Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹4.2 L+₹57,973 (16.2%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹4.3 L+₹70,441 (19.7%)Rejected-AOC | L3 | Rejected-AOC L3 | |
| 4 | L4₹4.3 L+₹72,540 (20.2%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹4.3 L+₹76,120 (21.2%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹7.5 L
EMD Value
₹14,934
Closing Date
13 Aug 2020, 3:00 pmClosed
Executive Engineer
EandM, APWD, Prothrapur, Port Blair
Re- Roofing of Workshop Building for Electrician Trade at ITI Dollygunj.
2020_APWD_627_1
NIT No.12/EE/EandM/20-21
Open Tender
Electrical Works
Item Rate
60 days
South Andaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
Yes
Executive Engineer, EandM Division, APWD
₹14,934
Yes
21 Oct 2020
30 Jul 2020
17 Aug 2020
30 Jul 2020
13 Aug 2020
31 Jul 2020
31 Jul 2020 - 3 Aug 2020
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FR PVC insulated copper conductor single core cable etc as required. a) Group-C
Wiring for light/power plug with 2x4 sq.mm FR PVC insulated copper conductor single core cable in surface/recessed PVC conduit along with 1 No 4 sq.mm FR PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/sub main wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
Supplying of following sizes of XLPE insulated Heavy duty Un-armoured Aluminium conductor UG Cable of 1.1 KV Grade conforming to IS : 7098 (Part - I) and IS No. 1554 (part - I) 1988 as applicable Make : CCI / GLOSTER / Havells / Polycab / Finolex. a) 6 Sq.mm x 4 Core
Supplying of following sizes of XLPE insulated Heavy duty Un-armoured Aluminium conductor UG Cable of 1.1 KV Grade conforming to IS : 7098 (Part - I) and IS No. 1554 (Part - I) 1988 as applicable Make : CCI / GLOSTER / Havells / Polycab / Finolex. a) 6 Sq.mm x 2 Core
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. a) Upto 35 sq. mm
Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
Supplying and fixing of surface mounted LED Batten fitting with extruded aluminium housing similar to PHILLIPS type - BN 550W LED 12 - 6500 or its equivalent.
Supplying and fixing of LED highbay fitting with in - built control gear housing similar to CROMPTON Galaxy I Cat - LHBBX - 90 - CDL - or its equivalent.
Supplying of AC Ceiling Fan (1200 mm) Sweep ISI marked 5 Star rated i/c down rod of standard length 30 cm with all accessories similar to Havells ES - 50 Premium 5 or its equivalent.
Installation, testing and commissioning of ceiling fan/ Wall Fan, including wiring the down rods of standard length (upto 30 cm) wiring with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable etc.as required.
Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing of 60 Watt LED Street Light Fitting similar to Crompton Cat No. LSTO - 60 - CDL or its equivalent.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator). a) 2 + 12 way, Single door
Supplying and fixing 5 amps to 32 amps rating, 240 volts, "C" series, miniature circuit breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole
Supplying and fixing 6 amps to 32 amps rating, "B" Series SP MCB (In Accordance with IS / IEC 60898 - 1) 240V, 50 Hz, 10 KA. Suitable for lighting and other domestic loads as required. a) Single pole
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 40 amps
Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2000mm, outer dia 50 mm, inner dia 25 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required
M K ENGINEERING
JOY GURU ENTERPRISES
M/s Sai Electrical Works
NAVJEEVAN ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .