Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.9 LAccepted-AOC 00 KIWADI SAFEDABAD BARABANKI BARABANKI UTTAR PRADESH 225001 | BARABANKI | UTTAR PRADESH | 225001 | L1 | Accepted-AOC L1 bidder is techno commercially qualified. | |
| 2 | L2₹30.1 L+₹50,770 (1.71%)Rejected-Finance AT DHORI STAFF QTR PO DHORI DIST BOKARO JHARKHAND | BOKARO | JHARKHAND | 825102 | L2 | Rejected-Finance Bid not be opened as per NIT terms. | |
| 3 | Rejected-Technical AT KARGALI BAZAR BERMO DIST BOKARO PIN NO 829104 JHARKHAND | BOKARO | JHARKHAND | 829104 | - | Rejected-Technical Technically disqualified |
Tender Value
₹32.4 L
EMD Value
₹40,500
Closing Date
27 Feb 2025, 10:00 amClosed
SO(EnM), Dhori
Office of the General Manager, Dhori area, Po- Dhori , pin-825102, Bokaro
(A)Reorganisation of the lighting OH line within the R/store campus (B)Complete repairing the house wiring system under conduction of the OH line sheds and offices(C)Fresh wiring of conference hall at Regional store, Dhori under CCD.
2025_CCL_329073_1
GM(D)/SO(EnM)/DA/24-25/67
Open Tender
Electrical and Maintenance Works
Item Wise
365 days
CCD
please refer tender documents
2 documents required · 2 mandatory
₹40,500
1 Apr 2025
15 Feb 2025
28 Feb 2025
17 Feb 2025
27 Feb 2025
17 Feb 2025
17 Feb 2025 - 24 Feb 2025
Amount
Part – A
Erection of cradle guard as required.
Supplying and erection of stay set complete (galvanised) with 19/20 mm dia x 1.8 metres long stay rod, anchor plate of size 45 cm x 45 cm x 7.5 mm, thimble, stay clamps, turn buckle (20 mm x 60 cm), 7/4.00 mm dia G.I. stay wire and strain wire and strain insulator etc in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Supply of cement pole.
Erection of RCC/PCC pole of following length in brick ballast and ramming the foundation, finishing with 150 mm thick cement concrete (1:3:6) layer on top with including excavation and re-filling etc. as required. : Above 6.5 metre and upto 8.0 metre
Supplying of channel iron 75 mm x 40 mm x 6 mm (7.14 kg per metre) cross arm for 2 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with and finished paint as required.
Supplying of channel iron 75 mm x 40 mm x 6 mm (7.14 kg per metre) cross arm for 4 wire over head line complete with clamps, bolts, nuts and washer etc including drilling of holes for insulator pins etc (as per drawing) and painting with primer and finished paint as required.
Erection of angle iron/ channel iron cross arm on wood/RCC/PCC/ steel tubular/ rail pole etc. as required.
Erection of all aluminium conductor of 7/1.96mm to 7/3.10 diameter and above including binding etc. as required.
Supplying and erection of 100 mm x 65 mm pin insulator with G.I. spindle and nuts etc. as required.
Supplying and erection of 75 mm x 90 mm shackle insulator with G.I. bolts, nuts and straps etc. as required.
Supply of G.I. wire.
Erection of G.I. wire no. 8 SWG including binding etc. as required.
Fixing of LED light top of the pole.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C a) Light point (for store shed)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with piano type switch, phenolic laminated sheet, suitable size MS box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C b) Tube light point (for store shed)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required: Group C a) Fan point (for office building)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required: Group C b) Light point (for office building)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required: Group C c) Tube light point (for office building)
Supplying and fixing metal box of 150 mm x 75 mm x 60 mm deep (nominal size) on surface in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing metal box of 180 mm x 100 mm x 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
Supply of changeover switch 100 Amp.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. a) 63 Amp. TP&N
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. b) 100 Amp. TP&N
Clamp
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 amps 240 volts ‘’C’’ curve DP MCB complete with connections, testing and commissioning etc. as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : a) 2 x 1.5 sq.mm + 1 x 1.5 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : b) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : c) 2 x 4 sq.mm + 1 x 4 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : d) 2 x 6 sq.mm + 1 x 6 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : e) 2 x 10 sq.mm + 1 x 6 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : f) 4 x 16 sq.mm + 2 x 6 sq.mm earth wire.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Supplying and fixing 3 pin, 5 amps ceiling rose on the existing junction box/ wooden block including connection etc. as required.
Supply and fixing of wall cat light 18 watt
providing and making steel pole collar with cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) of specified size and shape including form work, plastering if specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/pipe not to be deducted)
Earthing with copper earth plate 600 mm x 600 mm x 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required (for computer point)
PArt – B
Clearing jungle including uprooting of rank vegetation, grass, Brush wood, trees and saplings of girth upto 30cm measured at a height of 1M above ground level and removal of rubbish upto a distance of 50M outside the periphery of the area cleared.
Part – C
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group Ca) Bulb point
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C b) Tube light point
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C c) Fan point
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C d) Ex-haust fan point
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C e) Call bell point
Supplying and fixing metal box of 150 mm x 75 mm x 60 mm deep (nominal size) on surface in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing metal box of 180 mm x 100 mm x 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 amps 240 volts ‘’C’’ curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate as required.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 100 Amp TP&N.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : 2 x 4 sq.mm + 1 x 4 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : 2 x 1.5 sq.mm + 1 x 1.5 sq.mm earth wire.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required : 4 x 16 sq.mm + 2 x 6 sq.mm earth wire.
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long with charcoal/ coke and salt as required.
Supplying and fixing 3 pin, 5 amps ceiling rose on the existing junction box/ wooden block including connection etc. as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 63 Amp TP&N (for light control)
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 amps ‘’C’’ curve, SP, MCB, in sheet enclosure, on surface or in recess, with chained metal cover for socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Installation, testing and commissioning of pre-wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supply of Exhaust fan.
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. : upto 450 mm sweep.
Total impact of GST for the purpose of CTC
M/S A.R. CONSTRUCTION (BID ID -1132516)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .