Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.4 LAccepted-AOC | L1 | Accepted-AOC The lowest bidder | |
| 2 | L2₹9.8 L+₹8,950 (0.92%)Rejected-AOC H NO 309 REHARI COLONY JAMMU DISTT JAMMU J K 180005 | JAMMU | JAMMU AND KASHMIR | 180005 | L2 | Rejected-AOC Other than the lowest bidder | |
| 3 | L3₹12.7 L+₹3.0 L (30.7%)Rejected-AOC 3838 2ND FLOOR SECTOR 46 C CHANDIGARH UT 160047 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160047 | L3 | Rejected-AOC Other than the lowest bidder |
Tender Value
₹12 L
EMD Value
₹24,000
Closing Date
5 Jul 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (I) JUTOGH
GE (I) JUTOGH, JUTOGH CANTT SHIMLA (HP) - 171008
REPAIR AND MAINTENANCE OF LT ELECTRIC SUPPLY NETWORK ALONGWITH CONNECTED ITEMS AT RMS CHAIL UNDER GE(I) JUTOGH
2023_MES_601728_1
GE(I)/JUT-39 OF 2023-24
Open Tender
Civil Works
Item Rate
150 days
RMS CHAIL
CLASS E CATEGORY b (i)
7 documents required · 7 mandatory
₹500
GE (I) JUTOGH
₹24,000
Yes
2 Aug 2023
7 Jun 2023
7 Jul 2023
7 Jun 2023
5 Jul 2023
21 Jun 2023
7 Jun 2023 - 14 Jun 2023
Amount
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr deep in loose/soft soil and getting out for underground cable/erection of poles, stays , trench etc complete all as specified and as directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n.exc 25 cm thick layers complete all as specified and as directed
Removal of excavated material n.exc 50 mtr away and depositing where directed at a level n.exc 1.5 mtr above from starting point complete all as specified and as directed.
Supply, fixing or laying HDPE (DWC) tubing 100 mm dia as per IS:16205 part 24 fixing on poles, walls under floors, laying on surface etc as reqd at site including clamps to hold pipe at position complete all as specified and as directed. Note: All items and accessories , bend, joints, nut bolts, clamps for wall fixing as per site requirement etc are incl in quoted rates.
Description all as per Ser Item No 4.00 above but 65mm dia complete all as specified and as directed.
Description all as per Ser Item No 4.00 above but 40mm dia complete all as specified and as directed.
Disconnecting & taking out defective underground cable any size and any type from trenches, pole, pipe, floor, wall etc complete all as specified and directed. Note: Old cable may different size and length and credit will be given as actual obtained from site complete all as specified and as directed.
Supply and laying, connecting and testing XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 95 sqmm 3.5 core laid in trenches/ on poles/ road crossing or passing through existing/new pipe under road crossing, clamping on wall complete all as specified and as directed. Note: (i) Earth work, removing, returning filling and pipe will be measured and paid separately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments, machinery or tools if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
Description all as per Ser Item No 8.00 above but for 3.5 core 50 Sqmm complete all as specified and as directed.
Description all as per Ser Item No 8.00 above but for 4 core 25 Sqmm complete all as specified and as directed.
Description all as per Ser Item No 8.00 above but for 4 core 16 Sqmm complete all as specified and as directed.
Description all as per Ser Item No 8.00 above but for 3 core 10 Sqmm complete all as specified and as directed.
Supply, installation, testing and commissioning outdoor type cubical LT panel in replacement of size not less than 1.0 m x 1.0 m x 0.5 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 40 x 40 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , with pad lock , louvers and air vent, gasket ‘u’ type for natural flow of air, completed dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 200 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB 4 pole 100A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 25KA Main- 01Nos
OUTGOING:-
MCCB 4 pole 63A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA- 03Nos
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-200) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No.
Supply, installation, testing and commissioning outdoor type cubical LT panel in replacement of size not less than 1.0 m x 1.0 m x 0.5 m with outer shell made out of 3.15 mm thick MS sheet and MS angle section 40 x 40 x 5mm on PCC 1:2:4 type B-2 platform 60cm above the ground level and 45cm below the ground level, factory fabricated with front openable , lockable, having pad lock arrangement , with pad lock , louvers and air vent, gasket ‘u’ type for natural flow of air, completed dust & vermin proof suitable for 3 phase 4 wire 415 volt 50 Hz factor fabricated ( Factory approved from CPRI) having modern fabrication followed by powder coated painting having thickness not less than 100 microns TPN aluminum bus bar 200 Amps insulated with colour coded heat shrinkable and shall be mounted on suitable size ‘F’ class insulators, marking connection with aluminum strip conductor of and general construction to IS-8623 of 1993 comprising of the following:-
INCOMING:-
MCCB FP 63A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA Main- 01Nos
OUTGOING:-
MCCB 4 pole 40A, Adj Thermal Fixed Magnetic release, 50 Hz, 415 Volts, 16KA- 03Nos
Indicator lamps RYB with control fuses- 01 set (set of three)
Digital Multifunction meterwith Amps range (0-200) Amps & Voltage range (0-500) volt flush mounting type 4"X4" square dial with CTs of ratio 200/5- 01 No
Supply, installation, commissioning in replacement of Busbar panel outdoor Step Type Design of size 1.0x1.0x.6m with DMC insulators locking arrangement MS sheet covering 3.15 mm thick pedestal mounted vermin and weatherproof including four legs of 60 cm long of angle iron 40x40x5mm, front openable door having canopy for protection all surfaces painted with powder coated painting, embedding and including 400 Amp rated aluminium bus bars 4 Nos duly drilled for making connection with nut bolts of suitable size with colour code tape complete with PCC 1:3:6 type C1 using 20 mm graded aggregate for foundation for legs and dry 63mm aggregate of 75mm thickness around the panel upto 6 sqft after make good electrical connection complete all as specified and as directed. Note: The rate are included with thimbles lugs, nut bolts,PCC foundation and aggregate.
M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, using galvanised iron strip 32×6mm with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 40 mm dia and watering pipe medium grade of 20 mm dia and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC 1:3:6 type C-2 all as shown in electrical plate No-3 of SSR part-I of 2009 connected to earthing test point, including all earth work excavation, returning filling and disposal of surplus soil and testing on completion complete all as specified and as directed.
Supply and fix in replacement cable jointing kit for 1.1 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 ½ / 4 core XLPE, armoured, Al conductor cable of size 4-16 sqmm complete all as specified and as directed.
Description all as per Ser Item No 17.00 above but for cable of size 25 to 50 sq mm complete all as specified and as directed
Description all as per Ser Item No 17.00 above but for cable of size 70 to 150 sqmm complete all as specified and as directed
M&L MCCB 4 Pole, 415 V, Adjustable type, 630 Amps with breaking capacity 36 KA including taking down the unsv mccb complete all as specified and as directed
Description all as per Ser Item No 20.00 above but of size 400A complete all as specified and as directed
Description all as per Ser Item No 20.00 above but of size 160A complete all as specified and as directed
Description all as per Ser Item No 20.00 above but of size 100A complete all as specified and as directed
M&L CT of ratio 400/5 Amp including wiring and calibration with Ammeter including taking down the unsv ct from panel complete all as specified and as directed.
Description all as per Ser Item No 24.00 above but of ratio 200/5 Amp complete all as specified and as directed.
M/S A K ENGINEERS & CO.
naina devi constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .