| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.5 LAccepted-AOC C O SECTOR 02 HOUSING COLONY CHANNI HIMMAT JAMMU J K PIN 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L1 | Accepted-AOC L1 Accepted | |
| 2 | L2₹17.0 L+₹57,824.70 (3.51%)Rejected-Finance | L2 | Rejected-Finance Other than L1 after deducting schedule of credit Rs 65050.00 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
17 Aug 2022, 6:00 pmClosed
GE NORTH AKHNOOR
GE NORTH AKHNOOR PIN 181201 CO 56 APO
COMPREHENSIVE REPAIR MAINT OF SECURITY LIGHTS SOLAR STREET LIGHTS JUNCTION BOX TIMER SWITCH AND CONNECTED CABLES AT AKHNOOR UNDER GE NORTH AKHNOOR
2022_MES_539721_1
GE(N)/AKH-35/2022-23
Open Tender
Civil Works
Item Rate
180 days
AKHNOOR
Class E Cat b i
8 documents required · 8 mandatory
₹500
Yes
GE NORTH AKHNOOR
₹40,000
Yes
7 Dec 2022
21 Jul 2022
19 Aug 2022
21 Jul 2022
17 Aug 2022
3 Aug 2022
Amount
Taking down old unsv street lights and M&L for LED street light fitting of capacity 60 watt ( 5700 K) with high performance LED, Contemporary designed housing made of die cast aluminium with street optic lens for uniform light distribution rated IP 66 all as specified and directed. Make Wipro Cat part NoLR02-671-XXX-57-G2 or equivalent in make of phillips, ,Oshram, GE
Taking down old unsv street lights and M&L for LED street light fitting of capacity 90 watt ( 5700 K) with high performance LED, Contemporary designed housing made of die cast aluminium with street optic lens for uniform light distribution rated IP 66 all as specified and directed. Make Wipro Cat part NoLR02-102-XXX-57-G2 or equivalent in make of phillips, ,Oshram, GE
Taking down old unsv street lights and M&L for LED street light fitting of capacity 40 watt ( 5700 K) with high performance LED, Contemporary designed housing made of die cast aluminium with street optic lens for uniform light distribution rated IP 66 all as specified and directed. Make Wipro Cat part NoLR02-451-XXX-57-G1 or equivalent in make of phillips, ,Oshram, GE
Taking down old unsv street lights and M&L for LED street light fitting of capacity 25 watt ( 5700 K) with high performance LED, Contemporary designed housing made of die cast aluminium with street optic lens for uniform light distribution rated IP 66 all as specified and directed. Make Wipro Cat part NoLR02-291-XXX-57-XX or equivalent in make of phillips, Oshram, GE
Taking down old/unsv flood lights from high mast light of any type and M&L for LED flood light of capacity 250 watt IP 66 Lumainire with aluminium die cast housing toughened glass and unique lens system for enhancement illumination complete with all accessories Make Wipro cat part No LF3 -342-060-57XX or equivalent in specification of make phillips, Oshram,wipro, GE
Supply and fixing street light bracket for street light fittings made to shape as directed out of G.I. pipe light grade 32mm bore 1.5 mr long including fixing of light fittings and bracket with MS clamps, nuts and bolts of appropriate size complete all as specified and directed.
M&L for flat aluminium cable size 2.5 sqmm x 2 core required for street light connection all as specified and directed Make Havells, finolex, Anchor (Taking down burnt cable of any size).
Taking down old/burnt cable of any size and Supply and fixing Aerial bunched cable (AB) LT of size 3 core- x16 sqmm+1-core x 16 sqmm+ 1x25 sqmm for street lights .The 16 sq.mm. phase conductor shall be of aluminium solid round; outer diameter shall be within the limits.• The phase conductor shall be insulated with black weather resistant high-densitypolyethylene (HDPE) suitable to 1100 V insulation. The insulated conductors shall generally conform to the relevant standards.• Conductors: The properties of the aluminium wires before stranding shall be:• Tensile strength not less than 90 N/Sq.mm.• Resistivity at 20 Deg. C not exceeding 0.02845ohm / Sq.mm / m(V) and one bare messenger wire shall be stranded non compacted circular aluminium alloy conductor .all as specified and directed. Make Havells, Gloster,Polycab,KEI Note:- The following hardware fittings and accessories shall be used to install,erect and join the AB cable (i) Suspension clamp with eye hook (ii) Suspension fittings and corresponding eye hook (iii) Dead eye fittinngs (iv) Nylon Tie (v) connectors
Material and labour for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 meters deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron wire 4 mm dia and light grade protection pipe of 15 mm dia from earth electrode up to test point or up to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate No 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including charcoal, salt packed all around the earth electrode plate in layers, PCC earth pit chamber 1:3:6 type C1, of size 45cm x 45cm x 45 cm,RCC cover 1:2:4 type B1 of size 45x45x6 cm, excavation/earth work in any strata and returning filling, removal of surplus soil and testing/test point for required value including removing old item complete all as specified and directed. Note:- The required resistance of Earthing shall be less than 3 ohm, If not found to the required resisstance, the contractor has to re earthing for required resistance and the cost for the same included in the quoted rate and no extra shall be paid on failure of getting required resistance.
Supply laying and testing XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade, cross sectional area 25 sqmm 3.5 core all as specified and directed. Make Polycab,Gloster,Grandlay
Supply laying and testing XLPE Insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade, cross sectional area 16 sqmm 4 core all as specified and directed. Make Polycab,Gloster,Grandlay
S & F GI pipe light grade 50 mm bore for cable protection fixed on poles or laid in trenches under floor, ducts etc with fixing clamps, nuts , bolts etc. all as specified.
Excavation in tranches not exceeding 1.5 m wide and not exceeding 1.5 m deep for foundation of laying cable including getting out in soft/loose soil complete all as specified and directed.
Returning filling in including spreading watering and well ramming in layers not exc 25 cm complete all as specifed .
Removing surplus soil to distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed .
M & L for protection to cable with one layer of brick laid flat across the cable using all size sub class 'B' Bricks.
Sand cushioning to under ground electric cables including watering and consolidation all as per clause 19.75 of SSR Part-I
Material and labour Steel tubular swaged poles 9.00 mtr long type 410 SP-31 complete with cast iron base plate, final taper plug, bolts, nuts, screws as specified and directed by Engr-in-Charge.
M&L PCC (1:2:4) type B1 using 20 mm graded stone aggregates as in coping of poles etc including weathring, slightly rounded or chambered angle and throating, necessary form work finishing all exposed faces of concrete etc complete all as specified and directed by Engr-in-Charge.
M&L PCC 1:4:8 type D2 using 40 mm graded aggregate as in foundation of electric poles/struts etc including necessary form work and fair finish to exposed surfaces without using extra cement, complete all as specified and directed by Engr-in-Charge (Volume of poles / struts embedded in concrete shall be deducted)
(a) data overide by sms facility that work as per sunrise or sunset trigger or as per twilight with astro control longitude & latitude based alongwith lux controller (b) Parameters can be set remotely using SMS queries- like Output mode, Offset Hrs, UV, OV settings• Can remotely override relay output using SMS query Energy Meter Functionality Parameter like Load current, Supply voltage, Power, Energy can be known remotely • With the help of “Auto Error Code Update” onsite error can be retrieved remotely during output event (c) Manual mode operation of entire System even incase of availibility of single phase present in the system. (d) Having tripping on over & under voltage, Over Load, dead Phase faults. These faults send to the operator and alert the operator to override the system. (e) Auto/Auto on/Auto off As per user defined program settings, Instant ON up to next Auto Event and Instant OFF up to next Auto Event (f) Tiny Onboard Indication for TX-RX, Network, Power Indication and kwh pulse. (g ) Surge Suppressor to protect the pLc Modules form Harmful spikes and lightning. (h) Supply voltage – 110-240 vac, 50/60Hz, 160-240 vac 3Phase 4 wire { P-N }, 50/60Hz, supply variation – 20% to +15%, Storage Temperature -10 C to+60C, Operating Temperature – 10C to + 50C, Switching Contacts – 9 No, 8A { resistive load } @ 240 VAC and 5A { resistive, load } @ 30 VDC, Power reserve { for clock only } 1000h, Clock deviation - ± s1 per day over the operating temperature range, DST – settable, EMI / EMC Radio Interference Suppression – CISPR 14-1 Class B, ESD – IEC 61000-4-2 Level III, Electrical Fast Transients, IEC 61000-4-4 Level IV, Surges – IEC 61000-4-5 Level IV, Voltage Dips & Interruptions – IEC 61000-4-11 All 7 Levels.
Disconnecting all electrical connection of high mast lights 15m high , down all light accessories for repair/replace , incl replacement of non functional mech parts of winch, motor and Re-fixing of same after complete all as per site provided by Engr in - charge all as specified and directed. Note Flood lights replacement shall be paid and measured separetly.
Cross arms, bracings, supports,clamps and back plates fabricatedfrom structural steel sections including nuts, bolts, washers,welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint all as specified and directed.
S&F in replacement LT Cable junction box shall be made out of Polycarbonate with glass fiber reinforced and size should be not less than 200mm x 160mm x 98 mm (upto Cable Size 16sq.mm). The Polycarbonate Junction Box shall be environment friendly, recyclable, halogen & silicon free, anti acid & amp; anticorrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/69 in accordance with IEC 60529.Weatherproof UV-resistant, rainwater-proof, temperature-resistant. The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60998 - 1, IEC 60670 - 22& IEC 60670 - 2 - 5. The Junction Box Black Colour according to RAL 9011. The manufacturer ofJunction Box / Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC60695 - 2 - 11, DIN VDE 0304 Part - 3, UL Subject 94 for Flammability V-2. It should be tested atGlow Wire test for 960 degree Centigrade & Current Carrying Capacity upto 102Amps. The impactstrength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and one no. MCB SP 'C' curved 6/10 Amp 9/10KA and chromium plated clamps and nut bolts complete all as per manufacturer’s instructions. Make : Cat Part :- KF 1616 B of Hensel/Siemens/GEPower/Rittal. Manufacturer should submit routine test certificate of CJB/PJB strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical loadshall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and one no. MCB SP 'C' curved 6/10 Amp 9/10KA and chromium plated clamps and nut bolts complete allas per manufacturer’s instructions. Make : Cat Part :- KF 1616 B of Hensel/Siemens/GEPower/Rittal. Manufacturer should submit routine test certificate of CJB/PJB
Jiwan Singh
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .