Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹80.1 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹82.9 L+₹11.4 L (15.9%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹87.4 L+₹15.9 L (22.3%)Rejected-AOC PLOT NO F28 COMPLETE COOLING SOLUTIONS LLP PHASE 8 INDUSTRIAL AREA SAS NAGAR MOHALI PUNJAB 160055 | S A S NAGAR | PUNJAB | 160055 | L3 | Rejected-AOC L3 | |
| 4 | Rejected-Technical BU 02 SFS FLATS OUTER RING ROAD PITAMPURA NORTH WEST DELHI DELHI 110034 | NORTH WEST DELHI | DELHI | 110034 | - | Rejected-Technical Not qualified | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹1.1 L
Closing Date
12 Dec 2020, 5:00 pmClosed
XEN Electrical division No. 1 Shimla-9
The Executive Engineer Electrical Division No-1 HPPWD Shimla-9
CO Indoor Auditorium for cultural Activities at Solan SH Prov VRV VRF system in Hall Museum Art Gallery Library and seminar Hall Distt Solan HP
2020_PWD_42723_1
Electrical Div.No1PWD Shimla 2020-21-4834-39
Open Tender
Electrical Works
Item Rate
365 days
SHIMLA KASUMPTI -9
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,000
E.E.Electrical Division No-I Shimla-9
₹1.1 L
3 Jun 2021
2 Dec 2020
14 Dec 2020
2 Dec 2020
12 Dec 2020
2 Dec 2020
Amount
Supply, Installation, Testing and Commissioning of Variable refrigerant flow/volume type air-condition system suitable to operate from 415 ± 10% volt, 50 Hz,3 phase AC power supply for cooling/heating with compressors (100% Inverter based and should be of same make as of indoor/outdoor unit) Hermetically sealed scroll type complete with fittings, AHU kit, isolator of suitable size in weather proof enclosure,power cable, vibration isolators with necessary wiring, connection & termination etc. including full charging of R-410A refrigerant gas complete as per requirement. Minimum COP shoud be 3.65 at full load at AHRI condition. Make:-Daikin/O-general/ Mitsubishi/Hitachi.
64 HP ( MAXIMUM 6 nos. Compressor)
Supply, Installation, Testing & Commissioning of DX- type floor standing air handling units of following capacity suitable to operate at 415+10% volt, 50 Hz, 3 phase AC power supply as specified complete with the followings:(i)Fan Section with canvas connection - double skin type made of 25 mm thick panels consisting of preplasticized G.I. casing of thickness 0.6 mm outside layer and 0.6 mm thick plane G.I inside layer with polyurethane foam (PUF) insulation of density 40+2 Kg/m3 factory injected between them by injection moulding machine. The AHu should be with thermal break profile.(ii)1 Nos. DIDW Centrifugal forward curve supply air blower with static pressure of 50 mm WG static pressure.(iii)DX coil section with aluminium finned copper tubes (tube thickness not less than 0.30mm) 6 row deep type cooling coil. The coil should be arranged to connect with multi circuits of outdoor units of required capacity.(iv)Pre filters with filter section with 50 mm thick washable synthetic type air pre-filters having efficiency 90% down to 10 micron.(v)20 G SS Drain pan, drain connection.(vi)Drive motor, drive arrangement, guard etc. Belt drive package with TEFC(IE 2) suitable at 415+10% volts, 50 Hz, 3 phase AC power supply.(vii)Necessary vibration isolators,complete in all respect including controls, supporting arrangement & complete in all respect as required.(viii)AHUs will be VFD controlled, all necessary accessories required for same should be quoted along AHU cost.Make:-Zeco/ Edgetech/ System Air/ Nutech
13000 CFM, 60 HP AHU
Supply, Installation, Testing & Commissioning of DX- type ceiling suspended units as specified Necessary hanging arrangement, complete in all respect including remote controls, heating/cooling thermostat, etc as required.Make:-Daikin/O-general/ Mitsubishi/Hitachi.
DUCT TYPE INDOOR UNIT - CAPACITY : 20 HP AIR QUANTITY :170 CFM
DUCT TYPE INDOOR UNIT - CAPACITY : 10.0 HP AIR QUANTITY : 96 CFM
CASSETTE TYPE INDOOR UNIT CAPACITY : 2.5 HP AIR QUANTITY: 27 CFM 4 WAY TYPE
CASSETTE TYPE INDOOR UNIT CAPACITY : 1.5 HP AIR QUANTITY.: 21 CFM 4 WAY TYPE
HI-WALL INDOOR UNIT - CAPACITY : 2.5 HP AIR QUANTITY :19 CFM
Supply and Fixing in position the following UPVC condensate drain pipe (suitable for minimum 6kg/sq cm working pressure) insulated with 6 mm thick insulation.Make:-AKG/Polypack/supreme
32 mm dia drain pipe
Supply and Fixing of insulated GI class 'B' condensate drain water piping insulated with 6 mm thick insulation with bends reducers tees, supports etc.as required.Make:-SAIL/Jindal /National
25 mm dia drain pipe
32 mm dia drain pipe
Supply, Installation, Testing and Commissioning of Ceiling Hung 16000 cfm Air Axial flow fans of 20 mm WG static pressure complete with GSS casing, aluminium alloy impellers, directly driven by TEFC induction motor suitable at 415±10 % V,50 Hz, 3 Phase AC power supply, 1400 RPM, supporting frame,louvers, weld mesh inlet guard, TP isolator with MS enclosure box as required. Axial fans shall be AMCA and third party certified and should have rated motor and fan of Class- F.Make:-Greenheck/ System Air/ Kruger/ Lau
Supplying, Installation, Testing and Commissioning of Floor standing 16000 cfm Exhaust Air Axial flow fans of 20 mm WG static pressure complete with GSS casing, aluminium alloy impellers, directly driven by TEFC induction motor suitable for 415 V ± 10 %, 50 Hz ,3 Phase, 1400 RPM, supporting frame, Gravity louvers, weld mesh inlet guard, TP isolator with MS enclosure box as required etc. Axial fans for smoke ventilation shall be AMCA and third party certified and should have fire rated motor and fan of Class- H suitable for working at high temperature (250 deg. C for minimum 2 hrs.).Make:-Greenheck/ System Air/ Kruger/ Lau
Supply, Installation, Balancing and Commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets,elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.Make:-Rolastar/ Zeco/ Ductofab/ Waves
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Supply, Installation, Balancing and Commissioning of site fabricated GSS sheet metal rectangular ducting with supports as per IS 655-2006 complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following gauges.Make:-SAIL/Jindal /TISCO/ Tata Steel/ National
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Thickness 1.00 mm sheet
Thickness 1.25 mm sheet
Supply, Installation, Testing & Commissioning of 350 mm dia thermal insulated flexible duct duly supported at regular interval as per site requirement etc. complete as required.Make:-Atco / UP Twiga/ Global
Supply,Installation,Testing and Commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as required.Make:-Ruskin/Mapro/ Servex/Air Master
Supplying, Fixing, Testing and Commissioning of motorised fire dampers in supply air duct, return air duct as and where required inclusive of control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed/opened in the event of fire signal complete as required.Make:-Mapro /Ruskin/ Air master/ Servex
Fire damper
Actuator
Supply & Fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers with anti smudge ring & removable core..Make:-Mapro/ Titus/ Servex/ Air Master
Supplying & Fixing of powder coated extruded aluminium return / exhaust Air Grills with louvers but without volume control dampers complete as required.Make:-Mapro/ Titus/ Servex/ Air Master
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.Make:-Mapro/ Titus/ Servex/ Air Master
Supplying, fixing testing commissioning of return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.Make:-Mapro/ Titus/ Servex/ Air Master
Supply,Installation, Testing and Commissioning of extruded aluminum louvers with bird screen and volume control damper for fresh air intake in indoor units.Make:-Mapro /Ruskin/Servex/ Air Master
Supply , Installation , Testing and Commissioning of extruded aluminum louvers for exhaust air.Make:-Mapro /Ruskin/Servex/ Air Master
Supply, fixing and commissioning of non vision air transfer door grille of powder coated extruded aluminium, single deflection grille with horizontal vanes arrangement etc. as per specifications.Make:-Mapro /Ruskin/Servex/ Air Master
Supply,Installation,Testing and Commissioning of powder coated Al sheet double skin, jet nozzle (eye ball type) with double flap butterfly damper of Gi construction including gear assembly,nut bolts etc.300 mm dia. Make:-Trox/Air Master/Titus/Mapro/System Air. 300 mm dia
Supply& Fixing of Interconnecting copper refrigerant pipe work 19 mm / 13 mm thick duly insulated with Nitrile insulation between indoor and outdoor units as per specifications.. Make:-Rajco/ Mandev/ Mexflow.
44.5 mm dia with 19mm thick /nitrile rubber insulation
38.1 mm dia with 19mm thick /nitrile rubber insulation
31.8 mm dia with 19mm thick /nitrile rubber insulation
28.6 mm dia with 19mm thick /nitrile rubber insulation
22.2 mm dia with 19mm thick /nitrile rubber insulation
19.1 mm dia with 13mm thick /nitrile rubber insulation
15.9 mm dia with 13mm thick /nitrile rubber insulation
12.7 mm dia with 13mm thick /nitrile rubber insulation
9.5 mm dia with 13mm thick /nitrile rubber insulation
6.4 mm dia with 13mm thick /nitrile rubber insulation
Supplying and fixing of 13 mm thickness duly laminated aluminium foil of matfininshed closed cell Nitrile rubber (class "O'') insulation on duct after applying two coats of cold setting adhesive (The joints shall sealed with 50mm wide and 3 mm thick self afhesive nitrile rubber tape insulaton complete as per specifications and as required.Make:-Hylam/Superlon/Armaflex/Trocellen
Supply and fixing of acoustic lining of supply air duct and plenum with 25 mm thick resin bonded glass wool having density of 32 kg/m³, with 25 mm X 25 mm GI section of 1.25 mm thick, at 600 mm centre to centre covered with Reinforced Plastic tissue paper and 0.5 mm thick perforated aluminum sheet fixed to inside surface of ducts with cadmium plated nuts, bolts, stick pins, CPRX compound etc. complete as required and as per specifications.Make:-UP Twiga/ Owens Corning/Lloyd Insulation
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with 50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction fixed in 610mm x 610 mm frame work made of 25 X 50 X50 X 50 X 25 mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fiber glass tissue and finished with 0.80 mm perforated aluminium sheet etc. complete as required and as per specifications.Make:-UP Twiga/ Owens Corning/Lloyd Insulation
Supplying and erection of sheet metal Main cubical pedestal(confirming to ( IEC code -61439) of dimensions 1350mm (height) x 1800mm (width) x 350mm (deep) with plus-minus 5 cm variation, made from 1.6 mm thick M.S. sheet duly fabricated in a segregated manner for housing of switch fuse units, by welding each compartment on five sides & front side hinged, complete with locking arrangement, with sufficient No. vertical and horizontal intermediate switchgear housing compartments including 1 No 400 Amp (4 Pole) MCCB as main incomer and 9 Nos MCCB 63 Amp. 32A TPN MCB and 63A TPN MCB ,as outgoings copper busbar Strips 400 Amp.,63 Amp.including metering module& indicating lamp set. The cubical pedestal shall have cable entry box at one or two sides, with epoxy powder coated approved paint and bonding to the existing earth etc. The same shall be erected in the 1:2:4 cement concrete plat-form of suitable dimensions 15 cm high from ground level and 45 cm thick. The cubical pedestal shall be 15 cm from the top of cement concrete plat-form
Supplying and erection of sheet metal Starter cubical Panel(confirming to ( IEC code -61439) made from 1.6 mm thick M.S. sheet duly fabricated in a segregated manner for housing of switch fuse units, by welding each compartment on five sides & front side hinged, complete with locking arrangement, with sufficient No. vertical and horizontal intermediate switchgear housing compartments including 1 No 100 Amp (4 Pole) MCCB as main incomer and11KW S/D Starter ,63A TPN MCB - 2 no.,9-15A O/L Relay - 2 no.,18A TP CONTACTOR - 4 no.,9A TP CONTACTOR - 2 no.,as outgoings copper busbar Strips 100 Amp.including metering module& indicating lamp set. The cubical pedestal shall have cable entry box at one or two sides, with epoxy powder coated approved paint and bonding to the existing earth etc.
Providing, laying and fixing of one No. aluminium conductor, PVC insulated and PVC sheathed, armoured/XLPE power cable, working voltage 1100 volts grade on surface etc. of the required size:-
Armoured cable 10 sq. mm (four core)
Armoured cable 16 sq. mm (four core)
Armoured cable 35 sq. mm (3.5 core)
Armoured cable 300 sq. mm (3.5 core)
Supply & laying testing and commissioning of following sizes of XLPE insulated PVC sheathed armoured Copper conductor Control cable of 1.1 KV grade on existing cable tray/ surface including clamps, ties etc. complete as required.Make:-Havelles/Finolex/Polycab
Armoured cable 1.5 sq. mm (Threecore)
Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.
3x1.5 Sq. mm.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required:-
25 mm. dia
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.Make:-Power/Gripwell/Dowels
Armoured cable 10 sq. mm (four core)
Armoured cable 16 sq. mm (four core)
Supply, Fabricating and installation following size of perforated GI cable trays including horizontal and vertical GI bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders and including painting etc. complete as required & approved by the Engineer In Charge..Make:-Rico/ Indiana/ Profab
150 mm. Width x 50mm. Depth x 1.6mm. Thickness.
300 mm. Width x 50mm. Depth x 1.6mm. Thickness.
Earthing with copper earth plate 600 mmx600 mmx 3 mm thick, including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as required.
Extra for using salt and charcoal for G.I. or copper plate earth electrode complete as required.
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for horizontal run)
Supplying and fixing copper tape 20mmx3mm thick on parapet or surface of wall for lightning conductor as required ( for vertical run)
Supplying and laying 8 SWG Copper wire at 0.50 mtr. below ground level for earth electrode conductor, including soldering etc. as required.
Any kind of Civil work related to the VRF system such as foundation for AHU,outdoor units, making holes,cutting of glass & all kind of restorations including repainting, scaffolding etc.
modern cooling solution
COMPLETE COOLING SOLUTIONS LLP
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .