete all as specified and directed.
Supply and fixing in replacement of lift door shoe complete all as specified and directed.
Supply and fixing in replacement of lift channel guide complete all as specified and directed.
Dismantling of unserviceable UPS of 20 KVA,designed for output 400 Volt, make APLEB by opening its cover by unscrew its screw for carrying out necessary inspection and to find out the fault including cleaning and repair/replacement of unserviiceable parts in and including line syncronisation adjustment,L1 phase DC balance adjustment,L2 phase DC adjutment, PLL mode frequeny adjustment , L1 phase output voltage fine adjustment, L2 phase output voltage fine adjustment,L 3 phase output voltage fine adjustment and L3 phase DC balance adjustment complete all as specified and directed.Replacement of P 3 MC - R card and 3 PVS R 3 (inverter-BYP) sensing control supply in and including taking out of old u/s card(invertor control card ) suitable for 20 KVA UPS complete all as specified and directed. Note: Repair and service will be carry out by only by authorised compnay representative. Make : APLAB/MICROTECK/SUKAM
Dismantling of unserviceable UPS of 30 KVA,designed for output 400 Volt,make APLEB by opening its cover by unscrew its screw for carrying out necessary inspection and to find out the fault including cleaning and repair/replacement of unserviiceable parts in and including line syncronisation adjustment,L1 phase DC balance adjustment,L2 phse DC adjutment, PLL mode frequeny adjustment , L1 phase output voltage fine adjustment, L2 phase output voltage fine adjustment,L 3 phase output voltage fine adjustment and L3 phase DC balance adjustment complete all as specified and directed. Replacement of P 3 M C - R card and 3 PVS R 3 (inverter-BYP) sensing control supply in and including taking out of old u/s card(invertor control card ) suitable for 30 KVA UPS in and including repair of charger card (REC3P) complete all as specified and directed. Note: Repair and service will be carry out by only by authorised compnay representative. Make : APLAB/MICROTECK/SUKAM
S&F in replacement of old/unserviceable aluminium/copper conductor of any size and capacity with 2.5 sqmm FRLS copper conductor sub main wiring with 02 runs of 2.5 sqmm and 01 one of 2.5 sqmm copper conductor from push button to boom barrier mechanizm both left and right side complete including steel rigid conduit for size 25mm dia medium grade including cutting of road/hardstanding as per site requirement and making good disturbed surface complete all as specified and as directed Make:Havells/Plaza/Finolex
M&L for servicing of electric motor of capacity upto 15 HP coupled with compressor having capacity 566 lit per min installed at spyder including disconnecting from air compressor, cleaning, rewiding complete using existing guage material, greasing, insulating paper, varnishing and filling, replacement of bearings,, reassembling the motor etc including testing complete all as specified and as directed.
Servicing of air compressure any type any make coupled with electric motor installed at Spyder including calibration, replacement of release valve upto 40 mm, oil top-up as required at site, replacement of air filter, shaft ,oiling , greasing etc and necessary replacement of wornout bolts ,nuts , washers, gaskets etc .re-assembling the compressure with motor , commissioning and testing to the entire satisfaction of Engineer-in-charge .
M/S S.K.Electricals
Surjit and Sons
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .