| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.7 CrAccepted-AOC | ₹63.7 Cr | L1 | Accepted-AOC 1. Lowest tenderer (L1) and reasonable tender. |
| 2 | L2₹64.2 CrRejected-Finance | ₹64.2 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹64.5 CrRejected-Finance | ₹64.5 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹65.6 CrRejected-Finance | ₹65.6 Cr | L4 | Rejected-Finance Not being the lowest |
| 5 | L5₹74.3 CrRejected-Finance | ₹74.3 Cr | L5 | Rejected-Finance Not being the lowest |
Tender Value
₹65 Cr
EMD Value
₹15 L
Closing Date
1 Aug 2020, 6:00 pmClosed
CE (Navy) Mumbai
HQ CE (Navy) Mumbai,26 Assaye Building, Colaba Mumbai-400005
PROVISION OF DEFICIENT SINGLE SAILORS ACCOMMODATION INCLUDING FOREIGN TRAINEE SAILORS AND DEMOLITION AND RECONSTRUCTION OF INLIVING OFFICERS SERVANT QUARTERS AT INHS ASVINI MUMBAI
2019_MES_292088_4
87815/E8
Open Tender
Civil Works
810 days
GE (P) (NW) Mumbai
Please refer Tender documents.
7 documents required · 7 mandatory
₹3,000
GE (P) (NW) Mumbai
₹15 L
Yes
6 Oct 2020
30 Jun 2020
5 Aug 2020
30 Jun 2020
1 Aug 2020
8 Jul 2020
Amount
Schedule-A' Part-I 'Buildings & Structures' Total of Schedule-'A' Part-I B/F from serial page No. 34
Schedule-A' Part-II(A) 'Site Clearance' Total of Schedule-'A' Part-II(A) B/F from serial page No. 35
Schedule-A' Part-II(B) 'Site Clearance' Total of Schedule-'A' Part-II(B) B/F from serial page No. 37
Schedule-A' Part-II(C) 'Excavation, Earthwork & Site Clearance' Total of Schedule-'A' Part-II(C) B/F from serial page No. 40
Schedule-A' Part-III 'Demolitioin' Total of Schedule-'A' Part-III B/F from serial page No. 43
Schedule-A' Part-IV 'Internal Water Supply' Total of Schedule-'A' Part-IV B/F from serial page No. 45
Schedule-A' Part-V 'Internal Electrification' Total of Schedule-'A' Part-V B/F from serial page No. 51
Schedule-A' Part-VI 'Dumb Waiter Lift' Total of Schedule-'A' Part-VI B/F from serial page No. 52
Schedule-A' Part-VII 'Lifts' Total of Schedule-'A' Part-VII B/F from serial page No. 63
Schedule-A' Part-VIII 'Aviation Light' Total of Schedule-'A' Part-VIII B/F from serial page No. 64
Schedule-A' Part-IX 'Fire Fighting' Total of Schedule-'A' Part-IX B/F from serial page No. 76
Schedule-A' Part-X 'DG Set' Total of Schedule-'A' Part-X B/F from serial page No. 78
Schedule-A' Part-XI 'Lightning Protection' Total of Schedule-'A' Part-XI B/F from serial page No. 80
Schedule-A' Part-XII 'Walk-in-Cool & Cold Room' Total of Schedule-'A' Part-XII B/F from serial page No. 81
Schedule-A' Part-XIII 'External Electrification' Total of Schedule-'A' Part-XIII B/F from serial page No. 90
Schedule-A' Part-XIV 'External Water Supply' Total of Schedule-'A' Part-XIV B/F from serial page No. 93
Schedule-A' Part-XV 'Solar water heating system' Total of Schedule-'A' Part-XV B/F from serial page No. 95
Schedule-A' Part-XVI 'ROAD/PATH' Total of Schedule-'A' Part-XVI B/F from serial page No. 98
Schedule-A' Part-XVII 'Sewage Disposal' Total of Schedule-'A' Part-XVII B/F from serial page No. 100
Schedule-A' Part-XVIII 'Area Drainage' Total of Schedule-'A' Part-XVIII B/F from serial page No. 101
Schedule-A' Part-XIX 'Compound Wall' Total of Schedule-'A' Part-XIX B/F from serial page No. 104
Schedule-A' Part-XX 'Storm Water Harvesting' Total of Schedule-'A' Part-XX B/F from serial page No. 106
Schedule-A' Part-XXI 'Prime Cost Sum' as 'water fountain for aeration including electric & water connection and monoblock pump' Total of Schedule-'A' Part-XXI Notes: 1. The work under PRIME COST SUM shall be measured and paid as per condition 5 of IAFW 2249 (General conditions of Contracts) 2. This percentage subject to maximum of 15% (on plus side) shall be taken as the PC sum percentage
PART-XXII (Miscelleneous Items)
Internal Water Supply
S & F Chromium Plated Push cock for urinal 15mm dia bore complete all as specified and as directed Make: jaguar or equivalent PRS-073
S & F Two way bib cock 15mm dia complete all as specified and as directed Make - Jaquar Model No CQT-23041 or equivalent in Crab Tree/Kohler brand
S & F Health faucet (ABS body) with 01 meter long PVC tube & wall hook complete all as specified and as directed Make - Jaquar Model No ALD-CHR- 583 or equivalent in Crab Tree/Kohler brand
S & F ZOLOTO BRASS FORGED PRESSURE REDUCING VALVES complete all as specified for the following Dia:-
S&F Sink cock with swinging casted round shape spout (Wall mounted model) 20mm dia, quarter turn complete all as specified and directed Make - Jaquar Model No CQT-23347 or equivalent in Crab Tree/Kohler brand
S&F Angular stop cock of 15mm bore dia with wall flange complete all as specified and directed
Internal Electrictrification
S & F 63A panel mounted (3P + N + E) angled socket, conforming to IEC 60309- 1 & 60309- 2, having IP67 ingress protection & IK 08 impact protection suitable for 415V, 50Hz electric supply complete as specified and as directed. Make: Schneider PratiKa Cat-Part No. 81283 or equivalent model of Legrand or Havells
S & F 32A panel mounted (3P + N + E) angled socket, conforming to IEC 60309- 1 & 60309- 2, having IP 67 ingress protection & IK 08 impact protection suitable for 415V, 50Hz electric supply complete as specified and as directed. Make: Schneider PratiKa Cat-Part No. PKF32F735 or equivalent model of Legrand or Havells
S & F triple pole enclosure with a three pin and earth plug and socket suitabale for surface/flush mounting, conforming to IEC 61439-3, complete with one 20A, 415V, 50Hz TP MCB as specified and as directed Make: Legrand Ekinox³ Cat-Part No. 5078 17 or equivalent model of Havells or Anchor
S & F 10W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240V, input frequency 50- 60Hz, PF>0.95, including electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and as directed Make: BAJAJ Cat-Part No. 112407 BCLSB 10WH or equivalent model of Havells, Philips or Wipro
S & F 20W surface/wall mounted LED batten having high efficiency long life LED chips with luminous efficacy of > 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing and white coloured ABS end caps having input voltage 220- 240V, input frequency 50- 60Hz, PF>0.95, including electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and as directed Make: BAJAJ Cat-Part No. 112785 BCLAB 20W or equivalent model of Havells, Philips or Wipro
S & F 40W surface/wall mounted LED batten having complete internal wiring suitable for retrofit LED tube light with double side connections, powder coated CRCA sheet steel housing, white powder coated CRCA sheet reflector, push-fit type white polycarbonate lamp holders with corrosion resistant brass contacts having input voltage 220- 240V, input frequency 50- 60Hz, PF>0.95, along with 20W LED polycarbonate tube light having high efficiency long life SMD LED module with luminous efficacy of >100 lumen/W, integral SMPS based constant current electronic LED driver with THD< 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high quality polycarbonate end caps and polycarbonate housing in opal finish including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and as directed Make: BAJAJ Cat-Part No. 112688 BJI 218 LED PC & 112481 BRLB 21W CWc or equivalent model of Havells, Philips or Wipro
S & F 40W recessed mounted square shape 2' X 2' LED panel having high efficiency long life LED package in integral module with luminous efficacy of >100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high transmittance polystyrene opal diffuser, housed in white powder coated pressure die-cast aluminium heat sink having input voltage 220- 240V, input frequency 50- 60Hz, PF>0.95, including electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and as directed Make: BAJAJ Cat-Part No. 112669 BZRSQL 43W GZ1 NW or equivalent model of Havells, Philips or Wipro
S & F 45W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high effiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35mm to 42mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5m long bracket, having 40mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enemal paint over a coat of red oxide primer complete all as specified and as directed Make: BAJAJ Cat-Part No. BAJAJ 169799 BRTFG 45W LED I or equivalent model of Havells, Philips or Wipro
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200mm blade sweep, air-flow not less than 210CMM, operating voltage 220-240V and frequency 50Hz, including a downroad of suitable size and electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fan complete all as specified and as directed Make: Crompton Cat-Part No. ENTRUST50 or equivalent model of Orient or BAJAJ
S & F engery efficient non-metalic fresh air fan having blade sweep 250mm, air delivery not less than 860CMH, operating voltage 220-240V and frequency 50Hz, including electrical connection with 3 core flexible Copper conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and as directed Make: Crompton Cat-Part No. VENTILUS 10" or equivalent model of Usha or BAJAJ
S & F engery efficient metalic exhaust fan having blade sweep 300mm, air delivery not less than 900CMH, operating voltage 220-240V and frequency 50Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and as directed Make: Crompton Cat-Part No. TRANS AIR 12" or equivalent model of Usha or BAJAJ
S & F vertical triple pole & neutral DB, 4- way (double door), conforming to IEC 61439- 3, suitable for flush mounting with 250A insulated & shrouded copper busbar for each phase, 2 fully insulated & shrouded neutral bar, 2 earth bar, wire set and cable ties for cable management, IP 43 & IK 09 protection with reversible metal door with provision for FP MCCB as incomer and TP/SP MCBs as outgoing, all complete as specified and as directed Make: Schneider Cat-Part No. A9HVD04M or equivalent model of Legrand or Havells NOTES: [i] MCBs/MCCBs shall be measured and paid in separate items
S & F ISI marked MCB for AC applications till 63A, having breaking capacity Icn = 10kA, conforming to IS/IEC 60898-1-2002, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, all complete as specified and as directed Make: Schneider, Legrand, Havells
6A, SP MCB, C- curve
16A, SP MCB, C- curve
20A, SP MCB, C- curve
32A, SP MCB, C- curve
20A, TP MCB, C- curve
32A, TP MCB, C- curve
63A, TP MCB, C- curve
S & F 80A, TP MCB, C- curve, having breaking capacity Icn = 25kA, conforming to IEC/EN 60947-2, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, all complete as specified and as directed Make: Schneider, Legrand, Havells
S & F 80A, FP MCB, C- curve, having breaking capacity Icn = 25kA, conforming to IEC/EN 60947-2, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, all complete as specified and as directed Make: Schneider, Legrand, Havells
S & F 125A , 4 pole moulded case circuit breaker (MCCB), conforming to IEC 60947-2, having Ics = 100% of Icu = 25kA, adjustable thermal setting (0.7 - 1 X In) and fixed magnetic setting with compression lug connectors and thermal magnetic trip unit (TMD) all complete as specified and as directed Make: Schneider, Legrand, Havells
Supply, installation, testing and commissioning of 800A sandwich type silver flashed, bi-metal copper contact, aluminium busway (3L + N + PE), with original Mylar insulation from Dupont, 100% neutral, 50kA for 1 second, 50% integral earth, dual housing including Sl. item No. 26.25 to 26.53 herein below complete all as specified and as directed Make: Schneider, ABB, Siemens
The busbar trunking system shall conform to the following technical specifications: [A] General: [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tees, flanged ends, cable tap box and circuit breaker, etc.) shall be in accordance with IEC 61439 Part 6 (2012) or UL857 and from the same manufacturer as the busbar trunking system. Degree of protection of the BTS shall be IP 54 in accordance with IEC 60529
[ii] Rated operation voltage of the BTS shall be 1kV. The neutral conductor shall have the same cross-sectional area as the phase conductor. The earth busbar must be one continuous piece without bolting on housing
[B] Certificate: [i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6. The certificate shall be issued by an international independent testing authority (e.g. ASTA, KEMA, UL)
[ii] A product safety mark (e.g. KEMA-KEUR, ASTA DIAMOND, UL) shall be on the product offering a visible assurance to all of full product safety testing, factory inspection and ongoing surveillance under independent authority to ensure the ongoing safety of product
[iii] The BTS shall pass seismic tests with actual physical product and being certified complying with UBC seismic Zone 4 condition by an international recognized earthquake research body, e.g. Asian Pacific Network of Centers for Earthquake Engineering Research (ANCER)
[C] Short-Circuit Ratings & Tests: [i] The whole BTS shall be capable of withstanding the short circuit of the electrical installation without undergoing any electrical, mechanical and thermal stress under fault condition at a service voltage of 1kV at 50Hz frequency. The minimum rated insulation voltage shall be 1kV. [ii] Minimum certified short circuit ratings shall be 50kA for 1 sec for 800A BTS.
[D] Housing: [i] The busbar trunking housing shall be constructed of electro galvanized steel and aluminum to reduce hysteresis and eddy current loses and shall be provided with a suitable protective finish of ANSI 49 grey epoxy paint
[ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation. And it shall pass at least 2000hr salt spray test to ensure the anticorrosion ability
[iii] The totally enclosed housing shall be manufactured by the busbar trunking manufacturer. Modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking manufacturer voids the manufacturer’s warranty. Busbar trunking so modified is unacceptable without the written consent of the manufacturer
[E] Busbars: [i] Busbars shall be of aluminum with copper cladding utilized Molecular Fusion technology [ii] There shall be no bolts passing through the busbars of the busway [iii] Each busbar shall be insulated with Class B (130 ℃) DuPont Mylar insulation. Epoxy insulation is unacceptable
[iv] The temperature rise at any point of the busbar trunking enclosure shall not exceed 55°C above the ambient temperature of 40°C when operated at rated current.
[F] Joints: [i] The busbar trunking joint shall be of the one-bolt type which utilizes a high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt shall be torque indicating and at earth potential.
[iii] The bolt shall be two-headed design to indicate when proper torque has been applied and require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only one side of the busbar trunking for tightening joint bolts.
[v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths
[G] Plug-in Openings: [i] The connecting jaw of the plug-in unit shall plug directly on to the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable [ii] All contact on joint and plug-in opening should be silver plated copper [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in openings on each side
[iv] All openings shall be usable simultaneously [v] Busbar trunking shall be installed so that plugs are side mounted to permit practical use of all plug-in openings [vi] It shall be possible to inspect the plug-in opening and busbars prior to the installation of the plug-in units
[H] Plug-in Units: [i] The plug-in jaw shall be spring design composed of different metal to ensure the firm and tight contact with the busbar. [ii] Plug-in Units shall be type tested in accordance with IEC 61439-6 (Annex D: Part 1-5 and 9-13)
[iii] The earthing contact of the plug-in unit shall always be made before that of the live conductors and the last to break during removal. And it must connect to the earth bar of busway to ensure the safety
[iv] Covers of all plug-in units must have interlocks to prevent the cover from being opened when the switch is in the ON position [v] Plug-in units (circuit breaker type or fusible switch type) shall be operated with visible blade quick-make and quick-break mechanism
[vi] Presence of transparent shield shall be inside to avoid direct contact of human [vii] The plug-in units shall be equipped with internal barriers to prevent accidental contact of fish tape and conductors with live parts on the line side of the protective device during time of wire pulling
[I] Supporting Structure: Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3m for horizontally mounted run and 4.88m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing of up to 1.5m for horizontally or vertically mounted runs
[J] Voltage Drop: [i] The 3-phase line to line voltage drop 40% power factor concentrated loadshall not exceed 3.4V per hundred ft. [ii] The line-to line voltage drop at the load power factor shall not exceed 4.1V per hundred feet.
Straight riser length
90° elbow
Flange end
Support bracket/hangers for horizontal installation
Spring hangers for vertical installation
End cover
Tap-off units with FP MCCB (up to 125A)
Supply, installation, testing and commissioning of Din Rail mounted, self-powered direct connect watt-hour meter, conforming to IEC 62053-21, with accuracy Cl 1.0 to provide direct measurement of real energy (kWh) on a single phase network (92 VA to 276 VAC) up to Imax, frequency range 50/60 Hz, operating temperature range -25° C to 55° C with a 6+2 digit display for measurement up to 999999.99 in kWh and for configuration and equipped with a flashing red indicator to check the accuracy of the meter. The meter shall communicate via a Modbus RS-485 protocol and all measured values shall be available via the Modbus control. The meter shall be equipped with anti-tamper security feature to ensure the integrity of the measurement complete consisting of the following items all as specified and directed : (a) 1- Phase Din Rail Meter (Imax = 63 A) - 126 Nos
Supply, installation, testing and commissioning of ISO 50001: 2018 certified "Energy Management System" consisting of the following items all complete as specified and directed. Make:- Schneider, ABB, Siemens
(a) ISO 50001, ISO 50002 & ISO 50006, cyber security standard IEC62443 SL1 at the component level: IEC62443-4-1 and IEC62443-4-2 certified Power Monitoring and Energy software with builtin in SQL server standard edition, 01 Engineering Client & 03 Web Clients to view across the facility, OPC Client enabled User configurable inbuit dashboard Capability during runtime, Standard reports plus customisale reporting capability to configure total 120 devices. Database: SQL Server 2016 Or 2017 Standard/Enterprise Edition. Flexibility for the operator to create engaging dashboard displays of the power monitoring system information and easily share information with anyone in the facility. Software should have the capability to get advance power quality data thru ION technology to get wave forms, Harmonics compliance (IEEE519-1992) reports, Plot PQ events on an ITIC/CBEMA curve and get disturbance direction detection from ION compatible devices :- 1.00 No.
(b) Protocol Converter RS 485 to Modbus TCP , POE, Dual Ethernet port installed in cabinet to accomodate Converter, 24 V DC Power supplies, 4 port Ethernet TCP/IP unmanaged switch (Shielded RJ45 copper cable connection type, Supply voltage 24VDC, LED for power supply and per channel copper port activity, CE marking Ethenet switch) and necessary protection MCB's :- 8.00 Nos.
(c) Ethernet Patch Cable of 3 metre length :- 2.00 Nos.
(d) Cat5e Cable LAN U/UTP 2x4P as required
(e) Cat5e RJ45 connector :- 36.00 Nos.
(f) 10 port Ethernet network Switch :- 1.00 each
(g) IT cabinet to accommodate Network Switch and power supplies and necessary protection MCB's :- 1.00 No.
Supply & install Dell Precision Workstation (Server for monitoring and reporting) With Dell 22 Monitor | E2417H 21.5" Intel(R) Xeon(R) Processor E3-12xx (6 core) 24GB RAM 1TB 3.5inch SATA (7,200 Rpm) Hard Drive x 1 16X Half Height DVD +/- RW x 1 Intel XEON Processor Label x 1 NVIDIA(R) Quadro(R) K620 2GB (DP, DL-DVII) (1 DP to SL-DVI adapter) x 1 External Speaker Not Included x 1 1Gbit NIC add-in card (PCIe- Intel) x 1 No Wireless LAN x 1 Dell Optical Mouse MS116 Black x 1 Dell Multimedia Keyboard KB216 Black (US International -QWERTY) x 1 Windows 10 Pro (64bit) English x 1 Windows 10 Pro OS Recovery 64bit - DVD x 1
Antivirus Quick heal Server Edition with 3 years Subscription A. Limited Warranty: Initial Year (NBD) x 1 B. Limited Warranty: Initial Year (POW) x 1 C. Onsite Service Yr 2-3 x 1 3Yr Onsite Service x 1
S&F 1 kVA UPS with 30 minute back-up having single input and output, inbuilt SMF batteries and required accessories
Dumb Waiter Lift
Design supply, install, testing & commissioning 250Kg capacity Dumb waiter in building to serve G+04 upper floors with AC variable voltage & variable frequency (VVVF drive) drive complete with all standard accessories, call and send control operation from landings, with manually operated vertically opening bi-parting doors for car and landing complete all as specified below: (a) Type of lifts: Traction Geared (b) Load Capacity: 250Kg (c) Speed : 0.5m/sec with single speed motor (d) Power Supply : 415V, 3 phase, 50Hz (e) Type of Drive: AC variable voltage & variable frequency (f) Type of Machine: Horizontal traction machine type Geared Machine consists of worm gear and motor and both are directly coupled with electromagnetic DC operating Disc Brake (g) Car size (Inside): 1000mm wide x 1000mm deep x 1200mm height (h) Car door: Manually operated, vertically opening, Bi-parting doors, door panels and jamb made from stainless steel hair line finish, N-304 grade, 1.2mm thick sheet, with electrical interlocking
(j) Landing door at all floor: Manually operated, vertically opening, Bi-parting doors, door panels and jamb made from stainless steel hair line finish, N-304 grade, 1.2mm thick sheet, with electrical and mechanical interlocking (k) Car enlosure: Standard manufacturing with MS sheet frame not less than 3.0mm thick and stainless steel sheet side enclosures and ceiling, not less than 1.5mm thick with hair line finish (N-304), internal lighting arrangement with LED light fitting (l) Terminal buffers: Metal special spring buffers (m) Door opening: Clear opening size 1000mm wide x 1200mm height (n) Car & CWT guide: Machined guide for car and counter weight 50mm x 50mm x 5mm thick cold rolled finish with grove at end (o) Flooring: Stainless steel sheet 1.5mm thick chequered plate (p) Signals: Combined luminous hall buttons with Digital hall position indicators at all floor with stainless steel face plates
(q) Safety Devices: (i) Ultimate final limit switches at top and bottom floor (ii) Electrical & Mechanical interlocking for landing gates (iii) Electrical interlocking for car door (iv) UPS based ARD system to bring dumbwaiter to nearest floor in case of power failure Stops & opening: 05-05, (G+04) all opening on same side Control operation: Call and send from landing operating push panel and No operating button inside the car Hoist way size & construction: Existing made of RCC and brick wall clear inside require 1400mm wide x 1400 mm deep Machine room location & size: Located above the hoist way 1400mm wide x 1400mm deep x 1800mm ht AC-VVVF drive: Yaskawa make- 1000 model Counter weights: Cast iron or MS profile cut Conformity: IS 14665 latest
External Electrictrification
M&L for Cable path indicator made out of 3mm thick MS sheet of size 30x20cm fixed on 40x40x5mm 75mm long angle iron including letters writing (HT Cable 11000V) and PCC complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning Main LT panel board suitable for working on 3 phase, 4 wire, 415V AC, 50Hz, indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting, CPRI approved, separate compartment for ACB/MCCB/metering equipments/cable gallay etc ,front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting
(Item No. 28.02 Contd....) with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50x50x6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:-
(a) 2000A rated copper bus bar with colour coded heat shrinkable sleeve - 01 Job
(d) MCCB 3 Pole, 400A, 415V, 36kA - 01 No (Out going) (For LT Fire fighting panel) Make : Schneider/ABB/C&S or equivalent
(e) MCCB 3 Pole, 400A, 415V, 36kA - 01 No (Out going) (For DG AMF Panel) Make : Schneider/ABB/C&S or equivalent
(f) Ammeter, Digital type with suitable CTs (g) Voltmeter, Digital type - 01 set (h) R-Y-B phase indicating lamp- 01 set (i) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled
Supply, installation, testing and commissioning LT panel at Sailors Accn board suitable for working on 3 phase, 4 wire, 415V AC, 50Hz, indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting, CPRI approved, separate compartment for ACB/MCCB/metering equipments/cable gallay etc., front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom
(Item No. 28.10 Contd...) cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50x50x6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and as directed by Engineer-in-Charge comprising of following:-
(c) MCCB 4 Pole, 400A, 415V, 36kA (For LT bus trunking Sailors Accn - 01 No (Out going) Make: Schneider / ABB / C&S or equivalent (d) MCCB 4 Pole, 250A, 415V, 36kA - 01 No (Out going) (For Mechanical laundry panel) Make: Schneider/ABB/C&S or equivalent
(e) MCCB 4 Pole, 63A, 415V, 25kA - 01 No (Out going) (For Cold storage room) Make: Schneider/ABB/C&S or equivalent (f) MCCB 4 Pole,63A, 415V, 25kA - 01 No (Out going) (For Solar Panel on roof top) Make: Schneider/ABB/C&S or equivalent
(g) MCCB 4 Pole, 63A, 415V, 25kA - 01 No (Out going) (For Solar Panel on roof top) Make: Schneider/ABB/C&S or equivalent (h) Ammeter, Digital type with suitable CTs (j) Voltmeter, Digital type - 01 set (k) R-Y-B phase indicating lamp- 01 set (l) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, installation, testing and commissioning LT panel at Servant Qtrs Accn board suitable for working on 3 phase, 4 wire, 415V AC, 50Hz, indoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation with IP-54 protection fabricated out of 2mm thick CRCA sheet powder coated painting , CPRI approved,separate compartment for ACB/MCCB/metering equipments/cable gallay etc., front and rear hinged door with locking arrangement, copper bus bar duly covered with heat shrinkable sleeves colour coaded fixed on DMC/SMC insulators bottom cable entry holes for incoming and outgoing cables and connecting the outgoing MCCBs/switch gears with main bus bar by using aluminium bus links or copper conductor cable of suitable rating
(Item No. 28.16 Contd...) and connecting with terminal blocks of appropriate rating terminated by cable lugs, thimbles etc, earthing terminals, affixing danger notice plate, control wiring with flexible copper conductor cables of suitable size and adequate length, control fuses/MCBs and PCC foundation as per site requirement. Angle iron of size 50mmx50mmx6mm for mounting of LT panel 40cm above floor level complete including necessary PCC foundation all as specified and directed by Engineer-in-Charge comprising of following:-
(a) 800A rated copper bus bar with colour coded heat shrinkable sleeve - 01 Job
(c) MCCB 4 Pole, 400A, 415V, 36 KA - 01 No Out going (For Bus truncking Servant Qtrs Accn) Make : Schneider/ABB/C&S or equivalent
(d) Ammeter,Digital type, with suitable CTs (e) Voltmeter, Digital type - 01 set (f) R-Y-B phase indicating lamp- 01 set (g) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, installation, testing and commissioning Main LT panel, indoor type cubical panel board, (DG Utility Panel) made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators including necessary PCC foundation and all as specified and directed by Engineer-in-Charge comprising of the following:-
(a) 630 amps rated copper bus bars with epoxy insulators-LS (b) MCCB 4 Pole, 400A, 415V, 36kA - 01 No. (In coming) (c) MCCB 4 Pole, 125A, 415V, 25kA - 02 No. (Out going for Sailors Accn & servant Qtrs)
(d) MCCB 4 pole,400 Amps,415V,36KA -01 No. (For firefighting pumps) (e) MCCB 4 Pole, 100A, 415V, 25kA - 01
(f) Supply, installation, testing and commissioning of intelligent street light control Alpharex3 digital time switches - Astro suitable for 2kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, with combination function for creating switching programs in which the devices are switched according to astronomical time and/or fixed preset times, Daily astronomical calculation of the sunrise/sunset times based on the entered location with suitable contactor of 25A rating, 25A SPN MCB all complete as specified and directed - 01 No (For street light control)
(g) Ammeter,0-400A, Digital type, with suitable CTs - 01 set (h) Voltmeter, 0-500V, Digital type - 01 No. (j) R-Y-B phase indicating lamp- 01 set (k) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled. (l) MCCB 4 Pole, 40 Amps, 16KA, 415 Volts- 01 No. (For Gray Water Supply LT Panel)
Supply, installation, testing and commissioning Main LT panel, indoor type cubical panel board, (LT Panel for lift Sailor Accn) made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators including necessary PCC foundation and all as specified and directed by Engineer-in-Charge & provn of two Nos extra space for providing MCCB for future expansion including comprising of the following:-
(a) 200A rated copper bus bar with colour coded heat shrinkable sleeve (b) MCCB 4 Pole, 125A, 415V, 36kA - 01 No (In coming) (c) MCCB 3 Pole, 63A, 415V, 25kA - 02 Nos (Out going) (1 No For Lift panel at Machine Room Sailors Accn, 1 No. Common area lighting Sailors Accn)
(d) MCCB 3 pole,32, Amps,415V,16KA -14 No. (For out going, common area lighting and servant qtrs) (e) Ammeter, 0-100A, Digital type, with suitable CTs - 01 set (f) Voltmeter, 0-500V, Digital type - 01 No. (g) R-Y-B phase indicating lamp- 01 set (h) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, installation, testing and commissioning Main LT panel, indoor type cubical panel board, (LT Panel for Servant Qtrs Lift) made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators including necessary PCC foundation and all as specified and directed by Engineer-in-Charge & provn of two Nos extra space for providing MCCB for future expansion including comprising of the following:-
(a) 200A rated copper bus bar with colour coded heat shrinkable sleeve (b) MCCB 4 Pole, 125A, 415V, 25kA - 01 No. (In coming) (c) MCCB 3 Pole, 63A, 415V, 25kA - 01 No.(Out going) ((For Lift panel at Machine Room Servant Qtrs Accn)
(d) MCCB 3 Pole, 32A, 415V, 16kA - 04 Nos.(Out going) (For Common area lighting Servant Qtrs Accn) (e) Ammeter,0-100A, Digital type, with suitable CTs - 01 set (f) Voltmeter, 0-500V, Digital type - 01 No. (g) R-Y-B phase indicating lamp- 01 set (h) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, installation, testing and commissioning Main LT panel, out door floor mounted type cubical panel board, (LT Panel for Solar water heater at Foreign trainee Accn roof) made out of 3mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators including necessary PCC foundation and all as specified and directed by Engineer-in-Charge & provn of two Nos extra space for providing MCCB for future expansion including comprising of the following:-
(a) 100A rated copper bus bars with epoxy insulators-LS (b) MCCB 4 Pole, 63A, 415V, 25kA - 01 No.(Incoming) (c) MCB TP, 16A, 215V, 10kA - 4 Nos.(Out going) (d) Ammeter,0-100A, Digital type, with suitable CTs - 01 set
(e) Voltmeter, 0-500V, Digital type - 01 No. (f) R-Y-B phase indicating lamp- 01 set (g) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, installation, testing and commissioning Main LT panel, indoor type cubical panel board, (LT Panel for Mechanical laundry at Foreign Trainee Accn) made out of 2mm thick CRCA sheet, duly powder coated, compartmental design with locking arrangements, weather and vermin proof with proper ventilation slots, IP 52 free standing floor mounted with copper busbar of suitable size for phase and neutral mounted on hygroscopic insulators including necessary PCC foundation and all as specified and directed by Engineer-in-Charge & provn of two Nos extra space for providing MCCB for future expansion including comprising of the following:-
(a) 315 A rated copper bus bar with colour coded heat shrinkable sleeve (b) MCCB 4 Pole, 250A, 415V, 36kA - 01 No. (In coming) (c) MCCB 3 Pole, 63A, 415V, 25kA - 06 Nos (Out going) (02 Nos for washer extractor, 02 Nos for Electric steam generator & 02 Nos for Tumble drier)
(d) MCB 3 Pole, 6A, 415V, 10kA - 06 Nos (Out going) (02 Nos for Vaccum ironing table, 01 No for multi foam finsher, 01 Nos for stain removing machine, 01 No for Air compressor & 01 No for cuff and collar press)
(e) MCB 3 Pole, 16A, 415V, 10kA - 01 No (01 No for Electric steam generator) (f) MCB 3 Pole, 10A, 415V, 10kA - 01 No.(01 No for utility laundry press) (g) Ammeter, 0-100A, Digital type, with suitable CTs - 01 set
(h) Voltmeter, 0-500V, Digital type - 01 No. (j) R-Y-B phase indicating lamp- 01 set (k) Internal wiring with suitable size of PVC insulated stranded copper conductor duly crimped with copper lugs ferruled.
Supply, Installation, testing and commissioning of LED type street light fitting suitable for 70W capacity LED lamp, IP 66 pressure die cast housing with epoxy powder coated aluminium housing drak graphite gray colour finish Enclosure complete with control driver ,fixed on street light pole connecting with 1.5sqm 3 core copper cable from street light connector to junction box with suitable size lugs/thimble complete all as specified and directed by Engineer-in-Charge. Make:- Havells Cat Part No. ENDURAPEARLPLUSSL70WLED757PASYTOPC or equivalant in approved makes.
Supply and fixing of 40mm bore GI pipe, ISI Marked, light grade 1.5m long bent to shape, fixed on pole with flat iron 32x3mm MS clamps 02Nos, including suitable size nuts, bolts and washers made of GI/steel complete all as specified and directed by Engineer-in-Charge.
Supply and fixing of outdoor weatherproof PVC enclosure junction box of size 250x200x100mm fitted to the pole fixing with MS FI clamps size 25mm wide x 2mm thick 02Nos ,suitable size nut, bolts and washers complete including 3 amps MCB SP and Bakelite connector for terminating incoming and out going cables complete all as specified & directed by Engineer-in-Charge. Make:- National/Sintex
External Water Supply
Supply, laying and testing of ductile Iron pipe including specials, flanged type, class “K-9” complete of 200mm (8”) dia including rubber tyton joints all as specified and as directed Make : JINDAL/TATA or equivalent
Supply and fix CI Foot valve conforming to IS: 4038 supplied and installed complete of size 150mm complete all as specied and directed by Engr-in-charge.
Supply installation, testing and commissioning of centrifugal pump cast iron body 1630LPM at 90m (min) head , suitable capacity of electric driven motor and coupled with bronze impellers including provision for fixing safety valve, pressure guage and priming valve etc coupled with 3 phase induction motor suitable for operation on 415V, AC with coupling mounted on channel iron base frame including nuts, bolts & washers, with PCC foundation, foundation nuts, bolts & washers as per manufacturer' instructions complete all as directed. Make : Kirloskar/Crompton or equivalent
Supply, installation, testing and commissioning of factory made LT Panel board (Pump House Panel) cubical type floor mounting dust and vermin proof made out of 2mm thick CRCA sheet steel with angle iron base frame, free standing on cable duct with cable entry holes at the bottom suitable for operation on 440V, AC 3 phase, 4 wire, 50Hz with 200A rated copper Bus Bar,fully compartmentalised, vermin proof, painting with powder coating 7 tank process suitable for IP-52 protection including suitable PCC foundation as per manufacturer recommendation complete and comprising of the following :-
(a) 200A rated copper bus bars with epoxy insulators - 01 Job (b) MCCB, 4 pole, 200A, with ultimate breaking capacity of 36kA at 415V, with thermal magnetic release, 415V, 25kA, thermal overload setting 70% to 100%, short circuit setting 5 to 10 times, over voltage and shunt release all as specified and directed - 01 No (Incomer). (c) MCCB 3 pole 160A, 415V, 25kA - 02 Nos (Out going) (d) VFD starter suitable for 60HP pump set - 02Nos. including necessary connection from the pump set and starter. (e) MCB SPN 32A, 230V- 2 No. (Lighting DB) (f) Digital Voltmeter 0 to 500V- 1 No. (g) Digital Ammeter 0 to 200A with CTs- 1 No. (h) Phase indicating lamp LED type -set of three incoming. (j) Complete wiring of panel board with suitable size of PVC insulated copper conductor cables.
Cutting in position existing cast iron main pipe line of size 300mm dia, insertion of CI tee 300x300x200 mm bore for tapping out for filling UG sump including connected fittings i.e. CI Tee, collar, tail piece, run lead joints and necessary excavation, refilling and disposal of surplus material complete.
Supply, installation, testing and commissioning of vertical type, submersible monoblock pumpset, multistage mild steel body 330 LPM at 90m (min) head, suitable capacity of electric driven motor and coupled with stainless steel impellers including provision for fixing safety valve, pressure gauge etc. coupled with 3 phase induction motor suitable for operation on 415V, AC with coupling mounted on channel iron base frame including nuts, bolts & washers, with PCC foundation, foundation nuts, bolts & washers as per manufacturer's instructions complete all as directed. Make : Kirloskar Cat Part No. JVSB 1007 / Crompton
Supply and Lay PVC insulated submersible type copper flexible cable of size 16 sqmm 4 core with ISI marked complete all as specified and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning of factory made LT Panel board (Gray Water Supply Pump Panel) cubical type floor mounting dust and vermin proof made out of 2mm thick CRCA sheet steel with angle iron base frame, free standing on cable duct with cable entry holes at the bottom suitable for operation on 440V, AC 3 phase, 4 wire, 50Hz with 100A rated copper Bus Bar, fully compartmentalised, vermin proof, painting with powder coating 7 tank process suitable for IP-52 protection including suitable PCC foundation as per manufacturer recommendation complete and comprising of the following :-
(a) 100A rated copper bus bars with epoxy insulators - 01 Job (b) MCCB, 4 pole, 40A, with ultimate breaking capacity of 16kA at 415V, with thermal magnetic release, 415V, 16kA, thermal overload setting 70% to 100%, short circuit setting 5 to 10 times, over voltage and shunt release all as specified and directed - 01 No (Incomer). (c) MCCB 3 pole 40A, 415V, 16kA - 02 Nos (Out going) (d) DOL starter type MN with single phase protection feature for 10HP, 415 V, 50Hz, 3-Ph pump set - 02Nos. including necessary connection from the pump set and starter. (e) MCB SPN 32A, 230V- 2 No. (Lighting DB) (f) Digital Voltmeter 0 to 500V- 1 No. (g) Digital Ammeter 0 to 200A with CTs- 1 No. (h) Phase indicating lamp LED type -set of three incoming. (j) Complete wiring of panel board with suitable size of PVC insulated copper conductor cables.
Fire Fighting System
M & L for copper conductor, XLPE insulated armoured cables 1100 volts, conforming to IS: BS EN 60228, having annealed copper conductor, PVC inner sheath, single armouring of galvanized round steel wire, one layer of PETP tape wrapping, collective screen of PETP/Aluminum tape over tinned copper drain wire, RED in colour, including clamping, termination and ferruling complete all as specified and directed. Make: Havells or Polycab or RPG
2 core, 1.5 mm²
2 core, 2.5 mm²
Supply, installation, testing and commissioning of PN 1.6 rated 200mm NB CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps complete all as specified and as directed. Make: Kirloskar, Leader, Audco
Supply, installation, testing and commissioning of PN 1.6 rated CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories complete all as specified and as directed. Make: Kirloskar, Leader, Audco
Supply, installation, testing and commissioning of 2- way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instanteneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed. Make: Minimax, Vijoy, Safex, Ceasefire
Supply, installation, testing and commissioning of "Sprinkler Annunciation Panel" compatible for seamless integration with water flow devices with visual display, internal sounder, alarm/fault indications and stand-by 24 V lead-acid batteries with charger all complete as specified and directed. Make: Tyco, Agni, Safex NOTE: The panel shall be located in the Fire Pump House and connected to flow indicating switches in sprinkler system.
M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.
DG Set
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flexible coupling or close coupled and AMF Panel complete with platform as per requirement, control panel having meters, sound-proof canopy, etc of 200 kVA complete all as specified and directed. Make: Ashok Leyland, Kirloskar, Crompton Greaves, Cummins
[a] Engine: 6 cylinders, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude, Inline fuel pump with A1 class electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 12 V DC battery.
[b] Alternator: brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength [c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish.
The control panel consists of the following parts: [i] Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals [ii] Indicating lamps for ‘Load ON’ and ‘Set Running’ [iii] Instrument fuses duly wired and ferruled [iv] MCCB of suitable rating with overload and short circuit protections
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP
[e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours [f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency [g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level [h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing. [j] Data Logging: Engine hours, control hours and upto 5 recent fault codes [k] Configurable glow plug control
[l] 12 V DC operation [m] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB [n] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. Note : The rate quoted by the contractor is deemed to be included for proving suitable PCC foundation for mounting of DG Set and including AMF Panel 200 KVA capacity as per OEM specification complete all as specified and directed.
Aviation Light
Supply and fixing aviation light luminaire, LED type with integral LED aviation light comprising of aluminium housing with polycarbonate enclosure complete all as specified and directed. Make: Bajaj Cat Part No. BGAV 302 LED or equivalent of CG/Philips (Foreign trainee - 1 No)
Material and labour for supply and fixing of GI pipe medium grade 25mm dia 2m length including grouting in suitable PCC on roof for fixing the aviation light on top of the GI pipe with suitable fixing materials, clamps etc complete all as specified and as directed
Mechanical Laundry
Supply, install, testing and commissioning Washer Extractor of capacity 30Kg, soft mount, high spin, computer controlled, fully programmable, with electric heating complete with all electrical connection and including all accessories etc complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No.- RVWE 30 or equivalent in IFB / Stefab
Supply, install, testing and commissioning Tumbler drier of capacity 25Kg with electric heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. RTD 30 or equivalent in IFB / Stefab
Supply, install, testing and commissioning Vaccum ironing table with 2128 Iron and Buck with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge. Make: Ramsons Cat Part No. RV 4425-80 or equivalent in IFB / Stefab
Supply, install, testing and commissioning automatic electric steam generator suitable for 2 Irons with electric heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. MR06 or equivalent in IFB / Stefab
Supply, install, testing and commissioning Dry linerTrolley of 50 kg capacity made of stainless steel tubes and bends of size 850x650x1680mm electro treated foldable front fitted with 4 nos of swivelling type ball bearing wheels of net weight 44kg and crated of weight of 70 kg and of size 1900x1050x350 with crated volume of 0.69 cum all as shown on drg of M/S Stefab laundry Equipements and all as specified and directed by engineer-in-charge Make: Stefab cat part no.DTR50 or equivalent in Ramsons / IFB
Supply, install, testing and commissioning Utility Laundry Press with Steam Heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge. Make: Ramsons Cat Part No. RULP or equivalent in IFB / Stefab
Supply, install, testing and commissioning Form Finisher with steam heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. RMFF or equivalent in IFB / Stefab
Supply, install, testing and commissioning Cuff and Collar Press with steam heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. RCCP or equivalent in IFB / Stefab
Supply, install, testing and commissioning Stain removing machine with portable steam boiler with steam heating with all electrical connection and including all accessories etc. complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. CL1 or equivalent in IFB / Stefab
Supply, install, testing and commissioning Electric Steam Generator of dimensions 750x800x750mm with steam output 35-40Kg/Hr & power consumption 27KW with electric heating with all electrical connection and including all accessories etc complete as recommended by OEM and all as specified and directed by engineer-in-charge Make: Ramsons Cat Part No. MR27 or equivalent in IFB / Stefab
Supply, install, testing and commissioning Air Compressor of capacity 5HP with all electrical connection and including all accessories etc complete as recommended by OEM and all as specified and directed by engineer-in-charge.(Standard make as approved by GE)
Refrigerators
Supply, install, testing and commissioning Centralised water cooler system including factory fabricated 100mm thick PUF insulated SS body storage tank (SS-304) 500 ltr capacity and cooling capacity of 375 ltr/hr with twin cooling coil and twin outdoor unit (comprising compressor, condenser and all other safety measures, temperature cut out system, digital display, digital timer system etc) with approximate water inlet temperature of 30-35 degree celsius and outlet cooled temp of 6-10 degree celsius, EER of unit not below 2.9, complete with 02 industrial type water purifier system of min 100 ltrs/hr in parallel connection from the nearest storage tank including cutting/drilling and finish the surface as per exisiting finish complete all as per manufacturer's instructions and as directed by EIC. Make : Bluestar, Voltas and Carrier
Compound Wall
S & F barbed razor tape concertina coil SG hot galvanized spring tensile wire to particular here-in-after or other equivalent make as approved by GE of UTS 145 to 150 kg/Sqmm and Dia of coil when unstreched 601mm having minimum number of circles 10/Rm, minimum number of coils 25/RM and minimum weight of coil 1.625 Kg/Rm, hot dip galvanized razor ribbon tape of size 0.50mm thickness,19 mm width before wrapping on central core wire fixed with GI 1.66mm clips and special nut bolts to hold two coils together and extra 2 rows parallel wire of 10 gauge tied by binding wire wherever complete all as specified and directed by engineer -in-charge
Arboriculture
Supply of organic manure neem strid NPK 19:19:19 for mixing with good earth in required proportion all as specified and as directed
Supply & provide for plantation of good quality ready made korean jumping grass in modules of 600 x 300mm size as per approved design for lawn complete all as specified & as directed
M & L stone kerb of roughly squared stone of size 15cm x 30cm dressed so that the maximum depression from the straight edge held against the dressed surface shall not exceed 6mm for top and exposed surfaces of sides and 20mm for the rest of the surfaces jointed in cm (1:6) and struck flush complete all as specified & as directed
Supply and fixing different types of plants (Neem, mango, palm etc)
Manning and Operation for the lifts
Manning and Operation of electrically operated lifts of any make type and capacity to serve G+13 (i.e. 14 floors) 24 hrs daily i.e. (Three shifts of 08 hrs per day) including sundays and holidays (0600 hrs to 1400 hrs, 1400 hrs to 2200 hrs & 2200 hrs to 0600 hrs) including taking care of all lift from any pilferage, theft or damage etc. in INHS Asvini (Total four lifts). The attendant will look after all the four lifts.
(a) 1st year during defects liability period
(b) 2nd year during defects liability period
(c) 3rd year after expiry of defects liability period
(d) 4th year after expiry of defects liability period
(e) 5th year after expiry of defects liability period
(f) 6th year after expiry of defects liability period
Manning and Operation of electrically operated lifts of any make type and capacity to serve G+19 (i.e. 20 floors) 24 hrs daily i.e. (Three shifts of 08 hrs per day) including sundays and holidays (0600 hrs to 1400 hrs, 1400 hrs to 2200 hrs & 2200 hrs to 0600 hrs) including taking care of all lift from any pilferage, theft or damage etc. in INHS Asvini (Total four lifts). The attendant will look after all the four lifts.
(a) 1st year during defects liability period
(b) 2nd year during defects liability period
(c) 3rd year after expiry of defects liability period
(d) 4th year after expiry of defects liability period
(e) 5th year after expiry of defects liability period
(f) 6th year after expiry of defects liability period
Comprehensive Maintenance of Lifts
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 13 Passenger capacity lift installed against Sch 'A' Part- VII, Item No. 1, herein before in building (G+19), (Total 2 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 13 Passenger capacity lift installed against Sch 'A' Part- VII, Item No. 2, herein before in building (G+13), (Total 1 Lift) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 08 Passenger capacity lift installed against Sch 'A' Part- VII, Item No. 3, herein before in building (G+19), (Total 2 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 08 Passenger capacity lift installed against Sch 'A' Part- VII, Item No. 4, herein before in building (G+13), (Total 3 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated Dumb waiter lift of any make of 250kg capacity lift installed against BOQ Sl. item No. 27.01 herein before (G+4), (Total 1 Lift) comprising of all devices and accessories through out 12 months on all days including holidays for period of 03 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Download all tender documents and submit your bid