| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.0 LAccepted-Finance | L1 | Accepted-Finance Tender accepted by competent authority | |
| 2 | Rejected-Technical B 2 GANGA CLASSIC APPRTMENT KAMTHI ROAD SANATAN DARMSHALA NAGPUR MAHARASHTRA 440004 | 440004 | - | Rejected-Technical Technical Bid Evaluated and rejected |
Tender Value
Refer Docs
EMD Value
₹25,675
Closing Date
31 Oct 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer (E), BSNL ED Mumbai
The Executive Engineer E BSNL Electrical Division 5th Floor A Wing BSNL Admin Bldg Juhu Tara Road Santacruz West Mumbai 400054
One time repair and attending initial defects of 7 nos 7 TR HPAC units at NIB, Fountain, 6nos 7TR HPAC units at MUX Prabhadevi and 4 nos 7 TR HPAC units at MW Kopri
2023_BSNL_170202_1
NIT No 27/EEE/BSNL/ED/MI/2023-24
Open Tender
Electrical Works
Item Rate
30 days
Mumbai
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
AO (F and A ) BSNL
₹25,675
2 Dec 2023
9 Oct 2023
6 Nov 2023
9 Oct 2023
31 Oct 2023
9 Oct 2023
Amount
Arranging visit of technician of authorized by M/s Emerson for inspection and testing of package AC (Model HPAC Model No. GLOBEL PEX2 1030) complete by making Master-slave configuration for sequential running of package A.C. units for equal running hours, communication with each other units for controlling the desired condition with group action, setting of all parameters, etc. by offering testing to BSNL representative etc. as required.
Supplying and Installing of new 7 TR, M/s Copeland, Model: ZR108KCE scroll compressor including removing of old compressor including pumping down refrigerant gas, removing of electrical and control wiring, cutting refrigerant circuit, removing of foundation bolts etc. and installation of new compressor including re-jointing, brazing of refrigerant piping connections, reconnections of electrical and control wiring and fixing it back with nut bolting etc. & making the system same ready for pressure testing etc along with manpower, special tools & plant etc complete as required.
Providing nitrogen pressure testing for detecting of leakage in entire refrigerant circuit / compressor valves & arresting leakage by brazing / or other suitable means etc, vaccumizing & dehydrating entire refrigerant system as per BSNL specification & making the same ready for charging etc along with manpower , special tools & plant etc complete as required.
Supplying and Charging of Refrigerant Gas ( R-407 ) for charging in the existing AC Package unit i/c testing etc as reqd
Supplying and Fixing of following sizes of Liquid Line Filter drier of in the existing AC Package unit i/c testing, Commissioning etc as reqd. (Prabhadevi HPAC Unit No.VI)
7/8" Liquid Line
Supply , Installation of following ratings 4 pole contactor suitable for 415 VAC in existing outdoor condenser panel including connection, testing, commissioning etc. as required.(M/s L&T)
32 Amps ( MCX-03) (Coil Supply 220V)
Repairing of 7 TR single circuit high precision type package type AC unit (M/s Emerson ) by replacing following defective/worn out accessories of approved make i/c pumping down of refrigerant system, fixing, jointing, modification & offering testing to BSNL etc as required.
Electronic Expansion Valve Driver unit (EVD evolution user interface unit without display) of M/s Carel suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
IOC Card controller (ICOM Board) suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
High pressure gas Solenoid valve unit suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030) ( Make : M/s Danfoss)
LP Cut Out Switch for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
HP Cut Out Switch for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030).
Condenser Fan motor with blades and safety grill (outdoor) suitable for three phase,400V,50Hz.AC supply 28'' dia.0.62 KW ,1.7/1.05 A,900/600 RPM.(Make :ZIEHL-ABEGG/Transmonk/SS make))
Condenser Fan axial fan motor with blades and safety grill housing (outdoor) suitable for single phase, 220V, 50Hz.AC supply, 250 W, 1350 RPM. Suitable for 7TR HPAC unit of M/s Stulz, Model: SEC 271A. (Make :ZIEHL-ABEGG/Transmonk/SS make)
Crankcase heater for 7 TR , M/s Copeland, Model : ZR108KCE scroll compressor
Supplying of condenser coil of 7 TR M/s Emerson make HPAC at TE Prabhadevi Mumbai ( 11 th floor ) complete with transportation , loading & unloading by hiring requisite manpower ,tools & plant etc as required ( The following shall be specification of condenser coil. The vendor /supplier may visit the site for actual specification of condenser coil.) i) Overall dimension 1700 (W) x1200 (H) ii) The copper tubes shall be of seamless hard drawn copper pipe inner groove & wall thickness 0.28 mm with 3 rows and header made out of 18 gauge copper pipe, fins thickness of 38 SWG (0.15 mm )
Dismantling of existing deteriorated condenser coil of 7 TR M/s Emerson make HPAC complete with pump down the refrigerant circuit by hiring gas recovery pump at site and storing R 407 gas in System / Gas cylinder, cutting of condenser coil /copper refrigerant pipe by hiring requisite manpower, tools & plant etc as required (Note:- The agency shall take all possible efforts for recovery of R-407 gas to the maximum extent for re-utilization of gas .)
Installation of condenser coil in existing condenser unit including brazing of refrigerant piping connection complete with leak testing of system by filling nitrogen pressure for 24 hours, vacuumizing the system & charging the same with existing refrigerant, trial cum performance run test for 24 hours duration complete with testing and commissioning of HPAC package unit as per BSNL specification etc as required
Providing anti-corrosion nano coating (ULTRACORR ACX) for HPAC coils and condensers for providing a long-lasting corrosion protection of copper and aluminum condenser coils, preventing leakage of gas due to atmospheric and salty /chemical corrosion, complete etc as required
Credit for old 7TR , M/s Copeland make, ZR108KCE Scroll compressor.
Credit for Electronic Expansion Valve Driver unit (EVD evolution user interface unit without display)
Credit for IOC Card controller (ICOM Board) suitable for M/s Emerson make 7 TR HPAC Model No. GLOBEL PEX2 1030)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .