| 1 | L1₹9.6 LAccepted-AOC H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹13.9 L+₹4.1 L (42.0%)Rejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹15.3 L+₹5.5 L (56.3%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹16.9 L+₹7.2 L (73.4%)Rejected-Finance 225 NAROT COLONY MODEL TOWN PATHANKOT PB 145001 | PATHANKOT | PUNJAB | 145001 | L4 | Rejected-Finance Not Lowest |
Tender Value
Refer Docs
EMD Value
₹44,000
Closing Date
20 Nov 2023, 6:00 pmClosed
GE (SOUTH) PATHANKOT
GE (SOUTH) PATHANKOT
CRTN RPARS TO EM INSTALATION OF LT FEEDER PILLAR BOX LT CABLES MAINT OF DG SETS AND CONNECTED SWITCH GEARS INCL LT OH LINE AT OTM ACCN AT DHANGU CMPLX REPR OF LT PANEL UG CABLES MISC WORK AT DHANGU AND BHADOURIYA COMPX UNDER GE S PATHANKOT
2023_MES_624616_1
GES/PKT/T-28/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) PATHANKOT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (SOUTH) PATHANKOT
₹44,000
Yes
20 Dec 2023
21 Oct 2023
22 Nov 2023
21 Oct 2023
20 Nov 2023
6 Nov 2023
Amount
S&F in repair capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 10 KVAR capacitor.
S&F in repair capacitor duty contactor with 1 No Aux contact 230V AC coil voltage suitable for minimum 25 KVAR capacitor.
S&F in repair Double metalised paper and polypropylene technology(Mixed dielectric) capacitor cylindrical/box type for per KVAR power factor correction of 440 V, 50 HZ rated of capacity 20 to 25 KVAR
M&L in replacement of existing unserviceable contector of current caring range 25 A to 40 Amp (AC-3 duty at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed.
M&L in replacement of existing unserviceable contector of current caring range 9 A to 18 Amp (AC-3 duty at different places in APFC panels including required electrical connections with suitable size of single core pvc copper cable & testing all as directed.
M&L in replacement of existing unserviceable MCB 25-40 Amps TPN 415 volts at different places in LT panels/APFC panels including required electrical connections & testing all as directed .
M&L in replacement of existing unserviceable MCB 32-63 Amps TPN 415 volts at different places in LT paneles/APFC panels including required electrical connections & testing all as directed .
S&F in repair APFC relay with inbuilt PF meter suitable for 5A CTR suitable for 8 Stage.
Maintenance and servicing of DG set consisting of replacement of fuel filter, air filter and lub oil filter including replacement of eninge oil and coolent oil complete all as directed and testing on full connected load for the following capacity of DG Sets and any make as per OEM.Note: Engine oil and coolent oil will be measured and paid seperately.
All as per Srl item No.9 above but for capacity 500 KVA
All as per item No. 9 above but for capacity 320 KVA capecity
All as per item No. 9 above but for capacity 200 KVA
All as per item No. 9 above but for capacity 100 to125 KVA
All as per item No. 9 above but for capacity 50 to 62.5 KVA
Dismentling of self starter and supply and fix new self starter 12 V of capacity of suitable for 50 KVA to 125 KVA DG Set complete all as specified and directed.
Dismentling of self starter and supply and fix new self starter 12 V of capacity of suitable for 160 KVA to 320 KVA DG Set complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/alternator 12 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy suitable for 50 KVA to 125 KVA DG Set complete all as specified and directed.
M&L for repair and overhauling of unsv dynamo/alternator 12 V of any capacity DG set including repair/replacement unsv/defective spares such as field coil, armature winding, carbon bushes, clutch bushes and pinion assy suitable for 160 KVA to 320 KVA DG Set complete all as specified and directed.
S&F in repair AVR with functions to adjust generator output voltage, prevent voltage hunting, set under frequency roll off knee point, set generator droop to 5% at full load, match AVR input to accessory output, set the over excitation cut off level, set intial frequency related voltage dip, over-voltage protection cut off level, maximum short circuit current with sensing input voltage range 170 - 250 V AC max, 50 -60 HZ frequency with output max upto 120 V DC, continuous current 2.7A & transient 6A for 10 sec including necessary control wiring complete from alternator to AVR complete testing & commissioning for DG sets of capacity 50 to 125 KVA
All as per srl item No. 15 above but for DG set capacity 160 to 320 KVA
M & L for repair of Water pump of 50 to 320 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M & L for repair of Water pump of 160 to 320 KVA DG set including replacement of defective unsv spare part of any make and model and refix the same after repair complete all as specified and as directed
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 50 to125 KVA DG Set of any make and model complete all as directed.
M&L for Calibration of Fuel pump including replacement of unsv/defective spares of 160 to 500 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 50 to 125 KVA DG Set of any make and model complete all as directed.
M&L for overhauling and calliberation of fuel injector assembly including replacement of unsv/defective spares of 160 to 320 KVA DG Set of any make and model complete all as directed.
S&F in replacement battery leads set, PVC insulated multisranded, copper conductor of min size 35 sqmm 1 mtr long each duly fixed with brass clamps, copper lugs suitable for DG sets of different capacities.
M&L for replacement of coolant for radiator for DG set at various locations.
M&L for replecement of Lub Oil (Engine Oil) of grade 20W40 for Engine for DG set at various locations.
M&L for replacement of starter ring gear assembly for capacity 50 to 110 KVA DG set.
S&F in replacement of existing wornout unserviceable fan belt with new fan belt suitable of existing DG Set capacity 50 to 125 KVA complete all as specified and directed.
S&F in replacement of existing wornout unserviceable fan belt with new fan belt suitable of existing DG Set capacity 160 to 320 KVA complete all as specified and directed.
Dismantaling Radiator of DG Set and Servicing/ overhauling the same, making leak proof including soldering bracing cleaning the fins with antiscalent fixing on base frame capacity of 50 to 125 KVA DG Set complete all as specified and directed.
Dismantaling Radiator of DG Set and Servicing / overhauling the same, making leak proof including soldering bracing cleaning the fins with antiscalent fixing on base frame capacity of 160 to 320 KVA DG Set, complete all as specified and directed.
S&F in replacement of battery 12 volts ,130AH with connecting leads of copper cable of suitable size including brass terminals etc, complete all as specified and directed.
S&F in replacement of battery 12 volts, 80AH with connecting leads of copper cable of suitable size including brass terminals etc, complete all as specified and directed.
M&L for replecement of existing unservicible Hose Pipes with clamps and testing complete for the following capacity of DG Sets and any make
DG Set 50 KVA
DG Set 62 to110 KVA.
DG Set 320 KVA
Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables, Foundation filling of poles or stays, complete all as specified and directed.
Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point, complete all as specified and directed.
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required, complete all as specified and directed.
M&L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specifed and punned thickness shall be measured and paid.
Supply and laying sub class 'B' bricks of old size (230x115x75 mm) or of size locally available, laid along alignment of cable as protection to cable in trenches complete all as specified and directed.
Removing existing 1100 volts grade, XLPE/PVC, armoured, electric power cables (heavy duty) with aluminium conductor of sizes 25 Sqmm 3.5/4 core to 300 Sqmm 3.5 core from trench/ duct/ pipe carefully for identifying the defects and relaying the same after rectification of defects complete all as directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
Removing existing 1100 volts grade, XLPE/PVC, armoured, electric power cables (heavy duty) with aluminium conductor of sizes 6 Sqmm 4 core to 16 Sqmm 4 core from trench/ duct/ pipe carefully for identifying the defects and relaying the same after rectification of defects complete all as directed. Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining , cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
Supply and lay cable XLPE insulated armoured heavy duty electric cable with aluminium counductor, 1100 volts grade of crosssectional area 16 Sq mm 4 core.Note: Earth work ( Excavation, Returning & refilling and removal), sand cushining, cable protection cover, GI protection pipe shall be measured and paid for seperately under respective item of Schedule
All as per Srl. Item No. 41 above but of size 10 Sqmm 4 core
All as per Srl. Item No. 41 above but of size 25 Sqmm 4 core
All as per Srl. Item No. 41 above but of size 35 Sqmm 3.5 core
All as per Srl. Item No. 41 above but of size 50 Sqmm 3.5 core
All as per Srl. Item No. 41 above but of size 70 Sqmm 3.5 core
All as per Srl. Item No. 41 above but of size 95 Sqmm 3.5 core
All as per Srl. Item No. 41 above but of size 120 Sqmm 3.5 core
All as per Srl. Item No. 41 above but of size 240 Sqmm 3.5 core
S&F for PVC insulated copper conductor cable 16 Sq mm x 3 core for main Panel to main switch/starter,MCCB etc complete with thimbales of suitable size as required on site all including making connection, complete all as specifed and directed.
Supply and Repair/Replacement of laying/jointing GI Pipe light grade 40mm dia with all fittings laid/fixed on wall/pole or under road/PCC crossing, complete all as specifed and directed.
Supply and Repair/Replacement of laying/ jointing GI Pipe light grade 80mm dia with all fittings laid/fixed on wall/pole or under road/PCC crossing, complete all as specifed and directed.
M&L for Horizontal Boring/Cutting of Road/Foot Path for using through 40/80mm bore pipe for cable protection and finishing PCC after Boring/Cutting of road/Foot path, complete all as specified and as directed.
Supply and Repair/Replcement for weather proof flat twin core 6 sqmm multistrand aluminium conductor cable complete all as specified and directed.
Supply and Repair/Replacement for weather proof flat twin core 10 sqmm multistrand aluminium conductor cable complete all as specified and directed by Engineer-in-Charge.
M&L for fault finding on LT cables of any size and any length with fault detective machine by thumbing method/other suitable find out method with suitable high voltage and all as and directed by Engineer-in-charge.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for Stright through joint heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm to 300 sqmm complete all as specified and directed Engr-in-Charge.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for Stright through joint heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 25 sqmm to 50 sqmm complete all as specified and directed Engr-in-Charge.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for Stright through joint heat shrink type joint complete with jointing material and accessories suitable for 3.5/4 core XLPE armoured aluminium conductor cable of size 10 sqmm to 16 sqmm complete all as specified and directed Engr-in-Charge.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for Stright through joint heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to150 sqmm complete all as specified and directed.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for INDOOR / OUTDOOR END TERMINATIONS heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 sqmm to150 sqmm complete all as specified and directed.
S&F of Cable jointing kit for 1100 V (Earthed) grade cable for INDOOR / OUTDOOR END TERMINATIONS heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 185 sqmm to 300 sqmm complete all as specified and directed.
Supply and Repair/Replacement fixing Lug aluminium suitable cable size of 16 to 95 sqmm complete all as specified and directed.
Supply and Repair/Replacement fixing Lug aluminium suitable cable size of 120 to 400 sqmm complete all as specified and directed Engineer-in-Charge.
S&F in Replacement of industrial change over switch gear 400 Amp 415 V Four Pole Off Load Side Handle Operated In Sheet enclosure, Powder Coated, Weather proof conforming to IS: 13947 by connecting the electrical connection and fixing on wall or panel with clamp nut, bolt etc, complete all as specified and as directed.
S&F in Replacement of industrial change over switch gear 200 Amp 415 V Four Pole Off Load Side Handle Operated In Sheet enclosure, Powder Coated, Weather proof conforming to IS: 13947 by connecting the electrical connection and fixing on wall or panel with clamp nut, bolt etc complete all as specified and as directed.
S&F in Replacement of industrial change over switch gear 100 Amp 415 V Four Pole Off Load Side Handle Operated In Sheet enclosure, Powder Coated, Weather proof conforming to IS: 13947 by connecting the electrical connection and fixing on wall or panel with clamp nut, bolt etc complete all as specified and as directed.
S&F in Replacement for 400 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 36 KA with adjustable thermal and magnetic tripping system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement for 250 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 36 KA with adjustable thermal and magnetic tripping system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement for 63 AMP MCCB 4 pole 415 volt, AC 50 Hz, 4 pole, 10 KA with adjustable thermal and fixed magnetic setting system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement for 100 AMP, MCCB 4 pole 415 volt, AC 50 Hz, 4 pole, 10 KA with adjustable thermal and fixed magnetic setting system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement for 125 AMP, MCCB 4 pole 415 volt, AC 50 Hz, 4 pole, 10 KA with adjustable thermal and fixed magnetic setting system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement for 400 AMP MCCB, 4 pole 415 volt, AC 50 Hz, 4 pole, 36 KA with adjustable thermal and magnetic tripping system against over load and short circuit conditions incl neutral adjustment (Ics=100% of Icu) of capacity suitable of Existing panel board for replace of unserviseble MCCB complete all as specified and directed.
S&F in Replacement of panel mounted volt meter digital type 3 phase as per existing complete all as specied and directed
Repeir/Replacement of panel mounted Ammeter digital type 3 phase as per existing complete all as specied and directed
Taking out any damage of the already installed LT panel board doors/shutter and repair the broken doors by putting necessary nut,bolts,hinges,screw,welding etc and fix it again on the same panel board with two coats of synthetic enamel paint of existing colour complete upto 5 sqm complete all as specified and directed.
Taking out any damage of the already installed LT panel board doors/shutter and repair the broken doors by putting necessary nut,bolts,hinges, welding etc and fix it again on the same panel board with two coats of synthetic enamel paint of existing colour complete exc 5 sqm n exec 10 sqm complete all as specified and directed.
Dismantling the defective LT UT cable 3.5/ 4 core from panel/DB/ junction boxes, dismentling the cable gland if any, removing the pitted/burnt aluminium lugs and suplly and fixing of aluminium paim type lugs or lugs as per existing, crimping with suitable size crymping tool bit, refixing/ replacing cable gland, refixing the cable with suitable nut bolts & washers etc complete for the following size cable:- (Note:(i) one set of triple pole and neutral lugs will be measured as one job. (ii) The rate quoted deemed to be inclusive of insulation tape, nut bolts & washers etc complete. (iii)cable gland will be measured and paid separately.(iv) The rate quoted deemed to be inclusive the necessary earth work for removing loop of cable if any required complete all as directed
M&L for replacement of unsv/broken thermoplastic polycarbonate spring type locks suitable for panel locking (Mi DV 01 with Mi SR 4) complete.
Restretching of ACSR conductor of any size of over head lines LT/HT on poles including binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed. Note: ACSR conductor Required for winding etc to be included in quoted rates.
Supply and Repair/Replacement of 240V, 10 KA miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 240V, 10 KA miniature circuit breaker (MCB) of single poles and current carrying capacity 40 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 240V, 10 KA miniature circuit breaker (MCB) of SPN current carrying capacity 32 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 240V, 10 KA miniature circuit breaker (MCB) of SPN current carrying capacity 40 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 240V, 10 KA miniature circuit breaker (MCB) of SPN current carrying capacity 63 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 415V, 10 KA miniature circuit breaker (MCB) of TPN current carrying capacity 63 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Supply and Repair/Replacement of 415V, 10 KA miniature circuit breaker (MCB) of TPN current carrying capacity 40 AMP, in the MCB DB/Junction box/panel Complete with connection testing and commissioning complete all as specified and directed
Dismantling unserviceable cross arms including clamps, bolts, nuts, washers etc from pole.
Supply, fabricate and fix cross arms any size along with, brackets, clamps, bolts, nuts, washers, bracers etc including drilling holes, cold/hot complete and fixed to pole including one primer coat and one under and finishing coat of paint.
Dismantling of ACSR conductor of any size, from insulator etc from the structure/over head line all as directed.
M&L replacement of ACSR conductor of any size as ordered by Engr-in-charge including tightening and bindingh with new binding wires to insulators all as directed.
Dismantling insulators any type, size, complete all as specified and as directed.
M&L pin type insulator vitreous, white, brown, or green insulator includig one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 100 mm height, 65 mm dia for 1100 volts grade.
M&L for earthing with steel earth plate electrode of size 60x60cm x6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing).
Cutting, trimming of hanging/ extended braches of trees upto a distance 3 meter from the overhead HT/LT line and making the line clear upto the entire length of the feeder including removal and disposal of the cut tree branches 50 meters away from the site complete all as specified and directed. Note : The Rates shall inclusive of T&P, hydraulic ladder, equipment such as motorised diesel operated hacksaw etc complete. One span comprises of 3 to 5 conductors of any distance between one pole to adjacent pole including trimming of all tree branches in vicinty & around poles /conductor & will be measured as one span. Necessary prior permission shall be obtained from concerned I/C JE E/M before carrying out the work. All safety measures & insurance to the staff undertaking the Job shall be the Contractor's responsibility.
Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.
M/S SATPAL & BROTHERS
M/s. Aggarwal Engineers
M/S SHRI RAM BUILDERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .