Loading…
Loading…
Tender Value
₹3.7 L
EMD Value
₹7,400
Closing Date
22 Sept 2026, 1:00 pm
Executive Engineer Mand H D Srinagar
Executive Engineer Mand H D Srinagar
Replacement of old damaged panel by way of supply installation testing and commissioning of floor mounted power distribution electric control panel for boiler house at govt. bone and joint hospital srinagar
2026_PWDJK_324363_1
MHDS/TS /2026-27/58/e-tendering Dated11.09.2026
Open Tender
Electrical Works
Percentage
30 days
govt. bone and joint hospital srinagar
as detailed in nit
4 documents required · 4 mandatory
₹200
Executive Engineer MHD Srinagar or AO
₹7,400
11 Sept 2026
11 Sept 2026
22 Sept 2026
11 Sept 2026
22 Sept 2026
11 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling of the existing defunct electric panel at boiler house by way of disconnecting the existing electrical connections/ cable to the panel and the existing old MCCB and change over Panel . The job also includes cutting of the existing cable tray and fixed angle iron stand to the panel for making access for the new electrical panel along with re routing of the cable tray and the overlaid cables. The job includes SITC of cubical type floor mounted power distribution electrical panel for Boiler House of Govt. Bone and Joint Hospital, Srinagar suitable for 415V, 3 Phase, 4Wire 50Hz AC supply system fabricated in compartmentalized design .The panel shall be extensible ,high conductivity, air -insulated aluminium main busbars supported by heavy duty, non-hygroscopic, flame retardent DMC/SMC blocks. The entire assembly must be certified to feature a modern short circuit fault withstand capacity rating of 50 KA for 1 second includes 2 no of explicit copper earthing studs, interior copper bus link bridges to specific switch gears, and standarized 1.5 sqmm copper FRLS copper interior control circuit pre wiring. The panel shall be fabricated out of high grade CRCA sheet steel ,Framework structural chassis and structural panel doors must feature a minimum thickness of 2.0mm .Base/top detachable cable gland entry plates must feature upgraded thickness of 3.0mm to ensure structural load capacity for heavy cable entry loops .The details of pre wired panel are as follows; Size:-LBH=5'X 7'X18".The Job also includes fixing of panel with the wall as per the directions of the site engineer. (The earthing of the equipment is to be done as per recommendations of the site engineer.)
• Cubicle 1 :- 400 Amp ,4 Pole MCCB having following specifications and Conforms to IS/IEC 60947-2, 36KA breaking Capacity, Ics= 100% of Icu*Adjustable overload settings: 0.8 - 1.0 x In,Adjustable short-circuit settings: 6 - 10 x In, along with Phase barriers Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Cubicle 2 :- 400 A, 4-pole on-load changeover switch Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Cubicle 3 :- 400 A TPN (Three Phase & Neutral) Aluminum Busbar
• Cubicle 4: A Digital Multifunction Meter (MFM) with matching Current Transformer (CT) Coils to monitor V, I, Hz, and PF. Preferable makes:-Selec/schneider electric/siemens/meco instruments /Powertrac/multispan
• Cubicles 05 to 08 (for 04 No. Boilers):shall comprise of below mentioned items and Conforms to IS/IEC 60947 - 2 32 Amp TPN Industrial High-Rupturing MCBs having 15kA Breaking Capacity, C-Curve characteristic.
• Cubicles 09 to 14 :-Shall comprise of below mentioned item and Conforms to IS/IEC 60947-4-1 & IEC 60947-4-1
50 Amp 3-Pole MCCB with adjustable thermal-magnetic motor-protection trip unit coupled with ML2 Starter (AC3 rating: 32A, AC1 rating: 40A).
o Protection: Overload relay with a range of 28A–42A and an integrated Single Phase Preventer (SPP) for 06 No. HW Circulation Pumps).
o Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Cubicles 15 & 16 :Shall comprise of below mentioned item and Conforms to IS/IEC 60947-4-1 & IEC 60947-4-1
• 32 Amp,3 Pole MCCB with ML1.5 Starter having AC3 rating of 25A and AC1 rating of 25A Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Single Phase Preventer for HWG oil Pump -2No.Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Cubicle 17: 02 No. 10A TPN MCB for Raw Water Pumps - 2No .Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
• Cubicle 18 : single pole10 Amp MCB for lighting circuit etc - 10No. Preferable Makes:-Lauritz Knudsen/Schneider /ABB/Siemens/Havells/Legrand
Providing and fixing of shock proof and anti skid class A electrical insulation rubber sheet in a Standard width of 1 Mtr with Length 2 Mts and can resist upto 3.3KV.The item shall confirm to IS-15652-2006.The Job also includes testing of the panel on the full load | 1 | Complete job | 3,70,000 | ₹3,70,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.68 MB
Tendernotice_2.pdf
PDF • 0.53 MB
BOQ_1094089.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .