Executive Engineer Purba Medinipur Electrical D
Tamluk, Purba Medinipur, PIN-721636
Repair and renovation works for Shifting and Establishment of Blood Centre of Contai SDH, Nandigram HD --- SITC of Fire Alarm System.
2026_WBPWD_5015547_1
WBPWD/EE/PMED/NIQ-74/2026-27
Open Tender
ELECTRICAL WORKS ORG
7 days
Contai
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,540
Office of the Executive Engineer Purba Medinipu
15 Jun 2026
15 Jun 2026
29 Jun 2026
15 Jun 2026
27 Jun 2026
20 Jun 2026
19 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, Testing & Commisioning of Microprocessor based addressable OPC complied fully networkable fire alarm control panel ( VDS / UL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, conplying to IS 2189:2008 or its latest amendments, and with minimum 320 character alpha - numeric liquid crystal display.The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches with help monitor module whenever any alarm is triggered. The Panel should be able to store minimum 4000 log events
in its memory (EPROM). The panel should have extra loop card slot for future expansion. Two Loop Panel. | 1 | No | - | - |
| 2 | Supply, Installation,Testing & Commisioning of Micropresssor
controlled Addressable Multisensor detector ( VDS / UL / LPCB /
FM approved ) with inbuilt optical smoke sensors and heat detector
sensor with inbuilt short circuit fault isolator as per NFPA (Note :
Detectors without built-in fault isolator is also acceptable with one
independent short circuit fault isolator after every four (04) detector is
to be provided without extra cost) the detectors should have built in
response indicator with LED indicator. The detector should have 360
degree optical view with single / multiple LED that blinks on
actuation of detector. Reverse polarity or faulty zone wiring shall not
damage the detectors. Degree of protection as per OEM Standard. | 20 | each | - | - |
| 3 | Supply, Installation, Testing & Commissioning of Addressable Loop
Powered /panel powered Hooter (sound output of minimum 90 db )
cum strobe (strength of light 10 cd) complete with inbuilt short circuit
fault isolator as per NFPA (Note :Hooter without built-in fault isolator
is also acceptable with one independent short circuit fault isolator is
to be provided without extra cost). ( VDS / UL / LPCB / FM approved
) approved. Degree of protection as per OEM Standard. | 2 | each | - | - |
| 4 | Supply, Installation,Testing & Commisioning of Addressable Manual
Call Point ( VDS / UL / LPCB / FM approved ) with in built short
circuit fault isolator as per NFPA (Note : MCP without built-in fault
isolator is also acceptable with one independent short circuit fault
isolator is to be provided without extra cost). Degree of protection as
per OEM Standard. | 2 | each | - | - |
| 5 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) through 19 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision MMS) on the surface of the wall. | 160 | Mtr | - | - |