CE PWD (Bldg), Assam, Chandmari, Ghy-3
O/O The CE PWD (Bldg), Assam, Chandmari, Ghy-3
Up-gradation and Face lifting of AMCH into COVID-19 Hospital under SOPD-G (Installation of Gas Pipe line with manifold Room at different Departments) at AMCH, Dibrugarh
2021_PWBNH_21637_1
GMC.71/2020/14 Dated Guwahati the 4th May, 2021
Open Tender
Civil Works - Building
Item Rate
90 days
Dibrugarh
Please refer Tender documents.
6 documents required · 6 mandatory
₹12,500
Assam State Road Board Maintenance (Road) Fund
₹9.8 L
Yes
O/O The CE PWD (Bldg), Assam, Chandmari, Ghy-3
4 Sept 2021
6 May 2021
20 May 2021
6 May 2021
20 May 2021
10 May 2021
10 May 2021
Amount
Earthwork in excavation for foundation trenches of walls, retaining walls, footings of column, steps, septic tank etc. including refilling (return filling) the quantity as necessary after completion of work, breaking clods in return filling, dressing, (A) Up to a depth of 2.00m below the existing ground level. (a) In ordinary soil
Earth/ sand filling in plinth in layers not more than 150mm thick including necessary carriage, watering, ramming etc. complete as directed and specified including payment of land compensation, forest royalty, sales tax and other duties and taxes as may (c) With river sand or silt (predominantly non plastic) by truck carriage including loading and unloading.
Plain cement concrete works with coarse aggregate of sizes 13mm to 32mm in foundation bed for footing steps, walls, brick works etc. as directed and specified including dewatering if necessary, and curing complete (shuttering where necessary shall be meas (a) In prop 1cement: 3 sand :6 coarse aggregate by volume.
Providing and laying 25mm thick damp proof course with cement concrete in prop 1:1.5:3 with graded stone agg. of 10mm down nominal size including providing approved damp proof admixture in proportion as recommended by the manufacturer including curing etc
Providing and laying plain/reinforced cement croncrete works cement, coarse sand & 20mm down graded stone aggregate including dewatering if necessary, and curing complete but excluding cost of form work and reinforcement for reinforced cement concrete wor (I) Using Mixer Machine (A) In substructure up to plinth level Foundation, footing, columns with base tie and etc. (N) Without using admixture, plasticiser (b) M20 grade concrete or Prop. 1:1.5:3.
Providing and laying plain/reinforced cement croncrete works cement, coarse sand & 20mm down graded stone aggregate including dewatering if necessary, and curing complete but excluding cost of form work and reinforcement for reinforced cement concrete wor (I) Using Mixer Machine (B) In super structure from plinth level up to 1st floor level. (ii) Columns, pillars, posts, struts, suspended floor, roof, landing, shelf and support, balcony, lintel, sill band, beam, girder, bressumer, cantilever, staircase N) Without using admixture, plasticiser. (b) M20 grade concrete or Prop. 1:1.5:3.
Providing form work of ordinary timber planking so as to give a rough finish including centering, shuttering, strutting and propping etc., height of propping and centering below supporting floor to ceiling not exceeding 4.0M and removal of the same 3.1.1.1. :- Foundation, footings, bases of columns, pile cap, raft and mass concrete works etc. (b) Using 25mm thick plank
3.1.1.2. :- Sides of tie beams, grade beams etc. at or below ground level. (b) Using 25mm thick plank
3.1.1.3. :- Columns, Pillars, Posts & Strut (a) Square, Rectangular, polygonal in plan or any shape like Tee/L etc. having plane vertical face (ii) Using 25mm thick plank.
3.1.1.4. :- Sides and Soffits of Beams, beam haunchings, cantilever girders, bressumers, lintels and horizontal ties. (a) For depth not exceeding 1.0M. (ii) Using 25mm thick plank.
Providing soling in foundation and under floor with stone/ best quality picked jhama brick, sand packed and laid to level and in panel after preparing the subgrade as directed including all labour and materials and if necessary dewatering, complete. (a).Brick on flat soling.
Brick work in cement morter with 1st class brick including racking out joints and curing complete as directed. (I) In Sub-structure upto plinth level including dewatering if necessary (b) In proportion 1:4.
1st class brick nogged wall in cement mortar including racking out joints and curing complete as directed in super structure above plinth up to 1st floor level (protruding M.S rod/Tor steel of column to be embeded in cement mortar and will be measured (A) 112mm thick brick wall. (a) In cement mortar in proportion 1:4.
Cement plaster skirting with cement mortar in prop. 1:3 (1 cement : 3 coarse sand) finished with a floating coat of neat cement including rounding of junctions with floor. (b) 20 mm thick.
15 mm thick Cement plaster in single coat on single or half brick wall for interior plastering up to 1st floor level including arises, internal rounded angles, not exceeding 80mm girth and finished even and smooth including curing complete as directed. (A) On rough side (b) In cement mortar 1:4.
15 mm thick Cement plaster in single coat on single or half brick wall for interior plastering up to 1st floor level including arises, internal rounded angles, not exceeding 80mm girth and finished even and smooth including curing complete as directed. B) On fair side b) In cement mortar 1:4
Providing Pre Painted Galvanized Iron Sheet Roofing (PPGI) at all levels including fitting and fixing with self drilling, self tapping screws complete. (Roof trusses, purlins etc. to be measured and paid separately.) TATA Blue scope/ Dyna roof / Durako (iii) 0.50 mm thick
Providing and fixing flush door shutters solid core construction with frame of 1st class hard wood with cross band and face veneered ply wood face panels conforming to relevent I.S code including oxidised iron butt hinges (100mm x 75mm x 3.5mm) 6 nos with b) Non decorative type and block board core. (ii) 35 mm thick .
Providing, fitting and fixing M.S. grill of required pattern for windows/ clerestory windows/ openingwith M.S. flats at required spacing in frame all round, squre or round M.S. bars with round headed bolts and nuts or screws. I . Plain grill. (c) Fixed to Brickwork/P.C.C/R.C.C.
m) Distempering two coats with oil bound distemper of approved brand and manufacture and of required shade on new wall surface to give an even shade, over and including a priming coat with distemper primer of approved brand and manufacture after through (i).Priming coat with distemper primer.
m) Distempering two coats with oil bound distemper of approved brand and manufacture and of required shade on new wall surface to give an even shade, over and including a priming coat with distemper primer of approved brand and manufacture after through (ii). Top coat.
a) Applying one coat of cement primer of approved brand and manufacture on new wall surface after throughly brooming the surfaces free from mortar droppings and other foreign matter and including preparing the surface even and sand papered smooth.
Applying priming coat over new wood and wood based surfaces over 100mm in girth/width after and including preparing the surface by throughly cleaning oil, grease, dirt snd other foreign matter , sand papering and knotting. (b). With ready mixed paint , wood primer (white).
Painting two coats (excluding priming coat) on new wood and wood based surface with enamel paint of approved brand and manufacture (Asian paint/ Berger paint/ ICI paint/ J & N paint/ Nerolac) to give an even shade including cleaning the surfaces (i).Surfaces over 100mm in width or girth. (a). General purpose (Asian paint/ Berger paint/ ICI paint/ J & N paint/ Nerolac).
Applying primary coat over new steel and other metal surface over 100m in width or girth after preparing the surface by throughly cleaning oil,grease, dirt and other foreign matter and scoured with wire brushes, fine steels, wood scrapers and sand paper. a). With ready mixed "red-lead/ red oxide" primer.
Painting two coats (excluding priming coat) on new steel and other metal surface with enamel paint of approved brand and manufacture(Asian paint/ Berger paint/ ICI paint/ J & N paint/ Nerolac) to give an even shade including cleaning the surface (i).Surfaces over 100mm in width or girth. (a). General purpose (Asian paint/ Berger paint/ ICI paint/ J & N paint/ Nerolac).
Finishing old / new wall with water proofing weather coat smooth anti-fungal exterior painting of approved make of Berger paint of required shade after cleaning and clearing the surface etc. including scaffolding complete as directed at all levels
Supplying, fitting and fixing in position reinforcement bars conforming to relevant I.S. Code for R.C.C. work/ R.B. walling including straightening, cleaning, cutting and bending to proper shapes and length as per details, supplying and binding with 20G a (a) From Primary Producer: TATA/SAIL/Esser Steel/ Jindal steel/Shyam steel/RINL (ii)Super Ductile (SD) TMT reinforcement bars.
(c) ISI approved Mild steel reinforcement bar(M.S.Bar)
Providing fitting, hoisting and fixing of roof trusses including purlins fabricated using MS circular hollow section conforming to relevant I.S. code, as per approved design and drawings including providing M.S. cleats, base plates, bolts and nuts and one (b) Using other ISI marked approved circular hollow section
Supplying, fitting, fixing anodised aluminium fittings of approved make, resonably smooth, free from sharp edges and corners, flaws and other defects and with counter sunk holes for screws including necessary aluminium screws etc. complete. (a) Sliding door bolts (i) 300mm x 16mm.
b) Tower bolts iii) 200mm x 12mm.
c) Door handles iii) 150mm.
Demolishing the plastering from walls/ R.C.C. and P.C.C. members without causing any damage to the wall/ member upto any height including disposal of debris as directed for all levels.
Demolishing CC floors of various thickness including top layer and base course and disposal of debris as directed for all levels.
Providing VITRIFIED floor tiles of approved quality of specified size, shape and thickness not less than 18mm on floors, skirtings, risers and treads of steps over 15 mm thick base of cement mortar in prop. 1:3 (1 cement : 3 coarse sand ) including a) Normal range Somany/ Orient/Nitco /Varmora/VITA/ Marbito/ Make ii) Of size 600mmx600mm and above.
Providing polished ceramic wall tiles of approved quality, size, shape and thickness not less than 8mm on walls and skirtings over cement mortar bed 10 mm thick in prop. 1:3 (1 cement : 3 coarse sand ) including cutting where necessary finished b) Executive range Somany/ Orient/Nitco/Asian Make (ii) Of size 250mmx350mm and above
Labour for boring hole for inserting tube well pipes through different soil/ rock media including hire charges of drill pipes, scaffolding, tools and plants as necessary and taking out the same and lowering pipes, fittings complete as directed by the Depa (vi) Bore hole of 200mm diameter
Supplying, fitting and fixing pipes plain/bevel ended for casing, conforming to relevant IS codes of practice including supplying and fitting of tube well accessories, lowering of assembly pipes concentrically in the borehole followed by supplying (II) PVC PIPE. vii) 160mm diameter.
Supplying, fitting and fixing suction pipes plain/bevel ended, conforming to relevant IS codes of practice including supplying and fitting of accessories, lowering of assembly pipes concentrically in the casing pipes complete as directed. A) G.I. pipe. a) TATA / SAIL (Medium)socket should be welded to the pipes. (iv) 50mm diameter.
Supplying fitting and fixing ISI approved PVC filter 3.00 metre long. (v) 150mm diameter.
Supplying fitting and fixing check valve (non return valve) including thread to pipes. iv) 50mm diameter
Development of the tube well with compressor or by over pumping unit for 48 hours till sand free discharge is obtained
Flushing, clearing, washing and watering of the tube well
Electrical Wiring for light/fan/call bell point with 2x1.5 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface/ recessed conduit wiring system with 20mm dia 2mm thick / heavy rigid PVC IS: 9537 Part - III conduit (Berlia/ AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) including 6 Amp flush type switch/ bell push (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) GI/ MS switch board (ISI marked) with phenolic laminated sheet cover ,ceiling rose (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) etc. complete Short point up to 3.00 metre. length.
Medium point up to 6.00 metre. Length.
Long point up to 10.00 metre. Length.
Wiring to 5 a pin 6 Amps plug point with 1.5 sq. mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) with flat 19 mm ISI marked casing 'n' capping (AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) in surface system, including 5 pin 6 Amps flush type plug socket and 6 Amps F/T switch (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.), GI/ MS switch board (I.S.I. marked) with phenolic laminated sheet cover including earth continuity with 1.5 sq. mm. cable to third pin of the plug socket etc. as required complete, when placed elsewhere. Long point up to 10.00 metre. Length.
Wiring for 5/6 pin 16 Amps power plug point with 4 sq. mm. P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for Deptt.) in surface system, including providing and fixing 5/6 pin 16 Amps flush type socket outlets and 16 Amps flush type switch ( Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.),GI/ MS switch board (I.S.I. marked) with phenolic laminated sheet cover earth continuity with 2.5 sq. mm cable to the 3rd pin of the socket as required complete. Short point up to 3.00 metre. length.
Medium point up to 6.00 metre. Length.
Long point up to 10.00 metre. Length.
Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable FR conforming to IS-694: 1990 with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface flat ISI marked casing 'n' capping (AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) system including earth continuity. With 2 x 2.5 sq. mm. + earth continuity with 1x1.5 sq. mm. in flat 19 mm ISI marked casing 'n' capping system.
With 2 x 4 sq. mm. + earth continuity with 1x2.5 sq. mm. cable in flat 19 mm ISI marked casing 'n' capping system.
With 2 x 6 sq. mm. + earth continuity with 1x 4 sq. mm. cable in flat 25mm ISI marked casing 'n' capping system.
Wiring for drawing sub-main line with P.V.C. insulated single core unsheathed industrial (Multistrand) cable with flexible bright annealed electrolytic copper conductor for voltage grade up to 1100 volts (Finolex /RR Kabel /Nicco / Anchor or Equivalent Make as approved by the Deptt.) in surface with flat ISI marked casing 'n' capping (AKG / Precision/ Presto Plast/Polycab/ MW or equivalent make as approved by the Deptt.) system including earth continuity. With 3 x 6 sq. mm. + earth continuity with2x 4 sq. mm. cable in flat 25 mm ISI marked casing 'n' capping system.
With 3 x 10 sq. mm. + earth continuity with2x 6 sq. mm. cable in flat 25 mm ISI marked casing 'n' capping system.
Supplying with fitting and fixing single Pole 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 6 to 32A
Supplying with fitting and fixing DP 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series (ABB, Schneider MG, legrand, Hager make) 40A
Supplying with fitting and fixing sheet steel, phosphatised, powder painted dust & vermin proof Double door IP-43 double door surface mounting TPN MCB DB incorporated with bas-bar, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider MG, legrand, Hager make) 4 way TPN (4+12) double door
6 way TPN (4+18) double door
Supplying with fitting and fixing TPN 10 KA 240/415V 50Hz MCB of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. C Series (ABB, Schneider MG, legrand, Hager make) 63A
Supplying with fitting and fixing of Angle iron framing made 50 mmx50 mmx5 mm size angle iron for accommodation of 1.00 Ton to 2.00 Ton Window/split type A.C. Machine
Supplying fitting fixing and connection as approved by the Deptt.)1/2 inch & 3/4 inch copper piping with insulation along with connection as approved by the Deptt.)cable including testing and commissioning as directed by the department.
Supplying with fitting and fixing Voltage stabilizer of the following specification complete including making necessary connection as approved, specified and directed by the deptt. (SKYLAND / Vee-Dee / V GUARD / VERTEX/ INDO/ VENUS make) 5.0 KVA Automatic Input 90-280 V Out put 200-240 V
Supplying with fitting and fixing Single Phase D.O.L Starter of the following specification complete including making necessary connection as approved, specified and directed by the deptt. Overload Relay Range 6.0 -9.3 Amps for 3.7 KW
Supplying fitting and fixing industrial Plug & Socket in surface mounting SPN sheet steel powder painted MCB DB incorporated with MCB DIN rail, neutral link Earth bar of the following rating of DP MCB complete with making necessary connection etc. as specified and directed by the Deptt. 20A Capacity. (ABB, Schneider MG, legrand, Hager make)
Supplying with fitting and fixing panel mounting open execution 35/36KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 125 A
Installation of Exhaust fan up to 450 mm sweep in the existing opening including making the hole to suit the size of the above fan, making good the damages, testing, commissioning etc. as required complete
Supplying including fitting fixing of following A.C. Exhaust fan in the existing hole on the wall of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department.Domestic High Speed 225 mm sweep (ORIENT make), Trans Air 225 mm sweep (Crompton make), Ventil Air DX 250 mm sweep Louver type (Havells make)
Supplying including fitting fixing of following A.C. Ceiling fan complete with all accessories like down rod, canopy etc. of following sweeps with making necessary connection as approved by the Deptt.)as required complete and as directed by the Department [Without regulator]. Premium model 1400 mm Sweep ceiling fan (ORIENT PSPO make) /Premium model 1200 mm Sweep SS-390 Deco. Havells make)
Supplying fitting and fixing of ceiling fan regulator including connections etc. complete as required. Electronic Type type
Supplying and fitting of 18/20 Watt CFL lamp in the existing batten holder/angle holder/decorative bracket/bulk head fitting/ pendent holder etc. as specified and directed by the deptt.
Wiring for 5 pin 6 amp plug with 1.5 sq mm P.V.C. insulated single core unsheathed industrial (Multistrand) cable and 6 amp flush type switch (Anchor penta /Gold medal /Kolor kany.Kom/Havells or equivalent make as approved by the Deptt.) earthing the 3rd pin of the socket as required on the switch board in flat ISI marked casing 'n' capping system, when fitted on same board of light and fan.
Supplying and fixing of batten holder (Anchor Penta PC CHERRY /Gold medal /Kolor kany.kom/Havells or equivalent make as approved by the Deptt.) including connection as approved by the Deptt.)as required Without Lamp
Supplying and fitting fixing of electric storage water heater [Geyser] including necessary connection etc. as required complete and as directed by the Department. 10 Litre Capacity
Supplying including installation, commissioning of vermin and dust proof totally enclosed, Phosphatised Powder Painted cubical indoor type floor/wall mounting compartmentalize panel board of size 1.35M X 1.20MX 0.40M made of 16 SWG/1.66 mm thick C.R. sheet and 35mm X 35mm X 5mm size angle having 4 no legs at the bottom. The panel board is to be erected in 1 : 3 : 6 PCC foundation including brick soling / grouting etc. complete neatly Wiring done with provision for one no 250 A 4pole MCCB or Switch Fuse Unit as incomer and provision for 6nos DP or TPN out going as specified and directed by the deptt. confirming to IP 43 protection comprising of the following electrical items: 1. 50mm X 10mm 4 strip copper Bus - Bar 1.20 M length each i 25mm X 5mm 4 strip copper Bus-Bar 0.5M each 4 sets 2. Digital 3 Phase Voltmeter Accuracy class 0.5 - 1 no 3. Digital 3 Phase Ammeter Accuracy class 0.5 - 1 no 4. Pilot Lamp with integral ckt LED 110- 230 V (Red, Yellow etc.) (Incoming & Outgoing Switch Gear of reqd. rating will be measured and paid separately)
Supplying with fitting and fixing panel mounting open execution 35/36KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 35/36 KA 415V 50 Hz 4P MCCB (C&S, Indo Asian V-Guard or equivalent make as approved by the Deptt.) 160A
Supplying with fitting and fixing Four Pole 415V Front handle operated open execution On Load Change over switch fitted on the existing cubical panel of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. ABB, Schneider, legrand, L&T make) 100A
Supplying including installation, testing and commissioning of Air/Water Cooled Diesel Generator set coupled to suitable alternator of 220/415 V, AC, 1/3-Phase 0.8 p.f. mounted on a 1) M.S. Fabricated base frame.,2) M.S. fuel tank of required capacity.,3) Residual Silencer.,4) Standard Control Panel.5) Suitable batteries with lead.,5) First fill of lube oil.,6) Acoustic Enclosure complete with all accessories as specified and directed by the department conforming to IS comprising the Technical Specification.. as per manufacturer. (RANGE FROM 5 KVA TO 625 KVA) Kirloskar green/bliss, Leyland, Volvo Penta, Perkinson, Mahindra, Greaves, Escort engine and Kirloskar, Stamford, Leroy somer or equivelent alternator. 41.1.2.29 .2 62.5 3 3980x1240x1680 1920 Kg A/C
Supply and laying of following size PVC/XLPE insulated and PVC sheathed 1.1 KV Grade Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Armour balance all galvanised steel strip) armoured U.G. cable U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt. (Nicco/ Havells/ RPG/CCI/Polycab/Gloster/ Finolex make) 3 & 1/2 Core A2XFY. 35.00 Sq. mm.3 & 1/2 Core armoured U.G. cable
50.00 Sq. mm.3 & 1/2 Core armoured U.G. cable
70.00 Sq. mm.3 & 1/2 Core armoured U.G. cable
Supply and laying of following numbers and size of armoured cable in same trench, PVC/XLPE insulated and PVC sheathed 1.1 KV Grade Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, unarmoured/ armoured U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt. (Nicco/ Havells/ RPG/CCI/Polycab/Gloster/ Finolex make) . 4x240.00 Sq. mm. 1 Core armoured U.G. cable
4x400.00 Sq. mm. 1 Core armoured U.G. cable
Supply and laying of following size Power/Control Copper cables, Solid Copper conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Unarmoured/Armour (Galvanised for cables up to 10 x 1.5 sq mm.8 x 2.5 sq mm.2 x 10 sq mm.3 x 10 sq mm.4 x 6 sq mm balance all galvanised steel strip) , extruded PVC Type ST2 Sheathed, 650/1100 V grade as per IS 7098 (Part 1) 1988, U.G. cable laid in ground/partially in air (as required for termination over ground including excavation of cable trench up to depth of 75cm, refilling, protective brick covering, Sand cushioning etc complete handling of surplus spoil, debris et to proper place as specified and directed by the deptt. (Nicco/ Havells/ RPG/CCI/Polycab/Gloster/ Finolex make) . 16.00 Sq. mm.4 Core U.G. armoured cable
Supply and laying of following size Solid Aluminium conductor up to 10 sq mm balance stranded conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, LT armoured U.G. cable laid in pucca flooring, road crossing, drain crossing as per site requirement and partially in air to connection as approved by the Depts. the control switch, through medium duty G.I. pipe (Tata/ Nezone make or equivalent as approved by the Deptt) bend and socket including excavation and refilling the trench and making good damage done as specified and directed by the deptt. (Nicco/ Havells/ RPG/CCI/Polycab/Gloster/ Finolex make) 50.00 Sq.mm 3&1/2 Core U.G. cable in 50mm dia medium duty hot dip galvanised pipe (AKG or equivalent as approved by the Deptt.)
70.00 Sq.mm 3&1/2 Core U.G. cable in 50mm dia medium duty G.I. pipe
Supplying with fitting and fixing panel mounting open execution 25KA 415V 50Hz 4P MCCB (Ics=Icu, adjustable Ir setting 0.7) without enclosure) of the following capacity complete with making necessary connection as approved, specified and directed by the deptt. 25 KA 415V 50 Hz 4P MCCB (Schneider, legrand, Siemens, Indo Asian make) 100A
Supplying with fitting and fixing sheet steel, phosphatised, powder painted Single door surface mounting MCB enclosure incorporated with bas-bar, Neutral link, Earth bar and din rail etc fitted on wall with grouting nuts & bolts as reqd. complete with making necessary connection as approved, specified and directed by the deptt. Schneider neo break, C&S, Havells, INDOASIAN, HPL or equivalent as approved by the Deptt.)make) 2 way single door
4 way single door
Supplying and fixing of Jaquar or equivalent Philips/ Wipro LED down lighter fittings complete with Shade, back plate including connection cable, as approved by the Deptt.s etc. as required. Down light 5W
Supplying with fitting and fixing Surge protector of max operating voltage 350V at 400V network for maximum discharge current 40KA, with operator indicator and draw out cartridge of Schneider or equivalent make), of the following ways complete with making necessary connection as approved, specified and directed by the deptt. Surge protection Max operating voltage 340V Standard type 3P + N
10 KVA On-Line UPS System (Orion or equivalent make as approved by the Deptt.) with PWM-IGBT technology 230V AC Input (160V – 280V A 1 Ph input- 1 Ph output With Isolation Transformer 8KW output with 0.8 output PF 60 min backup using SMF battery
15 KVA On-Line UPS System (Orion or equivalent make as approved by the Deptt.) with PWM-IGBT technology 360V AC Input (300V – 470V A 3 Ph input- 1 Ph output With Isolation Transformer 12KW output with 0.8 output PF 60 min backup using SMF battery
30 KVA On-Line UPS System (Orion or equivalent make as approved by the Deptt.) with PWM-IGBT technology 360V AC Input (300V – 470V A 3 Ph input- 1 Ph output With Isolation Transformer 24KW output with 0.8 output PF 60 min backup using SMF battery
Supplying including fitting and fixing bus bar chamber ( HPL/ GECO / or equivalent make) with 4 strips bus bar of length 350/450/600/900 mm made of aluminium alloy or wrought aluminium suitable for 100 amp capacity complete with all accessories including connection etc. as required complete
Supplying including fitting and fixing bus bar chamber ( HPL/ GECO / or equivalent make) with 4 strips bus bar of length 450/600/900/1000 mm aluminium suitable for 200 amp capacity complete with all accessories including connection etc. as required complete
Supply, installation & testing of Copper Plate earth station with 600 mmx600 mmx6 mm heavy duty copper earth plate with necessary 40 mm dia. G.I. medium duty watering pipe with G.I. Fittings such as Socket, Tee, elbow, nipple and 50 mmx40 mm G.I. reducing socket for funnel including locking arrangement with 300 mmx300 mmx6 mm C.I. hinged cover plate complete with digging of earth pit, construction of brick chamber and plastering of both inner & outer surface of wall as specified and directed by the deptt .
Extra for using salt (5 K and Charcoal (96 K in G.I./Copper plate Earth Station pit to provide low impedance ground in location of high soil resistivity as and when required and specified by the deptt .
Supply, installation & testing of G.I. earth station with perforated 40 mm dia and 4.50 Metre long heady duty G.I. pipe with necessary 40 mm dia. G.I. Fittings complete with digging of earth pit, construction of brick chamber and plastering of both inner & outer surface of wall as specified and directed by the deptt .
Extra for using salt (5 K and Charcoal (64 K in pipe Earth Station pit to provide low impedance ground in location of high soil resistivity as and when required and specified by the Deptt.
Supplying & laying of 30x5 mm size Copper strips drawn on surface from earth electrode to Electrical switch gears, machineries etc complete with supply of Brass nuts & bolts, screws etc including riveting, soldering & making necessary connection as approved, specified and directed by the deptt.
Supplying & laying of 8 SWG G.I. earth from Earth Electrode (below G.L.) to electrical switch gears or electrical machineries including making necessary connection as approved, specified and directed by the deptt.
Supplying & laying of 8 SWG Copper. earth from Earth Electrode (below G.L.) to electrical switch gears or electrical machineries including making necessary connection as approved, specified and directed by the deptt.
Supplying with installation testing and commissioning of Hi -- wall 3 STAR rating non ducted split type air conditioner of the following capacity with cordless remote complete with indoor and outdoor unit, copper pipe and electrical connection as approved by the Deptt.)up to 5 m between the room unit and out door unit as directed by the department. (b) 2.0 Ton(3 star Inverter split with R-32/R410 gas)Voltas/Dalkin make(CE Approved Rate)
Installation of Medical Gas Pipe line :- medical Oxygen System Main Oxygen Manifold 2x8 Cylinders with NRVs, Tail Pipes & Middle Frame.
Oxygen Control Station with authoritic Changeover from Duty Bank to Reserve
Emergency Oxygen Manifold 4 Cylinders with NRVs Copper Pig Tail Pipes, Middle Frame andpressure reducing unit with Non Halogenated Polymer Diaphragms in HP Regulator.
Medical Vacuum System Vacuum System with Twin Vaccum Pumps Ingersold Rand Make Model V-255 or equivalent each having 60 cfm PD with 5 HP Motor, Rilencer, Filter, Interconnecting Pipes, NRV, Auto Switch Gear Assy.
Air Receiver Tank for Vacuum System 500 Ltr. Capacity.
Medical Air System Compressed Air System Comprising of 2 (Two) Set Duplex 36.66 CFM (actual) Capacity Non-Fabricated Reciprocating, Air Cooled Type Base Mounted Air Compressors, having 10 HP Motor and Non-Return Valve, Isolation Valves, make :- Anest Iwata / Ingersoll-Rand or Equivalent.
Air Receiver Tank for Compresed Air System Capacity 1000 Ltr.
Two stage Bacterial Filter Assembly make Dominic Hunter.
Air dryer capacity 45 cfm.
Pressure Reducing System with 2(two) Nos. Pressure Regulators.
Copper pipes Copper Pipe 12mm OD x 0.7 mm thickness.
Copper Pipe 15mm OD x 0.9mm thickness.
Copper pipe 22mm OD x 0.90mm thickness.
Zonal / Isolation Valves Brass Fittings 15 mm
Gas Outlets, Front Insertion Type, Double Lock with Probe Oxygen.
Medical Air (4 Bar)
Vacuum
Accessories Oxygen Flowmenter with Humidifier.
Ward vacum unit with 600 MI. Collection jar (Complete with Vacum Regulator).
Area Alarm, Indigenous Area Alarm $ Gas Service.
Area Alarm 3 Gas ervice.
Any other unseen item of work which are not covered in this BOQ that may be required at site during execution having an estimated provision of Rs.66,76,060.00 (Including GST). The rate for the items will be finaliased as per current APWD SOR/ Market Rate Analysis etc. in proportion to the quoted amount and the estimated amount. Note:- The amount against this item has been kept as a provission for any unforseen/ additional items of works which may arraise during the execution of the work. A Lump sum rate is to be quoted against these items which shall not be less than 10% below. Bids not complying to this shall summarily be rejected.
MD. ALIMUDDIN AHMED
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .