Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.6 LAccepted-AOC WARD NO 13 NEW SURATGARH | SURATGARH | L1 | Accepted-AOC ACCEPT | |
| 2 | L2₹17.6 L+₹86,277.50 (5.14%)Rejected-Finance | L2 | Rejected-Finance NOT BEING LOWEST | |
| 3 | L3₹19.1 L+₹2.3 L (14.0%)Rejected-Finance | L3 | Rejected-Finance NOT BEING LOWEST | |
| 4 | L4₹20.4 L+₹3.6 L (21.4%)Rejected-Finance | L4 | Rejected-Finance NOT BEING LOWEST |
Tender Value
₹26.5 L
EMD Value
₹53,000
Closing Date
10 Dec 2019, 6:00 pmClosed
GE (AF) SURATGARH
GE (AF) SURATGARH
REPAIR MAINTENANCE TO LT PANEL UG CABLE INTERNAL WIRING LED LIGHT DG SET EXTERNAL WATER SUPPLY AND CONNECTED EM WORKS AT AF ANUPGARH UNDER GE AF SURATGARH
2019_MES_296208_1
8773/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) SURATGARH
AS PER TENDER DOCUMENTS
10 documents required · 10 mandatory
₹500
GE (AF) SURATGARH
₹53,000
Yes
17 Mar 2020
8 Nov 2019
12 Dec 2019
8 Nov 2019
10 Dec 2019
26 Nov 2019
Amount
BOQ ( REPAIR/MAINTENANCE TO LT PANEL, UG CABLE, INTERNAL WIRING, LED LIGHT, DG SET, EXTERNAL WATER SUPPLY AND CONNECTED E/M WORKS AT AF ANUPGARH UNDER GE AF SURATGARH)
SCHEDULE 'A' PART-I (REPAIR / REPLACEMENT OF PIPE LINE, VALVE AND CONNECTED ITEMS)
Galvanized tubes 20 mm bore medium grade ISI marked as per IS 1239 part-I with all fitting ISI marked including cutting, threading etc as per site requirement and drilling holes/fixing clamp set for taking branch connection from main pipe line for laid in trenches/ road/ nallah or fixed along wall/ pole including mild steel clamps, screws etc, including taking down of old rusted galvanized iron tube , complete all as specified and directed by Engineer-in-Charge. Make: TATA/ JINDAL/ BST. Note : Earthwork to be measured and paid seperately.
Galvanized tubes 25 mm bore medium grade ISI marked as per IS 1239 part-I with all fitting ISI marked including cutting, threading etc as per site requirement and drilling holes/fixing clamp set for taking branch connection from main pipe line for laid in trenches/ road/ nallah or fixed along wall/ pole including mild steel clamps, screws etc, including taking down of old rusted galvanized iron tube , complete all as specified and directed by Engineer-in-Charge. Make: TATA/ JINDAL/ BST. Note : Earthwork to be measured and paid seperately.
Galvanized tubes 40 mm bore medium grade ISI marked as per IS 1239 part-I with all fitting ISI marked including cutting, threading etc as per site requirement and drilling holes/fixing clamp set for taking branch connection from main pipe line for laid in trenches/ road/ nallah or fixed along wall/ pole including mild steel clamps, screws etc, including taking down of old rusted galvanized iron tube , complete all as specified and directed by Engineer-in-Charge. Make: TATA/ JINDAL/ BST. Note : Earthwork to be measured and paid seperately.
Galvanized tubes 50 mm bore medium grade ISI marked as per IS 1239 part-I with all fitting ISI marked including cutting, threading etc as per site requirement and drilling holes/fixing clamp set for taking branch connection from main pipe line for laid in trenches/ road/ nallah or fixed along wall/ pole including mild steel clamps, screws etc, including taking down of old rusted galvanized iron tube , complete all as specified and directed by Engineer-in-Charge. Make: TATA/ JINDAL/ BST. Note : Earthwork to be measured and paid seperately.
Galvanized tubes 80 mm bore medium grade ISI marked as per IS 1239 part-I with all fitting ISI marked including cutting, threading etc as per site requirement and drilling holes/fixing clamp set for taking branch connection from main pipe line for laid in trenches/ road/ nallah or fixed along wall/ pole including mild steel clamps, screws etc, including taking down of old rusted galvanized iron tube , complete all as specified and directed by Engineer-in-Charge. Make: TATA/ JINDAL/ BST. Note : Earthwork to be measured and paid seperately.
Gun metal, globe or gate valve screwed down high pressure, heavy duty (ISI marked), with iron wheel head, screwed both ends for iron pipe or for unions suitable for 20 mm bore pipe, fixed in repairs, complete all as specified and as directed by Engineer-in-Charge.
Gun metal, globe or gate valve screwed down high pressure, heavy duty (ISI marked), with iron wheel head, screwed both ends for iron pipe or for unions suitable for 25 mm bore pipe, fixed in repairs, complete all as specified and as directed by Engineer-in-Charge.
Gun metal, globe or gate valve screwed down high pressure, heavy duty (ISI marked), with iron wheel head, screwed both ends for iron pipe or for unions suitable for 40 mm bore pipe, fixed in repairs, complete all as specified and as directed by Engineer-in-Charge.
Gun metal, globe or gate valve screwed down high pressure, heavy duty (ISI marked), with iron wheel head, screwed both ends for iron pipe or for unions suitable for 50 mm bore pipe, fixed in repairs, complete all as specified and as directed by Engineer-in-Charge.
Cast Iron sluice valve 80 mm bore both end flanged,long body,class PN-1.6 confirming to IS 14846-2000,duly ISI marked with iron wheel and brass spindle and fly nut,bolts, washers and rubber gasket etc, fixed in and including replacement of existing unservicable sluice return valve, complete all as specificed and directed by Engineer-in-Charge. Make : KIRLOSKAR or equivalent in KARTAR/BIR.
Ductile iron fittings conforming to IS: 9523/2000 with finishing as per class 13/IS 9523/2000 such as bends (any type, radius and angle) Tapers any type (straight bend increasing, decreasing double socket etc) Tee pieces single branch ‘Y’ junction double branch cross (all sockets or socket and spigot) collars caps and plugs etc suitable for upto 150 mm bore complete all as specified and directed.
SCHEDULE 'A' PART-II (REPAIR AND MAINT TO INTERNAL WIRING / REPLACEMENT OF LED LIGHT)
Taking down old unserviceable Switch socket plug of any size and making good disturbed surface of walls and floors, complete all as specified and directed by Engineer-in-Charge.
Taking down old unserviceable SPN DB, 8 way alongwith MCB and making good disturbed surface of walls and floors, complete all as specified and directed by Engineer-in-Charge.
Taking down old unserviceable MCB TPN DB, 4 way alongwith MCB and making good disturbed surface of walls and floors, complete all as specified and directed by Engineer-in-Charge.
Taking down old unserviceable submain wiring aluminium ete and making good the disturbed surfaces of walls/ floor etc matching with the existing surface, complete all as specified and directed by Engineer-in-Charge.
Taking down carefully aluminum point wiring (light, fans, socket etc) complete including battens and fittings such as switch, ceiling rose, light fittings, regulators, socket, etc. and making good disturbed surface of wall/floor, etc. ,complete all as specified and directed by Engineer-in-Charge. Note :- Temporary power supply shall be provided by contractor.
Sub-main wiring (concealed ) with two single core 4 sq mm FRLS PVC insulated unsheathed stranded copper conductor cable drawn through including chasing cutting in any type of masnory including 20 mm dia non-metallic PVC conduit fixed in wall including 2.5 sq mm copper earth continuity wire, accessories and connecting to earth dolly , complete all as specified and directed by Engineer-in-Charge.
Sub-main wiring (concealed ) with two single core 6 sq mm FRLS PVC insulated unsheathed stranded copper conductor cable drawn through including chasing cutting in any type of masnory including 20 mm dia non-metallic PVC conduit fixed in wall including 4 sq mm copper earth continuity wire, accessories and connecting to earth dolly , complete all as specified and directed by Engineer-in-Charge.
Point wiring (concealed) complete in and including rigid non metallic PVC heavy duty conduit, 19/20mm dia as per site requirement for concealed conduit wiring with 1.5 sq mm FRLS PVC insulated unsheathed multi standed copper conducctor cable with flush tye metal boxes modular type suitable for fixing modularswitches,sockets,fan regulators etc with white or any colour cover plate with and including PVC insulated unsheathed multi standard copper conductor cable of 1.5 sqmm as an earth wire connected to common earth and earth dolly as per IS specification and as specified for one light/fan/buzzer/socket point controlled by one modular switch. Note: Metal flush box and other modular accessories except switches, sockets, and fan regulators shall be deemed included in the rate quoted.
One light point controlled by one switch.
One ceiling fan point controlled by one switch.
One Exhaust fan point controlled by one switch.
One bell/buzzer point controlled by one push switch
One switch socket outlet 3 pin 5/6 amp on same board
All as per item No 19 above but 1.5 sq mm cable size and 1.5 sq mm earth continuity wire for one 3 pin socket outlet, 5 amps on Independent board.
All as per item No 19 above but 2.5 sq mm cable size and 2.5 sq mm earth continuity wire for one switch socket outlet, 3 pin 15 amps on same board.
All as per item No 19 above but 4 sq mm cable size with 2.5 sq mm earth continuity wire for one 3 pin socket outlet, 15 Amps on independent board.(AC/Geyser)
Notes for Item No. 19.01 to 19.09 :- (i) Metal flush box and other modular accessories except switches, sockets and fan regulators shall deemed to be included in quoted rates of contractor. (ii) The disturbed surfaces of wall for concealing the wiring shall be make good by applying cement plaster, putty and colour wash etc matching with the existing surfaces. The rate for point wiring shall be deemed to include the cost of making good.
Angle holder, PVC Polycarbonate type with back plate suitable for batten fittings, complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Step 0-4, modular type electronic regulator for ceiling fan 1200 mm sweep, 240 volts, 100 Watts humfree single pole, complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Door bell, AC, 230 Volts, single pole including connecting and testing , complete all as specified and directed by Engineer-in-Charge. Make : Anchor/Plaza/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Bell push Modular type,6 Amp, 1 modole.230 volts, including connecting and testing , complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor/Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Switch modular type, single pole one way 6 Amps, 250 volts Ac suitable for modular switch boxes without indicator, complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor/ Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Socket modular type single pole one way 6 Amps 2/3 pin 250 volts , complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor /Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Ceiling rose, surface bakelite, 65 x 50 mm, three terminals, including connecting and testing, complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Havell/Anchor or equivalent makes as specified in Appendix 'B' List of Makes.
Socket modular type 16 Amps, 3 pin combine, 2 module, 240 volts , complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor/ Roma/Crabtree or equivalent makes as specified in Appendix 'B' List of Makes.
Switch modular type 16 Amps, 1 module, 240 volts, complete all as specified and directed by Engineer-in-Charge. Make : Legrand/Anchor /Roma/Crabtree.or equivalent makes as specified in Appendix 'B' List of Makes.
Sheet metal enclosure with socket plug top single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 20 amps , 240 Volts, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/C&S or equivalent makes as specified in Appendix 'B' List of Makes.
Sheet metal enclosures for SPN DB's with double glazed door for incorporating MCBs,IP-43 , 8 way with 200 amps rated busbar, 240 volts, as per IS-8623, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/C&S or equivalent makes as specified in Appendix 'B' List of Makes.
Sheet metal enclosures for DB's for incorporating TPN, 4 way, IP-43 double glazed door with 200 amps rated busbar, 415 volts, as per IS-8623, complete all as specified and as directed. Make :- Legrand/L&T/Havells.
MCB four poles, 63 Amps, breaking capacity 10 kA 'C' curve confirming to IS-8828, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc including taking down old unserviciable MCB, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/C&S or equivalent makes as specified in Appendix 'B' List of Makes.
MCB SPN 32 amps 'C' series, breaking capacity 10 kA, 'C' curve 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc including taking down old unserviciable MCB, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/C&S or equivalent makes as specified in Appendix 'B' List of Makes.
MCB SP, 6 to 32 Amps, C series, breaking capacity 10 KA, 'C' curve 240 volts, 50 Hz including necessary incoming and out going electric connection with suitable size of copper lugs etc including taking down old unserviciable MCB, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/C&S or equivalent makes as specified in Appendix 'B' List of Makes.
LED bulb 7 watt with lumen 560 including taking down old unserviciable LED bulb, complete all as specified and as directed by Engineer-in-Charge. Make: Surya Cat No 7W LED 6500 K or equivalent in CG, Wipro & Philips.
Taking down old U/S light fitting and S&F 20 Watt LED Luminarie decorative box type fitting inlcuding LED tube with blue coloured end caps pre wired for LED tube energy saving with high efficiency PMMA diffuser gives soft glare free light with available lumen output from 2000 total lumen. The lamp shall be 1200 mm length with G13 base. The 20 Watt system shall be operating at 220-240V AC supply having internal driver, IP 20, surge protection 2 KV, ambient temperature -20 to 45 degree C, freequency 50 to 60 Hz, The system efficiancy must be between 80-100 lumen/watt, with 70% lumen maintenance up to 40000 Br Hrs with uniform visually comfortable light output at 150 degree beam spread, CRI minimum 80, PF should be greater than 0.95, THD <10%. Indivisual LED,s should not be visible for glare free output colour temperature 6500k filled on & including 2 Nos PVC block of suitable & connecting up to tube light fitting with connecting up with copper 3 core flexible white cord of min size of 0.5 sqmm all as specefied and directed. Make :Havells ENDURA LINEAR NEO Cat No 20W 857 Odering Code LHEWEBP7IN1W020,or equivalent CG / Surya/Syska LED
Taking down old U/S light fitting and Supply, installation, Testing and commissioning of LED Bulk head 10 Watt with a nominal system lumen output of 600 lumens and a minimum system efficiancy of 60 lm/W. The luminarie shall have a rated system lifetime of 50,000 burning hours at L70. The luminarie should have a color temperature of 6500K and CRI > 70. The luminarie shall meet IP 66 rating and IK 09 rating with THD < 20% and PF >0.9. The luminarie housing should made of high pressure die cast aluminium with polycarbonate front diffuser. The total power consumption should not exceed 10W complete all as specefied and directed. Make : Havells ENDURA RUGBY NEO - IP65 Cat Part No 10W 6000K Odering Code LHEOAOP7UZ6W010
SCHEDULE 'A' PART-III (REPAIR / REPLACEMENT OF LT PANEL, UG CABLE AND CERTAIN E/M WORKS)
MCCB four pole 63 Amps with breaking capacity 16 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCCB four pole 100 Amps with breaking capacity 16 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCCB four pole 125 Amps with breaking capacity 16 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCCB four pole 250 Amps with breaking capacity 36 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCCB four pole 350 Amps with breaking capacity 36 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCB TP, 40 Amps, breaking capacity 10 KA 'C' curve confirming to IS-8828, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc. fixed as in repair, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
MCB TP, 32 Amps, breaking capacity 10 KA 'C' curve confirming to IS-8828, 240 volts, 50 HZ including making necessary incoming and outgoing electrical connection with suitable size of copper lugs etc.fixed as in repair, complete all as specified and directed by Engineer-in-Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
Sand cushioning to cables with a layer of sand 8 cm deep before laying the cable and 15 cm depth (punned down to 10 cm depth after laying and stretching of cable), complete all as specificed and directed by Engineer-in-Charge. Note: Punned thickness (over all 18 cm) shall be measured & paid.
Brick of common burnt clay, sub class 'B' old size laid flat and dry on cables as in cable protection in trenches over cables perpendicular to direction of cables abutting each other , complete all as specified and directed by Engineer-in-Charge.
Taking out old unserviceable LT/HT cable from trenches /Wall/ floor etc and keeping aside for reuse or removal of any size , complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 16 Sqmm 4 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 35 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 50 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 95 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 120 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 150 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
Resin -Cast type straight Joint suitable for XLPE insulated LT cable 1100 Volts grade of size 240 Sqmm 3.5 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed. Make : Vishwa Power infrastucture ( P ) Ltd , Kit Code :SLA -11 or equvalent.
Resin -Cast type straight Joint suitable for XLPE insulated LT cable 1100 Volts grade of size 185 Sqmm 3.5 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed.Make : Vishwa Power infrastucture ( P ) Ltd Kit Code :SLA -09 or equvalent.
Resin -Cast type straight Joint suitable for XLPE insulated LT cable 1100 Volts grade of size 150 Sqmm 3.5 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed.Make : Vishwa Power infrastucture ( P ) Ltd Kit Code :SLA -08 or equvalent.
Resin -Cast type straight Joint suitable for XLPE insulated LT cable 1100 Volts grade of size 95 Sqmm 3.5 core complete with jointing material and acessories alongwith testing after jointing including taking out the old unserviceable joint kit complete all as specefied and directed.Make : Vishwa Power infrastucture ( P ) Ltd Kit Code :SLA -07 or equvalent.
Dismantling and taking down fluorescent tube light single/double of any wattage or any size of street light fittings complete all as directed.
Supply and fix 45 Watt LED street light with pressure die cast aluminium housing & toughened glass with IP-66 degree protection, individual LED's must have peanut lenses for better throw across & along the road with luminarie efficacy of greater than 100 lumen/Watt (Minimum lumen output of luminarie should be 4500 Lumens) color rendering (CRI) of > 75 and co-related color temperature (CCT) of 5700K (+ 500K), The luminarie should have 5 KV surge protection, PF > 0.95, and total harmonic distortion of THD < 10%, voltage range of 140-280V should be provided. Luminarie should have top maintainable driver compartment for easy access to driver during maintenance. The driver used must be a constant current driver with efficiency of > 85%. The manufactures LOGO must be embossed/Engraved in the housing of the luminarie. Manufactures to provide LM80 from source manufacturer and should have adequate testing facilities approved by ministry of science (Govt of India) to provide LM 79 report complete all as specefied and directed by Engr-in-charge. Make : Havells Cat No ENDURAPEARLNEOSL45WLED757SASYTOPC or equivalent make specefied in PS
Material and Labour for filteration and dehydration of transformer oil by dehydration machine to achieve the die-electric strength/ insulation value upto 65 KV/40KV (RMS) at standard gap of electrodes 2.5 mm for one minute in various capacity of transformers 33/11KV and 11/0.433KV including insulation testing of oil with help of suitable equipments before and after dehydration including BDV Test compete all as specified and as directed. Note: (i) Contractor will have to arrange the dehydration machine and transformer oil dielectric strength testing equipment as mentioned and same shall be deemed to be included in the item rate quoted. (ii) Test result of transformer oil before and after dehydartion is required to submit by contractor duly signed by all concerned. (iii) The contractor shall ensure that the conservator tanks are full to its level before commencement of dehydration process. (iv) Additional quantity of transformer oil if any required for making the oil level upto the requirement in transformer shall be measured and paid separately as supply and filling but its cost of heating shall be deemed to be included in the rate quoted for above item.
Supply and filling transformer power oil meeting IEC 60296-2003-11, 3rd edition standard specification and ASTMD 1275B test requirements for corrosive sulpher of BDV not less than 65 KV for filling in repaired transformer HT 11 KV complete all as specified and directed.
Brass terminal rod with nuts, bolts washers & bushings suitable for HT and LT side of the transformer of any make and capacity for 315 KVA complete all as specified and as directed.
SCHEDULE 'A' PART-IV (COMPREHENSIVE REPAIR / MAINT OF DG SETS AND AMF CONTROL PANEL)
Periodical maintenance of following size /capacity of DG sets through authorised service dealer of DG set and ensuring smooth functioning of DG sets of following capacities : -
160 KVA (Make : Mahindra )
20 KVA (Make : Mahindra )
Notes for item No- 63 to 63.02:- (i) Spares (Oils & Filters) required for maintenance of DG Set will be measured and paid separately. (ii) The rate quoted is not inclusive of major repair/overhauling of DG Set. In the event of any dispute the decision of Accepting Officer shall be final & binding. (iii) Repairer has to maintain the maintenance record, breakdown call register, periodical service report, Repair carried out register and the same are to be got signed from department rep(JE E/M)/ Engeneer-in- Charge and also duly signed by qualified Mech/Service Engineer of the contractor. (iv) All spares for repair are to be procured from manufacture`s authorised dealer only. (v) All tools, testing instruments are to be arranged by the contractor including necessary transport. (vi) The fixing/labour element for items catered here-in-after in BOQ as “Supply only” shall be deemed to be included in the quoted rate of this item. (vii) Printed log sheet pad duly binding with 31 pages on full scrap paper shall be provided by the contractor.
Supply only by pass filter element with O ring of Make MICO / Kirloskar for the following capacities of DG Sets :-
Supply only luberication oil filter element with 'O' ring of Make MICO / Kirloskar / Ruston as required at site for following capacities of DG Sets :-
Supply only Air filter element inner and outer as required at site with 'O' ring of Make MICO / Kirloskar / Ruston as required at site for following capacities of DG Sets :-
Supply only fuel filter element with 'O' ring of Make MICO / Kirloskar / Ruston as required at site for following capacities of DG Sets :-
Supply only fan belt of Make - Finner/ Dunlop/Kirloskar as required at site for the following capacities of DG Sets :-
Supply only distilled water to be filled in batteries ,complete all as specified and directed by Engineer-in-charge.
Supply only ignition switch with key in repair for DG sets of any capacities, complete all as specified and directed by Engineer-in-charge.
Material & labour for replacement of battery cable of size 70 sqmm PVC insulated multi stranded copper conductor single core cable with necessary lugs, complete all as specified and directed by Engineer-in-charge.
Supply only top up coolent for DG set radiator, complete all as specified and directed by Engineer-in-charge.
Supply only flexible braided hydraulic hose 5/8" dia x 600 mm length including suitable check nuts & washers, complete all as specified and directed by Engineer-in-charge.
Supply only solenoid switch in repair suitable for any capacity DG set, complete all as specified and directed by Engineer-in-charge.
Supply only control wiring kit suitable for any capacity DG Set, complete all as specified and directed by Engineer-in-charge.
Supply only lube oil SAE 15 W - 40 for Top up and filling up the oil in the sump after completely flushing the old oil out of the tank and cleaning of the tank for fresh filling, complete all as specified and directed by Engineer-in-charge. Make : Castrol/Power Supreme
Supply only battery terminal heavy duty as per sample made of brass with bolts and washers all as required at site,, complete all as specified and directed by Engineer-in-Charge.
Material and labour for electronic automatic voltage regulator ( AVR) of 100 V , 8 Amps suitable to DG Set of capacity upto 20 KVA including necessary terminals' sleeves etc as required at site of any type and make of DG Sets, complete all as specified and directed by Engineer-in-charge. Note :Make of AVR shall be same as supplied by the DG set manufacturer with new DG set.
Material and labour for electronic automatic voltage regulator (AVR) of 50 V , 16 Amps suitable for DG Set of capacity 160 KVA including necessary terminals' sleeves etc as required at site of any type and make of DG Sets, complete all as specified and directed by Engineer-in-charge. Note :Make of AVR shall be same as supplied by the DG set manufacturer with new DG set.
Supply and fixing in repair complete Dry cell 12 V 180 AMPH battery and initial charging complete including inbuilt charger including required electrolyte /distilled water etc and fixing as required at site to the concerned DG Set, complete all as specified and directed by Engineer-in-charge. Make:-Luminous / Exide / Bosh / Amron
Supply and fixing in repair complete Dry cell 12 V 90 AMPH battery and initial charging complete including inbuilt charger including required electrolyte /distilled water etc and fixing as required at site to the concerned DG Set ,complete all as specified and directed by Engineer-in-charge. Make:-Luminous / Exide / Bosh / Amron
Taking down unserviceable fuel injection pump from any type/ capacity DG set, carrying to workshop for repairing including necessary spares and calibration, refixing the same duly repaired to its original position and testing for its serviceability at site, complete all as specified and directed by Engineer-in-charge.
Material and labour for rewinding the self starter assembly 12/24 Volts by taking out from the DG set dismantling & cleaning , providing proper insulation rewinding with super enameled copper wire of existing size & insulating the field coil assembly replacing bentec assembly & fixing back after repairs and testing , complete all as specified as directed by Engineer-in-charge.
Supply & fixing Rubber hose set for following DG set radiator by replacing the unserviceable hose set , complete all as specified as directed by Engineer-in-charge:-
Material and labour for dismantling of radiator from engine taking it to work shop repair of leakage pipes, cleaning the radiator with cleaning agents, re-assembling to the engine completely to enting satisfaction of Engineer-in-Charge
Inspection/checking of AMF panel of DG set of capacity 20 KVA & 160 KVA installed at various installations of any make and shape and rectify the defects, replacement of unserviceable part as required at site and cleaning of AMF panel as detecting during inspection or pointed out by users/department and carry out maintenance , complete all as specified as directed by Engineer-in-charge. Note:- Spare parts required shall be measured and paid separately or issued by the department.
Supply only 4 Pole power contactor with AC coil 200 Amps, 3 phase 415 volt 50 HZ suitable for AMF panels in respect of serial item No 86 here-in-before , complete all as specified as directed by Engr-in-Charge Make:-Havells/GE/L&T/Siemens
Supply only under voltage monitor relay 415 volt three phase suitable for AMF panels in respect of serial item No 86 here-in-before , complete all as specified as directed by Engineer-in-Charge. Make:-UG/PIC
Supply only thermal overload relay 3 PH, 415 Volt (0-300 Amp) suitable for AMF panels in respect of serial item No 86 here-in-before, complete all as specified as directed by Engineer-in-Charge. Make:- LT/Siemens
Supply only cranking relay 12/24 volts DC 8/11 stage suitable for AMF panels in respect of serial item No 86 here-in-before , complete all as specified as directed by Engineer-in-Charge. Make:- Eagle Man or equivalent as approved
Supply only cranking relay 220 volts AC 8/11 stage suitable for AMF panels in respect of serial item No 86 here-in-before Complete all as specified as directed by Engr-in-Charge Make:- Eagle Man or equivalent as approved
Material and labour in replacement of MCCB 4 pole 200 Amp, 36 kA with adjustable thermal and adjustable magnatic setting including making all incoming and outgoing connections, complete all as specified as directed by Engineer-in-Charge. Make: Legrand/ABB/Siemens/L&T/Havells.
Material and labour in replacement of MCCB 4 pole 160 Amp, 36 kA adjustable thermal and adjustable magnatic setting including making all incoming and outgoing connections, complete all as specified as directed by Engineer-in-Charge. Make: Legrand/ABB/Siemens/L&T/Havells.
Supply and fixing in replacement of MCB 63 Amp, 240 Volts, SPN, breaking capacity 10 KA, C curve complete all as specified and as directed by Engineer-in-Charge. Make: Legrand/SIEMENS/L & T/Havells/Standard
Supply and fixing in replacement of MCB 63 Amp, 415 Volt, TPN, breaking capacity 10 KA, C curve , complete all as specified and as directed by Engineer-in-Charge. Make: Legrand/SIEMENS/L & T/Havells/Standard
SCHEDULE 'A' PART-V (COMBINE ITEMS & MISC ITEMS)
Excavation in trenches not exc 1.5m wide and and not exc. 1.5m depth wide in soft/loose soil for laying electric cables/pipes etc including getting out excavated earth and trimming the sides and bottoms of trenches , complete all as specificed and directed by Engineer-in-Charge.
Returning , filling in including spreading, leveling, watering and well ramming in layers not exc. 25cm in soil, complete all as specificed and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exc. 50m and depositing where directed at a level not ex. 1.5m above the starting point , complete all as specificed and directed by Engineer-in-Charge.
XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured, electric power cables (Heavy duty) with stranded aluminium conductor, 1100 volts grade (earthed) cross sectional area 300 Sqmm 3.5 core, laid in trenches, through pipe in road crossing, ducts, fixed along poles ,complete all as specified and directed by Engineer-in-Charge.
MCCB four pole 400 Amps with breaking capacity 36 KA , 415 Volts, fixed thermal & magnetic release including making all incoming/ outgoing connections fixed as in repair complete all as specified and directed by Engineer in Charge. Make :- Legrand/L&T/Schneider /C&S/Havells or equivalent makes as specified in Appendix 'B' List of Makes.
Contract Amount shall be derived after affecting the amount of Schedule of Credit in General Summary on serial page No 15(R)(R) of tender documents.
DASHMESH ENTERPRISES
SHARMA CONSTRUCATION COMPANY
AJAY ELECTRIC COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .