Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.3 LAccepted-AOC | L1 | Accepted-AOC being lowest | |
| 2 | L2₹25.0 L+₹5.3 L (26.9%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹26.1 L+₹6.4 L (32.6%)Rejected-Finance | L3 | Rejected-Finance Being not lowest | |
| 4 | L4₹28.2 L+₹8.5 L (43.3%)Rejected-Finance | L4 | Rejected-Finance Being not lowest | |
| 5 | L5₹33.3 L+₹13.6 L (69.2%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L5 | Rejected-Finance Being not lowest |
Tender Value
Refer Docs
EMD Value
₹68,000
Closing Date
8 Oct 2020, 6:00 pmClosed
MR ARJUN PATRO
GE U ELECTRIC SUPPLY DELHI CANTT-10
Repair and replacement of defective MCCB ACB LT Panel cables termination pole painting feeder piller LT earthing pole boxes of OTM I II III Yogender Vihar Bana Singh 180 Qtr Upper Shankar Vihar 35 Inf Bde and Tarapore enclave of AGE U Elect Supply No
2020_MES_374436_1
GE ELECT/D-83/2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY DELHI CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹68,000
Yes
21 Dec 2020
8 Sept 2020
10 Oct 2020
9 Sept 2020
8 Oct 2020
23 Sept 2020
Amount
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 400 A,4 pole,35KA,MCCB Microprocessor based type along with sprader terminals-1 no, (b)Outgoing:-(i) 250 A,3 pole, 35KA,MCCB Microprocessor based type along with sprader terminals-2 nos (ii) 160 A,3 pole, 35KA,MCCB Microprocessor based type along with sprader terminals-4 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at Upper Shankar Vihar. (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 315 A,4 pole,35KA,MCCB Microprocessor based type along with sprader terminals-1 no, (b)Outgoing:-(i) 100 A,3 pole, 35KA,MCCB Microprocessor based type along with sprader terminals-6 nos (ii) 60 A,3 pole, 35KA,MCCB Microprocessor based type along with sprader terminals-4 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at Bana Singh. (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 250A,4 pole,35KA,MCCB along with sprader terminals along with sprader terminals-1 no (b)Outgoing:-(i) 100A,3 pole, 35KA,MCCB along with sprader terminals-4 nos (ii) 60A,3pole,35KA,MCCB along with sprader terminals-4 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at 180 qtr. (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 315 A,4 pole,35KA,MCCB Microprocessor based type along with sprader terminals-1 no (b)Outgoing:-(i) 160 A,3 pole, 35KA,MCCB along with sprader terminals-3 nos (ii) 125 A,3 pole, 35KA,MCCB along with sprader terminals-2 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at OTM III (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 250 A,4 pole,35KA,MCCB Microprocessor based type along with sprader terminals-1 no (b)Outgoing:-(i) 160 A,3 pole, 35KA,MCCB along with sprader terminals-3 nos (ii) 125 A,3 pole, 35KA,MCCB along with sprader terminals-2 nos (ii) 60 A,3 pole, 35KA,MCCB along with sprader terminals-1 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at Upper Shankar Vihar. (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Supply, install, test and commissioning in replacement of Out door LT panel / Pillar Box of comprising of the following all as directed by removing the old existing panel Para-2(a) (xvi) : Confirmed Fabrication Details : Main frame 3 mm thick CRCA sheet, partition sheets / covers / doors of 2 mm thick CRCA sheet, gland plates 2 mm thick MS sheet (undrilled), base frame of 75 mm MS channel with provision of incoming and outgoing cable entry at the bottom side for installation, seperate chambers for Main Bus Bars, MCCBs /ACB and Cable end connections free standing floor mounted with degree of protection IP 54 and with heavy duty Hinges for double doors and locking arrangements with Aldrops at front and Back Bus bar details : Material shall be alluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for R, Y, B & N 1.5 times the Rating of incommer MCCB /ACB and out going shall be of rated capacity and bus bar links/dropers shall be support of epoxy type insulators , earthing of 40x6 mm GI Flat.
Accessories for Pillar Box : - 0-500V Digital voltmeter - 01 No and 0-1000 A Digital Ammeter - 01 No,(Flush type) and Indication Lamps (LED) - 03 No.CT of rated capacity and Indicating lamps : 01 set of three (a)Incommer:- 250 A,4 pole,35KA,MCCB Microprocessor based type along with sprader terminals-1 no (b)Outgoing:-(i) 160 A,3 pole, 35KA,MCCB along with sprader terminals-3 nos (ii) 100 A,3 pole, 35KA,MCCB along with sprader terminals-2 nos
Note : - (i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples. (ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint. (iii) All MCCB should be connected to Bus bar directly through expended links (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt. II/1993 (Latest Version). The MCCB should have Ics=100% Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacture. (v) Location : at OTM I. (vi) Location cannot be changed without permission of GE, approval of GE is mandatory for any changing in location.
Material and Labour for disconnecting burnt end or portion of cable removing the cable from loop including necessary excavation & earth work in soft/loose soil relaying and reconnecting the cable by removing burnt portion of cable and preparing fresh terminals including fixing of new lugs for 50 Sqmm 3½ / 4 to 400 Sqmm of LT cable to pole / main switch complete all as specified and directed.
Material and labour in replacement of Voltmeter 0-500 V digital type as per existing size complete all as per specified and directed.
Material and labour in replacement of Ammeter 0-400 Amp digital type per existing size complete all as per specified and directed.
Supply and fixing in replacement of indicator lamp for RYB phases complete all as specified and directed.
Material and labour in replacement for CRCA MS sheet of thickness 3.15 mm powder coated finish over one coat of red oxide on out side surface and painted in side with two coats of red oxide primer with apran for cable entry closing locking arrangement including all fixing acessories i.e. suitable size of hinge, nuts, bolts, washers, cutting and welding works etc complete all as specified and directed.
S&F (in replacement) Main switch 100 Amps, 415 volts, 3 phase capacity TPN complete with rewireable fuses including all necessary electric connection by lugs and gland etc. complete alll as specified & directed.
S&F (in replacement) change over switch 200 Amps ON load in sheet enclosure four pole complete with all electric connection complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 100 Amps rupturing capacity 35 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 160 Amps rupturing capacity 35 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 200 Amps rupturing capacity 35 KA Ics=100% Icu on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 250 Amps Microprocessor based type rupturing capacity 25 KA based adjustable type type on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 320 Amps Microprocessor based type adjustable type rupturing capacity 36 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 3 pole 400 Amps Microprocessor based type adjustable type rupturing capacity 36 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement MCCB 4 pole 400 Amps rupturing capacity 36 KA Microprocessor based type adjustable type on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacementMCCB 4 pole 630 Amps Microprocessor based type adjustable type rupturing capacity 36 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement
Supply and fixing in replacement ACB 4 pole 1000 Amps Microprocessor based type adjustable type rupturing capacity 50 KA on LT panel/feeder pillar including dismantling/taking down existing unserviceable MCCB complete all as specified and directed as per site requirement.
S&Fin replacement fabricated steel enclosure made out of 18 SWG Sheet suitable for mounting of MCCBs of any type and size including clamp made of 40x5mm FI,Nuts,bolts,washers complete all as specified and directed.
Material and labour for painting of LT panel boards out door/in door of size 6 to 10 Sqm floor mounted installed at different locations including preparation of exposed surface by removing old paint from the body, cleaning the surface with thinner and applying two coats of synthetic enamelled smoke grey paint complete all as specified and directed.
Material and labour for painting of LT panel boards out door/in door of size 2.5 to 5 Sqmm floor mounted installed at different locations including preparation of exposed surface by removing old paint from the body, cleaning the surface with thinner and applying two coats of synthetic enamelled smoke grey paint complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel/feeder pillar up to 50 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel/feeder pillar for 70 sqmm cable to 240 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of cable gland for LT panel for 300 sqmm cable to 400 Sqmm cable complete all as specified and directed.
Supply and fixing in replacement of galvanised iron strip 32 X 6 mm for additional earthing lead beyond 7.5 meter.
Earthing complete in replacement with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth wire 32 X 6 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in hard/rocky soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in soft/loose Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
M & L for cutting and removing grass, vegetation bushes etc from surrounding of installation/LT Panel/Four Pole structure/Sub Stations and removing all rubbish to a distance not exceeding 50 m as directed.
M&L Brick work with sub-class 'B' bricks, straight or curved on plane exc 6 m mean radius, built in cement mortar 1:6 complete as specified and directed including dismantling of old unserviciable brick work.
M&L Rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar (1:4) finished fair and even without using extra cement complete all as specified and directed including
M&L for Demolition of path /concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) .complete all as specified and as directed.
Material and labour for coarse aggregate filling using stone gravels, rounded, of size n exc. 40 mm suitable to site, in the area covered by four pole structures complete all as specified and directed.
Material and labour for providing cement concrete 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) complete all as specified and directed by Engr in charge.
Material and labour for providing cement concrete 1:2:4 type B-1 (using 20 mm graded crushed stone aggregate) including necessary form work and finished the surface complete all as specified and directed.
Preparation of old painted surfaces of Steel tubular LT/HT poles, any height including cross arms, MS strap, nuts, bolts, washers, cable protection pipe wherever provided etc and painting of complete poles with one coat of aluminium paint cross arms and protection pipe and painting of bottom area of pole upto ground level with synthetic enamel paint including writing pole number in white letter of approved size on black ground along with white wash/ cement based paint on the plinth of pole.
Supply & Fix in replacement Junction/loop in - loop out box weather proof incluiding made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120 mm out side and 300x200x105 mm inside dimensions comprising of aluminium bus bar 4 strip for 3 phase and neutral 63 Amps and 02 Amps MCB SP with base incluiding embossing/ painting of danger notice of size not less than 10cm x 7.5 cm with letters,figures band conventional skull and bones in signal red colour on front face of junction box body complete all as specified and directed.
Supply and fixing in replacement of Automatic Light Timer switch with Natural switch Cat No. SWADEEP-02EC12KW3P, infra ray sensor with pre sawn switching off timer, 4-8 hrs, of Maximum load capacity of 4KW per phase. Degree of protection conforms to IP 65 Make- Nature Switch/Schneider/Seimens complete all as specified and directed.
Material and labour for providing galvanised chain linkfencing of height 2 metre from GL right around the 11 KV 2 pole structure/ transformers structures/DG sets with ms angular of size 60 x 60 x 6mm thick duly painted with a coat of redoxide and two coats of synthatic enamel paint grouted with post holes and PCC at span of every one metre distance around along with 1 mtr width hinged gate and providing of slag brickwork of 2 feet height from Ground level with proper basement along with perimeter of the fencing and plastering the surfacewith1:6 ratio around the fencing complete asspecified by the engineer in charge.
Supply and making in replacement new LT 1100 V end termination with suitable size of aluminium lugs duly crimped for LT 3 ½ core armoured aluminium conductor cable after isolating supply to transformer/LT panel and disconnecting brunt/fault cable from the bunch of cables in trenches, galleries, removing cable loop, opening the cable blank and connecting back after end terminals, testing and commissioning for 3 ½ core 185 to 400sq.mm (XLPE) all as specified and directed.
Cable Size 185 Sqmm to 240 Sqmm
Cable Size 300 Sqmm to 400 Sqmm
Taking down the LT air circuit breakers of various capacities form 800 amps to 1250 amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts all as specified and directed (a) Checking/repair of mechanical system of ACB. (b) Checking/repair of the manual closing/tripping of breaker.
Laying only LT UG Cable in replacement LT cable of PVC sheathed XLPE cable armoured aluminium conductor 1100 V graded , 2/4 core,10 sqmm to 25 sqmm, after taking out/down old existing unserviceable from trenches / ducks/ road crossing and poles complete all as specified and directed.
All as per item No 44 above but of size 3.5 core,35 sqmm to 3.5x 50 sqmm
All as per item No 44 above but of size 3.5 core,70 sqmm to 3.5x 95 sqmm
All as per item No 44 above but of size 3.5 core,120 sqmm to 3.5x 185 sqmm
All as per item No 44 above but of size 3.5 core,240 sqmm to 3.5x 400 sqmm
Excavation in trenches in soft and loose soil n.exc 1.5 mtr wide and n.exc. 1.5 mtr depth for laying and taking out of electric power cable and getting out all as specified and directed by engineer –in-charge.
Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm thick all as specified and directed.
Removing excavated material not exceeding 50 mtr away and depositing where directed at a level n. exc 1.5 mtr above the starting point .
Material & labour for river washed and screened dry sand for filling under and above the under ground cable for cushioning of cables etc.complete all as specified and directed by engr –in-charge
S&Laying in replacement sub class B bricks having minimum compressive strenth 75 Kg/sqm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.
All as per Srl item No 53 here in before but using old bricks obtain under item No 49
Material and Labour for providing door Hinges- 2 Nos/ Door fixing by means pf welding / fabrication/ Nut & Bolts to the LT outdoor panel complete all as speecified and directed.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
MV Engineers And Contractors
Surjit and Sons
Rajindera Enterprises
Vijay Electricals
mayur enterprises
Buddham Builders
M/s Adhikari construction co.
ALLIED CONSTRUCTION
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .