Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹4.4 LAccepted-Finance | 1 | Accepted-Finance L1 LOWEST BIDDER | |
| 2 | 2₹4.5 L+₹2,095.20 (0.47%)Rejected-Finance | 2 | Rejected-Finance RATES ARE ON HIGHER SIDE | |
| 3 | 3₹4.6 L+₹18,519.20 (4.17%)Rejected-Finance NEW MADHOPUR COLONY SURAJKUND GORAKHPUR UTTAR PRADESH 273001 | GORAKHPUR | UTTAR PRADESH | 273001 | 3 | Rejected-Finance RATES ARE ON HIGHER SIDE |
Tender Value
₹4.5 L
EMD Value
₹4,500
Closing Date
26 May 2020, 5:00 pmClosed
SE ETC UPPTCL AZAMGARH
220KV S/S COLONY HAFIZPUR AZAMGARH
INSTALLATION OF NEW 63 MVA T/F IN PLACE OF 40 MVA T/F I FOR INCCREASING CAPACITY OF 132 KV SUB STATION SHAHGANJ 2X40 MVA TO 1X63 AND1X40 MVA UNDER ETD II JAUNPUR
2020_UPTCL_457556_1
141/AETC/2019-20
Open Tender
Electrical Works
Item Wise
120 days
JAUNPUR
UTR SLIP OF EMD TENDER FEE PAN CARD GST CERTIFICATE WORK EXPERIENCE etc.
2 documents required · 2 mandatory
₹531
SE ETC UPPCL AZAMGARH
₹4,500
3 Jun 2020
9 Apr 2020
27 May 2020
9 Apr 2020
26 May 2020
9 Apr 2020
9 Apr 2020 - 26 May 2020
Amount
Dismantling of 40 MVA T/F-I, drain out T/F oil upto required level, removal of all radiators, conservator tank, oil pipe lines. HV/LV neutral, bushing, removal of the HV/LV turrets, fan & marshalling box etc. banking of radiators, oil pipe lines, conservator tank proper gasket alngwith nuts and bolts etc.
Shifting of main tank of 40 MVA T/F-II from plinth upto near pen space upto 30 meter distance including turning the T/F tank and performing all other associate work.
Additional shifting of main tank upto 60 meter @ 5.00 meter/job.
Shifting of main tank of 63 MVA T/F from unloading place to plin h with the help of rail, pulling device, slippers etc. upto 30 meter distance including truning the tank and performing all other associated work.
Additional shifting of main tank upto 60 meter @ 5.00 meter/job.
Complete erection of 63 MVA T/F including radiators, conser ator tank, HV/LV Neutral bushing, turrets; connectiong all pipe lines, cooling fans, control cables, motor drive mechanism of OLTC, RTCC panels etc, topping up of transformer (not circulation) and final oil filling in tank anc attending leakage if any and all other associated work for satisfactorily completion of work.
Complete earthing of 63 MVA T/F as per standard practice w th 75x10 mm/50x6 mm M.S. Flat main tank of the T/F. marshalling box, drive mechanism of cooling fans etc. shall be earthed as per standar practice including painting. M.S. flat shall be provided by contractor at his own cost.
Earthing of 63 MVA T/F neutral with 75x10 mm and 50x6 mm flat run old ladder, its grounding painting and connecting with delta with flat at wo point, painting of flat and other associated work M.S. flat to be provic 2d by the contractor at his own cost
Jumpring of the 63 MVA T/F HV side with Twin ACSR panther conductor
LV side with Twin ACSR Moose/Zebra conductor
Proper packing of HV/LV neutral bushing of dismantal T/F including proper wrapping with polythene sheets in the wooden crates got emptied a ter taking out bushing of 63 MVA T/F
Dismantling of 132 KV LA opening of jumpers cutting of earthi1 g etc, re-erection of 132 KV LA and related associated work to complete the job satisfactorily.
Complete control cable termination in Transformer in marsha ing box, OLTC box, RTCC panel, colling fans including laying of new :ables as required with all associated work.
Centrifuging of complete Transformer oil in transformer by connecting centrifusing pipe circulating the transformer oil through PVT, centrifuging machine and taking the VDB, value of oil periodically till the requ red value is achieved.
SAI KRIPA LIFT SHIFT COMPANY
ARK ENGINEERING
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .