Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹70.5 LAccepted-Finance | L1 | Accepted-Finance Accepted as 1stLowest Bidder for the execution of subjected e-NIT work | |
| 2 | L2₹77.1 L+₹6.5 L (9.27%)Accepted-Finance | L2 | Accepted-Finance Accepted as 2nd Lowest Bidder for the execution of subjected e-NIT work | |
| 3 | L3₹79.3 L+₹8.8 L (12.4%)Accepted-Finance | L3 | Accepted-Finance Accepted as 3rd Lowest Bidder for the execution of subjected e-NIT work | |
| 4 | Rejected-Technical | - | Rejected-Technical Non-Submission of EMD, NIC code ineligible, e-NIT CVC criteria not met |
Tender Value
₹86.0 L
EMD Value
₹1.7 L
Closing Date
16 Aug 2022, 4:00 pmClosed
Executive Engineer, KPDCL, ED2nd, Rajbagh
Office of the Executive Engineer, KPDCL, ED2nd, Rajbagh, Srinagar
Renovation and Modernization of existing 02 No 250 kVA and 01 No 400 kVA Sub-Stn and laying of LT underground distribution network for providing power supply to Dongas along Left Bank of Jhelum River -(under Srinagar Smart City Project) on SITC Basis
2022_PDD_181714_1
ED-II/05 of 2022-23 Dated 28/07/22
Open Tender
Electrical Works
Turn-key
45 days
Left Bank of Jhelum River Rajbagh, ED2nd Srinagar
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,000
Ex. Engineer,KPDCL, ED2nd Credited to MH0801 Power
₹1.7 L
20 Sept 2022
30 Jul 2022
17 Aug 2022
30 Jul 2022
16 Aug 2022
2 Aug 2022
30 Jul 2022 - 2 Aug 2022
Amount
Substation Renovation & Modernization
Supply, Installation, Testing and Commissioning of 250 kVA 11/0.433 kV, 3-phase Distribution Transformer Energy Level-2 (Copper Wound) with Bimetallic Terminal Connectors (HT / LT side both), with LV Cable Box having detachable Aluminium Gland plate including its loading, carriage and unloading at site. (Test Certificates to be provided) "Bidders are advised to quote testing charges for 250 kVA EL2 DT also as same shall be got tested at some equipped SSI unit/firm before installation at site"
Supply, Installation, Testing and Commissioning of 400 kVA 11/0.433 kV, 3-phase Distribution Transformer Energy Level-2 (Copper Wound) with Bimetallic Terminal Connectors (HT / LT side both), with LV Cable Box having detachable Aluminium Gland plate including its loading, carriage and unloading at site. (Test Certificates to be provided) "Bidders are advised to quote testing charges for 400 kVA EL2 DT also as same shall be got tested at some equipped SSI unit/firm before installation at site"
Supply, Installation, Testing and Commissioning of 11 KV Gapless Surge Arrestor, 9 kV, 10 kA, LA with polymer housing, Stn. Type
Providing, Fabrication and Fixing of 9' Steel Pole butt support with 6" inner dia and 6mm thickness (including base plates) including cement bottoming
Supply, Installation, Testing and Commissioning of 11 KV Horn Gap Fuse Set 3 Phase 200A
Supply, Installation, Testing and Commissioning of 11 KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type comprising of 9 No. insulators, pipes and lock pad etc complete job
Providing and Painting of ST Poles with 2 coats of Red Oxide and 1 coat of Aluminium Paint
Providing, Fabrication and Fixing of Galvanized Ch. Iron 8.5 ft long x 2 No. (100x50x6mm) duly fabricated
Providing, Fabrication and Fixing of Galvanized Ch. Iron 8.5 ft long x 8 no. (75x40x6mm) duly fabricated
Providing, Fabrication and Fixing of Galvanized Channel Support for Operating Handle of GO AB Switch - Top (75X40 ISLC) 0.515 m long (1 No), Bottom(75X40 ISLC) 0.343 metre long (1 No) and Galvanized Iron Bracing support for operating handle (50X80 ISLC) 500 mm (1 No)
Supply, Laying, Testing and Commissioning of 300 mm sq 1-Core, 1.1 KV Grade xlpe Insulated Unarmoured Conductor FRLS Type.(4 runs)
Supply, Laying, Testing and Commissioning of 630 mm sq 1-Core, 1.1 KV Grade xlpe Insulated Unarmoured Cable FRLS Type.(4 runs)
Providing, Fabrication and Fixing of Galvanized Angle Iron Brace 10 ft x 2 no. (50x50x6mm) as Transformer Belt - duly fabricated including side angle support
Providing, Fabrication and Fixing of Galvanized Angle Iron Brace (35x35x6mm) for cable tray - duly fabricated
Providing and Laying of Earthing of substation Complete with all accessories --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. Interconnection of 3 earthing pipes by 50x60 mm GI Flat. GI Strip of size 25 mm x 3 mm for neutral earthing ( Two distinct connections) / connection of transformer body and LA. besides 8 sgw GI Wire conncetions for Transformer body , LT Distribution Box (2 connections) , AB Switch Handle (2 distinct connections) and earthing terminal of Poles (Description as per Approved Drawing Titled Earthing for 250/400 KVA DTR on 9 mtr Poles)
Supply, Installation, Testing and Commissioning of LT Distribution Box housing 400 amps adjustable TP MCCB for incomer, 200 Amps /160 amps TP MCCBS outgoing, busbars of appropriate rating & SFU's (link disconnector) for Outgoing Circuits including glands for incomming and outgoing circuits (as per drawing attached). This also includes cost of galvanized angle iron frame (50x50x6mm), duly grouted.
Supply, Installation, Testing and Commissioning of LT Distribution Box housing 630 amps adjustable TP MCCB for incomer, 200 Amps TP MCCBS outgoing, busbars of appropriate rating & SFU's (link disconnector) for Outgoing Circuits including glands for incomming and outgoing circuits (as per drawing attached). This also includes cost of galvanized angle iron frame (50x50x6mm), duly grouted.
Providing and Fixing of Aluminium Solderless Clamp suitable for 250 kVA transformer
Providing and Fixing of Aluminium Solderless Clamp suitable for 400 kVA transformer
Providing and Fixing of 300 sqmm Aluminium lugs
Providing and Fixing of 630 sqmm Aluminium lugs
Providing and Fixing of 11 KV Danger Plate with Clamp
Providing and Fixing of Galvanized Nuts and Bolts of Sorts
Providing and Fixing of GI Wire 8 SWG
Providing and Fixing of Galvanized Iron Pole Collars 50x8 mm (Back Clamps Dimensions as per Drawing attached) for D.O/Fuse/Operating handle/ AB Switch/Belting Angle etc (1.44 kg weight per Clamp)
Providing and Fixing of Anti-Climbing Device with Clamps
Providing and Earthing of ST Poles 9 mtr long using GI Pipe 40 mm or GI Rod 20 mm 2.5 mtr long through GI Strip.
Providing and Fixing of 11 KV Polymeric composite Pin Insulator 12 kV, 5 kN, Lighting Impulse 75 kV Positive and 80 kV Negative, creepage distance 320 mm (complete)
Providing and Fixing of 11 kV Polymeric composite Disc Insulator 12 kV,min failing load 45 kN, Lighting Impulse 75 kV Positive and 80 kV Negative, creepage distance 320 mm with fittings
Providing and Laying of Cement Bottoming of ST Poles 9 mtr long 1:2:4 mix as per REC standards (0.5 cum /pole)
Providing and Fixing of Suspension Clamp with Eye Hook
Dismantaling of old 03 No. Sub-Stations
Dismantaling of old sub-stations (DT/ DT equipments /Channels/angle brace arms) including its loading, carriage and unloading upto divisional stores at Bemina
Dismantaling of old ST/wooden poles along with single phase conductor spans including its loading, carriage and unloading upto divisional stores at Bemina
LT Line
Supply, Laying, Testing and Commissioning of 70 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type
Supply, Laying, Testing and Commissioning of 120 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type
Supply, Laying, Testing and Commissioning of 185 mm² 3½ Core Cable,1.1kV Grade, Armoured, XLPE Insulated Stranded Conductor FRLS type
Providing and Laying of Corrugated HDPE Pipes (3 inch inner dia)
Supply, Installation, Testing and Commissioning of 3 phase 4 wire, 415V, 1no. of 4 pole 160 Amps incoming MCCB along with SFU, Distribution Pillar suitable for outdoor installation, made out of CRCA sheet painted through 7-tank process with PU painted Busbars Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories (to be housed on a concrete block of height atleast 1.5' above ground) including arrangement for entry of cables in and out through concrete block . (as per drawing attached). This also includes Earthing job using GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Supply, Installation, Testing and Commissioning of 3 phase 4 wire, 415V, 1no. of 4 pole 100 Amps incoming MCCB along with SFU , Distribution Pillar suitable for outdoor installation, made out of CRCA sheet painted through 7-tank process with PU painted Busbars Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories (to be housed on a concrete block of height atleast 1.5' above ground) including arrangement for entry of cables in and out through concrete block . (as per drawing attached). This also includes Earthing job using GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Supply, Installation, Testing and Commissioning of 3 phase 4 wire, 415 V, 1no. of 200 Amps incoming MCCB along with SFU , Distribution Pillar suitable for outdoor installation, made out of CRCA sheet painted through 7-tank process with PU painted Busbars Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories (to be housed on a concrete block of height atleast 1.5' above ground) including arrangement for entry of cables in and out through concrete block . (as per drawing attached). This also includes Earthing job using GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Supply of HDPE pipes (3 inch inner dia) with necessary sockets and bends for housing the 120mm² and 70mm² 3½ Core Cables,1.1 kV Grade
Supply of HDPE pipes (4 inch inner dia) with necessary sockets and bends for housing the XLPE 185mm² 3½ Core Cable,1.1kV Grade
Laying of HDPE pipe in excavated trench alongwith laying of 3.5 core LT cables
Excavation (width x depth = 1.5'x2.5') in any type of soil including hard laterite soil
Back Filling of required volume of excavated soil with proper disposal of remaining earth material to suitable place
Providing and Laying of Warning Tape
Providing and Fixing of Route Marker at appropriate positions
Supply, Installation, Testing and Commissioning of 3 phase 4 wire, 415 V, 1no 4 pole MCCB of rating 100, 63 Amps (as per site location) with outgoing 02 No 40 Amps SP MCBs for Service Connections, Distribution Service Pillar (double door) suitable for outdoor installation with space for housing 02 nos Energy meters , made out of CRCA sheet painted through 7-tank process with PU painted Busbars Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories (to be housed on a concrete block of height atleast 1.5' above ground) including arrangement for entry of cables in and out through concrete block (as per drawing attached). This also includes Earthing job using GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Supply, Installation, Testing and Commissioning of 3 phase 4 wire, 415 V, 1no 4 pole MCCB of rating 160, 100, 63 Amps (as per site location) with outgoing 02 No 40 Amps SP MCBs for Service Connections, Distribution Service Pillar suitable for outdoor installation with space for housing Energy meters(02 nos) , made out of CRCA sheet painted through 7-tank process with PU painted Busbars , Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories (to be housed on a concrete block of height atleast 1.5' above ground) including arrangement for entry of cables in and out through concrete block . (as per drawing attached). This also includes Earthing job using GI Pipe 40 mm 3 mtr long through GI Strip 25x3 mm
Providing and Laying of 16 mm² Cable (1C) 1.1k V Grade, PVC Insulated Stranded Conductor Water Resistant Cables AD7 PROTECTION AGAINST WATER IN ELECTRIC CABLES. (including conduit as well)
Laying of LT cable through trenchless HDD (Horizontal directional drilling), wherever required, (including road cross/parking spaces etc) - cost of HDPE pipes excluded
M/s Mohammad Yaqoob Baba
M/S MOHAMMAD IDREES KUCHAI
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .