Karnataka Power Transmission Corporation Limited
Renuka S
1.Replacement of existing 1X100MVA, 220/66kV Power Transformer 1 by 1X150MVA, 220/66kV Power transformer at 220/66/11kV Dabaspet substation in Nelamangala Taluk & Bengaluru Rural District.2.Strengthening of existing 220kV Dabaspet Nelamangala (B3) SC line from 400/220kV Nelamangala substation to 220/66/11kV Dabaspet substation by replacing existing Drake ACSR conductor by High Performance Conductor (HPC) for a distance of about 24.469km.3.Modification of existing 220kV line Terminal Bay of 220kV Nelamangala line at 220/66/11kV Dabaspet substation due to strengthening of existing 220kV Nelamangala-Dabaspet (B3) SC line by replacing existing Drake conductor by High Performance Conductor(HPC).4.Dismantling of existing allied equipments/materials for augmentation of 1X100MVA by 1X150MVA, 220/66kV Power transformers and strengthening of existing 220kV Dabaspet Nelamangala (B3) SC line of Drake conductor by HPC on Total Turnkey basis.
KPTCL/2023-24/TL/WORK_INDENT415
KPTCL/2023-24/TL/WORK_INDENT415
Open
Transmission Line
Two Tender Document System(Two Cover)
KPTCL CEE Corporate Office Tendering and Procurement Bengaluru
11 documents required · 11 mandatory
Tenderer shall upload P.O, LOI/LOA, DWA, Work done, Performance Certificates issued by the end users not below the rank of Executive/ Divisional Engineer as documentary proof as stipulated in clause no.3.2 (b)(i) of ITT as in the format at 1.3 of Qualification Information (For Transformer bay Work).
Tenderer shall upload P.O, LOI/LOA, DWA, Work done, Performance Certificates issued by the end users not below the rank of Executive/ Divisional Engineer officer as documentary proof as stipulated in clause no.3.2 (b)(ii) of ITT as in the format at 1.3 of Qualification Information (For Transmission line work).
Tenderer shall upload Documentary proof as stipulated in Clause No. 3.2(d) IV A(a) of ITT High Performance Conductor (HPC) Manufacturer shall be an ISO 9001/9002 certified manufacturer and should have a minimum experience of not less than Five (5) years as a regular manufacturer in the design, manufacture, testing and supply of High Performance Conductor (HPC) of same technology as stipulated in technical specification of the subject tender. Bidder shall upload documentary evidence such as i) P.O. copy ii) Order completion certificate iii) Test certificates in support of the same.
Tenderer shall upload Documentary proof as stipulated in Clause No. 3.2(d) IV A(b) of ITT manufacturer should have supplied to Indian Utilities/Consumers at least 50% of the total requirement of High Performance Conductor (HPC) equivalent to Drake ACSR of the same size or of higher cross section as envisaged in technical specification of the subject tender i.e., 37.25Km in the last 10 (Ten) years as on the date of Bid Submission and the same should have been in satisfactory operation for a period of at least Two years as on the date of bid submission. Bidder shall upload documentary evidence such as P.O./LOI/LOA/DWA copies/performance certificate issued by the end users i.e., Indian Utility/Consumer not below the rank of Executive Engineer
Tenderers shall upload the Audited Financial statements i.e Balance sheets, P&L statements, Turnover certificates duly certified by chartered Accountant as documentary evidence as stipulated in clause no.3.2 (a) of ITT and as per clause No.1.7 of Section 3 - Qualification Information.
The Tenderer shall upload Bankers Certificate duly signed by authorized person in the prescribed format as at Annexure XVIII of Section-4 and as per the clause no.3.3 (b) of ITT (Liquid Assets and /or availability of credit facilities).
Documentary proof for Clause No: 3.6 of ITT: Assessed available tender capacity such as, Statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent as sought in Note of the said clause in the prescribed format as in clause No: 1.5 of Qualification Information.
Tenderers shall upload the Self-declarations in respect of Litigation, disqualification/Black listed due to non-performance, Risk & cost, Country which shares a land border with India as per clause no. 2.3 & 2.4 (b), (c), (d), (e) of ITT
Tenderer shall upload No Deviation Certificate as per Annexure-I of Section-4
The Tenderer shall upload valid Super grade Electrical Contractors License issued by the Government of Karnataka as on the date of opening of techno-commercial bid of the Tenderer, failing which the offer is liable to be rejected as stipulated in clause no.2.3 of ITT
The Tenderer shall upload Documentary proof as stipulated in Clause No. 3.2(d) IV A(d) of ITT, Calculation for the ampacity, Guaranteed Technical particulars and Sag Tension calculations at various conditions mentioned in Clause no.1.4 of Technical specification for the proposed High Performance Conductor (HPC) equivalent to Drake ACSR along with supporting calculations for AC resistance as indicated in Technical specification.
The Bidder/Tenderer shall upload an undertaking stating that, in the event of an Award, they will procure the High Performance Conductor (HPC) as tendered from the manufacturers who meet the stipulated requirements as at 3.2(d) of ITT. The Bidders are required to upload all the documents required as stipulated in Clause No. 3.2(d) IV B (a) of ITT.
The Bidder/Tenderer shall upload an undertaking stating that, in the event of an Award, they will procure the High Performance Conductor (HPC) as tendered from the manufacturers who meet the stipulated requirements as at 3.2(d) of ITT. The Bidders are required to upload all the documents required as stipulated in Clause No. 3.2(d) IV B (b) of ITT.
The Bidder/Tenderer shall upload a legally enforceable deed of undertaking with the manufacturer of High Temperature Low Sag (HTLS) Conductor on Rs.200/- Non-Judicial Stamp Paper as stipulated in Clause No. 3.2(d) IV B (b) of ITT.
UNDERTAKING-1 Undertaking Regarding procuring HPC Conductor Equivalent to Drake ACSR.
UNDERTAKING-2 Joint Deed of undertaking on Rs.200/- non-judicial stamp paper to guarantee Quality, timely supply, performance and Guarantee obligations as specified for the HPC Conductor.
UNDERTAKING-3 Undertaking to conduct type tests on HPC Conductor as tendered
Self declaration as sought in Clause No. 3.6 Note (ii) of ITT by the bidder stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Tenderer shall upload Constitution or legal status, Place of Registration (upload copy) and Principal place of business of tenderer as per clause No.1.1 of Section-3-Qualification Information
The Tenderer shall upload total value of works executed (Works on Hand details) (KPTCL & Non KPTCL works) and payments received in the last five years (in Rs. Lakhs) of Tenderer i.e. for 2018-19 to 2022-23 as per clause no.3.6 of ITT, as in the format at 1.2 of Qualification Information.
The Tenderer shall upload Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded as per clause No.1.8 of Section-3-Qualification Information.
The Tenderer shall upload Name, address, telephone number & e mail id of the Tenderers bankers who may provide references if contacted by the Employer as per clause No.1.9 of Section-3-Qualification Information.
The Tenderer shall upload Information on litigations in which the Tenderer is involved as per prescribed format as at 1.12 of Qualification Information.
The Tenderer shall upload proposed methodology and program of construction backed with equipment planning and deployment, duly supported with broad calculations and quality control procedures proposed to be adopted, justifying their capability of execution and completion of the work as per technical specifications within the stipulated period of completion as per approved Activity chart as per clause No.1.13 of Section-3-Qualification Information.
The Tenderer shall upload an undertaking to source the supply of equipment/material from KPTCL approved Vendors only as per the QR for Vendor registration, available in the KPTCL website i.e., https//kptcl.karnataka.gov.in, Link Tendering & Procurement application for Vendor registration etc.
Certificate is to be uploaded by the Tenderer agreeing to source the equipment/ material for the work from the Vendors who meet the eligibility clauses regarding restrictions on procurement from a country which shares a land border with India.
The Tenderer shall upload Certificate of Incorporation of the Individual or any relevant document in respect of Partnership/Proprietorship firms as per the tender document as per clause no.3.10 (xii) of ITT
All details as called for in the Technical specifications of all the equipments/ materials of the Tender.
Any other relevant documents as per the qualifying requirements, terms and conditions of the tender, NIT & Technical specifications shall be uploaded
All other Undertakings and annexures as per terms and conditions of Tender documents shall be uploaded
₹7,500
₹39.4 L
5 Jan 2024
5 Jan 2024
13 Feb 2024
6 Jan 2024
STATION SUPPLY portion - 220kV Dabaspet-Nelmangla -TLTB:
150MVA, 220/66/11 kV Power Transformer: 3 ph, 50 Hz, Core type, 3 winding star/star/delta, transformer Vector group YNyn0d11, OLTC, bushing CT...
ISOLATORS : (without mounting structure) : Isolators & Terminal connectors etc., as per technical specification including solid core cylindrical post insulators:
220kV, 2500A, 40kA Class Double Break...
b. Upright mounting type without earth Switch - Live Point Height 8250mm
Terminal connectors for Isolators:
Rigid type terminal connector suitable for double Moose ACSR conductor.- 9 nos
Flexible typ...
ISOLATORS (without mounting structure) : Isolators & Terminal connectors etc., as per technical specification including solid core cylindrical post insulators: (For LV side of proposed 150MVA, 220/66k...
b. Live Point Height 4250 mm
c. Under hung mounting type without earth switch
Note: Terminal connectors for Isolators :
a. Rigid type terminal connector suitable for double Drake ACSR conductor. 30 nos
b. Flexible type terminal ...
CURRENT TRANSFORMER :Oil filled Current Transformers with rigid terminal connector suitable for double Moose ACSR conductor etc., as per technical specifications:
220 kV, 40 kA CT of Ratio 3000-2000/1...
CURRENT TRANSFORMER :Oil filled Current Transformers with rigid terminal connector suitable for double Drake ACSR conductor etc., as per technical specifications: (For Transformer LV, Bus coupler & NC...
MOUNTING STRUCTURES:
Current transformer: For 220/66 kV NCTs Mounting structures (excluding Bolts & nuts) (TOTAL)
MOUNTING STRUCTURES:
Current transformer: For 220/66 kV NCTs Bolts & nuts of Mounting structures (TOTAL)
PVC insulated Copper Control Cable with Lugs / Ferrules:
19 Core 2.5 Sq.mm. Copper Control Cables
4 Core 2.5 sq.mm. Copper control Cables
4 Core 4.0 Sq.mm. Copper Control Cables
10 Core 2.5 Sq.mm. Copper Control Cables
Copper PVC instrumentation cable, armored (screened cable) 2PX1.5sqmm
Terminal connectors:
a. Rigid type terminal connector suitable for existing 220 kV Circuit Breaker & Double Moose ACSR conductor
b. Rigid type terminal connector suitable for existing 220 kV CVT & double Moose ACSR conductor
c. Rigid type terminal connector suitable for existing 198 kV lightning Arrestor & double Moose ACSR conductor 3 nos
Busbar formation:
Moose ACSR conductor
11 kV, 120 KN Disc insulators (2x16x3 ….96)
11 kV, 90 KN Disc insulators (4x8…..112)
INSULATOR HARDWARE & CLAMPS:
Bolted type Double Tension clamp to suit HPC
Bolted type Suspension clamp to suit HPC
C type Wedge connector suitable for double Moose ACSR to double Moose ACSR.
Connector suitable for HPC to Double Moose ACSR
Spacers for Double Moose ACSR
PLCC equipments:
Wave trap 0.5mH, 2000A, 40 kA suspension type along with terminal connector suitable for double Moose ACSR/HPC.
Connector suitable for HPC to Double Moose ACSR (For existing 220 kV Bay of Dabaspet-Nelamangala B-3 line (at 400/220kV Nelamangala sub-station)
Station Erection
STATION SUPPLY portion - 220kV Dabaspet-Nelmangla -TLTB:
Power Transformer: 3 ph, 50 Hz, Core type, 3 winding star/star/delta, transformer Vector group:YNyn0d11, OLTC, bushing CT for tertiary of rati...
ISOLATORS : (without mounting structure) : Isolators & Terminal connectors etc., as per technical specification including solid core cylindrical post insulators:
220kV, 2500A, 40kA Class Double Break...
ISOLATORS (without mounting structure) : Isolators & Terminal connectors etc., as per technical specification including solid core cylindrical post insulators: (For LV side of proposed 150MVA, 220/66k...
c. Under hung mounting type without earth switch
Note: Terminal connectors for Isolators :
a. Rigid type terminal connector suitable for double Drake ACSR conductor.- 30 nos
b. Flexible type terminal...
CURRENT TRANSFORMER :Oil filled Current Transformers with rigid terminal connector suitable for double Moose ACSR conductor etc., as per technical specifications:
220 kV, 40 kA CT of Ratio 3000-2000/1...
CURRENT TRANSFORMER :Oil filled Current Transformers with rigid terminal connector suitable for double Drake ACSR conductor etc., as per technical specifications: (For Transformer LV, Bus coupler & NC...
PVC insulated Copper Control Cable with Lugs / Ferrules: of various Sizes
Note: For break up refer Techno commercial sheets uploaded.
PLCC equipments:
Wave trap 0.5mH, 2000A, 40 kA suspension type along with terminal connector suitable for double Moose ACSR/HPC.
Earthmat formation:
Providing C.I. Pipe of 100mm ID 13mm thick 2.75 mtr. long with 2 part GI Flat 50x6mm clamp welded allround the pipe etc.
Earthmat formation:
a. Grounding of equipment with 50 x 6 mm G.I. Flat and connecting equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, dril...
Supplying & providing 450 mm dia 450 mm height 1.5 inch to 2 inch thick hume pipe collar (non pressure type) for earth pits including all lead and lifts etc.
Nitrogen Fire Protection System(NIFPS) of Power Transformer:
Re-commissioning of NIFPS in case of replacement of power transformers (Includes all modification works required to connect all the access...
b. Replineshment of Nitrogen Gas(50Kg)
Erection of Mounting structures and PI Structures (including Bolts & nuts).
For details refer Techno commercial sheets uploaded.
DISMANTLING/ RELEASING PORTION:
Dismantling of existing 1X100 MVA, 220/66/11 KV, Power Transformer & parts like Radiator, bushings draining of oil from transformer, complete as per the direction of si...
Moving of Transformer from the plinth to the loading point as per direction of site Engineer.(157MT X 50mtrs=7850)
Dismantling of existing 220kV Upright mounting type Isolators - Total.
For details refer Techno commercial sheets uploaded.
Dismantling of existing 66kV Upright mounting type Isolators - Total
For details refer Techno commercial sheets uploaded.
Dismantling of existing 66kV Under hung type without earth switch Isolators - Total
Releasing of existing 220kV class, 31.5 kA CT of ratio 800-600-400-300/ 1-1-1A
Releasing of existing 66kV, CT of ratio 1000-600/ 1-1-1A
Releasing of existing 220kV and 66kV NCT mounting structure2 Nos. (0.3 plus 0.34)MT
For details refer Techno commercial sheets uploaded.
Releasing of existing Drake ACSR conductor connected between equipments (50 mts approximately)
Dismantling of existing wave trap in the line bay
Civil Works Dabaspete
Earth work excavation by manual means for drains,canals, waste weir,draft, approach channels, key trenches, foundation of bridges andsuch simillar works in all kinds of soils , as per drawing and tech...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work excavation for Foundation by Mechanical means depth upto 1.50m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, includin...
Earth work excavation for Foundation by Mechanical means depth upto 1.50m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, includin...
Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite /trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant I...
Total weight Mild Steel of towers(excluding Bolts and nuts)
Note: For break up refer Techno commercial sheets uploaded.
Total weight Hign Tension Steel of towers (excluding Bolts and nuts)
Note. For break up refer Techno commercial sheets uploaded.
Total weight of Bolts and nuts
Note. For break up refer Techno commercial sheets uploaded.
Number Plates and Danger Boards 12 Nos. each and Circuit plate 24 Nos.
Phase plate (Set of 3 Nos.)
Earth bond 300 mm long
Earth bond 450 mm long
Grounding of towers including cost of 40 mm dia 2.5 mm thick, class C G.I. Pipe of 3 Mtr length as per specifications, with 50 X 6 mm GI Flats 3 Mtr long, salt charcoal.
Conductor and Earthwire:
a. High Performance conductor (HPC) (physical properties equivalent to Drake ACSR)
Conductor and Earthwire:
b. GI wire 7/3.65 mm for Ground Conductor: wherever missing in the existing line.
Insulator strings:
A. Tension insulator strings
For details refer Techno Commercial sheets uploaded.
B. Suspension insulator strings For details refer Techno Commercial sheets uploaded.
Insulator hardwares:
A. For HPC conductor:
a. Single Tension fittings and Clamp suitable for HPC Conductor along with jumper pad/cone.
b. Double Tension fittings and Clamp suitable for HPC Conductor along with jumper pad/cone.
c. Single Suspension fittings and Clamps suitable for HPC Conductor
d. Double Suspension fittings and Clamps suitable for HPC Conductor
e. T Clamps suitable for HPC Conductor
B. For Drake conductor:
a. Single Tension Clamps along with arcing horns suitable for Drake ACSR
b. Single Suspension clamp along with arcing horns suitable for Drake ACSR
Accessories for Conductors:
A. For HPC conductor:
a. MSC Joints suitable for HPC
b. Repair sleeves suitable for HPC
c. Vibration dampers for HPC
B. For Drake conductor:
a. Vibration dampers for Drake ACSR
b. C type Wedge Connectors suitable for Drake ACSR
Tack welding of Bolts and nuts (No. of Towers x 250)
Painting of Rusted tower parts includes Supplying and painting of two coats of good quality Red Oxide primer after cleaning andscrapping the surface with 2 coats of good quality Aluminium paint after ...
LINE ERECTION portion -Dabaspet - Nelmangla-TLTB- Check survey using their own equipment as per Technical specifications: 220kV line
Note: Specification as per Vol-6 of Common SR 2023-24
Total weight Mild Steel of towers
(excluding Bolts and nuts)
For details refer Technocommercial sheet uploaded.
Total weight Hign Tension Steel of towers
(excluding Bolts and nuts)
For details refer Technocommercial sheet uploaded.
Total weight of Bolts and nuts
For details refer Technocommercial sheet uploaded.
Setting up of stub templates and aligning, dismantling and transportation of templates from one location to another location
TOWER ACCESSORIES:
a. Supplying and fixing GI angle 45 X 45 X 5mm, 1 Mtr length with cleats, bolts nuts as per specification and fixing above 0.5 Mtr length each at inner and outer surface of tower t...
b. Supplying and fixing Barbed wire
Phase plate (Set of 3 No.)
Grounding of towers including cost of 40mm dia 2.5 mm thick, class 'C' G.I. Pipe of 3 Mtrs length as per specifications, with 50 X 6 mm GI Flats 3 Mtr long, salt charcoal.
b)Laying, stringing, tensioning clamping, jointing etc HTLS DRAKE ACCC Conductor including hoisting of insulators, fitting of all necessary hardware & accessories i.e. fittings, armour rods, vibrati...
b. GI wire 7/3.65mm for Ground Conductor: wherever missing in the existing line.
Releasing & Re-stringing of Existing Ground Wire.
Releasing & Re-stringing of Existing DRAKE ACSR Conductor in Line
Dismantling of existing A type Towers 04 Nos.
Releasing of the existing Drake ACSR conductor along with accessories. For details refer Technocommercial sheet uploaded.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Drawings- dabaspete.zip
Tender Document • 16.22 MB
Tech spec.zip
Tender Document • 16.49 MB
Annexures Dabaspete.zip
Tender Document • 1.32 MB
NIT-Dabaspet.pdf
Tender Document • 0.50 MB
section 11 -Techno commercial sheets Dabaspete(27.12.2023).xlsx
Techno-Commercial Worksheet • 0.91 MB
Tender Documents Dabaspete.pdf
Tender Document • 1.55 MB
Pre bid Proceedings- Dabaspete.pdf
Others - Pre bid Proceedings- Dabaspete • 0.11 MB
Pre bid Clarifications- Dabaspete.pdf
Others - Pre bid Clarifications- Dabaspete • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .