Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.3 LAccepted-AOC SADASHIV PHUGE NAGAR OPP SANDVIK FACTORY RADHIKA RESIDENCY F WING FLAT NO 7 PHUGEWADI PUNE 411 012 | PUNE | MAHARASHTRA | 411012 | L1 | Accepted-AOC THE LOWEST TENDERER | |
| 2 | L2₹21.9 L+₹2.6 L (13.2%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 3 | L3₹23.1 L+₹3.7 L (19.0%)Rejected-Finance 3RD FLOOR BHAKTAMAR RESIDENCY SOMNATHNAGAR ROAD PUNE 411014 | PUNE | PUNE | MAHARASHTRA | 411014 | L3 | Rejected-Finance NOT THE LOWEST TENDERER | |
| 4 | L4₹23.4 L+₹4.1 L (21.0%)Rejected-Finance NAGPADA MUMBAI 10TH LANE KAMATHIPURA S P ROAD TELANG BLDG NO 23 ROOM NO 5 10TH LANE MUMBAI 400008 | MUMBAI | MUMBAI | MAHARASHTRA | 400008 | L4 | Rejected-Finance NOT THE LOWEST TENDERER |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
21 Aug 2023, 6:00 pmClosed
GE MH AND RH KHADKI
Military Engineer Services Garrison Engineer MH and Range Hills Range Hills Road Khadki, Pune 411003
REPAIR REPLACEMENT AND IMPROVEMENT OF LT DISTRIBUTION SYSTEM BY REPLACEMENT OF UNSERVICEABLE LT CABLES AND SWITCHGEARS AT MH KHADKI UNDER GE MH AND RH KHADKI
2023_MES_610163_1
8465/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE MH AND RH KHADKI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE MH AND RH KHADKI
₹60,000
1 Feb 2024
21 Jul 2023
23 Aug 2023
21 Jul 2023
21 Aug 2023
9 Aug 2023
21 Jul 2023 - 14 Aug 2023
Amount
Disconnecting incoming and outgoing cable/busbar connections, taking out from the cradle and overhauling of manually/electrically operated, draw out type air circuit breaker of any make, 03 or 04 pole, 415 volts, AC, current rating 800 A all as specified under: - Make : C &S (a) Cleaning of dust, spider web, foreign particles etc. (b) Removal of old grease from various parts. (c) Cleaning of various parts with CRC-2-26. (d) Check the tightness of all hardware. (e) Replacement of damaged parts shall be measured & paid seperately as supply only. (f) Re-greasing and lubricating of all rotating, moving parts. (g) Checking, setting and fault attending of spring charging mechanism operation. (h) Checking, setting and fault attending of closing and tripping mechanism operation. (j) Checking, setting and fault attending of breaker auxiliary switch contact healthiness. (k) Checking of breaker operation in isolating / test and service position. (l) Confirming of Insulation resistance value of each live part w.r.t earth.
Supply only Motor Auxiliary isolating contact assembly CS-AIH-2-116(4P)
Supply only Motor Compact UVT Coil 6D- 16D/06N-2OS, CS-AUH-V-A-NA
Supply only Motor Shunt Trip 6D-16D/06N-2OS,CS-AVH-S-116-MA
Supply only Motor Closing Coil 6D-16D/06N-2OS,CS-AVH-S-116-MA
Supply only Motor Arcing Contact, CS-ARCCONT-O8D
Supply only Motor Main isolating Contact(Jaw Contacts) CS-MIC-O8D(50k)
Supply only Motor Cradle terminal for drawout AH ACB
Supply only Motor Arc Chutes
Supply only Motor Charging Motors (220 Volts AC / DC)
Supply only Motor Control relay for charging Motor (220 V AC)
Supply only Motor Micro switch for motor cut off 6 D
Supply only Motor Drawout Handle
Supply only Motor Complete lower mechanism assly of 800 A
Disconnecting incoming and outgoing cable/busbar connections, taking out from the cradle and overhauling of manually/electrically operated, draw out type air circuit breaker of any make, 03 or 04 pole, 415 volts, AC, current rating 630-2500 A all as specified under :- Make : L & T (a) Cleaning of dust, spider web, foreign particles etc. (b) Removal of old grease from various parts. (c) Cleaning of various parts with CRC-2-26. (d) Check the tightness of all hardware. (e) Replacement of damaged parts shall be measured & paid seperately as supply only. (f) Re-greasing and lubricating of all rotating, moving parts. (g) Checking, setting and fault attending of spring charging mechanism operation. (h) Checking, setting and fault attending of closing and tripping mechanism operation. (j) Checking, setting and fault attending of breaker auxiliary switch contact healthiness. (k) Checking of breaker operation in isolating / test and service position. (l) Confirming of Insulation resistance value of each live part w.r.t earth. NOTE FOR ITEM NO 1.00 & 2.00 :- 1. The contractor has to submit detail service report for each breaker over-hauled. 2. All the necessary tools and tackles shall be arranged by contractor for the subject work. 3. The contractor shall replace minor spares like spring washers, washers locking pin, circlip, spring, small nut-bolts etc. free of cost. 4. Contractor shall to arrange for necessary cleaning agent (petrol, diesel, CRC 2-26 etc.) and lubricating material like grease, oil and lubricating sprays if any, as required for subject work. 5. The servicing / overhauling of breaker is to be carried out at site. However, if any breaker requires to be taken to contractor’s work-shop, then contractor shall to arrange transportation of such breakers from site to Work-shop and back to site without extra cost. 6. Major spares required to be replace during servicing will be measured and paid under relevant item as specified in the schedule hereforth. 7. Load break test should done in front of Engineer-in-Charge. 8. All required load bank should be carried by Contactor without extra cost. 9. Servicing work done with prior permission of Engineer-in-Charge as breaker installed inside the hospital. 10. All working executive must performed technical qualification and necessary exprience of work.
800A S1 EDO 3P SR18G
CN-CS 1000C EDO 3P
1600A S1 MDO 3P SR18
1600A S1 EDO 3P SR18G
1600A S1 EDO 4P SR18G
2000A S1 EDO 4P SR18G
2500A S1 EDO 3P SR18G
L&T ACB Spares
Supply only Pole Assy. 400-1250 S1 D/O
Supply only Pole Assy. 1600 S1 D/O
Supply only Pole Assy. 2000 S1 D/O
Supply only Pole Assy.2500 S1 D/O
Supply only CTs for SR18 800S1
Supply only CTs for SR18 1600S1
Supply only CTs for SR18 2000S1
Supply only CTs for SR18 2500S1
Supply only Jaw contact Assy 400-1250A S1
Supply only Jaw contact Assy 1600S1 / 2000S1
Supply only Jaw contact Assy 2500 S1
Supply only Vertical Terminal Adapter 400-1250 S1
Supply only Vertical Terminal Adapter 1600/2000 S1
Supply only Vertical Terminal Adapter 2000 C
Supply only Vertical Terminal Adapter 2500 S1
Supply only Arc Chute 630-1250 S1
Supply only Arc Chute 1600/2000S1
Supply only Arc Chute 2500 C/H/S1
Supply only Fixed Arcing Contact 630-1250 S1
Supply only Fixed Arcing Contact 1600 S1
Supply only Fixed Arcing Contact 2000 S1
Supply only Fixed Arcing Contact 2500S1
Supply only Moving Arcing Contact 630-1250 S1 2000S1
Supply only Moving Arcing Contact 2500 Amps
Supply only Shutter Assy 400-2000 S1
Supply only Shutter Assy 3200 S1
Supply only Cradle Terminal Assy 400-1250 S1
Supply only Cradle Terminal Assy 1600 / 2000 S1
Supply only Cradle Terminal Assy. 2500 S1
Supply only Cradle Terminal support 400-1250 S1
Supply only Cradle Terminal support 1600/2000A S1
Supply only Cradle Terminal support 2500S1
Supply only Shunt Release EA 220V DC
Supply only Under-voltage Release 240V AC
Supply only Closing Coil 240V AC/ 220V DC
Supply only FRCD 400-3200S1 (3P & 4P)
Supply only Left-plate Assy 400-3200 S1
Supply only Motor 240V AC
Supply only Spring charge motor gear assembly
Supply only Spring charge limit switch
Supply only Spring charge motor assembly plunger
Supply only Power Contact 800 amps
Supply and fix inciuding taking down following type MCCBs in various panels complete all as directed by Engineer-in-Charge.
MCCB 400 Amp four pole, Adjustable type 415 volts, 36 kA, suitable for existing of panel and as per sample
MCCB 300-350 Amp four pole, 415 volts, 36 kA suitable for existing of panel and as per sample
MCCB 250 Amp four pole, 415 volts, 36 kA suitable for existing of panel and as per sample
MCCB 200 Amp four pole, 415 volts, 36 kA suitable for existing of panel and as per sample
MCCB 160 Amp four pole, 415 volts, 36 kA suitable for existing of panel and as per sample
MCCB 125 Amp four pole, 415 volts, 25 kA suitable for existing of panel and as per sample
MCCB 100 Amp four pole, 415 volts, 25 kA suitable for existing of panel and as per sample
MCCB 63 Amp four pole, 415 volts, 25 kA suitable for existing of panel and as per sample
Supply and fix 3 Pole 630/800 Amps contractor with 2 NO + 2 NC operation coil voltage 230 Volt AC and having interlocking arrangement as per existing contractor installed at change over panel at MRS MH Kirkee
Supply and fix 3 Pole 315/400 Amps contractor with 2 NO + 2 NC operation coil voltage 230 Volt AC and having interlocking arrangement as per existing contractor installed at change over panel at MRS MH Kirkee
M & L Control wiring of ACB Panel with using suitable size PVC tray of required size including all necessary material/hardware as per existing parameter and manutacturers specification all as directed and specified
Supply and Fix in repair Rectifier Unit as per exsting panel all as specified and directed
Supply and Fix in repair SMPS Units with incoiming 240 VAC and outgoing 24 VAC as per exsting panel all as specified and directed
Supply and Fix in repair PLA relay with 5/8/11 pin and base as per exsting panel all as specified and directed
S & F in repair on delay timer for ACB in distribution panel along with necessary timer setting as per site requirement all as specified and directed
S & F in repair control break switch as per site requirement all as specified and directed
M&L for Repair of APFC panel by replacing old unserviceable damaged electrical components/ parts and providing new part same shall be measured and paid seprately as supply only for 50 KVAR.
Supply only heavy duty power contactor for capacitor of 50 KVAR
Supply only heavy duty capacitor for of 50 KVAR APP type
M&L for Repair of APFC panel by replacing old unserviceable damaged electrical components/ parts and providing new part same shall be measured and paid seprately as supply only for 25 KVAR.
Supply only heavy duty power contactor for capacitor of 25 KVAR
Supply only heavy duty capacitor for of 25 KVAR APP type
M&L for Repair of APFC panel by replacing old unserviceable damaged electrical components/ parts and providing new part same shall be measured and paid seprately as supply only for 20 KVAR.
Supply only heavy duty power contactor for capacitor of 20 KVAR
Supply only heavy duty capacitor for of 20 KVAR APP type
M&L for Repair of APFC panel by replacing old unserviceable damaged electrical components/ parts and providing new part same shall be measured and paid seprately as supply only for 12.5 KVAR.
Supply only heavy duty power contactor for capacitor of 12.5 KVAR
Supply only heavy duty capacitor for of 12.5 KVAR APP type
M&L for Repair of APFC panel by replacing old unserviceable damaged electrical components/ parts and providing new part same shall be measured and paid seprately as supply only for 10 KVAR.
Supply only heavy duty power contactor for capacitor of 10 KVAR
Supply only heavy duty capacitor for of 10 KVAR APP type
S & F in repair APFC Relay meter for 08 stage suitable for existing panel of 144 x 144 mm size
S & F in repair APFC Relay meter for 12 stage suitable for existing panel of 144 x 144 mm size
S & F in repair 80 A control fuse links top and base
S & F in repair 63 A control fuse links top and base
S & F in repair 40 A control fuse links top and base
S & F in repair 32 A control fuse links top and base
S & F in repair illuminated push buttons red/green
S & F in repair LED type RYB indicating lamps(set of three)
Supply and fix in repair Voltage meter as per site requirement sutiable incoming braker
Supply and fix in repair Amps meter as per site requirement sutiable incoming braker
Supply and fix any size id any shape of CT for Ammeter of capacity upto 800/5
Supply and fix including taking down of burnt aluminum bus bar of any size and capacity and fix with all necessary provision cutting, bending, drilling, fixing with nut bolt washers as directed by Engineer-in-Charge
M&L for servicing of LT indoor/outdoor Panel/feeder pillar box any type by disconnecting and removing all the incoming and outgoing cable connection from MCCBs, cleaning of dust with air blower, replacement of unserviceable MCCBs, burnt busbars, burnt thimbles, unserviceable indicator lamps, unserviceable Ammeter, unserviceable Volt meter, reconnections after proper cleaning of contacts with CRC solution and fixing of hanging front and rear openings with new hinges welding etc. including painting of complete panel included stand (after proper scrubbing) with synthetic enamel paint (ordinary tint) one coat as per specified colour code including writing of panel/feedar panel location using black systhetic paint complete all as specified and directed by Engr -in- charge. Note : (i) Cost of labour, painting of panel, cotton waste insulator and thimbles and T&P required for upkeeping/maint work is deemed to be included under unit rate quoted. (ii) MCCBs, Bus bars, indicator lamps, Ammeter, Volt meter, shall be measured & paid separately as supply only.
S & F Change over of capacity 100 amps 4 pole including taking down of old change over removing all connected cable and fixing of new change over with all suitable connection as specified and directed by Engineer-in-Charge
All as per item No 33 above but 250 Amps
Taking down unserviceable cable of any size upto 300 sq mm carefully from trenches / poles / ducts / LT Panel OH conducts and relay at different locations all as specified and directed by Engr-in-Charge
Supply and Fix or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of following sizes including aluminium cable gland, nut bolts washers & lugs, all as specified and directed
35 sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
120 sqmm 3.5 core
150 sqmm 3.5 core
185 sqmm 3.5 core
240 sqmm 3.5 core
Supply and fix in repair Heat shrink straight through joint LT 1100 volts grade 25-50 sqmm, 4 core, Make-Raychem, Cat No-EPKJ0130 or equivelent of M-Seal/MS Seal/3M
Supply and fix in repair Heat shrink straight through joint LT 1100 volts grade 70-120 sqmm, 4 core, Make-Raychem, Cat No-EPKJ0137 or equivelent of M-Seal/MS Seal/3M
Supply and fix in repair Heat shrink straight through joint LT 1100 volts grade 150-185 sqmm, 4 core, Make-Raychem, Cat No-EPKJ0144 or equivelent of M-Seal/MS Seal/3M
Supply and fix in repair Heat shrink straight through joint LT 1100 volts grade 240-300 sqmm, 4 core, Make-Raychem, Cat No-EPKJ0144 or equivelent of M-Seal/MS Seal/3M
Excavating in trenches, not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of pipe line, cable etc and getting out in soft / loose soil complete all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in soft/loose soil all as specified & directed
Removing excavated meterial to a distance n.exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified & directed by Engineer-in-Charge
M&L for crushed stone grid for cushioning to under ground cable in trenches/existing cable trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable complete all as specified and directed by Engr in charge. Note:- Measurement shall be taken after gentling puning.
M&L for PCC cable cover class LV, type-I, flat size 250x 150x 40 mm factory casted ISI marked all as specified and directed.
S&F in repairs 400A FN Type switch with bollet HTC Fuse. Make L & T or equivalent make as approved by GE.
PURVA ELECTRICALS AND ENGINEERS
Adinath Technical Services
SHREE SHIV ELECTRICAL
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .