Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 LAccepted-AOC | L1 | Accepted-AOC Being L1 Bidder | |
| 2 | L2₹1.4 L+₹942 (0.69%)Rejected-Finance NICHUPATTY BOLPUR BIRBHUM | BIRBHUM | WEST BENGAL | 713129 | L2 | Rejected-Finance BEING L2 BIDDER | |
| 3 | L3₹1.4 L+₹2,717 (2.00%)Rejected-Finance | L3 | Rejected-Finance BEING L3 BIDDER | |
| 4 | L4₹1.4 L+₹3,389 (2.49%)Rejected-Finance | L4 | Rejected-Finance BEING L4 BIDDER |
Tender Value
Refer Docs
EMD Value
₹2,727
Closing Date
20 Mar 2024, 1:00 pmClosed
E.E P.W.DTE BIRBHUM ELECTRICAL DIVISION
OFC Of The EXECUTIVE ENGINEER P.W.DTE. Birbhum Electrical Division P.O. Suri,Dist Birbhum, Pin 731101
Electrical Installation at the Audiometry Room of Bolpur Sub Divisional Hospital, Electrical Installation work and Air Conditioning Machine Installation work.
2024_WBPWD_685123_1
BIRED/75/e-NIQ (1st call) of 2023-2024
Open Tender
ELECTRICAL WORKS ORG
Item Rate
5 days
BOLPUR
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,727
OFC OF THE E.E P.W.DTE BIRBHUM ELECTRICAL DIVISION
9 Aug 2024
13 Mar 2024
22 Mar 2024
13 Mar 2024
20 Mar 2024
14 Mar 2024
14 Mar 2024
Amount
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by ElC) in suitable size PVC casing-capping (Precision make) with Ix22/0.3 (1.5 sqmm) single core stranded FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish [PVC casingcapping on surface and Switch board concealed] i) Average run 5 mtr
Wiring in 1.1 KV grade single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) of following sizes in 25mm PVC casing- capping (Precision make) incl. necy. PVC clips, fittings etc. i) 2 x 22/0.3 (1.5 sqmm) + 1 x 22/0.3 (1.5 sqmm)
ii) 2x 36/0.3 (2.5 sqmm) + I x 22/0.3 (1.5 sqmm) [16A Switch Board]
ii) 2x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) [A.C. Point]
Distribution wiring in 1.1 KV single core stranded FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required i) 2x 84/0.3 (6 sqmm) + l x 56/0.3 (4 sqmm) ECC [Sub-main Wiring]
Distribution Wiring in 1.I KV grade 2x22/0.3 (1.5 sqmm) single core stranded FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with lx22/0.3 (1.5 sqmm) single core stranded FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. with S & F 6A 5 pin Modular type plug socket and switch (Brand approved by EIC) fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. necy. connection making earthing Jattachment, painting and mending good damages to building works [PVC casing-capping on surface and Switch board concealed] i) On Board
ii) Average run 3 mtr [6A Switch Board]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket (Brand approved by EIC) with 16A Modular type switch, without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [16A Switch Board] [E-18/9 (b)]
Supplying and fixing double-door SPN MCB Distribution Board with IP.42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Legrand / Havells Siemens /L&T) i) 2+4 Way SPN DB [Enclosure (607710)]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Legrand Havells / Siemens / L&T). [D-6/7] i) Single pole 6-10A MCB.(M-Legrand)
ii) Single pole 20A MCB [A.C. Point](M-Legrand)
iii) Double Pole 32A MCB (M-Legrand)
Supplying and fixing Sheet steel Main Switches on flat iron frame on wall Make - Standard Havells HPL. [D-1/1] i) 32A 240V [with fuse on L&N]
Supply & delivery of single 4ft LED tube light fitting incl. 4ft LED tube, 1200 mm, Efficacy>= 100 Im/W, THD<10%, complete with all accessories. (Mas LEDtube 1200mm) [Philips: TMC 501 P 1xMas LEDTube 18W, 2100lm 865 T8] or equivalent of Havells, Crompton etc. [Approved by EIC] [NS]
Supply & Delivery at site 9 watt LED Bulb, Efficacy>=90 Im/W, Base Cap:- B22 [Make-Havells, LED ADORE PLUS9 W B22 CDL 3 STAR LAMPJ] or Jequivalent of Crompton, Philips etc. [Approved by EIC] [NS]
Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener. [C-2/14]
Fixing only lamp [9 watt LED Bulb] [C-2/11]
Supply and Delivery of Split type Room Air Conditioner having following specification. Cooling Capacity (Kcal/Hr):- 3024 Kcal/Hr (1 TR/1.1TR) ISEER Rating:- 3 Star/2018-2019 as per BEEBIS IS Compliance:- IS 1391 Refrigerant:- R32/R410A |Compressor:- Rotary/Scroll Evaporator & Condenser Coil : Copper Power Supply:- 240V, 50 Hz (Tolerance as per applicable standard) [Make: Mitsubishi Electric, Hitachi/O-General equivalent [NS]
Supply & installation of single phase AC timer DB comprising of 2+ 10 way IP 43 SPNMCBDB (Legrand CAT no. 5076120 Conceled in wall with 32 A DP MCB -1 no (legrand cat no 4086170 with I no analog time switch (cat no Make legrand make Microrex t31 daily time switch cat no. 412812), 32 A DP power Contactor (L& T Make cat no MNX 32-2P) ,32 A MCB Change over with led indecation two different (R & B) colour with suitable interconnection. [NS]
Installation, Testing & Commissioning of Indoor & Outdoor unit with necessary fixing on wall ( Indoor unit & outdoor unit ) as per direction of EIC by providing of 40x40x5 mm MS angle iron frame with necessary anchoring facilty on one side for necessary support on outer wall / making pedestal by angle & flat with necessaery welding each other etc. & Making hole for providing holding with outdoor unit by proper gauge Gl nut bolt &washer with necessary painting by synthetic enamel paint two coat of one after another over one coat of RO primer or Providing of ISI marked bracket provide on wall by necessary providing of 100 mm MS / Gi Fastner arrangwement not less than 6 (six ) no for each unit with making hole on wall and making connection of refrigeration pipe, power cable, drain pipe etc as per direction of the EIC. [NS]
S&F of following items for complete installation and commissioning of above AC machines including supply and fixing of Refrigerant pipe with insulation (nitrile rubber) tube of minimum thickness 9 mm (Make:-Armaflex/ Accoflex) (dia as required at site) including wrapping insulation and copper wire with GKB Gold wrapping tape & 3 core PVC insulated FRLSZH grade copper cable (Make:-Havells/Polycab/R.R. Kabel] [NS]
Supply & Fixing of PVC drain pipe 1" dia (make approved by EIC) [NS]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F15 mm dia Gl pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above i) By TATA-Medium GI pipe.
Extra for providing masonery enclosure on the top of the earth clectrode of overall size 86.36 cm x 86 36 cm x 46 cm deep (below Ground level) complete with cemented brick work( 1 6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36 56 em x 35.56 em with locking arrangement, Gl reducer including drilling of 46 nos 12 mm dia holes on the Gl pipe. [G-2/3 (a)]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with Gl bolts, nuts, washers, spacing insulators etc as required.[G-2/4(a)]
Connecting the equipment’s to earth busbar including S & F GI (Hot Dip) wire of size as below on wallloor with staples buried inside wall/ floor as required and making connection to quipment with bolts, nuts, washers, cable lugs etc. as equired and mending good damages.Solid GI wire i) No. 6 SWG
MOON LIGHT
MODERN ENGINEERING ENTERPRISE
NIRMAN ENTERPRISE
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .