Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | l1₹23.7 LAccepted-AOC | l1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹25.6 L+₹1.9 L (8.02%)Rejected-Finance | L2 | Rejected-Finance BIDDER NOT LOWEST | |
| 3 | L3₹26.4 L+₹2.7 L (11.4%)Rejected-Finance | L3 | Rejected-Finance BIDDER NOT LOWEST | |
| 4 | L4₹34.3 L+₹10.6 L (44.6%)Rejected-Finance | L4 | Rejected-Finance BIDDER NOT LOWEST | |
| 5 | L5₹41.6 L+₹17.9 L (75.4%)Rejected-Finance | L5 | Rejected-Finance BIDDER NOT LOWEST |
Tender Value
₹40.3 L
EMD Value
₹80,500
Closing Date
19 Sept 2022, 6:00 pmClosed
GE WEST DELHI CANTT 10
GE WEST DELHI CANTT 10
REPAIR REPLACEMENT OF EXTERNAL ELECTRICAL LT SIDE WATER SUPPLY AND OTHER CONNECTED WORKS AT DGBR AREA UNDER GE WEST DELHI CANTT 10
2022_MES_520781_1
GE/DW-59/2022-23
Open Tender
Civil Works
Item Rate
180 days
DELHI CANTT
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE WEST DELHI CANTT
₹80,500
27 Oct 2022
23 Aug 2022
21 Sept 2022
24 Aug 2022
19 Sept 2022
6 Sept 2022
Amount
Servicing of DG sets 100 KVA installed at HQ DGBR; including routine checking of all Engine and alternator parts for its servicing/durability complete all as per manufacturer recommendatations and including repair of followings parts in all DGs :- (a) Drain out the lubricating oil from sump and refilling after proper cleaning. (b) Replace Engine Oil filter cartridge with New one. (c) Replace fuel filter cartridge with New one. (d) Replace coolant fine filter with new one. (e) Replace air filter with New one. (f) Check tightness of all nuts and bolts (g) Check adjustment of V belt, driving engine water pump and alternator. (h) Assembling complete old serviceable parts and repair of old unserviceable parts by new one as per direction of Engr-in-Charge. (j) Testing of DG set after servicing as per Engr –in Charge. (k) Cleaning of air filter, fuel tank and radiator (Radiator should be clean with commpressed air and commpressor should be arrange by Contractor itself) every month as per requirement as per manufactures manual. Note:- (i) Any minor parts such as screws, washers, split pin , circlip etc shall be supplied by the firm, rate for the same shall be deemed to be included in the unit rate quoted. (ii) The servicing of DG Sets shall be carried out all as per direction of Enge-in-Charge and site requirements. (iii) Any parts required to be replaced during servicing of DG/engines shall be measured and paid for separately.
S & F Oil filter as per exsting make and size for DG Set of capacity 100 KVA as per sample.
S & F Fuel filter as per exsting make and size for DG Set of capacity 100 KVA as per sample. .
S & F Air filter as per exsting make and size for DG Set of capacity 100 KVA as per sample. .
Supply and Filing of coolant in DGs all as specified and directed by Enger-in-Charge.
Supply and Filling of lubricant oil (15-20)W-40 in replacemen in DGs all as specified and directed by Enger-in-Charge.
M & L for taking down repair and refixing of self starter of 100 KVA DG capacity including repair of burn field coil repair of armature and carbon bush holder and carbon bush point and solinoid coil, complete all as specified.
M & L for Repair/servicing of radiator assembly of 100 KVA DG Set (Greaves) after dismanteling and removing cooling fans, guard plates and lowering the same from engine after draining out water from radiator and scrapping / removing sludge / scale inside tank with acid including repair MS tank (botom portion) at rusted portion by cutting/ welding / brazing with 2mm thick copper plate including painting. Remounting the same at its original position and repalcement of pre mixed coolent as per the ratio fixed by manufacturer and testing complete all as directed by Enginer-in-Charge. (Note- Pre mixed coolent shall be measured and paid separately under relevant item of schedule)
M & L for Repair of battery Charger of any make including taking out from site and transporting to the electrical repair shop and taking back after repair and fix to the site complete all as specified and directed by Engr-in-Charge.
M & L for Disconnecting, taking out carefully old unserviceable AVR unit, supply & fixing, connecting and testing new AVR unit as per existing make and model suitable for DG set of 100 KVA capacity.
Material and labour in repair for CI butterfly valve of following sizes, stainless steel disc, gear mountable as per 13095 Class PN-1.0 complete with nuts, bolts, washers and rubber gaskets including taking out old unserviceable butterfly valve and deposting to MES store yard complete all as specified and directed by Engr-in-charge.
(a) 100 mm bore
(b) 80 mm bore
(c) 50 mm bore
Material and labour in repair for gun metal gate valve with iron wheel head screwed both ends for iron pipe and fixed, bore of pipe of following sizes including taking out old UNSV gate valve and depositing to MES store yard complete all as specified and directed by Engineer-in-Charge.
(a) 25 mm dia
(b) 40 mm dia
(c) 50 mm dia
M&L GI pipe 25 mm bore medium grade including all fittings such as tees,bends,elbows,sockets ,union ,reducer any type as reqd at site and nipples fixed to wall by means of clamps and other accessories incl of taking down of old U/S pipe.
M&L GI pipe 40 mm bore medium grade including all fittings such as tees,bends,elbows,sockets ,union ,reducer any type as reqd at site and nipples fixed to wall by means of clamps and other accessories incl of taking down of old U/S pipe.
M&L GI pipe 50 mm bore medium grade including all fittings such as tees,bends,elbows,sockets ,union ,reducer any type as reqd at site and nipples fixed to wall by means of clamps and other accessories incl of taking down of old U/S pipe.
M&L GI pipe 80 mm bore medium grade including all fittings such as tees,bends,elbows,sockets ,union ,reducer any type as reqd at site and nipples fixed to wall by means of clamps and other accessories incl of taking down of old U/S pipe.
M&L in repair CI foot valve swing type of size 100 mm,vertically mount including packing,nuts,bolts and washers.
M&L for taking down of burnt motor winding of induction motor and complete rewinding of electric motor 10 HP capacity with appropriate size of enamelled copper winding wire as recommended by manufacturer including insulation varnish and paper all as directed by engr-in charge and testing complete.
S&F in repair fully automatic star delta starter suitable for motor of capacity 12.5 HP including all contactors and wiring with suitable size of copper wire.
M&L for cleaning of under & over ground RCC water sump of cap 30,000 gallon thoroughly by scrapping/removing setteled silt on the wall and bottom surface washing with clean water after removing silt algess etc including colour wash as per existing colour on outer surface of the sump complete all as speciifed and directed.
M&L for flux board of size not more than 1.0 m X 1.0 m with lamination on wooden base frame with wood bidding including working details of plant of machinery of E/M installations (as directed by Engr-in-Charge) including fixing on wall with suitable nos of hooks complete all as specified and directed.
M & L for Detecting leakage of water supply pipe lines of Galvanised iron of size 100 mm bore from any location, any depth and repairing by providing jointing material,"D" joints, union, clamps, nuts, washers & bolts and including any GI fittings etc. complete all as directed and specified including earth work etc.
All as per Srl item No.28 here -in - before but 80 mm bore
All as per Srl item No.28 here -in - before but 40/ 50 mm bore
All as per Srl item No.28 here -in - before but 20/ 25 mm bore
M&L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregates as in foundation of, PCC blocks etc including necessary form work complete all as specified and directed.
M&L for dewatering, desludging and cleaning of wet and dry sewage sump well at HQ DGBR upto bottom of sump by mechanical methode with proper safety measures as prescribed in Govt. Norms and Taking out sludge from the sump and dump it to the suitable place away from the any defence land complete all as specified and directed.
Taking down LT Panel Board of any type and size from site complete all as specified and directed.
M & L in repair for earthing complete with galvanized steel earth plate 600x600x6mm thick buried vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of the plate not less than 1.50 mtr below normal ground level, connected to earth lead GI 4mm dia by means of bolts, nuts, check nuts and washers of galvanized iron and connection to main switch board of panel, including watering pipe GI 20 mm bore light grade 15mm bore for earthing lead, wire mess, funnel, salt, charcoal dust, excavation and refilling pit with PCC 1:2:4 type B1(using 20mm dia stone aggregate) reinforced with 6mm dia round bar @ 75mm cement concrete both always with MS handle 12mm dai and frame all as shown in electric plate No 3 in page 497 of SSR Part I (2009) including testing ion completion all as directed.
M&L in repair of LT panel bus bar copper strip 20 x 3 mm as panel internal electrical connections complete all as directed including taking down the old unserviceable complete.
M&L in repair of earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to pole or any other indicated situation using GI strip 25 x 4 mm as earthing lead complete all as directed including taking down the old unserviceable complete.
M&L in repair of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised iron or steel wire as earthing lead complete all as directed including taking down the old unserviceable complete.
M&L for Supply and lay in repair XLPE cable PVC insulated armoured and heavy duty PVC sheathed LT 1100 volts grade with aluminium conductor of size 3.5 core 240 sqmm in trench/on wall with metallic saddle clamp complete all as specified and directed.
All as per Ser item No-41 but 3.5 core 185 sqmm.
All as per Ser item No-41 but 3.5 core 120 sqmm.
All as per Ser item No-41 but 3.5 core 95 sqmm.
All as per Ser item No-41 but 3.5 core 70 sqmm.
All as per Ser item No-41 but 3.5 core 50 sqmm.
All as per Ser item No-41 but 3.5 core 35 sqmm.
All as per Ser item No-41 but 3.5 core 25 sqmm.
All as per Ser item No-41 but 3 core 16 sqmm.
M&L in repair in repair for GI pipe light grade galvanized with all fitting laid in trenches/poles for cable protections with a size of 50 mm all as specified and directed by Engr-in-Charge.
M&L in repair in repair for GI pipe light grade galvanized with all fitting laid in trenches/poles or cable protectionswith a size of 80 mm all as specified and directed by Engr-in-Charge.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 400 Amp, 36 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 350 Amp, 36 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 250 Amp, 25 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 200 Amp, 25 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 160 Amp, 25 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type , 125 Amp, 16 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair MCCB 4 pole suitable AC 3 phase 415 volt Adjustabble type 100 Amp, 16 KA rupturing capacity, with thermal magnetic release fixed on existing LT panel all as specified and directed.
S & F in repair time switches astro type (Having longitude and latitude of Indian cities in memory) 250 V, single phase of 20 Amps rating with contactor fitted inside steel enclosure complete.
S & F in repair of 3 Pole power Contactor AC3 type having 18 Amps rating with click fit DIN construction .
M&L in repair for on load changeover with advance neutral 630 Amp AC 415V,50Hz complete all as specified and directed.
M&L in repair for on load changeover with advance neutral 400 Amp AC 415V,50Hz complete all as specified and directed.
M&L in repair for on load changeover with advance neutral 200 Amp AC 415V,50Hz complete all as specified and directed.
M&L for boring of holes horizontally under the road below 0.5 mtr from the road/hard surface by manually/machanically for laying Pipes up to 100 mm dia and inclduing necessary machine without damaging the existing road and getting out in any type of soil and disposal of soil to a distance not exceeding 50m from the site of work complete all as directed.
M&L for cutting the existing road straight by manual,depth & width not less than 30 cm for pipes up to 100 mm dia & 60 cm for pipes up to 150 mm dia & filling back with excavated soil up to 75% road portion & 25 % shall be made with cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregate complete all as specified & diected.
S & F In repair, 1100 volts grade heavy duty cable with PVC insulated aluminium solid conductor served with an inner sheathing of PVC armoured, PVC sheathed 10 sq. mm nominal cross section, 2 core.
S & F in repair of New 90 watt LED fitting for street light on pole complete with electronic drivers and other accessories prewired complete all as specified and directed.
S & F in repair of LED drivers suitable for 90W outdoor road way luminaries complete all as directed and specified.
S & F in repair CORAL (OPAL) IP65 New generation Post Top Lantern ,energy saving environmental frindly, long life aesthetically designed with semetrical light distribution, spum aluminium landscape luminaire with high power LEDs as light source complete all as specified and directed.
S & F in repair Flood light 100W Energy saving IP65 High power COB LED as light source Havells complete all as specified and directed.
S & F Earthing Display Board made of UV based fibreglass material dully mounted on MS rod stand with PCC near earth Pit as per IS standard complete all as specified and directed.
M&L in repair for preparation of old painted steel surface of LT pole /strut along with nut ,bolts etc and appling one coat of red oxide and two coat of aluminiam paint including writing pole number with black synthetic enammeled paint and making alternative strip of black ,white and yellow paint from coping of pole at height of 0.50 mtr complete all as directed by engr-in-charge.
M&L for repair of water lavel indicator mechanical type having indicators making an every steps indicating 100 galon of an gap made out of angle iron 40x40x6mm and 16SWG steel wire rope ,pully ,and float as per existing size and length including complete water lavel indicator painting all as specified and directed .
M&L for excavation in trenches in soft soil n.exc 1.5 Mtr wide and n.exc 1.5 meter in depth for laying of cables/pole etc setting out trimming the site forming bottom surface to required level complete all as specified and directed by Engr-in-Charge.
M&L for returning filling in-trenches including spreading leveling watering and well ramming in layers with soft/loose/dense soil n.exc 25 cm thick in each layer of soil complete all as specified and directed by Engr-in-Charge.
M&L for removing/excavated soil to a distance n.exc 50 Mtr and depositing where directed at a level not exc 1.5 Mtr above the starting point complete all as specified and as directed by Engr-in-Charge.
M&L for sand cushioning with a layer of sand Jamuna 23 cm thick (8 cm under and 15 cm above the cable) in trenches complete all as specified and as directed by Engr-in-Charge
Supply and laying un-reinforced precast concrete cable covers for cable protection of class LV type 1 flat of size 250 x150 x 40 mm.
S&F in repair PCC cover with steel reinforce trench cover of size not less than 600X450X60 MM in size incl cleaning of trenches and cable, complete all as specified and directed all as per sample.
M&L in repair for Tubular Battery 12 Volt 180 AH, complete all as specified and directed.
S & F in repair Aluminum cable Lug 25mm
S & F in repair Aluminum Cable Lug 35mm
S & F in repair Aluminum Cable Lug 50mm
S & F in repair Aluminum Cable Lug 70mm
S & F in repair Aluminum Cable Lug 95mm
S & F in repair Aluminum Cable Lug 120mm
S & F in repair Aluminum Cable Lug 185mm
S & F in repair Aluminum Cable Lug 240mm
S & F danger notice plate of size 25x20cm & 1.6mm thick, mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamp, bolts and nuts of approved size for LT, complete all as specified and as directed.
S&F in repair BUS BAR cable juction box/cable distribution box with door made out of CRCA sheet not less than 1.6 mm thick with 200 Amp rated aluminium 3 phase bus bar including connecting all cable with Cable Lug on bus rail including nut and bolt and all required accessories complete all as specified and directed by engr-in-charge .
M&L for writing of LT Panel Signage/Front/Back Side with approved colour of paint/Printed Sticker of size not more than 50 mm all as directed at site by Engr-in-charge.
M&L in repair for Earthing complete with copper plate electrode 600x600x3.15mm thick electrode burried directly in ground not less than 1.5 mtr deep below normal ground level with top edge of earth plate not less than 1.5 mtr below normal ground level connected to and including and 20x3 mm copper strip as earth lead by means of bolt ,nuts, check nuts, and washers of stainless steel and duly welded incl PCC pit in PCC 1:2:4 type B-I angle iron 40x40x3mm frame, pit in PCC 1:2:4 type B-I cover 40mm reinforced with XPM weight not less than 4 Kg/Sqm and 6mm dia bar handle, excavation and earth work in any type of soil, charcoal dust and salt light grade GI watering pipe 20mm bore with funnel and wire mashand medium grade GI protection pipe 40mm bore and earth wire up all as shown in electrical plate No 3 of MES SSR- Part-I all as directed and specified by Engineer-in-charge. Note : Excavation work should be done by manpower/Manual only.
M&L in repair for taking down of burnt winding of induction motor and complete rewinding of electric motor 12.5 HP capacity with appropriate size of enamelled copper winding wire as recommended by manufacturer including insulation varnish and paper complete all as specified and directed.
M&L for dewatering, desludging and cleaning of wet and dry sewage sump well at CVD Line upto bottom of sump by mechanical method with proper govt safety norms and Taking out sludge from the sump and dump it to the suitable place away from the any defence land complete all as specified and directed.
M & L for disconnecting monoblock pump set assembly of 12.5 HP and taking out of the sump well deep up to 9 meter at CVD line sewage pump installation with the help of chain,pully & rope etc and carried it to the repair shop ,for servicing,greasing,repair work and refixing at site after two coat of spray paint of existing colour ,complete all as specified and directed.
M & L for Cutting wild grass, bushes, creaper, unwanted vegetation from inside/ surrounding of E/M installations, near sweage pump installations as when directed and removing of unwanted material from installation compound and depositing where directed.
M&L in repair copper cable flexible 3 core PVC insulated of size 2.5 Sqmm as specified and directed by Engr-in-Charge.
M&L in repair for disconnecting and taking down of impeller of Non clog 12.5 HP centrifugal sewage pump and replace the existing impellar as recommended by manufacturer all as specified.
M&L for taking down of burnt winding of induction motor and complete rewinding of electric motor 5 HP capacity with appropriate size of enamelled copper winding wire as recommended by manufacturer including insulation varnish and paper all as directed by engr-in charge and testing complete.
M & L in repair flat 3 core copper 16 Sqmm PVC armoured induction motor cable dully making connection in star delta starter conplete all as specified and directed.
Supply and fixing In repair, 1100 volts grade heavy duty cable with PVC insulated aluminium solid conductor served with an inner sheathing of PVC armoured, PVC sheathed 6 sq. mm nominal cross section, 2 core.
M & L for disconnecting monoblock pump set assembly of up to 10 HP and taking out at HQ DGBR sewage pump installation and carried it to the repair shop ,for servicing,greasing,repair work and refixing at site after two coat of spray paint of existing colour ,all as specified and directed.
M & L in repair float valve assembly for of size 25 mm to 50mm all as specified and directed.
M & L for painting Sewage pump installation bldg (inside and outside ) at HQ DGBR & CVD LINE with two coat of distemper paint after scrapping out old paints from wall/ceilings etc and prepare smooth surface with white putty complete all as specified and directed.
M & L for painting of pump house bldg (inside and outside ) at HQ DGBR with two coat of distemper paint after scrapping out old paints from wall/ceilings etc and prepare smooth surface with white putty complete all as specified and directed.
S & F in repair monoblock centrifugal pump set 01 HP of size 25x25mm single phase, 240 volts, complete all as specified and directed.
S & F in repair monoblock centrifugal pump set 01 HP of size 40x25mm single phase, 240 volts, complete all as specified and directed.
M & L in repair for construction of chain link fencing net of Eyelet size not more than 2x2 inch around the 250 KVA transformer fondation at Otm accmd of HQ DGBR of size (LxH) 5mx1.5m including vertical and horizontal supporting MS angle of size 20x20x3 mm dully welded or tightened with suitable size of nuts and bolts, including PCC work for fixing vertical section of MS angle complete all as specified and directed.
M&L in repair copper cable flexible 2 core PVC insulated of size 1.5 Sqmm as specified and directed by Engr-in-Charge.
S & F in repair exhaust fan motor copper winding for 450 mm sweep as per sample complete all as specified and directed.
Supply and fixing in repair MCB given below ,415V 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and directed.
(i) TP 63 AMP
(ii) TPN 100 AMP
(iii) SPN 40 TO 63 Amp
M&L for construction of brick masonnary with full brick wall chamber size of 900x900x900mm internal dimension with earth work in any type of soil , PCC M-10 (Nominal Mix ) type C-2 as in foundation , brick work in CM1:4, 15mm thick plaster in CM1:4 internally and externally , flush pointed in same mortar as work proceeds , 75mm thick PCC coping all around M-15 (Nominal Mix ) with 20mm stone aggregate , flooring shall 40mm thick PCC M-15 (Nominal Mix ) laid over 75mm thick hard core. Top cover shall be made out of MS sheet 3mm thick fixed in angle iron frame made out of angle iron size 40x40x6mm with two numbers of hinges on one side and locking arrangement at other side complete including painting with two coats of synthetic enamel paint over a coat of red oxide primer including dismentaling/ taking out old chamber complete all as specified and directed.
M&L for PCC 1:3:6 type C1 (20 mm graded stone aggregate) as in sub base complete all as specified and directed.
Deduct Credit: for demolished/dismantled material of (-) Rs 335725.00 (Minus) as listed in Schedule 'A' Part II (Credit Schedule) Note: Tenderer's shall not quote against this item. The amount of Credit Schedule is tentative, however the same shall be considered to arrive at the contract sum
NAVDURGA BUILDERS
M/s S.G. BUILDERS
GAUTAM ELECTRIC WORKS
Surjit and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .