| Sl No | Description | Qty | Unit | Fire Shield Engineering & Equipments L3 | BALAJI FIRE PROTECTION SYSTEMS L2 | Creative Projects L1 |
|---|---|---|---|---|---|---|
| 1.00Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the next items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | ||||||
| 1.01 | Six Loop Panel for Academic Block I (Detector and Devices - 572 Nos) | 1 | Set | 5,25,000 ₹5,25,000 | 5,12,000 ₹5,12,000 | 4,78,000 ₹4,78,000 Lowest |
| 1.02 | Six Loop Panel for Academic Block II (Detector and Devices - 522 Nos) | 1 | Set | 5,25,000 ₹5,25,000 | 5,12,000 ₹5,12,000 | 4,78,000 ₹4,78,000 Lowest |
| 1.03 | Six Loop Panel for Academic Block III (Detector and Devices - 472 Nos) | 1 | Set | 5,25,000 ₹5,25,000 | 5,12,000 ₹5,12,000 | 4,78,000 ₹4,78,000 Lowest |
| 2.00Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | ||||||
| 2.01 | Four Loop Panel for Central Library (Detector and Devices - 176 Nos) | 1 | Set | 4,20,000 ₹4,20,000 Lowest | 4,36,000 ₹4,36,000 | 4,48,000 ₹4,48,000 |
| 3.00Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | ||||||
| 3.01 | Two Loop Panel for Students Activity Center (Detector and Devices - 52 Nos) | 1 | Set | 3,12,000 ₹3,12,000 | 2,80,000 ₹2,80,000 Lowest | 4,18,000 ₹4,18,000 |
| 4.00 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector ( VDS / UL / LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector is to be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. Degree of protection as per OEM Standard. | 1,641 | Nos | 2,220 ₹36,43,020 | 2,180 ₹35,77,380 | 2,100 ₹34,46,100 Lowest |
| 5.00 | Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector ( VDS / UL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector in the loop is to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard. | 7 | Nos | 2,110 ₹14,770 | 2,120 ₹14,840 | 1,900 ₹13,300 Lowest |
Tender Value
Refer Docs
EMD Value
₹1.5 L
Closing Date
28 May 2026, 2:30 pmClosed
SENIOR SUPERINTENDING ENGINEER
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER (P.W.Dte) South-Western Electrical Circle PWD Compound,Midnapore,Paschim Medinipur
Construction of SRM University Jhargram in the district of Jhargram ---Supply, Installation, testing and Commissioning of FDA system at Academic Buildings (I,II,III), Central Library Building and Student Activity Centre.
2026_WBPWD_5013941_1
WBPWD/SSE/SWEC/NIQ01/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
JHARGRAM
Please refer Tender documents.
4 documents required · 4 mandatory
₹1.5 L
OFFICE OF THE SENIOR SUPERINTENDING ENGINEER
3 Jul 2026
12 May 2026
30 May 2026
12 May 2026
28 May 2026
15 May 2026
14 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the next items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | |||||
| 1.01 | Six Loop Panel for Academic Block I (Detector and Devices - 572 Nos) | - | Set | - | - |
| 1.02 | Six Loop Panel for Academic Block II (Detector and Devices - 522 Nos) | - | Set | - | - |
| 1.03 | Six Loop Panel for Academic Block III (Detector and Devices - 472 Nos) | - | Set | - | - |
| 2Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | |||||
| 2.01 | Four Loop Panel for Central Library (Detector and Devices - 176 Nos) | - | Set | - | - |
| 3Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events in its memory (EPROM). The panel should have extra loop card slot for future expansion. | |||||
| 3.01 | Two Loop Panel for Students Activity Center (Detector and Devices - 52 Nos) | - | Set | - | - |
| 4Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector ( VDS / UL / LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector is to be provided without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. Degree of protection as per OEM Standard. | |||||
| 5Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector ( VDS / UL / LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have minimum triggering temperature programmable from 58 deg. C to 68 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA (Note : Detectors without built-in fault isolator is also acceptable with one independent short circuit fault isolator after every four (04) detector in the loop is to be provided without extra cost) the detectors should have built in response indicator with LED indicator.Degree of protection as per OEM Standard. | |||||
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
Tendernotice_2.pdf
PDF • 1.79 MB
BOQ_5081838.xls
BOQ • 0.36 MB
ApprovedMakeListFDA.pdf
Tender Documents • 0.63 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .