Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.0 LAccepted-AOC 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L1 | Accepted-AOC L1 | |
| 2 | L2₹10.0 L+₹1.0 L (11.3%)Rejected-Finance 601 603 EROS APARTMENT 56 NEHRU PLACE NEW DELHI 110019 | NEW DELHI | NEW DELHI | DELHI | 110019 | L2 | Rejected-Finance L2 | |
| 3 | L3₹10.7 L+₹1.7 L (19.4%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | - | Rejected-Technical found not fair enough |
Tender Value
Refer Docs
EMD Value
₹18,000
Closing Date
22 Nov 2024, 12:00 pmClosed
The Executive Engineer, Kolkata Electrical Div
The Executive Engineer Kolkata Electrical Division P.W.Dte. BlockI (1st Floor) Writers Buildings, Kolkata 700 001
Special Electrical repair and renovation of building at 306 B.B Ganguly street Kolkata----SITC of Split type room AC , FD and Lighting Protection System EI Work attached to KP HQ under Lalbazar Electrical Section-I. ----SITC of Fire Detection Alarm
2024_WBPWD_767443_1
WBPWD/EEKED/eNIQ-20Q2nd/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
Lalbazar
Please refer Tender documents.
5 documents required · 5 mandatory
₹18,000
O/O The Executive Engineer Kolkata Electrical Divi
16 Apr 2025
6 Nov 2024
25 Nov 2024
6 Nov 2024
22 Nov 2024
19 Nov 2024
18 Nov 2024
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based addressable fully networkable fire alarm control panel ( VDS / UL /ERTL/ LPCB / FM approved ) suitable for the devices along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel should have extra loop card slot for expansion of capcity twice. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 60 minutes during Emergency condition, with integral battery charger complete in all respect as required. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 modbus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface.The system must be preloaded with licenced software. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls / Edward /Secutron/ Apollo / Morley / GST /Ravel) Necessary OEM licensed software and/or dongle for programming (addition /alternation) of the fire alarm control panel with lifetime validity has to be provided by L1 bidder before handover.
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable multisensor detector IP 42 (VDS / UL /ERTL/ LPCB / FM approved) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : Cerberus Pro / Honeywell /Johnson Controls / Edward/ Secutron/ Apollo / Morley / GST /Ravel)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point (VDS / UL /ERTL/ LPCB / FM approved) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Cerberus Pro/ Honeywell/ Johnson Controls/ Edward /Secutron/ Apollo / Morley / GST / Ravel)
Supply, Installation, Testing & Commissioning of Addressable Hooter cum Strobe ( sound output of minimum 75 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 (VDS / UL /ERTL/ LPCB / FM approved). (Approved Make: Cerberus Pro/ Honeywell / Johnson Controls / Edward /Secutron/ Apollo / Morley / GST / Ravel)
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : Cerberus Pro/ Honeywell/ Johnson Controls / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton/ GST/System Sensor/Agni Suraksha / Ravel)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kabel/Polycab/Gloster) through 20mm dia PVC "FR" type Rigid Conduit pipe with necessary arrangement as per GS. (Make: Precision / AKG / Universal / Polycab) on the surface of the wall. Incl. Supply and laying 20mm of PVC rigid conduit on ceiling/wall (Precision make)
Globe Detective Agency Pvt. Ltd. (BID ID -5771469)
PERFECT IMAGE SOLUTIONS (BID ID -5771506)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .