Tender Value
₹36 L
EMD Value
₹72,000
Closing Date
4 Jul 2023, 6:00 pmClosed
GE (UTILITY) SECUNDERABAD
GE UTILITY SECUNDERABAD MUDFORT SECUNDERABAD-500003
PROVISION OF 01 NO 200 KVA DG SET ALONGWITH AMF PANEL WITH BYPASS ARRANGMENT, 01 NO 5 HP CAPACITY SUBMERSIBLE PUMPSET WITH CONNECTED PIPELINE AND COMPLETION OF INCOMPLETE WORK IN RESPECT OF PROVISION OF 100 KVA GENERATOR SET UNDER AGE E/M NO II OF GE
2023_MES_599394_1
GE (U)/SEC/TOKEN/05 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SECUNDERABAD
AS PER NIT
8 documents required · 8 mandatory
₹500
GE (UTILITY) SECUNDERABAD
₹72,000
Yes
8 Aug 2023
29 May 2023
11 Jul 2023
29 May 2023
4 Jul 2023
17 Jun 2023
Amount
Supply, install, test and commissioning of silent Diesel Engine Generating set 415 volts, 3 phase, 4 wire engine as per IS : 10001/10002 conforming to CPCB Norms II, and alternator as per IS : 13364 of capacity 200 KVA/ 160 KW at site complete with control panel having meters, sound proof canopy etc including all accessories as per Relevant IS with latest amendments and manufactures standard and as per the details given below and independent relay panel for automatic on mains failure :- AC Generator should be suitable for ambient conditions at Secunderabad and confirming to IS. Make : Engine : CUMMINS/CATERPILLAR/ KIRLOSKAR GREEN Alternator : STAMFORD / CATERPILLAR / LEROY SOMER / KIRLOSKAR GREEN / CROMPTON GREAVES Battery : EXIDE / AMAR RAJA / AMCO
Item No 1 Contiuned....... (Note :- The capacity of generator set shall be net after all de-rating factor as per relavent IS design) (A) Alternator :- Standard design alternator rated at (160 KW) net output at site after considering all de-rating factors, site conditions and at power factor 0.8, AC, 3 phase 4 wire, 415 V, 50 Hz, 1500 RPM self excited, self regulated, screen protected, drip proof IP 23 enclosure, brush less design, voltage regulation ± 2.5 %.
Item No 1 Contiuned....... (B) Diesel Engine :- Diesel engine of suitable capacity, water cooled, closed circuit as per BS-649 or IS-1002 direct injuction type . Electric starting system having rated speed 1500 RPM. The DG set Shall be capable for running 24 hrs continuously with 10% over loading for 01 hour in every 12 hours as per BS-5514/BS-649. Engine shall be multi cylinder, multi stroke, direct injection and equipped with all standard fitting as per manufacture's recommendations and mounted on common base frame with following Specifications :-
Item No 1 Contiuned....... (i) Fly wheel with housing :- Common base frame of sturdy design suitable for anti vibration mounting and permanent concrete foundation (as per OEM design) for mounting engine and alternator as per manufacturer's instructions "(ii) Cooling system :- (a) Mounted radiator with fan & belts & guard, rubber hoses and thermostat. (b) Cooling water pump . " (iii) Governer :- Electronic Governer. (iv) Electric Starting System :- Electric Self starter, 12 volts DC (12 volt, 180 AH battery 2 No's/As per OEM provision to suit the requirement) charging alternator as per manufacturer's design, S&F Suitable size and length of copper leads with lugs of adequate size complete with initial charging of maintenance free battery 1x12 volt 180 AH capacity.
Item No 1 Contiuned....... (C) Acoustic Enclosure (Sound Proof Canopy) :- All as per CPCB norms and OEM of DG Set's design.
Item No 1 Contiuned....... (d) Civil Works:- All civil works related to foundation, installation of panel and equipment and depth of foundation shall be minimum 300mm with antivibration pads, or as recommended by the manufacturers. Cables from DG set to AMF panel, AMF panel to main panel will be measured under relevant schedule. The foundation should be water levelled atleat 300 mm above the Ground level to avoid flooding. Note:- (i) The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. Contractor should indicate suitable date and time in advance for testing of DG Set complete with suitable testing equipment and Rep of OEM in presence and as directed by Rep of Accepting Officer. All other necessary equipments like resistance load strip heater or water testing arrangement etc of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department. (ii) The testing of Genset for continuos 12 Hours shall be done by an officer detailed by accepting officer after installation at site No load - 1/2 Hour 25% load - 1/2 Hour 50% load - 1 Hour 75% load - 1 Hour 100% load - 8 Hours 110% load - 1 Hour
AMF CONTROL PANEL SUITABLE FOR OUTDOOR INSTALLATION WITH BY PASS ARRANGEMENT : Supply, Installation, Testing and commissioning of AMF (Automatic Mains Failure) panel suitable for generating set of capacity 200 KVA factory made, fabricated out of CRCA sheet (3.00 mm thick) of suitable size, totally enclosed, dust , damp and vermin proof free standing floor mounted type and front operated, degree of protection required will be IP-55 conforming to IS 2147 with and including necessary foundation ( Minimum height of the base of the panel board should not be less than 0.45 Meter) having the following features / facilities:-
S&F steel work in tubular trusses/pole(unframed) including purlins, rafters and special shaped washers etc complete using ERW or induction butt welded tubes confirming to IS-1161-1979 grade St-240 incl painting complete all as specified and directed.
M&L for pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws including ridge complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches not exceeding 1.5 m width and not exc 1.5 m in depth and getting out in hard/dense soil for removing/laying of pipe line complete all as specified and directed.
Removing excavated material (soils) n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Excavating in post holes( or similar holes) each n exc 0.5 Cum getting out returning filling in hard/dense soil.
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundation /bed concrete
M&L Pre-cast cement concrete block masonry Type C1 1:3:6 (20mm graded aggregate) with solid blocks, exc. 10cm in width and setting in cement mortar 1:6 complete
M&L for 100 mm thick cement concrete 1:2:4 type B-2 (using 40mm graded crushed stone aggregate) as in sub base or sub floors finishing the surfaces even and rough to receive the topping layer complete all as specified and directed.
M&L Rendering 10mm thick in CM 1:6 on fair faces of brick work or concrete surfaces
M&L for Three coats of white wash including preparing new surfaces plastered or unplastered
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of 185 sqmm x 3.5 core sizes
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in soils complete all as specified and directed.
Spreading riddled earth ( after preparation of excavated earth) in Cable duct for cushioning of cable laid in trenches complete all as directed by Engineer-in-Charge Note:- Punned thickness 18 CM( 6.25 Cm below cale and 11.75 cm above cale) will be measured for payment purpose. The earth removed during excavation to be used as rddled earth after crushing and sieving. Quoted rate inclusive of all arrangement as mentioned.
M&L brick protection with common burnt bricks sub class ‘B’ of size 230x115x75mm for cable protection complete all as directed by Engineer-in-charge.
Cutting the existing road straight by manual, depth and width not less than 1 mtr below ground level for passing of underground cable and filling back with excavated soil upto 75% road portion and 25% shall be made with cement concrete 1:2:4 (using 20 mm graded aggregate stone complete all as specified and directed. Note: Necessary work permissions for the works to be carried in Civil/Public ares/Defence areas to be taken by the contractor prior to starting the work. Laision with concerned departments is the responsibility of contractor. Department will do the necessary authorised correspondence for the said approvals. No extra payment will be entertained on this account.
Supply and lay GI tubing 80 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as directed by Engineer-in-Charge.
Supply, Install, Testing and Commissioning of Advance Maintenance Free G.I. SAFE EARTHING Electrode with PIPE of not less than 50 mm outer dia) and two meter length, The electrode should be of galvinised (80 -100 micron) along with earth lead as Galvanised steel strip of size 32 X6 mm 7.5 m. The GI Electrode shall be pre-filled with Cristaline Conductive Material (CCM). The GI electrode shall be surrounded with 25 kg BackFill compound to provide maximum contact between the electrode and Back Fill Compound. The earting pit cover should be factorty built (size TOP- 10 Inch, Bottom -13 Inch, Height 10.25 Inch ) made of heavy duty Polypropylene complete all as specified and directed. Note : The min distance between two earth pits to be 2m apart.
S&F earth continuity conductor or main earthing lead fixed to wall on batten or fixed to pole GI strip 32 x 6 mm all as specified and directed.
Supply, lowering, testing and commissioning of submersible multi stage electric driven pumpset (pump and motor) 440 volts, Three phase 5 hp capacity, 2900 RPM , 12 Stage delivery 50 mm dia ( suitable for 150mm casing/ bore well) centrifugal type head not less than 100 mtr and discharge of 230 LPM Suitable as per yield available in the borewell complete all as specified and directed .
Supply and laying water proof submersible flat cable PVC sheathed multistranded copper conductor 3 core 4 sqmm 1100 volts grade laid between submersible pump and control panel
Supply & fixing HDPE heavy duty column pipe internal dia 50mm PN 16kq/Sqmm including necessary all fixings
S&F gun metal non return valve 50mm dia,
Supply and fix Gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipes and fixed complete all as specified and directed for the following sizes:-
25mm dia bore
40mm dia bore
50mm dia bore
Supply and laying steel water tubing medium grade, galvanised with all fitting, laid in trenches and testing for leakages complete all as specified and directed for the following sizes:- Note :- Earth work excavation shall be measured and paid separately under relevant items.
25 mm bore.
40 mm dia
50 mm dia
Supplying and laying unreinforced precast concrete cable cover class LV , Type 1 flat with size 250mm x150 mm x 40mm all as specified and directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core
Supply and installing weather proof starter panel outdoor type fabricated out of 3mm thick with MS sheet including iron angle support frame of size 50x50mm 60cm grouted in floor complete suitable for 5 HP 3 phase, 415 V, 50Hz DOL system with ammeter cts and voltmeter digital 1set, front opening and locking arrangement to accommodate in and including the following :-(a) DOL Starter panel 3 phase 415 volts suitable for submersible pump set here-in-before with single phase preventer, over load protection and dry run protection.(b) Indiaction lamps - 1 set (c) MCB-6-32 Amps 3 pole -01incomer
.M&L for earthing complete with Galvanised steel earth plate electrode 60cm x 60cm x 6.3mm, buried directly in ground( earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including GI wire 4 mm protected with GI medium grade pipe 15mm dia for earth electrode upto test point or upto 7.5 mtr whichever is less by means of bolts, nuts, check nuts and washers all shown in electrical plate No 3 (of SSR part-I) connected to earthing test point all as specified or indicated including provision of necessary excavation and earth work of any type of soil, PCC pit , RCC cover, 50mm thick with 8mm dia TMT bar @ 100cm c/c both way , 40mm bore light grade watering pipe, water funnel, 40mm bore GI medium grade protection pipe, comman salt, charcoal dust, returning filling, in of soil, removal of soil to a distance of not exceeding of 50 mtr etc, including testing on completion complete all as specified shown in drawing. Note: Resistance limit of earthing shall be less than 5 ohm.
Supply , installation, commissioning and testing of water Softner of capacity 3000 LPH. The equipment shall be suitable to operate on a single phase 220v/50Hz power supply including necessary foundation and UPVC water supply pipe line of suitable size for water connection with accessoris and control valve, electrical works all as recommended by manufacterer and any other items required at site for smooth functioning of plant complete all as specified and directed by Engineer-in-Charge. Make:- Aqua Soft Softner/ Purit Softener/SVS. The feed shall be having following characters :- (i) Raw water pump - 1.5 HP.(ii) Sand Filter and carbon filter vessel (IS 1865)- 1 Each. (iii) Carbon- 900 iv,- 150 Each.(iv) Sand- 50 KG bag- 6 Nos. (v) Pebbles – 4 Each set. (vi) Multiprt Valve - 40nb-2 Nos. (vii) Distribution Strainer - 4 Nos. (viii) Dosing System- 0-61ph - 1Nos. (ix) 20" Jumbo housing and Jumb filter - 2 Nos. (x) High Pressure Pump - 4E-19- 1 No. (xi) Membrane 8" - 3 No.(xii) SS Skid - 40mm- 1 No. (xiii) Control Panel - 1*3 - 1 Set. (xiv) Flow meter - 4800LPH - 2Nos. (xv) Float - 2 Nos. (xvi) LPS - 1 No. (xvii) Pressure Gauge SS- 21/1”- 2 Nos. (xviii) Solenoid Valve 1”-1 Nos (xix) Dosing Chemical- 5 Lts (xx) Pipe and fittings – 1 Set.
COMPLETION OF INCOMPLETE WORK IN RESPECT OF PROVISION OF 100 KVA GENERATOR SET UNDER AGE E/M NO II OF GE (U) SECUNDERABAD
ONLY Installation, testing and commissioning of silent Diesel engine driven Generating Set, AC, 415 Volt, 3 Phase 4 wire 50 Hz, 1500 RPM of capacity 100 KVA with Accoustic enclosure, AMF Panel comprising of the following and testing complete all as specified and as directed by Engineer-in-Charge. (A) DIESEL ENGINE : Four cylinder, Liquid cooled, Naturally aspirated and developing 156 BHP @ 1500 RPM, vertical engine, electric start, compression ignition, 4 stroke designed to run continously @ 1500 RPM confirming to IS 10002, ISO 3046, BS : 5514 standards with an overload capacity of 10 % for one hour in every 12 hrs operation, DG set to comply with CPCB-II norms and shall comprise the following accesories
Item No 32.01 Contiuned....... (i) Radiator cooling system with fan (ii) Micro fuel pump with electronic governor (iii) Dry tube Air cleaner (iv) Lubricating Oil filter (Spin on type) (e) 12 Volts Electric Starting system (f) Battery Charging Alternator (g) Stop solenoid (h) Lub Oil Pressure Gauge (j) Water Temperature Gauge (k) Ammeter Battery Charging (l) K Cool Super Plus Coolant (m) First Fill of Lub Oil (n) Safety Shut Down system for Low Lube Oil (o) Air valve and drain plug arrangement
Item No 32.01 Contiuned....... (B) ALTERNATOR : Alternator suitable for continous operation rated at 1500 RPM, 415 Volts, 3 Phase, 4 wire system, 50 Hz, 0.8 PF in SPDP enclosure, self excited and self regulated, brushless, foot mounted in single/ double bearing construction on end shields conforming to IS 4722, BS EN 60034-1 and will be suitable for tropical condition. (C) ACOUSTIC ENCLOSURE : The acoustic enclosure shall be designed and manufactured confirming to relevant standards suitable for outdoor installation exposed to weather conditions, and to limit noise level of <75 db (A) at a distance of 1 metre from the enclosure as per CRCB II norms. The enclosure shall be fabricated out of FRCA sheet of thickness not less than 2.0 mm thick and shall be powder coated. (D) CONTROL PANEL : CONTROL PANEL ALONG WITH SUITABLE CONTROLLER AND MCCB4 POLE 25 ka ADJUSTABLE TYPE TO BE PROVIDED INSIDE CANOPY (E) AMF CONTROL PANEL SUITABLE FOR OUTDOOR INSTALLATION WITH BY PASS ARRANGEMENT : Installation, Testing and commissioning of AMF (Automatic Mains Failure) panel suitable for generating set of capacity 100 KVA factory made, fabricated out of CRCA sheet (3.00 mm thick) of min size 1.675 M X 1.300 M X0.50 M, totally enclosed, dust , damp and vermin proof free standing floor mounted type and front operated, degree of protection required will be IP-55 conforming to IS 2147 with and including necessary foundation ( Minimum height of the base of the panel board should not be less than 0.45 Meter) having the following features / facilities:-
Supply, lay and connecting by using lugs of LT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty, 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm core, complete all as specified and directed.Make : KEI/Polycab/Havells/Gloster
Supply, lay and connecting by using lugs of LT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable, heavy duty, 1100 Volts grade with stranded aluminium conductor of size 70 Sqmm core, complete all as specified and directed. Make : KEI/Polycab/Havells/Gloster
Excavation in trenches not exc 1.5 mtr wide and n.exc 1.5 mtr in deep and getting out in Hard/Dense soil laying of cables etc.
Returning filling in including spreading, leveling watering and well ramming in layers n.exc 25cm thick using excavated soil
Removing excavated surplus soil to a distance n.exc 50 mtr and depositing where directed at a level n.exc 1.5mtr above from the starting point
Supplying and laying unreinforced precast concrete cable cover class LV , Type 1 flat with size 250mm x150 mm x 40mm all as specified and directed by Engineer-in-Charge.
Supply and spread approved dry river sand for foundations/Cable duct including watering and consolidation, cushioning of cable laid in trenches complete all as directed by Engineer-in-Charge. Note:- Only Punned thickness will be measured for payment purpose
M & L cutting of road, hard standing made of concrete or premix carpet, WBM, soiling and morrum filling including excavation for laying of cable pipe all as directed and making good the road/hard standing by using all old/new materials and with PCC (1:2:4) etc, required to match with the existing surface complete all as specified and directed.
Excavation in post holes (or similar holes ) each nexc 0.5 cum getting out returning filling in shoft/loose soil.
M&L PCC 1:4:8, type D-2 (using 40 mm graded crushed stone aggregate) as in foundations filling and mass concrete complete all as specified and directed.
M&L Pre-cast cement concrete block masonry Type C1 1:3:6 (20mm graded aggregate) with solid blocks, exc. 10cm in width and setting in cement mortar 1:6 complete
M&L Rendering 15mm thick in CM 1:6 on fair faces of brick work or concrete surfaces
M&L for Three coats of white wash incl preparing new surfaces plastered or unplastered
S&F steel work in tubular trusses / poles (unframed) including purlins, rafters and special shaped washer etc complete using ERW or induction butt welded tubes confirming to IS-1161-1979 grade St-240 complete all as specified and directed.
M&L for pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50 mm thick of an colour having tensile strength of 550Mpa as in roof covering/ cladding to wall, fixed with self tapping screws including ridge complete all as specified and directed.
M&L for Two coats of synthetic enamel paint on steel surfaces of any description, over 10cm in width or girth, over a coat of primer incl preperation of new surfaces all as specified
Note for BOQ items:- Bidders to note that as this is clubbed work of 02 sanctioned works and 01 completion of incomplete work, certain similar items may have occurred/repeated hence, Bidders are advised to quote same rate for similar items of BOQ. If different rates are quoted for similar items, lowest rate of similar items will be considered for arriving total amount. GE's decision regarding similar items is final and binding and no representation regarding the same will be entertained.
DPS sales and services india
LEOENTERPRISES
POWER CONSTRUCTION COMPANY
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .