Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.1 LAccepted-AOC 225 NAROT COLONY MODEL TOWN PATHANKOT PB 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC OK | |
| 2 | L2₹8.8 L+₹1.7 L (24.3%)Rejected-Finance B XXIII 56 A PREM NAGAR SAINGARGH PATHANKOT 145001 PUNJAB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance Not being L1 |
Tender Value
Refer Docs
EMD Value
₹24,000
Closing Date
9 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Pathankot
HQ CWE Pathankot
REPAIR/MAINT OF HT NETWORK OF DOMESTIC AND DEPOT AREA AND ALLIED WORK AT UNCHIBASSI UNDER GE SOUTH PATHNAKOT
2020_MES_376826_1
CWE/P-76/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Unchibassi
class E and above Category b ii
9 documents required · 9 mandatory
₹500
Yes
GE (South) Pathankot
₹24,000
Yes
26 Oct 2020
11 Sept 2020
12 Oct 2020
11 Sept 2020
9 Oct 2020
25 Sept 2020
60 days
Amount
Excavation in trenches n.exc 1.5 metre wide and not exc 1.5 metre depth for pole, cable laying, etc and getting out in soft/loose soil all as directed.
Returning and filling in of excavated soil including spreading,levelling,watering and well ramming in layers not exceeding 25 cm thickness each layer complete all as specified.
Removal of surplus soil not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified.
M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fine sand as specifed and punned thickness shall be measured and paid.
M & L for Sub class `B` bricks laid dry flat transversely along the length of cable with width equal to the length of bricks over sand cushioning as protection cover of cable laid, complete all as specified and directed.
Laying only sub class 'B' bricks as retrieved against srl item 01 above laid dry flat over the cable abutting each other, length of cable equal to width of brick all as required.
M & L in replacement of GI pipe light grade 80 mm bore with all fittings for cable protection fixed to walls/ poles or laid in trenches, under road/ under culvert/ under path/ under floor /on wall etc with fixing clamps, nuts bolts etc all as specified.
Dismantling poles and taking down existing HT/LT pole 11 mtr long PCC/steel including earth work and PCC of the poles all as specified and directed by Engr-in-charge Supply and erection in vertical position
M & L Prestressed cement concrete poles of size 11 mtr long 152 mm x 152 mm at top and 152 mm x 260 mm at bottom class-9 complete erected truly in vertical position and painting by applying two coats of synthetic enamel upto 1.5 mtr from the coping above ground level and colours black and yellow alternate strips of 30cm width upto 1.5 mtr from the top of coping complete including making suitable holes where required all as specified and directed .Note : PCC in foundation, coping, Earth work ( Excavation, Returning & refilling and removal) will be measured and paid separately under respective items of BOQ/ Sch 'A'.
Dismantling insulators any type, any size and depositing to the MES store yard complete all as specified and directed.
Supply and fix disc type composite polymer insulators, specified mechanical load 45 KKN(min) P F (dry) withstand voltage 65 KV/mint, P F (wet) withstand voltage 40 KV/mint, impulse withstand voltage 80 KVP for tension with tension clamp for conductors working pressure 11000 volts complete all as specified and directed.
Dismantling and taking down old existing ACSR conductor any type from existing HT/LT pole all as specified and directed by Engr-in-charge
Supply, laying in trenches or passing through pipe/ducts, fixed to wall or poles XLPE insulated screened PVC sheathed galvanized steel strip or wire armoured electric power cable with alumn conductor of cross sectional area 95 Sqmm 3 core 11/6.35 KV rated suitable for earthed system including testing and commissioning all as specified and directed Note : (Excavation and earth work, sand cushioning brick covers and GI pipe etc shall be measured and paid separately.
Supply and fix cable end jointing kit for 11 KV grade cable for outdoor//indoor termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm complete all as specified and directed..
Supply and fix cable end jointing kit for 11 KV grade cable for outdoor//indoor termination straight through type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 Sqmm complete all as specified and directed..
Supply and fix pin type polymer insulator of size 190 mm length and 150 mm dia including galvanised mild steel strap, washer and one galvanised iron nut of suitable size for 11000 volts all as specified and directed.
M&L for PCC ( 1 :4 : 8 ) type D2 using 40mm graded crushed stone aggreghate for foundation of poles and stay assembly completed all as specified and directed
M&L for PCC ( 1:3:6) type B1 using 20mm graded crushed stone aggregate for coping pedestal of poles. Including necessary form work fair finished to exposed surface completed all as specified and directed.
Dismantling of steel work ( brackets,clamps, channels including disc and pin insulators, nut & bolts) from existing pole all as specified and direc ted by Engr-in-Charge.
S&F in structural steel work conforming to grade Fe-410S as in cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections, including , nuts, bolts, washers, welding , bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat , one finishing coat of aluminium paint and epoxy coating, including taking down old corroded structural steel all as directed.
M & L in replacement stay assembly complete comprising of 20mm dia 40cm long stay bow rod 20mm dia x 1.8 metre long galvanised stay rod threaded and with nuts including 300mmx300mmx6mm thick plate necessary clamps etc as shown on plate No. 1 on page 495 of SSR Part-I, 2009 complete all as specified and directed. Note : Loop type insulator, stay clamp, stay wire, excavation and concrete work measured separately).
M & L for platform brick masonary for HT bus bar/LT panel with surafce finishing using extra cement of size 2500 X 2500 X 800 mm complete with chain link fencing and gate all as shown in Drg No CEPZ/C-TD/002/13 Dated 2/5 and as specified and directed by Engr-in-charge.
S & F in replacement of HT bus bar outdoor type factory fabricated duly painted with two coat of enammeled paint, pedestal type made out of mild steel sheet 3.15mm thick, factory made, using angle iron 40mm x 40mm x 6mm and 700 x 600 x 400mm high, front opening double shutter weather proof, rust proof, dust proof with provision of rubber gasket and locking arrangement including following fixtures and necessary earth work:-
Disconnecting electrically of HT cable from HT bus bar and replacement of HT bushes & insulator (each set of 3) for HT bus bar and making cable re-connection properly all as directed by Engr-in-Charge.
M & L for ACSR conductor of any size drawn straight horizontal on over haed lines on poles including binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed.
Repair/maint of existing cattle fencing with replacement of damage, rusted chain link complete all as specified and directed.
M & L for lightning arresters High tension 11000 volts expulsion type complete with all fittings transmission class discharge capacity 65 kilo Amps complete all as specified and as directed
Taking out U/s HT cable up to 120 Sqm from trecnches and relaying same, after repair, same or other indicated location including laying old bricks received from the site after testing complete all as directed.
Taking down old unsv lightning arrestor from the existing HT pole complete all as specified and as directed.
S & F MCCB 4 Pole 415 Volts 3 phase 400 Amps 35 KA, thermal magnetic release S1 -01 No (incoming) complete all as specified and directed.
S & F MCCB 4 Pole 415 Volts 3 phase 250 Amps 35/36 KA thermal magnetic release complete all as specified and directed.
S & F MCCB 4 Pole 415 Volts 3 phase 160 Amps 25 KA thermal magnetic release complete all as specified and directed.
S & F MCCB 4 Pole 415 Volts 3 phase 100 Amps 25 KA thermal magnetic release complete all as specified and directed.
M&L for coarse aggregate of 20 mm graded nominal size without any vegetation or chemical incl leveling spreading surrounding HT 2 pole / 4 pole structure , HT/LT panel/bus bar chamber complete all as specified and directed.
Trimming/cutting tree branches with clearing space upto 2.0 metre from the over head conductor's any side , all around for HT distribution system and as directed. Note- (i) Contractor shall take shutdown from JE Incharge and proper enter in to the shut down register at Power house and complete the work within the time, and clear the shut down from main power house after compltion the work. (ii) The overhead line will be maintained for whole period of contract and the payment will be made on in final bill only. (iii) One span shall be measured from one pole to next immediate pole and shall be irrespective of number of conductors in each span. (iii) Tree/branches shall be Govt property
Removal of unwanted vegetation/bushes/small plants shrubs around the elect supply installations and surface excavation not exceeding 15 cm depth leveling the ground and removing the excavated material to a distance exceeding n exc 50 metre complete all as specified and directed.
Supply, installation in replacement connecting electrically & commissioning switch air break, gang operated, outdoor type, tripple pole mounted on insulators 15 Nos vertical type provided with locking arrangement consisting of MS chanel , HT post type insulator contracts of copper alloy high pressure heavy duty contract assy operating rod 25mm dia GI pipe medium grade for operating from 1.2 mtr above ground level, drop out fuse, for current rating upto 200 Amps and working voltage 11kv incl dismentling & taking down old u/s existing GOD.
Material and labour earthing with steel earth plate electrode of size 600x600x6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in electrical plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing) and dismantling old defective earthpit.
Earthing complete with galvanised steel earth plate electrode of size (600 x 600 x 6) mm thick buried directly into ground vertically to depth not less than 2.25 metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, surrounded on all sides by alternate layers of 150 mm thick charcoal and common salt, connected to galvanized earh lead wire of size 4.0 mm by means of lugs, bolts, nuts, washer, check nuts of galvanised iron or steel all as shown in Electrical plate No. 3 of SSR Part I, wire protected by dia 15 mm bore light grade GI Pipe laid in floor and fixed to wall with proper size of clamps and watering pipe of bore 20 mm dia GI medium grade including wire mesh funnel, PCC, earth chamber pit with PCC 1:2:4 type B-1 using 20 mm grade stone aggreate including form work cement mortar including CI Pit cover with frame, necessary excavation and earth work in any type of soil including testing on completion for desired result all as specified. Note: The rate quoted include cost of 7.5 metre earthing wire with protection pipe.
Notes : The Schedule of Credit amount shall be deducted from the total of this schedule(BoQ) to arrive at Contract Sum.
SATISH AND CO
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .