Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance KUNZER KUNZER TANGMARG BARAMULLA JAMMU KASHMIR 193401 | BUDGAM | JAMMU AND KASHMIR | 193401 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹74.3 L
EMD Value
₹1.5 L
Closing Date
17 May 2025, 2:30 pmClosed
Executive Engineer, STD-II, Rajbagh,Srinagar
Office of the Executive Engineer, STD-II, Rajbagh,
Providing dedicated power supply to CHC Kremshore and Chattargam, PHC Soibugh,Ompora and Khag in District Budgam under District Mineral Fund PMKKY 2024-25
2025_PDD_276289_1
eNIT No STD-II / 07 of 2025-26 Dated 22-04-2025
Open Tender
Electrical Works
Turn-key
BUDGAM
Please refer Tender documents.
3 documents required · 3 mandatory
₹2,000
Executive Engineer, STD-II, Rajbagh,Srinagar
₹1.5 L
29 May 2025
26 Apr 2025
19 May 2025
26 Apr 2025
17 May 2025
26 Apr 2025
Amount
Part A: SITC OF 11KV Dedicated Feeder for CHC Kremshore from receiving station Kremshore
Supply,Installation, Testing and commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
Supply,installation,testing and commissioning of Gapless Surge Arrestor,9 kV ,10 kA with Polymer housing, Stn. Type as per the specification
Proviidng,Laying,stringing ,tensioning and binding of 100 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any)
Supply,installation,testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Supply,installation,testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing and fixing of Galvanised iron of sorts including Pole Clamps as per site requirement
Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements
Supply, Laying,Testing, and commissioning of 185 mm² XLPE 11KV Cable 3-Core through HDPE pipe as per IS3961(Part 7): 2017. Rate is inclusive of HDPE pipe and laying also.
Providing and fixing of 11kV Indoor Heat Shrinkable Cable Termination Kit suitable for 3-core 185sqmm 11kV XLPE Cable
Providing and fixing of 11kV Outdoor Heat Shrinkable Cable Termination Kit suitable for 3-core 185sqmm 11kV XLPE Cable
Supply, installation, testing and commissioning of 11 kV Isolator, Double Break,3-pole, 630Amp, horizontal mounting Type, with Earth Switch.
Supply and Erection of 9 Mtr. Long Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Providing and laying of Cement bottoming 1:2:4 mix as per REC standards .48cum/pole
Providing and fixing of Danger Plates with clamps of standard make
Providing and fixing of Anti Climbing Devices with clamps of standard make
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing and painting of Red Oxide to give even shade of reputed brand
Providing and painting of Aluminium Paint to give even shade of reputed brand
Providing Retro-reflective regulatory sign board of size 0.9m x 0.9m made out of 1.5mm thick MS sheet, face to be fully covered with high intensity encapsulated lens type retro-reflective sheeting as approved by Engineer-in-charge. Letter, symbols, borders, etc. will be as per IRC:67 with required colour scheme on the boards and with the high intensity grade A. the MS sheet to be riveted to M.S. frame of angle iron of size 40x40x4mm. The boards will be fixed to 2 No. 50x50x3mm square post made of M.S. square hollow tube, 4m long welded to the frame with adequate anti-theft arrangement. Sheet work to be painted with two or more coats of synthetic enamel paint over an under coat (primer) and back side of MS sheet to be painted with two or more coats of epoxy paint including appropriate priming coat complete in all respects as per directions of Engineer-in-charge.
Part B: Power supply to the CHC Chattergam by creation of 400KVA 33/0.433kv distribution Sub-station on 33kv Khanda tapline
Supply,Installation, Testing and commissioning of 400KVA ,33/0.433 kV, 3-phase Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Copper wound) with Automatic OLTC on 33 kV side (min 35% and max 5% ) with a provision of 3 Phase back up supply and with LV Box having detachable Alumunium Gland Plate.
Supply and Erection of 11Mtr long pole(ST 410-SP56) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Supply,installation,testing and commissioning of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with fitting
Supply,installation,testing and commissioning of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm WITH FITTINGS
Providing and fixing of GI V cross-arm/ Channel X-arm/ braces/top Brackets including clamps
Providing Retro-reflective regulatory sign board of size 0.9m x 2m made out of 1.5mm thick MS sheet, face to be fully covered with high intensity encapsulated lens type retro-reflective sheeting as approved by Engineer-in-charge. Letter, symbols, borders, etc. will be as per IRC:67 with required colour scheme on the boards and with the high intensity grade A. the MS sheet to be riveted to M.S. frame of angle iron of size 40x40x4mm. The boards will be fixed to 2 No. 50x50x3mm square post made of M.S. square hollow tube, 4m long welded to the frame with adequate anti-theft arrangement. Sheet work to be painted with two or more coats of synthetic enamel paint over an under coat (primer) and back side of MS sheet to be painted with two or more coats of epoxy paint including appropriate priming coat complete in all respects as per directions of Engineer-in-charge.
Proviidng,Laying,stringing ,tensioning and binding of 0.1ACSR conductor
Supply and Erection of 9 Mtr. Long Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Providing and fixing of G.I Pipe with dia 150mm,5.9mm thick 3 m long (27 No.s) with G.I Base Plate 8mm Thick
Supply,installation,testing and commissioning of 33 kV, Lightening Arrestor,(33 kV ,10 kA ,Station class,ZnO, Polymer) gapless
Supply,Installation, Testing and commissioning of 33 kV Isolator, with Earthing Blade (36kV,800 A, Outdoor ,3 poles,25 kA).
Supply,installation,testing and commissioning of 33 kV Horn Gap Fuse set
Providing and fixing of Galvanised iron of sorts as per requirement
Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements
Supply,Laying,Testing, and commissioning of 630 mm² XLPE LT Cable 1 Core, armoured, FRLS
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.48 cum / pole
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.6cum / pole
Providing of Earthing of 400kVA SubStation--Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing of Earthing Complete by GI Pipe 40 mm 3mtr long through GI Strip.25x3mm
Supply,installation, Testing, and commissioning of LT Distribution Box measurng not less than 1200mm(H) X 1500mm(W) X 450mm (D) made out of 2.0mm CRCA sheet thickness including cleaning and finishing complte with powder coaing in approved shade having aluminium bus bar of rating 1000A(50mm x 12mm double layer or equivalent), high conductivity connections, with nuts and bolts, clamps,Aluminium lugs, DMC busbar supports etc having 3 phase ,415V, 2 No. of 630 Amp incoming MCCB 4P 36kA fitted with outgoing 4 No. 200 Amps MCCBs 3P, 25KA for out going circuits, complete in all respects as per standards. all MCCB's shall have busbar for suitable cable termination standard make. this also included GI stand of suitable size alongwith cement groting
Supply and underground Laying,Testing, and commissioning of 185 mm² XLPE LT Cable Single Core through HDPE pipe (outer dia 50mm, inner dia 38mm) by way of trench excavation in hard soil(WxD= 0.3m x 1m). The job further includes refilling back the soil and removal of surplus excavated material. Rate is inclusive of HDPE pipe and laying also.
Providing and fixing of warning tape
Providing and fixing of Wedge Connectors / PG Clamps
Providing and fixing of Danger Plates with clamps of standard make
Providing and fixing of Barbared wire as Anti Climbing Devices with clamps of standard make
Providing and painting of Red Oxide to give even shade of reputed brand
Providing and painting of Aluminium Paint to give even shade of reputed brand
33 kV HT METERING CT AND PT OPERATED.
1. Supply, Installation, Testing & Commissioning of A) 33kV CT/PT Combined Unit, 3-phase, 50 Hz, ONAN cooled, outdoor type. The combined unit, CTs and PTs shall be as per below specifications. The CT ratio shall be 20/5 for 400 KVA, 33/0.433kV Transformers. The PT shall be 33 kV/110 volts / √3, Three phase PT with rated burden 20VA per phase with proper colour coded identification. PTs shall be of uniform insulating and One minute power frequency dry withstand voltage 70kV B) 3Ph4 Wire HT CT/PT operated Fully static Smart Tri-Vector Energymeters DLMS Compliant Category 'C' with RS232 port . 33kV/√3 /110V/√3, Ph-N (3P, 4W) meters for measurement of different electrical parameters including Active Energy (kWh/ MWh), Reactive Energy (kVArh/MVArh), Apparent Energy (kVAh/ MVAh) etc. 2. Providing & fixing of : A) Metering cubicle for 3phase 4 wire metering system suitable for 3 phase, HT, tri-vector meter with sealing and locking facility made of MS Sheet steel thickness not less than 2mm duly power coat painted suitable for indoor as well as outdoor as per the site requirement. The cubicle shall be painted through 7-tank process. The External dimensions should be adequate. Provided with synthetic or semi synthetic gasket firmly glued to the sufrace, Dust, weather and Vermin proof and shall comply degree of protection IP 65 both the chambers having one sided hinged door arrangments. The panel shall be provided with two No MS channels of size 100 x 50 mm on the front and rear sides duly welded and 4 No of lifting hooks. It should be possible to take meter reading manually, through CMRI and computer without opening door including supply and fixing of 75mm GI pipe between CT/PT combined unit and metering cubicle for CT/PT wiring to tri-vector meter. B) GI Channels for mounting CT PT Combined Units with nuts and bolts of size (100 x 50 x 5 mm) C) PVC Copper wire flexible multi-strand of required size for secondary connections for CT wiring the minimum wire size shall be 4 mm2 (RYB) and for PT wiring minimum wire size shall be 2.5 mm2 (RYB). D) Copper Lugs preferably ring type duly crimped for termination of wires and tapes COMPLETE JOB AS PER REC STANDARD
Providing and fixing of ACSR Jumpers with hardware fittings like ACSR to CT/PT unit bush clamp, other hardwares as per site requirement
Providing of Earthing by way of 40 mm 2.5 mtr long GI Pipe. Job includes , excavation, enhancement material and Main Hole Chamber (500x450x600)mm with frame and cover.
Part C: SITC OF 11KV Dedicated Feeder for PHC Soibugh from receiving station Soibugh
Supply,installation,testing and commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
Supply,installation,testing and commissioning of Gapless Surge Arrestor,9 kV ,10 kA with Polymer housing, Stn. Type as per the specification
Proviidng,Laying,stringing ,tensioning and binding of 100 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any)
Supply,installation,testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Supply,installation,testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fittings
Providing and fixing of Galvanised iron of sorts as per requirement
Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements
Supply, Laying,Testing, and commissioning of 185 mm² XLPE 11KV Cable 3-Core through HDPE pipe as per IS3961(Part 7): 2017. Rate is inclusive of HDPE pipe and laying also.
Providing and fixing of 11kV Indoor Heat Shrinkable Cable Termination Kits
Providing and fixing of 11kV Outdoor Heat Shrinkable Cable Termination Kits
Supply,Installation, Testing and commissioning of 11 kV Isolator with Earth Switch ,with three posts per phase, double break,3-pole, 630 Amps, gang operated out-door type, silver plated contacts with horizontal operating blade and isolator posts arranged vertically. Rotating blade feature with pressure relieving contacts is necessary
Supply and Erection of 9 Mtr. Long Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.48 cum / pole
Providing and fixing of Danger Plates with clamps of standard make
Providing and fixing of Anti Climbing Devices with clamps of standard make
Providing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing and painting of Red Oxide to give even shade of reputed brand
Providing and painting of Aluminium Paint to give even shade of reputed brand
Providing Retro-reflective regulatory sign board of size 0.9m x 0.9m made out of 1.5mm thick MS sheet, face to be fully covered with high intensity encapsulated lens type retro-reflective sheeting as approved by Engineer-in-charge. Letter, symbols, borders, etc. will be as per IRC:67 with required colour scheme on the boards and with the high intensity grade A. the MS sheet to be riveted to M.S. frame of angle iron of size 40x40x4mm. The boards will be fixed to 2 No. 50x50x3mm square post made of M.S. square hollow tube, 4m long welded to the frame with adequate anti-theft arrangement. Sheet work to be painted with two or more coats of synthetic enamel paint over an under coat (primer) and back side of MS sheet to be painted with two or more coats of epoxy paint including appropriate priming coat complete in all respects as per directions of Engineer-in-charge.
Part D: SITC of 11KV Dedicated Feeder for PHC Ompora from receiving station Ompora
Supply,Installation, Testing and commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
Supply,installation,testing and commissioning of Gapless Surge Arrestor,9 kV ,10 kA with Polymer housing, Stn. Type as per the specification
Proviidng,Laying,stringing ,tensioning and binding of 100 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any)
Supply,installation,testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Supply,installation,testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fittings
Providing and fixing of Galvanised iron of sorts as per requirement
Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements
Supply, Laying,Testing, and commissioning of 185 mm² XLPE 11KV Cable 3-Core through HDPE pipe as per IS3961(Part 7): 2017. Rate is inclusive of HDPE pipe and laying also.
Providing and fixing of 11kV Indoor Heat Shrinkable Cable Termination Kits
Providing and fixing of 11kV Outdoor Heat Shrinkable Cable Termination Kits
Supply,Installation, Testing and commissioning of 11 kV Isolator with Earth Switch ,with three posts per phase, double break,3-pole, 630 Amps, gang operated out-door type, silver plated contacts with horizontal operating blade and isolator posts arranged vertically. Rotating blade feature with pressure relieving contacts is necessary
Supply and Erection of 9 Mtr. Long Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.48 cum / pole
Providing and fixing of Danger Plates with clamps of standard make
Providing and fixing of Anti Climbing Devices with clamps of standard make
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing and painting of Red Oxide to give even shade of reputed brand
Providing and painting of Aluminium Paint to give even shade of reputed brand
Providing Retro-reflective regulatory sign board of size 0.9m x 0.9m made out of 1.5mm thick MS sheet, face to be fully covered with high intensity encapsulated lens type retro-reflective sheeting as approved by Engineer-in-charge. Letter, symbols, borders, etc. will be as per IRC:67 with required colour scheme on the boards and with the high intensity grade A. the MS sheet to be riveted to M.S. frame of angle iron of size 40x40x4mm. The boards will be fixed to 2 No. 50x50x3mm square post made of M.S. square hollow tube, 4m long welded to the frame with adequate anti-theft arrangement. Sheet work to be painted with two or more coats of synthetic enamel paint over an under coat (primer) and back side of MS sheet to be painted with two or more coats of epoxy paint including appropriate priming coat complete in all respects as per directions of Engineer-in-charge.
Part E: SITC of 11KV Dedicated Feeder for PHC Khag from receiving station Khag
Supply,installation,testing and commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port
Supply,installation,testing and commissioning of Gapless Surge Arrestor,9 kV ,10 kA with Polymer housing, Stn. Type as per the specification
Providing and fixing of Galvanised iron of sorts including Pole Clamps
Providing and fixing of Gavanized Nuts & Bolts of sorts as per site requirements
Proviidng,Laying,stringing ,tensioning and binding of 100 Sqmm ACSR Conductor as per REC construction standard (with latest amendments if any)
Supply,installation,testing and commissioning of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fitting
Supply,installation,testing and commissioning of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with fittings
Supply, Laying,Testing, and commissioning of 185 mm² XLPE 11KV Cable 3-Core through HDPE pipe as per IS3961(Part 7): 2017. Rate is inclusive of HDPE pipe and laying also.
Providing and fixing of 11kV Indoor Heat Shrinkable Cable Termination Kits
Providing and fixing of 11kV Outdoor Heat Shrinkable Cable Termination Kits
Supply, installation, testing and commissioning of 11 kV Isolator, Double Break,3-pole, 630Amp, horizontal mounting Type, with Earth Switch.
Supply and Erection of 9 Mtr. Long Pole(ST-410 SP33) with base plate and top cap including excavation of pit and back filling by boulders as per REC construction Standard (with latest amendments if any)
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.48 cum / pole
Providing and fixing of Danger Plates with clamps of standard make
Providing and fixing of Anti Climbing Devices with clamps of standard make
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Providing and painting of Red Oxide to give even shade of reputed brand
Providing and painting of Aluminium Paint to give even shade of reputed brand
Providing Retro-reflective regulatory sign board of size 0.9m x 0.9m made out of 1.5mm thick MS sheet, face to be fully covered with high intensity encapsulated lens type retro-reflective sheeting as approved by Engineer-in-charge. Letter, symbols, borders, etc. will be as per IRC:67 with required colour scheme on the boards and with the high intensity grade A. the MS sheet to be riveted to M.S. frame of angle iron of size 40x40x4mm. The boards will be fixed to 2 No. 50x50x3mm square post made of M.S. square hollow tube, 4m long welded to the frame with adequate anti-theft arrangement. Sheet work to be painted with two or more coats of synthetic enamel paint over an under coat (primer) and back side of MS sheet to be painted with two or more coats of epoxy paint including appropriate priming coat complete in all respects as per directions of Engineer-in-charge.
Note: The material utilized/works executed shall be stritctly as per REC Standards with Latest amendments there off.
M/S WATT ELECTRICAL CONTRACTS (BID ID -2368910)
M/S R R ELECTRICAL SERVICES (BID ID -2371644)
Barraq Enterprises (BID ID -2371779)
M/S KHAN ELECTRICAL ENTERPRISES (BID ID -2372031)
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .