Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.8 LAdmitted-Finance 211 KRALPORA BUDGAM JAMMU KASHMIR 191113 UDYAM JK 04 0011111 | BUDGAM | JAMMU AND KASHMIR | 191113 | L1 | Admitted-Finance | |
| 2 | L2₹15.2 L+₹40,225 (2.72%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹15.7 L+₹89,720 (6.06%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | L4₹16.5 L+₹1.7 L (11.8%)Admitted-Finance | L4 | Admitted-Finance | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-Tender Fee and EMD Not submitted |
| Sl No | Description | Qty | Unit | S and S Enterprises L4 | sofi and sons L2 | M/S WANI ELECTRA & SUPPLIERS L1 | M/S WATT ELECTRICAL CONTRACTS L3 |
|---|---|---|---|---|---|---|---|
| 1.01 | Providing,Loading , Unloading ,Carriage , Installation ,Testing and Commissioning of 400 KVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Pre Ammendment ( Cu wound ) with OCTC (Off Ckt Tap Changer), and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable. | 1 | No | 8,99,000 ₹8,99,000 | 8,45,000 ₹8,45,000 Lowest | 11,00,000 ₹11,00,000 | 8,51,217 ₹8,51,217 |
| 1.02 | Providing,Fixing ,Testing and Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type | 1 | No | 3,500 ₹3,500 | 3,000 ₹3,000 | 2,000 ₹2,000 Lowest | 12,121 ₹12,121 |
| 1.03 | Providing,Fixing ,Testing and Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type along with earthing of operating handle ( including lugs/thimbles --all accessories) | 1 | Set | 11,000 ₹11,000 | 12,000 ₹12,000 | 3,000 ₹3,000 Lowest | 12,121 ₹12,121 |
| 1.04 | Providing,Fixing ,Testing and Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A | 1 | Set | 4,500 ₹4,500 | 3,500 ₹3,500 | 2,000 ₹2,000 Lowest | 5,121 ₹5,121 |
| 1.05 | Providing,Laying ,Testing and Commissioning of 400 mm² 1.1kV Grade,unarmoured XLPE Insulated Stranded Conductor FRLS type | 30 | Mtr | 1,380 ₹41,400 | 500 ₹15,000 | 100 ₹3,000 Lowest | 777 ₹23,310 |
| 1.06 | Providing ,Loading , Unloading ,Carriage , Installation ,Testing and Commissioning of 9 Long Pole alongwith earthing channel piece (ST-410 SP33) . | 3 | No | 16,900 ₹50,700 | 18,000 ₹54,000 | 10,000 ₹30,000 Lowest | 15,786 ₹47,358 |
| 1.07 | Providing,fabrication,Fixing of GI Channel/Angle/Flat of sizes including clamps for sub station (as per approved Drawings) | 725 | Kgs | 135 ₹97,875 | 140 ₹1,01,500 | 95 ₹68,875 Lowest | 171 ₹1,23,975 |
| 1.08 | Providing,Fixing of Galvinized Nuts and Bolts. | 30 | Kgs | 135 ₹4,050 | 130 ₹3,900 | 95 ₹2,850 Lowest | 121 ₹3,630 |
| 1.09 | Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. (as per approved Drawings) | 3 | No | 2,000 ₹6,000 Lowest | 4,000 ₹12,000 | 2,000 ₹6,000 Lowest | 5,555 ₹16,665 |
| 1.10 | Providing,Fixing ,Testing and Commissioning of 11 kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm | 15 | No | 500 ₹7,500 | 200 ₹3,000 | 100 ₹1,500 Lowest | 333 ₹4,995 |
Tender Value
₹18.8 L
EMD Value
₹37,600
Closing Date
10 Mar 2026, 2:30 pmClosed
Ex. Engineer ED 2nd
Office of Ex. Engineer ED 2nd
Providing, Installation and commissioning of dedicated 400 KVA Tap Changing Transformer ( OFF CIRCUIT TAP CHANGER TYPE) at Kashmir Government Polytechnic, Srinagar
2026_PDD_305076_1
e-NITNoED-II21 of 2025-26 Dt 6-2-26
Open Tender
Electrical Works
Turn-key
45 days
Rajbagh
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Ex. Engineer ED 2nd
₹37,600
Yes
11 Jun 2026
3 Mar 2026
12 Mar 2026
3 Mar 2026
10 Mar 2026
3 Mar 2026
Providing,Loading , Unloading ,Carriage , Installation ,Testing and Commissioning of 400 KVA 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, Pre Ammendment ( Cu wound ) with OCTC (Off Ckt Tap Changer), and with LV Cable Box having detachable Al. Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable.
Providing,Fixing ,Testing and Commissioning of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Providing,Fixing ,Testing and Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type along with earthing of operating handle ( including lugs/thimbles --all accessories)
Providing,Fixing ,Testing and Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing,Laying ,Testing and Commissioning of 400 mm² 1.1kV Grade,unarmoured XLPE Insulated Stranded Conductor FRLS type
Providing ,Loading , Unloading ,Carriage , Installation ,Testing and Commissioning of 9 Long Pole alongwith earthing channel piece (ST-410 SP33) .
Providing,fabrication,Fixing of GI Channel/Angle/Flat of sizes including clamps for sub station (as per approved Drawings)
Providing,Fixing of Galvinized Nuts and Bolts.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover. (as per approved Drawings)
Providing,Fixing ,Testing and Commissioning of 11 kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing,Fixing ,Testing and Commissioning of LT Distribution Box for:- 400 kVA DTR with a)630 Amp MCCB 3P 36 kA adjustable 1 No for incomer & b) 400 Amp MCCB 3P 35 kA adjustable typer 1 No C)200 Amp MCCB 2 No fixed type for Outgoing Circuits . Including link disconnectors, d)32 Amp SP MCB ( as per drawing)
Providing of Painting of Poles with two coats of Red Oxide and two coats of Aluminium Paint per pole
Providing , Fabrication, fixing of pole post of MS Pipe Post 10 feet long and 6 inch diawith proper size end Plates for support to Bed Structure including earthing, mproper Paint ( Redoxide/ aluminum /tractor orange ) and cement bottoming of 0.25 Cum / pole post
Providing,Fixing of 11 kv Danger Plates with Clamps
Providing,Fixing of Anti Climbing devices using GI Barbed Wire with end clamps (2 Kg Barbed wire per job/pole with 2 GI Clamps with GI Nuts and bolts with washers )
Providing of Cement bottoming of 9 mtr ST pole using 1:2:4 mix as per Standards 0.48um /pole
Providing, Fixing aluminium lugs of 400/300 mm sq size
Providing ,Loading , Unloading ,Carriage , Installation ,Testing and Commissioning of 8 Mtr. Long Pole alongwith earthing channel piece (ST-410 SP15)
Providing,Laying ,Testing and Commissioning of 300 mm² 1.1kV Grade,unarmoured XLPE Insulated Stranded Conductor FRLS type
Providing,Fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting set of 3 Nos
Providing of Earthing of 9mtr and 8 mtr ST poles complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Providing of Cement bottoming of 8 mtr ST pole using 1:2:4 mix as per Standards 0.40cum /pole
Providing , fixing / laying of conductor 30 mm sq ACSR for tapping of HT line / Jumpers
Providing , fixing / laying of conductor 50 mm sq ACSR for LT Network connections/ Modification.
Providing , fixing of GI Muki Clamps fibricated out of 50x8 mm galvinized flat (0.75 Kg per Muki) having end inner dia 18 mm for Shackle insulatuo suitable for ST Pole with back clamp and galvinized nuts and bolt
Providing , fixing of 16 KN Polymer LT Shackle insutor
Straightening of existing tilted LT poles including its cement bottoming of using 1:2:4 mix as per Standards 0.30 cum /pole
Dismantelling of existing LT wooden/ST pole
Providing , installation testing & commissioning of 11kV Pilfer resistant metering cubicle for 3phase 4 wire metering system made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Panel having two compartments upper Meter compartment and lower CT/PT compartment. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The metering panel shall be provided with two No G.I channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening the LV chamber door. (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation testing & commissioning of A) set of three numbers ,Single Phase, Single core, single ratio, Epoxy resin Cast Current Transformers suitable for 11kV, copper wound primary type with rated burden 5VA and accuracy class 0.5 or better and conforming to IS2705 (part-I & II) amended upto date. ISF shall be upto 5. The CT ratio shall be 15/5 B) 11kV/ 110 V, Three phase epoxy resin cast PT with rated burden 15VA per phase and accuracy class 0.5 or better and conforming to IS:3156 (part-I&II) amended upto date with proper colour coded identification. PTs shall be of uniform insulating and withstand separate source 23kV pf for one minute. (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation testing & commissioning of Bus Bar CTs bus bar:- 40x6 mm copper strip or adequate size ,PTs bus bar: Copper wire 8 SWG or 30x0.6mm copper flat strip to connect PT terminal or adequate size duly insulated by the monoplast tape . PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm² (RYB) and for PT wiring minimum wire size shall be 2.5 mm² (RYB). Copper Lugs preferably ring type duly crimped for termination of wires and tapes Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm² (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation testing & commissioning of BIDIRECTIONAL 3Ph 3 Wire HT CT/PT operated Fully static Smart Tri-Vector Energy meter DLMS Compliant Category 'C' with RS 232 port for modem compatibility. 11kV/110V, Ph-Ph (3P,3W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc .Independent flexible PVC pipes for CT wiring and PT wiring of appropriate size from HT compartment to meter compartment Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 5) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation testing & commissioning of 3 Core 11 kV Aluminium cable XLPE armoured 35 mm² including cost of clamp for its fixing where ever required.
Providing , installation testing & commissioning of Cable termination kits suitable for 3 x 35 mm² XLPE Cable (Indoor/Outdoor) (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation testing & commissioning of Earthing by way of 40 mm 2.5 mtr long GI Pipe. Job includes , excavation, enhancement material and Main Hole Chamber (500x450x600)mm with frame and cover. (for 11 KV HT METERING CT AND PT OPERATED)
Providing , installation of LT line Spacers of appropiate size and configration
Providing , installation of Wedge connectors/ PG clamps
Providing and submission of both Pre and Post work execution Geo-tagged coloured photographs of the subjected work on A4 size glazed photo paper ( 2 pics per page ) pre and post
Providing and fixing of fluorescent sign board of appropiate size ( 4'X3') showing details of the work like name of the Department, Name of the work,Head of account, Date of Start ,Date of Commissioning,and any othe relivant details as rwquired ,fixed over GI Angle of appropiate size and Specification.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.78 MB
retender21New.pdf
Tender Documents • 0.77 MB
SBD21VF.pdf
Tender Documents • 1.72 MB
BOQ_990986.xls
BOQ • 0.29 MB
Listofall.pdf
Tender Documents • 0.40 MB
spe21new.pdf
Tender Documents • 25.50 MB
964ploadingnameobiddersofPPKPDCL.pdf
Tender Documents • 2.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .