S.E. E D C- MVVNL,Unnao
Superintending Engineer Electricity Distribution Circle-Unnao
QUANTUM OF WORKS INVOLVED IN INCREASING CAPACITY OF DISTRIBUTION TRANSFORMER AND PROVIDING NEW DISTRIBUTION TRANSFORMER DUE TO OVERLOADING UNDER THE SPECIAL BUSINESS PLAN YEAR 2023-24 UNDER THE AREA OF EDSD-MAURAWAN UNDER THE EDD-PURWA, UNNAO.
2023_MVVNL_842009_1
137/E.D.C./Unnao/2023-24
Open Tender
Electrical Works
Fixed-rate
180 days
Unnao
AS PER TENDER DOCUMENT
2 documents required · 2 mandatory
₹3,540
A/C-No.3355002101008374,IFSC-Code-PUNB0335500
₹13,300
Yes
17 Oct 2023
22 Sept 2023
30 Sept 2023
22 Sept 2023
28 Sept 2023
22 Sept 2023
Amount
Carriage of following materials from Elec. Store Center Unnao to work dump site along with loading unloading and propoer stocking.
PCC Pole 8.5 mtr long
Other loose line materials with including conductor, Single and double Pole accessories, complete stay & earthing, insulator, x-arm, etc.
11 KV O/H Line Three Phase
Three Phase LT Line by ABC
LT PVC Cable size 1x120 sq mm
Carriage of following T/F from Elec. Store Center Unnao to diff. work dump site along with loading unloading and propoer stocking.
T/F 250 KVA 11/0.4 KV
T/F 100 KVA 11/0.4 KV
T/F 63 KVA 11/0.4 KV
T/F 25 KVA 11/0.4 KV
Dismantling of following Transformer from Plinth / Double Pole with Safe Carriage from work site to dump site along with loading unloading and propoer stocking.
T/F 160 KVA 11/0.4 KV
T/F 100 KVA 11/0.4 KV
T/F 63 KVA 11/0.4 KV
T/F 25 KVA 11/0.4 KV
T/F 16 KVA 11/0.4 KV
T/F 10 KVA 11/0.4 KV
Construction of T/F Plinth of size 2x2x1.5 m on a padding 0.25 M deeo in ground 1:5:10 cement sand and brick ballast on the top of padding brick work Ist class brick of 0.95 mtr height & 0.35 mtr wall will be constructed. Rest wall should be 0.23 mtr thick, brick work in ration 1:4 cement & cores sand in the hollow portion the sand should be filled from the ground level up to 15 centimeter below from the top of wall, cement, sand & brick ballasts should be filled up to 15 centimeter. Two nos. of channel 100x50 in length 1500 mm will be grouded, 0.35 CM. RCC will be done with cores sand, cement and stone ballast in the ratio of 1:2:4. The T/Fs plinth should be plastered on all sides 12 mm thick in ratio 1:6 by cement and cores sand. (All the material will be arranged by the contractor)
Placement of 11/0.4 KV T/F from dump site to newly constructed T/Fs Plinth & installation and commissioning of 250 KVA T/Fs of T/F Plinth and including jumpering with the system. (All the required materials as Al. Lugs Crimping Type for 250 KVA T/F Copper L-piece 62x225x12 mm etc for above job shall be provided by contractor except T/Fs and LT PVC Cable)
Construction of retaining wall, fabrication & erection of Wiremesh fencing around Transformer with retaining wall & 01 nos. gate with locking arrangement made of MS Angle Iron of size 50x50x6 mm jointed with nuts and bolts. Wiremesh of size 10 swg rectangle type, its painting as per norms of RESPO. (All the materials will be arrangement by the contractor)
Earthing of Neutral of Transformer, Transformer body and double pole by way of boring and lowering of ‘B’ class G.I. Pipe 1.5” dia from ground up to the water level (Minimum 20 Mtr. Deep) with a solid cone at the lower end of G.I. pipe. Connecting and bringing out contineous G.I. Strip size 32X6 mm. from the cone to the ground surface where it will be connected with G.I. pipe clamp from which Transformer neutral, Body & D.P. connection being done by G.I. Strip.(All the materials will be arrangement by the contractor)
Mounting of following Transformer on double pole including its cartage and dragging from dump site to pit site.
T/F 100 KVA
T/F 63 KVA
T/F 25 KVA
Safe Carriage of following T/F from work dump site to Electricity store center Unnao with loading, unloading and proper stocking.
T/F 160 KVA 11/0.4 KV
T/F 100 KVA 11/0.4 KV
T/F 63 KVA 11/0.4 KV
T/F 25 KVA 11/0.4 KV
T/F 16 KVA 11/0.4 KV
T/F 10 KVA 11/0.4 KV
Erection of PCC/ST Pole (11 KV Line) including digging of pits, fitting of all accessories along with cartage & dragging from dump site to pit site.
Erection of PCC/ST double pole (11 KV Line) including digging of pits, fitting of all accessories along with cartage & dragging from dump site to pit site.
Erection of PCC/ST Pole (LT Line) including digging of pits, fitting of all accessories along with cartage & dragging from dump site to pit site.
Making T-off arrangement including fabrication & fitting of accessories.
Grouting of PCC/ST Pole as per RESPO Norms with grouting materials.
Earthing of pole as per RESPO Norms.
Digging of pits, fixing nuzzling and grouting of stay rods as per RESPO Norms with grouting materials.
Safe Carriage of following T/F from work dump site to Electricity store center Unnao with loading, unloading and proper stocking.
11 KV O/H Line Three Phase
L.T. Line by ABC Three Phase
Fixing of 3-Phase Distribution Box with clamp, N&B (Only D.B. Box Provided By Department)
Riya Electricals
M/S RATHORE ELECTRICALS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .