Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 LAccepted-AOC | L1 | Accepted-AOC Being lowest bidder for the work | |
| 2 | L2₹7.0 L+₹71,467 (11.4%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹8.0 L+₹1.7 L (27.9%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹8.4 L+₹2.1 L (34.1%)Rejected-Finance HOUSE NO C 214 SECTOR C INDRA VIHAR COLONY TILAK NAGAR HOUSING SOCIETY AIRPORT ROAD LANDMARK NEAR BHOPAL GIRLS SCHOOL PANCHVATI BHOPAL MP 462030 | BHOPAL | BHOPAL | MADHYA PRADESH | 462030 | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹10.0 L+₹3.8 L (60.2%)Rejected-Finance | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
31 Aug 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND MAINTENANCE OF VCBS AT 33 KV MRS AT SI LINE UNDER GE BHOPAL
2021_MES_463063_1
83674/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
GE Bhopal
₹20,000
Yes
16 Sept 2021
5 Aug 2021
2 Sept 2021
5 Aug 2021
31 Aug 2021
19 Aug 2021
60 days
Amount
Dismantling of the existing VCBs from existing position, transporting them to workshop, carrying out necessary repair and maintenance, bringing back to MRS substation including testing, commissioning, calibrating complete all as specified and as directed. Notes: - (a) The works shall be carried out for M/C serial No: 3106700217/01/2. (b) Servicing, overhauling, calibration and testing etc. shall be carried out as per the Manufacturer’s instructions/ guideline and by the authorised of the manufacturer and the necessary literature shall be made available to the department. The quoted rate shall be inclusive of these aspects. (c) The quoted rate shall be inclusive of required T & P for including servicing, overhauling, calibration and testing etc. (d) The quoted rate shall be inclusive of transportation cost from substation to workshop and bringing back. (e) The new spare parts required for replacement shall be paid and measured separately as S & F in repairs.
Opening of VCB 33 kV of any Make for servicing, cleaning, tightening of loose mechanical mechanism, greasing inspection of busbar, CTs/PTs, internal wiring of control panel, indicators, measuring of IR value, calibration of relays, replacement of unserviceable spare parts, testing of tripping system and removing all type of dust and settled dirt by mechanical means including testing complete all as specified and directed by Engineer-in-Charge. Note: -Spare parts excluding wiring shall be measured & paid separately.
Opening of VCB 11 kV of capacity 400 Amps to 800 Amps of any Make for servicing, cleaning, tightening of loose mechanical mechanism, greasing inspection of busbar, CTs/PTs, internal wiring of control panel, indicators, measuring of IR value, calibration of relays, replacement of unserviceable spare parts, testing of tripping system and removing all type of dust and settled dirt by mechanical means including testing complete all as specified and directed by Engineer-in-Charge. Note: -Spare parts excluding wiring shall be measured & paid separately.
S & F in repairs jaw contacts 800 A (Part code- MVIG00134-01) complete all as specified and as directed.
S & F in repairs bus bar separator complete all as specified and as directed.
Laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in hard/ dense soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Supply & laying unreinforced precast concrete cable cover class HV type 1, flat shape, dimension 300 mm X 180 mm X 40 mm as per IS 5820: 1970 complete all as specified and directed.
S & F in repairs Master relay Type- VA, model No- VA1H13F82A, LH voltage 24 VDC complete all as specified and as directed.
S & F in repairs Vacuum interrupter unit VG2 (Part code:-DRCVG2002-01) complete all as specified and as directed.
S & F in repairs closing and tripping coil 24 V DC Complete all as specified and as directed.
S & F in repairs contactor with relay coil . model no: 3TH30-40 E complete all as specified and directed .
S & F in repairs TNC switch Model No: RBC401, P129-R-1, rating 40 ampere, 660 VAC complete all as specified and as directed.
S & F in repairs fuse SN type . HBC fuse link of rating 32 Amps complete all as specified and as directed .
S & F in repairs limit switch assembly (Part code:-MVIF00372-01) complete all as specified and as directed.
S & F in repairs Auxiliary switch (Part code:-MVIE0011-01) (including 6 numbers of NO contact + 06 numbers of NC contact) complete all as specified and as directed.
S & F 24 pin plug & socket assembly (Part code:-MHU39S0019000FN) Complete all as specified and as directed.
POONAM ELECTRIC INDUSTRY
virendera singh
S R BUILDERS AND SUPPLIERS
PRADEEP SISODIYA
ELITE WORKS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .