GE I R AND D RCI, HYDERABAD
GE(I) RND RCI, MILITARY ENGINEER SERVICES, VIGNYANAKANCHA, RCI, HYDERABAD
REPAIRS REPLACEMENT OF ELECTRIC UG CABLES LT PANELS AND APFC PANELS UNDER GE I RND RCI HYDERABAD
2021_MES_438987_1
8620
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GE I R AND D RCI
MES enlisted Class D category b i Un enlisted Meeting enlistment criteria of D class in MES and having no recovery pending. For further details ref NIT
8 documents required · 8 mandatory
₹500
Yes
GE I R AND D RCI, HYDERABAD
₹90,000
Yes
26 Jul 2021
28 Apr 2021
3 Jun 2021
28 Apr 2021
27 May 2021
13 May 2021
Amount
Excavation in trenches not exceeding 1.50m wide and not exceeding 1.50m depth for foundation, for laying of pipes/cables/poles etc., and getting out in any type of soil complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each layer as in soil complete all as specified and as directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Supply and spreading natural river sand of approved quality for cushioning of cable laid in trenches including compacting and leveling complete all as specified and as directed Note: Punned thickness will only be measured and paid.
Supply and laying un reinforced precast concrete cable cover, class HV Type 1, size 300mm x 180mm x 40mm, laid flat adjacent to each other, perpendicular to cable in trenches for protection of cable complete all as directed.
Supplying, laying, jointing, testing and commissioning 1100 volts grade, 3.5Core 120Sqmm LT XLPE insulated, PVC sheathed as per IS-7098 (Part-I), 1988 galvanized steel strip or wire armoured, heavy duty, electric cables, with multistranded aluminium conductor laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including disconnecting and taking down unserviceable cable complete all as specified and directed for the following sizes:- Note: Earthwork Excavation, sand cushioning, GI pipe and cable protection will be measured and paid separately.
Supplying, laying, jointing, testing and commissioning 11000 volts grade, Earthed, HT XLPE insulated, insulation screened with extruded semi-conducting compound in combination with copper tape cores laid up, PVC inner sheath with fillers, galvanized steel flat strip armoured, heavy duty, electric cables, with multistranded aluminium conductor, conductor screen with extruded semi conducting compound and overall PVC sheathed cable as per IS-7098 (Part-2) 1988 with latest amendments, laid in trenches/ passing through pipe/duct/road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including disconnecting and taking down unserviceable cable complete all as specified and directed for the following sizes:- Note: Earthwork Excavation, sand cushioning, GI pipe and cable protection will be measured and paid separately.
3core 120Sqmm
3core 95Sqmm
Supply and jointing new outdoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120sqmm to 185sqmm for 11KV(Earthed) grade including testing complete all as specified and directed.
All as per item No 8 above but cable of size 3core 95sqmm
Supply and jointing new straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120sqmm to 185sqmm for 11KV (Earthed) grade including testing complete all as specified and directed.
All as per item No 10 above but cable of size 3core 95sqmm.
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 1200Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for ACBs/MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
ACB 4pole, 800Amps with adjustable thermal and magnetic settings (over load, short circuit, earth fault protection and metering relay), 50KA rupturing capacity at 415volt, mechanical draw out type with manual spring charge mechanism with self contained CTs - 01 No (Incoming)
MCCB 4pole, 630Amps, with adjustable thermal and magnetic settings, 50KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
MCCB 4pole, 250Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 06 No (Outgoing)
MCCB 3pole, 100Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
S&F in repairs, 3pole 400Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4220 02 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 320Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4220 01 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 250Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4202 39 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 200Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4202 38 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 160Amp MCCB, 36KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4200 87 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 125Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4200 06 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 100Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4200 05 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
S&F in repairs, 3pole 63Amp MCCB, 16KA rupturing capacity at 415volt with adjustable thermal and magnetic settings, conform to IEC -60947-II/ IS-13947-II including provision of copper cables/extended terminals of suitable ratings from MCCB to busbar and connection of LT cables with MCCB with suitable lugs complete all as specified. Make: Legrand CAT No.4200 03 or equivalent in L&T/ Siemens/Schneider/C&S as approved by GE
Supply, Install, testing and commissioning, factory made and tested, CPRI approved LT panel board indoor type, weather, dust and vermin proof, free standing floor mounting type mounted on floor, separate cable alley for all the feeders, suitable for 440Volts, 3 Phase 4wire 50Hz AC supply system, conforming to IS, IP-54 class protection and made of 2mm CRCA mild steel sheet & angle iron frame, compartmentalized with rubber gasket hinged doors, front & rear opening and locking arrangement (including provision of 65mm Godrej (freedom) lock with 2 keys) with necessary bus bar arrangement with electrolytic grade aluminium bus bar 600Amps rating for phase and neutral 4 strips with colour coded PVC sleeves, installed on epoxy insulators housed in separate bus chambers covered with heat shrinkable sleeves with necessary bus bar
tapings for MCCBs, copper control wiring using suitable size of PVC insulated, multi stranded copper conductors with all connected accessories, duly powder coated on the outside and inside including air ventilation for heat dissipation, suitable size knock out holes for cable glands, cable gland and lugs for incoming and outgoing cable etc., independent multilayer chambers to accommodate accessories including dismantling the unserviceable LT panel board from the existing position after disconnection of all electrical connections complete all as specified and directed with and including the following accessories :-
MCCB 4pole, 400Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 01 No (Incoming)
MCCB 4pole, 200Amps, with adjustable thermal and magnetic settings, 36KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
MCCB 4pole, 125Amps, with adjustable thermal and magnetic settings, 25KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
MCCB 4pole, 63Amps, with adjustable thermal and magnetic settings, 16KA rupturing capacity at 415volt, conform to IEC -60947-II/ IS-13947-II - 02 No (Outgoing)
Indicator lamp R,Y,B LED type with 3 Nos of 2A HRC fuses - 01 Set
Note: Necessary arrangement shall be made for connecting and proper alignment of the panel board with the existing panel boards.
M&L in repairs, Earthing complete with galvanized steel earth plate electrode of size 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5m below normal ground level connected to GI strip 25x4mm as earth lead by means of bolts, nuts, washers and check nuts made out of galvanized iron or steel all as shown on Electrical Plate No. 3 of SSR Part-I including testing on completion complete all as specified and directed.
Note 1: The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, 50mm thick RCC 1:2:4 type B-1 using 20mm graded stone aggregate cover slab reinforced with 6 Nos of 8mm dia TMT bars both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe light grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (Notes) under sub-heading earthing, specified on Sl Page No. 422 of SSR Part-II.
Note 2: Earthing lead beyond 7.5m will be measured and paid separately.
S&F GI Earth strip 25 x 4mm as in earth continuity conductor fixed to wall on battens or buried on ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing complete all as specified and directed.
Checking of APFC panels/capacitors bank panels, servicing of the same, cleaning of the switch gears, busbars with CTC to remove the carbon deposits, checking the connections, functioning of the components such as capacitors, contactors, switch gears etc., disconnecting and removing of burnt out cable end portions, crimping with new suitable lugs, removing of burnt out thyristors reconnecting back and testing complete for maintaining efficient power factor at the sub station all as directed. Note: Inspection of APFC panel shall be carried by the representative of OEMs of L&T/Neptune/Epcos only.
S&F, LT automatic power factor shunt capacitors, All Poly Propylene (APP) box type, heavy duty, rectangular in shape, conform to IEC 831-1 with total losses not more than 0.25W/KVAR for 3 phase, 440 Volts, 50 Hz system in the power factor capacitor panel board with suitable fixing arrangement including connection with suitable copper cables and testing including taking down the unserviceable power factor capacitors of different capacities from the capacitor panel board complete all as specified and directed. Make: L&T/Capco/Neptune
S&F, LT automatic power factor shunt capacitors, Cylindrical type, heavy duty, conform to IEC 831-1 with total losses not more than 0.25W/KVAR for 3 phase, 440 Volts, 50 Hz system in the power factor capacitor panel board with suitable fixing arrangement including connection with suitable copper cables and testing including taking down the unserviceable power factor capacitors of different capacities from the capacitor panel board complete all as specified and directed. Make: L&T/CAPCO/NEPTUNE/C&S/BCH/ABB Note for Sl item No 25 & 26: Copper cables, thimbles shall be measured and paid separately under respective items.
S&F, capacitor duty contactors for 25 KVAR ratings of capacitors including necessary electric connections and testing including dismantling unserviceable/ burnt thyristors/ power contactors from the power factor capacitor panel boards after disconnecting electric supply complete all as specified and directed. Make: L&T/CAPCO/NEPTUNE/C&S/BCH/ABB
S&F, power factor control relay (APFC) 12 step including necessary electric connections and testing including dismantling unserviceable power factor control relay from the panel boards, complete all as specified and directed. Make: L&T/Neptune/EPCOS
Dismantling unserviceable/ burnt electric wiring from the power factor capacitor panel boards, cleaning the panel with CTC to remove the carbon deposits, rewiring of control circuit of the panel boards with suitable size of PVC insulated, sheathed, stranded copper cable of 2.5/4.0/6.0/10 Sqmm/existing size, including provision of suitable copper lugs, bolts, nuts, washers etc., complete including electric connections and testing complete all as specified and directed.
S&F, 50 Sqmm size HRFR PVC insulated, unsheathed, single core industrial flexible copper cable, 1100 Volt grade, conforms to IS: 694, ISI marked, in the panel boards including necessary electric connections and testing including taking down unserviceable/ burnt electric cables connected with capacitors, complete all as specified and directed.
S&F, 35Sqmm size HRFR PVC insulated, unsheathed, single core industrial flexible copper cable, 1100 Volt grade, conforms to IS: 694, ISI marked, in the panel boards including necessary electric connections and testing including taking down unserviceable/ burnt electric cables connected with capacitors, complete all as specified and directed.
S&F in repairs, medium duty copper lugs suitable for 50Sqmm size cable complete all as directed.
S&F in repairs, medium duty copper lugs suitable for 35Sqmm size cable complete all as directed. Make for item No 32 & 33:DOWELLS/JOHNSON/COMET
S&F, push buttons with 1 NO / 1 NC, screw type for operation of capacitors all as per sample available at sub stations including necessary electric connections and testing including dismantling unserviceable push buttons (start/stop button) from the power factor capacitor panel boards complete all as specified and directed.
S&F in repairs, ISI marked synthetic rubber mat of size 1m x 2m, 2.0mm thick to resist 1100/440 volts grade voltage complete all as specified and directed.
S&F in repairs, ISI marked synthetic rubber mat of size 1m x 2m, 2.5mm thick to resist 11000 volts grade voltage complete all as specified and directed.
S&F in repairs, digital type ammeter, 96mm x 96mm square type suitable for three phase supply with suitable capacity CTs including electric connection and testing complete all as specified and directed
S&F in repairs, analog type ammeter 600/5 to 1000/5 ratio suitable for three phase supply with suitable capacity of CTs including electric connection and testing complete all as specified and directed.
S&F in repairs, 3 phase LED digital type voltmeter of 0-500 volt range including electric connection and testing complete all as specified and directed.
S&F in repairs, Single Phase digital type ammeter square type including electric connection and testing complete all as specified and directed.
S&F in repairs, Single Phase LED digital type voltmeter of 0-500 volt range including electric connection and testing complete all as specified and directed. Make for item No 37 to 41: L&T/AE/MECO/SIEMENS/ RISHABH/CONZERV/ENERCON
S&F in repairs, LED indicating lamps of red/yellow/ blue/green /amber with bulbs including connection and testing complete all as specified and directed. Make : AEI/IMP/MECO/L&T/SIEMENS/C&S
S&F repairs, Switch disconnector fuse unit, suitable for panel mounting open execution, 250Amps capacity, TPN, 415 volts with HRC DIN/Bolted fuse links complete all as specified
S&F repairs, Switch disconnector fuse unit, suitable for panel mounting open execution, 125Amps capacity, TPN, 415 volts with HRC DIN/Bolted fuse links complete all as specified
S&F repairs, Switch disconnector fuse unit, suitable for panel mounting open execution, 63Amps capacity, TPN, 415 volts with HRC DIN/Bolted fuse links complete all as specified.
S&F repairs, ON Load change over switch with sheet steel enclosure, side handle, 4Pole, 400Amp, 415 volts and making connections complete all as specified.
S&F repairs, ON Load change over switch with sheet steel enclosure, side handle, 4Pole, 250Amp, 415 volts and making connections complete all as specified.
S&F repairs, ON Load change over switch with sheet steel enclosure, side handle, 4Pole, 125Amp, 415 volts and making connections complete all as specified.
Disconnecting the electric supply to the panel boards, cleaning and removing the carbon deposits in the panel board, bus bar with CTC/CRC, tightening of nuts, bolts and replacement of unserviceable lugs, bolts, nuts and washers etc., complete all as directed.
Complete removal of creepers and vegetation from chain link fencing including all connected mild steel sections of 11 KV substation protection switch yard and main step down station (132/11 KV) protection switch yard and applying two coats of aluminium paint complete all as specified and directed.
S&F in repairs, 3 Pole Power contactor 415 Volts, 50Hz, type MNX, 185Amp AC3 rating complete all as specified and directed.
S&F in repairs, 3 Pole Power contactor 415 Volts, 50Hz, type MNX, 140Amp AC3 rating complete all as specified and directed.
S&F in repairs, 3 Pole Power contactor 415 Volts, 50Hz, type MNX, 95Amp AC3 rating complete all as specified and directed.
S&F in repairs, 3 Pole Power contactor 415 Volts, 50Hz, type MNX, 70Amp AC3 rating complete all as specified and directed.
S&F in repairs, 3 Pole Power contactor 415 Volts, 50Hz, type MNX, 25Amp AC3 rating complete all as specified and directed. Make for item No 44 to 56: Legrand/Schneider/ L&T/ Siemens/ C&S as approved by GE
c devender reddy and co
SUN LIGHT HOUSE
BHAGYARAM ENTERPRISES
SHRI GANESH ENTERPRISES
Maruthi international
SHANTI MARKETING AND SERVICES
Aziz Traders
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .