Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.2 LAccepted-AOC | L1 | Accepted-AOC Lowest and Reasonable | |
| 2 | L2₹14.7 L+₹79,700 (5.75%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹14.9 L+₹1.1 L (7.61%)Rejected-Finance CHESHIRE HOME ROAD SHAKTI KUNJ BARIATU RANCHI 834009 | RANCHI | JHARKHAND | 834009 | L3 | Rejected-Finance Not Lowest |
Tender Value
₹14.9 L
EMD Value
₹29,800
Closing Date
15 Jun 2020, 6:00 pmClosed
GE DIPATOLI
GE DIPATOLI MES DIPATOLI MIL STATION P.O. HOTWAR RANCHI -835217
REPAIR/ MAINT OF CUBICAL PANEL BOARD WATER SUPPLY INSTALLATION AT DIPATOLI MIL STATION
2019_MES_309910_2
8000/1555/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
DIPATOLI
CLASS E CATEGORY b(i)
7 documents required · 7 mandatory
₹500
Yes
GE DIPATOLI
₹29,800
Yes
14 Jul 2020
18 Apr 2020
18 Jun 2020
18 Apr 2020
15 Jun 2020
2 May 2020
Amount
Construction of 100 HP pump sets foundation chanels of size (250x250x10) mm with and including cutting, welding and drilling etc. Before fixing the base plate contractor shall remove pump set and electric connection digging old base plate from PCC foundation. Note:- (i) Grouting of nuts, bolts and alligement of pump set shall be carried out by the contractor complete all as specified and as directed by Engr-in-Charge. (ii) Before execution contractor shall submit the sketch of foundation to Engineer-in- Charge for approval.
Earthing complete with Galvanised steel earth plate electrode (600 x 600)mm x 6.3 mm thick buried directly in the ground vertically to depth not less than 3 Mtr below the ground level with the top edge of earth plate, depth not less than 2.25 Mtr below the ground level connected to galvanised earth lead wire (32 x 6) mm size by means of bolts, nuts and washers, protected by GI tubing light grade 40 mm dia upto test point 20 mm dia watering GI pipe medium grade with funel & wire mesh, PCC pit in PCC (1:2:4) using 20 mm stone aggregates chamber 40 mm thick RCC cover slab (1:2:4) type B-1 using 20 mm graded stone aggregates complete all as specified and shown in electrical plate No.3 of SSR Part-I including earth work in any type of soil, removal of surplus sil and providing charcol dust & salt layers all around the earth plate upto 15 cm complete all as required, specified & directed by Engr -in- charge. Note:- Up to 7.5 Mtr length of pipe of 40 mm dia and GI strip shall be deemed to be included in unit rate quoted by tenderer. GI pipe and GI strip beyond 7.5 Mtr shall be measured separately under respective item.
S&F in replacement CI Sluice valve confirming to IS 14846 – 2000 PN-1.6 flanged ends stainless spindle of following sizes with necessary packing materials and nut, bolts including taking down existing sluice valve complete all as directed at site:- (a) 150mm bore
(b) 250mm bore
Supply & fixing in replacement CI Non return valve IS 5312 with ISI mark brass spindle with GM check nut of following sizes:- (a) 150mm bore
(b) 250 mm bore
Om Construction
ashiyana electrical company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .